L1 V4 03 MiCOM C264 Hardware Presentation E 01

download L1 V4 03 MiCOM C264 Hardware Presentation E 01

of 42

Transcript of L1 V4 03 MiCOM C264 Hardware Presentation E 01

  • MiCOM C264 Hardware Presentation

    PCL

    PACiS PACiS PACiS PACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining

    CS&P CS&P CS&P CS&P Support TeamSupport TeamSupport TeamSupport Team

  • Schneider Electric 2- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 3- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 4- CS&P C264 Hardware Presentation E01

    MiCOM C264C4U / 170mm / 40 TE

    with 4 or 6 slots for I/O boards

    MiCOM C2644U / 170mm / 80 TE

    with 14 or 15 slots for I/O boards

    Modular Racks

  • Schneider Electric 5- CS&P C264 Hardware Presentation E01

    Modular Construction (Back)Easy to Install

    Removable connectors for 0.8 to 2.5 mm2 wires I/Os

    boards &Power supply

    Optional connectorsfor 4 mm2 wires

    direct CT/VT connection

    Optional : optic/Ethernet IED Com,

    IRIG B

    Connector Screwing

    Connections

    Shed Contacts shouldbe grounded

  • Schneider Electric 6- CS&P C264 Hardware Presentation E01

    Boards ListShort designation Designation DetailsGHU 2xx Graphic Humain Unit Front panel / LCD

    BIU 2x1 Basic Interface Unit Power supply and 2 RS

    CPU 2x0 Computer Processing Unit

    TMU 2xx Transducerless Measurement Unit4 CT / 4-5 VT DSP 2xx Digital Signal Processor TMU Signal

    DSPIO 2xx Digital Signal Processor Input Output TMU Signal + 5 DI / 5 DO (1 slot)

    DIU 2xx Digital Input Unit 16 DI

    DOU 2xx Digital Output Unit 10 DO

    CCU 2xx CB Control Unit 8 DI + 4 DO

    AIU 2xx Analog Inputs Unit (4) 8 AI

    AOU 2xx Analog Output Unit 4 AO

    SWx 2xx SWitch Ethernet max 6 ports SWU 2xx SWitch Unit (standard switch) 2 Fx + 4 Tx

    SWR 2xx SWitch Ring Redundancy 2 Fx Redundant + 4 Tx

    SWD 2xx SWitch Dual Hamming redundancy 2 Fx Redundant + 4 Tx

    CAS 2xx Package CASe (rack 4U) Package CASe (rack 4U)

    FBP 2xx Front Back Plane ( Bus ) Front Back Plane ( Bus )

  • Schneider Electric 7- CS&P C264 Hardware Presentation E01

    6 (48 AI)6 (48 AI)AIU211 (8 AI, mA)

    6 (24AO + 24DO)6 (24AO + 24DO)AOU200 (4AO + 4DO)

    C264-P: 1 (4CT, 4VT)C264-P : 1 (4CT, 4VT)TMU210

    1 (4 CT, 5 VT)1 (4 CT, 5 VT)TMU220

    6 (24 AI)6 (24 AI)AIU201 (4 AI, mA or V)

    15 (120 DI + 60 DO)6 (48 DI + 24 DO)CCU211 (8 DI + 4 DO)

    15 (150 DO)6 (60 DO)DOU201 (10DO)

    15 (240 DI)6 (96 DI)DIU220 (16DI)

    15 (240 DI)6 (96 DI)DIU211 (16DI)

    11GHU 2xx :20x=LCD, 21x=no LCD, 22x=remote

    11CPU260 (2RS + RJ45) / CPU270 options :Optic Fx, IRIG-B, DSP

    11BIU 241 (power + 2RS)

    MiCOM C26414/15 slots

    MiCOM C264C4/6 slots Capabilities

    With CPU270, boards 2x1 address is defined in SCE (jumpers optional) :DIU211, CCU211

  • Schneider Electric 8- CS&P C264 Hardware Presentation E01

    Example of 80TE Rack Content Front Automatic Production Placement

    BIU 241

    B

    CPU260

    C

    SWX

    D

    AIU201

    _@0

    E

    AIU210

    _@0

    F

    AIU210

    _@1

    G

    DOU

    200_@

    0

    H

    DOU

    200_@

    1

    I

    DOU

    200_@

    2

    J K L

    CCU200

    _@2

    M

    CCU200

    _@1

    N

    CCU200

    _@0

    O

    DIU200

    _@2

    PDIU

    200_@

    1Q

    DIU200

    _@0

    A

    BIU 241

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    BIU 241

    CPU260

    SWX

    AIU201

    _@0

    AIU210

    _@0

    AIU210

    _@1

    DOU

    200_@

    0

    DOU

    200_@

    1

    DOU

    200_@

    2

    CCU200

    _@2

    CCU200

    _@1

    CCU200

    _@0

    DIU200

    _@2

    DIU200

    _@1

    DIU200

    _@0

    BIU 241

    1 2 3 4 5 6 7 8 9 10 11 12 13 14

    CT / VT

    TMU

    200

    BIU 241

    CPU260

    SWX

    AIU201

    _@0

    AIU210

    _@0

    AIU210

    _@1

    DOU

    200_@

    0

    DOU

    200_@

    1

    DOU

    200_@

    2

    CCU200

    _@2

    CCU200

    _@1

    CCU200

    _@0

    DIU200

    _@2

    DIU200

    _@1

    DIU200

    _@0

    BIU 241

    CT / VT

    TMU

    210

    DSP IO

    B C D E F G H I J K L M N O P QA

    B C D E F G H I J K L M N O P QA

    Basic

    With TMU200

    With TMU210

    ProtectionDSP IO Slot

    1 2 3 4 5 6 7 8 9 10 11 12 13

  • Schneider Electric 9- CS&P C264 Hardware Presentation E01

    Example of 40TE Rack Content Front Automatic Production Placement

    B C D E F G HA

    BIU 241

    CPU260

    SWX

    AIU210

    _@0

    DOU

    200_@

    0

    CCU200

    _@0

    DIU200

    _@1

    DIU200

    _@0

    BIU 241

    1 2 3 4 5 6

    BIU 241

    CPU260

    SWX

    DOU

    200_@

    0

    DIU200

    _@1

    DIU200

    _@0

    BIU 241

    1 2 3 4

    CT / VT

    TMU

    200

    BIU 241

    CPU260

    SWX

    DOU

    200_@

    0

    DIU200

    _@0

    BIU 241

    CT / VT

    TMU

    210

    DSP IO

    1 2 3

    B C D E F G HA

    B C D E F G HA Basic

    With TMU200

    With TMU210ProtectionDSP IO Slot

  • Schneider Electric 10- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 11- CS&P C264 Hardware Presentation E01

    Rack Mounting Cubicle Mounting (6 screws) on 19 Rack LCD Removal (6 Poz drive 10)

    CabinetMounting

    19 Rack Support

    Front Face Screwing

    C264 Screwing

  • Schneider Electric 12- CS&P C264 Hardware Presentation E01

    BIU

    CPU

    DIU DOU CCU AIU

    Board Number Board NameBus

    Rack / Board Overview Board + rail removing (torque drive 10)

  • Schneider Electric 13- CS&P C264 Hardware Presentation E01

    Each board has an address, unique per type, starting from 0by jumpers

    CLOSED = 0 OPEN (see below)

    If Open : address = address + 1If Open : address = address + 2If Open : address = address + 4If Open : address = address + 8

    Rules :

    Example :=> + 2

    => + 8=> 2 + 8 = 10

    Board Number (Address)

  • Schneider Electric 14- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 15- CS&P C264 Hardware Presentation E01

    Front Faces

    GHU200 40 TE Front Panel Leds + L/R switch + Graphic Display LCD 2071004GHU210 40 TE Front Panel Leds + L/R switch 2071010GHU220 40 TE Front Panel : Simple Blind 2071174GHU201 80 TE Front Panel : Leds + L/R switch + Graphic Display LCD 2070962GHU211 80TE Front Panel : Leds + L/R switch 2070966GHU221 80 TE Front Panel : Simple Blind 2071172

    RJ11

  • Schneider Electric 16- CS&P C264 Hardware Presentation E01

    Main characteristics : Power Supply (4 possible ranges : 24 / 48 / 110 / 220V) 1 Watchdog contact 2 DI & 2 DO used for redundancy RS1 (232/485) RS2 (232/422/485)

    Basic Interface Unit BIU241

  • Schneider Electric 17- CS&P C264 Hardware Presentation E01

    Main characteristics : 32-bit Power PC-base processor (80 MHz) DRAM (64Mo) & Flash (16Mo) VxWorks for RT OS Powerful DSP TMS320C6713 for CT/VT Ethernet-Based 10/100Base-FX or Base-TX 2 Serial links up to 64 Kbit/s RS232 IRIG-B port Bus

    CentralProcessing Unitboard

    CPU260

    RJ-45(female)

    1 2 3 4 5 6 7 8

    RS232

    #

    Serial

    link 4GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    10/100 Base-Tx

    Ethernet-based link

    RS232

    #

    Serial

    link 3GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    OPTIONNAL LINKS:

    10/100 Base-Fx

    Ethernet-based link

    1

    2

    3

    4

    5

    6

    7

    8

    9

    1

    2

    3

    4

    5

    6

    7

    8

    9

    IRIG B

    Central Processing Unit CPU260

  • Schneider Electric 18- CS&P C264 Hardware Presentation E01

    Main characteristics : 32-bit Power PC-base processor (260 MHz) More DRAM (128Mb) and Flash (64Mb) VxWorks for RT OS Powerful DSP TMS320C6713 for CT/VT 2 Ethernet ports 10/100Base-TX 2 Serial links up to 64 Kbit/s RS232 IRIG-B port New bus

    Good Practice : In Boot Parameters from CMT, make sure IP address 1 and IP address 2 are belonging to different domains.

    CentralProcessing Unitboard

    CPU270

    RJ-45(female)

    1 2 3 4 5 6 7 8

    RS232

    #

    Serial

    link 4GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    10/100 Base-Tx

    Ethernet-based link

    RS232

    #

    Serial

    link 3GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    10/100 Base-Tx

    Ethernet-based link

    1

    2

    3

    4

    5

    6

    7

    8

    9

    1

    2

    3

    4

    5

    6

    7

    8

    9

    IRIG B

    RJ-45(female)

    1 2 3 4 5 6 7 8

    !

    Central Processing Unit CPU270

  • Schneider Electric 19- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 20- CS&P C264 Hardware Presentation E01

    Main characteristics A01 Vnom : 24-30 Vdc A02 Vnom : 40 Vdc (range 20 to 60 Vdc) A03 Vnom : 100 Vdc (range 40 to 150 Vdc) A04 Vnom : 220 Vdc (range 180 to 264 Vdc)

    16 Opto Isolated DI but 40% Thresholds Board addressing

    SPS, DPSSCT, DCTDM

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Digital Input Unit

    board

    DIU20x

    VIN

    -

    VIN

    -- -

    ++ DI8DI7

    VIN

    -

    VIN

    -- -

    ++ DI2DI1

    VIN

    -

    VIN

    -- -

    ++ DI4DI3

    VIN

    -

    VIN

    -- -

    ++ DI6DI5

    VIN

    -

    VIN

    -- -

    ++ DI10DI9

    VIN

    -

    VIN

    -- -

    ++ DI12DI11

    VIN

    -

    VIN

    -- -

    ++ DI14DI13

    VIN

    -

    VIN

    -- -

    ++ DI16DI15

    Signal inputs

    Digital Input Unit DIU200

  • Schneider Electric 21- CS&P C264 Hardware Presentation E01

    Main characteristics Capabilities : 40TE 80TE A01 Vnom : 24-30 Vdc 2 8 A02 Vnom : 40 Vdc (range 20 to 60 Vdc) 6 15 A03 Vnom : 100 Vdc (range 40 to 150 Vdc) 3 10 A04 Vnom : 220 Vdc (range 180 to 264 Vdc) 1 5

    1 ms Time-tag16 Opto Insulated DI 2kV (1mn)Peak > 25mA when Set

    SPS, DPSSCT, DCTDM

    Digital Input Unit DIU210

  • Schneider Electric 22- CS&P C264 Hardware Presentation E01

    Main characteristics : Accept all Nominal Voltages

    according on jumpers definition

    1 ms Time-tag Opto Isolated (2kV during 1mn) 27mA peak for 2ms Board Auto-addressed (CPU3)

    16 DI usable for :SPS, DPSSCT, DCTDM

    Board address

    Digital Input Unit DIU211

  • Schneider Electric 23- CS&P C264 Hardware Presentation E01

    Main characteristics : Accept 2 different Nominal Voltages :

    VA, nom : 48 Vdc (range 20 to 60 Vdc)VA, nom : 110 Vdc (range 40 to 125 Vdc)

    1 ms Time-tag Opto Isolated (2kV)

    16 DI usable for :SPS, DPSSCT, DCTDM

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Digital Input Unit

    board

    DIU20x

    VIN

    -

    VIN

    -- -

    ++ DI8DI7

    VIN

    -

    VIN

    -- -

    ++ DI2DI1

    VIN

    -

    VIN

    -- -

    ++ DI4DI3

    VIN

    -

    VIN

    -- -

    ++ DI6DI5

    VIN

    -

    VIN

    -- -

    ++ DI10DI9

    VIN

    -

    VIN

    -- -

    ++ DI12DI11

    VIN

    -

    VIN

    -- -

    ++ DI14DI13

    VIN

    -

    VIN

    -- -

    ++ DI16DI15

    Signal inputs

    Digital Input Unit DIU220

  • Schneider Electric 24- CS&P C264 Hardware Presentation E01

    Main characteristics 8 outputs NO contacts and 2 outputs NO/NC UN 250 Vdc / 230 Vac Isol. 2kV Making 70 VA/W 2.5 A permanent 100 A peak for 30ms

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Digital Output Unitboard

    DOU200

    Signal outputs

    DO 1

    DO 2

    DO 3

    DO 4

    DO 5

    DO 6

    DO 7

    DO 8

    DO 10

    DO 9

    Digital output Board DOU200

  • Schneider Electric 25- CS&P C264 Hardware Presentation E01

    Main characteristics : 10 DO (8 NO contacts & 2 NO/NC contacts) UN 250 Vdc / 230 Vac Isolation 2kV Making Power : 140 VA/W Permanent : 5 A Peak for 30ms : 250 A

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Digital Output Unitboard

    DOU200

    Signal outputs

    DO 1

    DO 2

    DO 3

    DO 4

    DO 5

    DO 6

    DO 7

    DO 8

    DO 10

    DO 9

    Digital output Board DOU201

  • Schneider Electric 26- CS&P C264 Hardware Presentation E01

    DI main characteristics like DIU2xxDO main characteristics :

    4 power output relays (2 NO contacts each)

    Making Power 140 VA/W Permanent : 5A 500ms : 30A 30ms : 250A

    8DI and 4DO

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Circuit breakerControl Unitboard

    CCU 200

    Signal outputs

    VIN

    -

    VIN

    -- -

    ++DI2DI1

    VIN

    -

    VIN

    -- -

    ++DI4DI3

    VIN

    -

    VIN

    -- -

    ++DI6DI5

    VIN

    -

    VIN

    -- -

    ++DI8DI7

    Signal inputs

    CO 2

    CO 1B

    A

    B

    A

    CO 4

    CO 3B

    A

    B

    A

    CB Control Unit CCU200

  • Schneider Electric 27- CS&P C264 Hardware Presentation E01

    CB Control Unit (8DI and 4DO) DI Voltage selected by jumpers DI Trigger threshold selected by jumpers 4 DO Double Cut Board Auto-addressed (CPU3) 1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Circuit breakerControl Unitboard

    CCU 211

    Signal outputs

    VIN

    -

    VIN

    -- -

    ++DI2DI1

    VIN

    -

    VIN

    -- -

    ++DI4DI3

    VIN

    -

    VIN

    -- -

    ++DI6DI5

    VIN

    -

    VIN

    -- -

    ++DI8DI7

    Signal inputs

    CO 2

    CO 1B

    A

    B

    A

    CO 4

    CO 3B

    A

    B

    A

    CB Control Unit CCU211

  • Schneider Electric 28- CS&P C264 Hardware Presentation E01

    CCU board wiring :Double pole relays (A&B contacts) wired in serial

    CCU pins no

    Internal CCU relaysdescriptionCircuit Breaker

    side

    Vcc+

    Open CoilCB1

    Vcc-

    Close CoilCB1

    Vcc+

    Open CoilCB2

    Vcc-

    Close CoilCB2

    Simultaneouschange of both contacts A and B

    CCU211 Double Cut

  • Schneider Electric 29- CS&P C264 Hardware Presentation E01

    Main characteristics : 4 opto-isolated AI (Current or Voltage) 20 ms time tagging (acquisition) 16 bits A/D converter with 0.1% accuracy SMRR : 98dB CMRR : 150dB

    Analogue Input Board AIU201

  • Schneider Electric 30- CS&P C264 Hardware Presentation E01

    Main characteristics : 8 independent opto-isolated AI (Current only) 20 ms time tagging (acquisition) 16 bits A/D converter 0.1% accuracy SMRR : 98dB CMRR : 150dB Input impedance : 75ohms

    This board is replacing the AIU210!

    Analogue Input Board AIU211

  • Schneider Electric 31- CS&P C264 Hardware Presentation E01

    Main characteristics : 4 AO + 4DO as Read Inhibit signals 100 ms stabilisation time external voltage power source 48VDC 0.1% accuracy 4-20mA, 10mA, 20mA

    Analogue Output Board AOU200

    N Description1 External power supply +48V2 NIL3 External power supply (0V)4 NIL5 WDOG+6 WDOG-7 NIL8 READ INHIBIT AO n 1+9 READ INHIBIT AO n 1-10 READ INHIBIT AO n 2+11 READ INHIBIT AO n 2-12 READ INHIBIT AO n 3+13 READ INHIBIT AO n 3-14 READ INHIBIT AO n 4+15 READ INHIBIT AO n 4-16 NIL17 AO n 1+18 AO n 1-19 AO n 2+20 AO n 2-21 AO n 3+22 AO n 3-23 AO n 4+24 AO n 4-

  • Schneider Electric 32- CS&P C264 Hardware Presentation E01

    4 CT 2 ranges each (1-5A) Range 0.2 In to 4 In accuracy 0.2%

    5 VT for TMU220 (4VT on old TMU200) Input Nom: 57 to 500V Range 4V to 500V(800V) acc. 0.2%(possibility to use TMU220 instead of TMU200 on old substations without changing configuration)

    Direct measurement RMS values of line/phase voltage (Van, Vab, ...) RMS values of line current (Ia, Ib, Ic) RMS values of residual current and voltage (Ir and Vr) Frequency Active power (Pa, Pb, Pc and Ptotal) Reactive power (Qa, Qb, Qc and Qtotal)

    Derived Measurements Fundamental magnitudes and phase angles Apparent Power (Sa, Sb , Sc and Stotal) Import/Export active and reactive energy Power factor (displacement, distortion and true factor) Fundamental Sequence components (Id, Ii, I0, Vd, Vi, V0) Rolling, Peak, Dip demand values Phase and amplitude difference 15th Harmonic 64 samples/period

    + Daughter Board DSP on CPU board

    Transducerless Measure Unit TMU220

  • Schneider Electric 33- CS&P C264 Hardware Presentation E01

    TMU220 wiring : Transducerless Measure Unit TMU220

  • Schneider Electric 34- CS&P C264 Hardware Presentation E01

    3 Phase + 1 neutral current transformer (3*I + Io) Ratings In: 1 or 5 Amperes by jumper Phase Current: 0.1 to 40 In Earth Current: 0.002 to 1 Ien

    0.01 to 8 Ien 0.1 to 40 Ien

    Thermal heating 4 In permanent, 30 In during10secs,100 In 1sec

    Bandwidth : 10th harmonic (no MV) Threshold acc : 2% Compatibility with external CT : 5VA, 5P10

    4 Phase voltage transformer (4 VT) Nominal voltage 57 to 130 VRMS Thermal heating : 2 Vn (Phase-N )permanent

    2.6 Vn (Phase N) -10seconds Connection options : defined by setting Threshold acc : 2%

    CT/VT acquisition module (32 samples/period)

    Sensitivity

    Transducerless Measure Unit TMU210

  • Schneider Electric 35- CS&P C264 Hardware Presentation E01

    CPU Daughter board using one slot CDigital Signal Processor (DSP TMS320C6711)

    for protection functions (like P127 + P923)5 Digital Input - isolated

    A02_48Vdc , A03_110-125Vdc, A04_220Vdc Consumption 5mA in 48V Settable filtering

    4 Digital Output - isolated contacts (NO type) 250Vdc 50W resistive or 25W inductive (L/R=40ms) Carry : 5A 30A during 30s Operation time DSPIO211

  • Schneider Electric 36- CS&P C264 Hardware Presentation E01

    Fixed inputs, usage defined in SCE

    Blocking Selectivity Cold Load Start Disturbance Start

    Evolution DSPIO 210 to DSPIO 211

    DSPIO 211 3 Separate trip contacts DO 5 for CloseCB in Auto Rec DO 4 for Blocking

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    PIN

    Digital Signal ProcessorInput Output

    Board

    DSPIO

    VIN

    -

    VIN

    -

    -

    -

    +

    +

    COLD LOAD START

    DI7

    VIN

    --

    +BLOCKING

    VIN

    --

    + SELECTIVITY

    Signal inputs

    DIST REC START

    TRIP C

    TRIP B

    TRIP A

    123456

    9101112131415161718192021222324

    PIN

    Digital Signal ProcessorInput OutputBoard

    DSPIO211

    COLD LOAD

    BLOCKING

    Signal inputs

    DIST REC

    TRIP C

    TRIP B

    TRIP A

    IN

    --

    +

    SELECTIVITYIN

    --

    +

    IN

    --

    +

    IN

    --

    +

    IN

    --

    +78

    K5

    K4

    Wiring DSPIO210 to DSPIO 211

  • Schneider Electric 37- CS&P C264 Hardware Presentation E01

    Pin N. Signal1 DI BLOCKING +2 DI BLOCKING Common3 DI SELECTIVITY +4 Not Configurable5 DI SELECTIVITY Common6 COLD LOAD START +7 DISTURBANCE START +8 STARTS COLD LOAD / DREC Common9 K5/1 + Close CB

    10 K5/1 - Close CB11 K5/2 + Close CB12 K5/2 - Close CB13 K4/1 + Not Configurable14 K4/1 - Not Configurable15 K4/2 + Not Configurable16 K4/2 - Not Configurable17 Not connected18 Trip Phase C +19 Trip Phase C -20 Trip Phase B +21 Trip Phase B -22 Trip Phase A +23 Trip Phase A -24 Trip Phase A -

    123456

    9101112131415161718192021222324

    PIN

    Digital Signal ProcessorInput OutputBoard

    DSPIO211

    COLD LOAD

    BLOCKING

    Signal inputs

    DIST REC

    TRIP C

    TRIP B

    TRIP A

    IN

    --

    +

    SELECTIVITYIN

    --

    +

    IN

    --

    +

    IN

    --

    +

    IN

    --

    +78

    K5

    K4

    DSPIO 211 Wiring

  • Schneider Electric 38- CS&P C264 Hardware Presentation E01

    Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards

    Content

  • Schneider Electric 39- CS&P C264 Hardware Presentation E01

    SWU200 4 TXSWU202 -multimode - 2FX - 4 TX

    Switch Board SWU2xx

  • Schneider Electric 40- CS&P C264 Hardware Presentation E01

    SWR202 - multimode 2FX -> 4 TX SWR204 - monomode 2FX -> 4 TX

    ! SWR21x is new version able to communicate with Switch Manager software Switch Board SWR2xx

    Good Practice : switch number = end of BCU IP

  • Schneider Electric 41- CS&P C264 Hardware Presentation E01

    SWD202 - multimode 2FX -> 4 TX SWD204 - monomode 2FX -> 4 TX

    ! SWD21x is new version able to communicate with Switch Manager software Switch Board SWD2xx

    Good Practice : switch number = end of BCU IP

  • Schneider Electric 42- CS&P C264 Hardware Presentation E01

    ECU200 / ECU201 Extended Communication Unit for CPU

    ECU200 : converts RS232 -> Fx ST connector Wavelength : 820nm Jumper set : Light On Jumper reset : Light Off

    ECU201 : converts RS232 -> RS4xx Jumper set : RS422 (4 wires) Jumper reset : RS485 (2 wires)

    Communication Module ECU20x