Leibniz Supercomputing Centre

Liquid Cooling CommissioningLessons Learned @LRZ

Detlef Labrenz ([email protected])EE HPC WORKING GROUP, SC13, Denver, Nov. 17-22, 2013

Page 2: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Leibniz Supercomputing Centre

-2-

Munich Bavaria Germany & Europe

• We provide generic IT services to all Munich universities• We provide special IT services to all universities in Bavaria

• Network, High Performance and Grid Computing• Backup and Archive Services• IT Management

• We provide supercomputing resources to scientists in Europe• Member of the German Gauss Supercomputing Centre• Third party of the European HPC Infrastructure PRACE• PRACE Tier-0 Supercomputing Center (SuperMUC system)• Investigations on Future HPC Systems:

• Hardware Architectures• Programming Models & System Software• Zero Emission Data Center Infrastructures• Re-Use of Waste Heat

Page 3: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Data Center Infrastucture

-3-

Page 4: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Layout of Cooling Infrastructure

-4-DH

Cold Water -1

WW 30/36°C

CW 14/20°C

VCW 4/10°C

W/Gly

Htg/CCA

CRAH

DAR

KLT19RCT

RCT

KLT11RCT

KLT12RCT

KLT13RCT

KLT14RCT

KLT15Ch+RCT

KLT16Ch+RCT

KLT17CT

KLT18Fountain

KLT04Ch+RCT

KLT05Ch+RCT

KLT02Ch+RCT

HE

9

HRRDLC RHEx

NSRDLC RHEx

DARRHEx

EG

UG

CRAH

CRAH

CRAH

CRAH

CRAC

CRAC

CRAC

CAVE Office 2CRAH/C

Htg CCCA

AC SAN

LECTURESOffice 1

RLT

AC SAN

Htg CCA

KLT03Ch+RCT

HE

11

KLT01Ch+RCT

HE

1H

E10

2

HE20

HE ?

HE6

HE4

HE1

HE8

HE4HE20 HE8

HE11HE12

Warm Water Cold Water -2 Very Cold Water

CRAC

CCA

Page 5: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

SuperMUC: IBM System x iDataPlexWith Direct Water Cooling

-5-Torsten Bloth, IBM Lab Services - © IBM Corporation

iDataplex DWC Rack w/ water cooled nodes

(rear view of water manifolds)

Page 6: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Heat Profile of SuperMUC (2/2013)

-6-

Page 7: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

CASE #1: Cooling Towers

-7-

Page 8: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Malfunction of Water Level Sensors

• Issue: • Water demand cooling loop increased

• Filling volume: 7 m³• Typical feed: 1+ m³/h• Observed losses: 1 – 2 m³ in hours or days

• Investigations:• Load tests of the cooling towers• Inspection of the control system• Examination of the measuring devices

• Reason: • Wrong dimensions of the filling level sensor

installed

• Root cause: • Main contractor did not use the sensor

recommended by the manufacturer of the cooling tower

-8-

Page 9: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

CASE #2: Operating ControlWarm Water Cooling Infrastructure

-9-

SuperMUC

M

Cluster

M

M

M

∞ KLT 12 ∞M

T T

MM

∞ KLT 11 ∞M

M

∞ KLT 14 ∞M

M

∞ KLT 13 ∞

N NNN

SS S

S

T T

M

T T

M

T T

M

HRR NSR

M

M M

Page 10: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Operating Control: Test of DTinlet(NSR) = -20 KResponse of Warm Water Cooling Infrastructure

-10-

Page 11: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Operating Control: Test of DTinlet(NSR) = -20 KResponse of Warm Water Cooling Infrastructure

-11-

COP = Cooling Capacity/ Power Input

COP

Page 12: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

WWW.SIMOPEK.DE

-12-

Page 13: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Thank You!

Zero Emission Supercomputing Centre

Page 14: Liquid CoolingCommissioning LessonsLearned@LRZ · PDF fileVictor Apostolescu Created Date: 11/13/2013 10:20:31 AM

Energy Efficient HPC: The Four Pillar Model

Data Center (Goal: Reduce Total Cost of Operation)

Uti

lity

Pro

vid

ers

Ne

igh

bo

rin

g B

uil

din

gs

Building Infrastructures

HPC System Hardware

HPC SystemSoftware

HPC Applications

Goal:Improve PUE (Power Usage Effectiveness)

Goal:Reduce Hardware Power Consumption

Goal:Optimize Resource Usage, Tune System

Goal:Optimize Application Performance

-14-