8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
1/12
Auto-Recloser
Configuration
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
2/12
Schneider Electric 2- CS&P – C264 Autorecloser – E01
• Content
Reminder
Configuration
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
3/12
Schneider Electric 3- CS&P – C264 Autorecloser – E01
• Content
Reminder
Configuration
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
4/12
Schneider Electric 4- CS&P – C264 Autorecloser – E01
GOAL :
repair after transient fault
80 % to 90 % of faults to the electrical network are transient
Cycle temporisation :
time that is long enough to allow the fault to be cleared
Autorecloser : what for?
• Generalities
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
5/12
Schneider Electric 5- CS&P – C264 Autorecloser – E01
• Autorecloser Cycles (1)
TRIP 1 CB 1rst CYCLE CB RECLAIM
OPENED DELAY RECLOSED DELAY
1RST1RST1RST1RST
CYCLECYCLECYCLECYCLE
2nd2nd2nd2nd
CYCLECYCLECYCLECYCLE
TRIP 2 CB 2nd CYCLE CB RECLAIM
OPENED DELAY RECLOSED DELAY
3rd3rd3rd3rd
CYCLECYCLECYCLECYCLE
TRIP 3 CB 3rd CYCLE CB RECLAIM
OPENED DELAY RECLOSED DELAY
TRIP 4 CB 4thCYCLE CB RECLAIM
OPENED DELAY RECLOSED DELAY
4th4th4th4th
CYCLECYCLECYCLECYCLE
TRIP CONFIRMATION : 150 ms(not configurable)
1st CYCLE can be 1P / 3P
2nd, 3rd, 4th CYCLE all 3P
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
6/12
Schneider Electric 6- CS&P – C264 Autorecloser – E01
• Autorecloser Cycles (2)
FIRST TRIP MONO
1P (1st PFM)
1P (1st PFM) + 3P (2nd PST)
1P (1st PFM) + 3P (2nd PST) + 3P (3rd PST)
1P (1st PFM) + 3P (2nd PST) + 3P (3rd PST) + 3P (4th PST)
PFM =Period Fast Mono, PST = Period Slow TRI, PFT=Period FAST TRI
FIRST TRIP TRI3P (1st PFT)
3P (1st PFT) + 3P (2nd PST)
3P (1st PFT) + 3P (2nd PST) + 3P (3rd PST)
3P (1st PFT) + 3P (2nd PST) + 3P (3rd PST) + 3P (4th PST)
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
7/12
Schneider Electric 7- CS&P – C264 Autorecloser – E01
• Autorecloser AlgorithmA u t o - r e c l o s e r
o u t o f s e r v i c e
I n S e r v i c e r e q u e s t
A u t o - r e c lo s e r i n
s e r v i c e
T R I P /T R I P _ 1 P_ X
A n a l y si s o f t h e
r e c e iv e d t r i p
1 p h a s e3 p h a se s
A R l o c k e d
C B o p e n
L a u n c h c y c l et i m e r ( f o r f ir s t
s i n g l e - p h a s e c y c l e )
T R IP _ 1 P _
X a l w a y s
T R I
E n d o f
t i m e r
C lo s in g t h e C B
E n d o f 1 5 0 m s ti m e r
A R l o c k e d
T R I
C B c lo s e d
L a u n c h
r e c o v e r i n g t im e r
E n d o f
t im e r
T R I
L a s t c y c l e ?
A R l o ck e d
y e s
n o
W a i t in g C B
o p e n i n g
A R l o c k e d
C B o p en
L a u n c h c y c l e ti m e r
( f o r 3 - p h a s e s c y c l e )
C y c l e n ° = 1
C y c l e n ° = 2
T R I P
a l w a y s s e tE n d o f
t i m e r A R l o c k e d
C lo s in g t h e C B
C B
c l o s e d
C y c l e = c y c l e + 1
L a u n c h
r e c o v e r i n g t im e r
N e wT R I
E n d o f
t i m e r
T R I P
E n d o f 1 5 0 m s
t i m e r
W a i tin g C Bo p e n i n g
A R _ B L O C K I N G
= R E S E T ?
y e s
n o
C B _ H E A L T H Y
= S E T ?
y e s
n o C B _ H E A L T H Y
= S E T ?
n o
y e s
A R _ B L O C K I N G= R E S E T ?
n o
y e s
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
8/12
Schneider Electric 8- CS&P – C264 Autorecloser – E01
• Content
Reminder
Configuration
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
9/12
Schneider Electric 9- CS&P – C264 Autorecloser – E01
• Add / Configure a AR (1)1) Autorecloser can be added at Bay Level .
Built-in function :Autorecloser type 1
2) Autorecloser attributes : General Tab
Functioning mode 1P :1P, 1P-3P, 1P-3P-3P, 1P-3P-3P-3P (CB-1ph)
Functioning mode 3P :
3P, 3P-3P, 3P-3P-3P, 3P-3P-3P-3P (CB-3ph)
Unlocking way :not used / reinitialisation / manual close / both
Fast 3P reclose enable :bypass Synchrocheck during 1st cycle 3P
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
10/12
Schneider Electric 10- CS&P – C264 Autorecloser – E01
• Add / Configure a AR (2)
4) Autorecloser attributes : Cycles and delays Tab
Cycles time
Other timers :
• inhibition
• not used => starts reclaimml timer if alllocking conditions disappear and CB closed(cf. C264_FT). If CB not closed at the end oftimer, AR is locked again.
• manual close => starts reclaimmc timer ifbreaker is closed manually and AR isinhibited during this delay (cf. C264_FT). IfCB not closed at the end of timer, AR is
locked again.
Reclaim timer
3) Unlocking way :• not used = when locking conditions disappear and CB closed • manual close = when operator is closing manually CB • lock/reinit = when LOCK/REINIT SPS or SPC is set
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
11/12
Schneider Electric 11- CS&P – C264 Autorecloser – E01
• AR Sons & Relations (1)1) Autorecloser basic configuration :
MPS AR FAULTYGives reason of AR
Failure
MPS AR STATEGives current step of ARExecution
SPC Force Trip 3Pwhen 1st cycle 1P, force
IED to next trip in 3P
On/off DPSAR is active or not => initial status to be “Set”
Trip 3 phases SPSAcquired SPS giving 3ph. trip status
Hardwired SPS is strongly advised, butcan come from IED or PSL.
Relation with CB
-
8/20/2019 L2-V4-09-C264 AutoRecloser-E-01
12/12
Schneider Electric 12- CS&P – C264 Autorecloser – E01
• AR Sons & Relations (2)2) Autorecloser enhanced configuration :
=> Possible sonsSPS AR BLOCKINGWhen “SET” => AR does not close at end of current cycle hardwired or produced by PSL then wait for 1st cycle
SPS LOCK/REINITSPS giving order to unlock. If active, AR is unlocked.Cannot be configured if SPC LOCK/REINIT exists.
3 Trip phases SPS
Acquired SPS giving Trip status per phase Hardwired SPS is strongly advised
SPC LOCK/REINITSPC giving order to unlock or reinit AR.Cannot be configured if SPS LOCK/REINIT exists.
DPS on/off ctrlDPS giving order to activate/deactivate AR Cannot be configured if DPC on/off ctrl exists
DPC on/off ctrlDPC giving order to activate/deactivate AR Cannot be configured if DPS on/off ctrl exists