    Auto-Recloser

    Configuration

    PCLPCLPCLPCL

    PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2

    CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    2/12

    Schneider Electric 2- CS&P – C264 Autorecloser – E01

    • Content

    Reminder

    Configuration

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    3/12

    Schneider Electric 3- CS&P – C264 Autorecloser – E01

    • Content

    Reminder

    Configuration

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    4/12

    Schneider Electric 4- CS&P – C264 Autorecloser – E01

    GOAL :

    repair after transient fault

    80 % to 90 % of faults to the electrical network are transient

    Cycle temporisation :

    time that is long enough to allow the fault to be cleared

    Autorecloser : what for?

    • Generalities

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    5/12

    Schneider Electric 5- CS&P – C264 Autorecloser – E01

    • Autorecloser Cycles (1)

    TRIP 1 CB 1rst CYCLE CB RECLAIM

    OPENED DELAY RECLOSED DELAY 

    1RST1RST1RST1RST

    CYCLECYCLECYCLECYCLE

    2nd2nd2nd2nd

    CYCLECYCLECYCLECYCLE

    TRIP 2 CB 2nd CYCLE CB RECLAIM

    OPENED DELAY RECLOSED DELAY 

    3rd3rd3rd3rd

    CYCLECYCLECYCLECYCLE

    TRIP 3 CB 3rd CYCLE CB RECLAIM

    OPENED DELAY RECLOSED DELAY 

    TRIP 4 CB 4thCYCLE CB RECLAIM

    OPENED DELAY RECLOSED DELAY 

    4th4th4th4th

    CYCLECYCLECYCLECYCLE

    TRIP CONFIRMATION : 150 ms(not configurable) 

    1st CYCLE can be 1P / 3P 

    2nd, 3rd, 4th CYCLE all 3P 

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    6/12

    Schneider Electric 6- CS&P – C264 Autorecloser – E01

    • Autorecloser Cycles (2)

    FIRST TRIP MONO

    1P (1st PFM)

    1P (1st PFM) + 3P (2nd PST)

    1P (1st PFM) + 3P (2nd PST) + 3P (3rd PST)

    1P (1st PFM) + 3P (2nd PST) + 3P (3rd PST) + 3P (4th PST)

    PFM =Period Fast Mono, PST = Period Slow TRI, PFT=Period FAST TRI 

    FIRST TRIP TRI3P (1st PFT)

    3P (1st PFT) + 3P (2nd PST)

    3P (1st PFT) + 3P (2nd PST) + 3P (3rd PST)

    3P (1st PFT) + 3P (2nd PST) + 3P (3rd PST) + 3P (4th PST)

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    7/12

    Schneider Electric 7- CS&P – C264 Autorecloser – E01

    • Autorecloser AlgorithmA u t o - r e c l o s e r

    o u t o f s e r v i c e

    I n S e r v i c e r e q u e s t

    A u t o - r e c lo s e r i n

    s e r v i c e

    T R I P /T R I P _ 1 P_ X

    A n a l y si s o f t h e

    r e c e iv e d t r i p

    1 p h a s e3 p h a se s

    A R l o c k e d

    C B o p e n

    L a u n c h c y c l et i m e r ( f o r f ir s t

    s i n g l e - p h a s e c y c l e )

    T R IP _ 1 P _

    X a l w a y s

    T R I 

    E n d o f

    t i m e r

    C lo s in g t h e C B

    E n d o f 1 5 0 m s ti m e r

    A R l o c k e d

    T R I

     

    C B c lo s e d

    L a u n c h

    r e c o v e r i n g t im e r

    E n d o f

    t im e r

    T R I 

    L a s t c y c l e ?

    A R l o ck e d

    y e s

    n o

    W a i t in g C B

    o p e n i n g

    A R l o c k e d

    C B o p en

    L a u n c h c y c l e ti m e r

    ( f o r 3 - p h a s e s c y c l e )

    C y c l e n ° = 1

    C y c l e n ° = 2

    T R I P

    a l w a y s s e tE n d o f

    t i m e r A R l o c k e d

    C lo s in g t h e C B

    C B

    c l o s e d

    C y c l e = c y c l e + 1

    L a u n c h

    r e c o v e r i n g t im e r

    N e wT R I

     

    E n d o f

    t i m e r

    T R I P

    E n d o f 1 5 0 m s

    t i m e r

    W a i tin g C Bo p e n i n g

    A R _ B L O C K I N G

    = R E S E T ?

    y e s

    n o

    C B _ H E A L T H Y

    = S E T ?

    y e s

    n o C B _ H E A L T H Y

    = S E T ?

    n o

    y e s

    A R _ B L O C K I N G= R E S E T ?

    n o

    y e s

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    8/12

    Schneider Electric 8- CS&P – C264 Autorecloser – E01

    • Content

    Reminder

    Configuration

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    9/12

    Schneider Electric 9- CS&P – C264 Autorecloser – E01

    • Add / Configure a AR (1)1) Autorecloser can be added at Bay Level .

    Built-in function :Autorecloser type 1

    2) Autorecloser attributes : General Tab

    Functioning mode 1P :1P, 1P-3P, 1P-3P-3P, 1P-3P-3P-3P (CB-1ph) 

    Functioning mode 3P :

    3P, 3P-3P, 3P-3P-3P, 3P-3P-3P-3P (CB-3ph) 

    Unlocking way :not used / reinitialisation / manual close / both 

    Fast 3P reclose enable :bypass Synchrocheck during 1st cycle 3P 

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    10/12

    Schneider Electric 10- CS&P – C264 Autorecloser – E01

    • Add / Configure a AR (2)

    4) Autorecloser attributes : Cycles and delays Tab

    Cycles time

    Other timers :

    • inhibition 

    • not used => starts reclaimml timer if alllocking conditions disappear and CB closed(cf. C264_FT). If CB not closed at the end oftimer, AR is locked again.

    • manual close => starts reclaimmc timer ifbreaker is closed manually and AR isinhibited during this delay (cf. C264_FT). IfCB not closed at the end of timer, AR is

    locked again.

    Reclaim timer

    3) Unlocking way :• not used = when locking conditions disappear and CB closed • manual close = when operator is closing manually CB • lock/reinit = when LOCK/REINIT SPS or SPC is set 

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    11/12

    Schneider Electric 11- CS&P – C264 Autorecloser – E01

    • AR Sons & Relations (1)1) Autorecloser basic configuration :

    MPS AR FAULTYGives reason of AR

    Failure 

    MPS AR STATEGives current step of ARExecution 

    SPC Force Trip 3Pwhen 1st cycle 1P, force

    IED to next trip in 3P 

    On/off DPSAR is active or not => initial status to be “Set” 

    Trip 3 phases SPSAcquired SPS giving 3ph. trip status 

    Hardwired SPS is strongly advised, butcan come from IED or PSL.

    Relation with CB

  • 8/20/2019 L2-V4-09-C264 AutoRecloser-E-01

    12/12

    Schneider Electric 12- CS&P – C264 Autorecloser – E01

    • AR Sons & Relations (2)2) Autorecloser enhanced configuration :

    => Possible sonsSPS AR BLOCKINGWhen “SET” => AR does not close at end of current cycle hardwired or produced by PSL then wait for 1st cycle 

    SPS LOCK/REINITSPS giving order to unlock. If active, AR is unlocked.Cannot be configured if SPC LOCK/REINIT exists.

    3 Trip phases SPS

    Acquired SPS giving Trip status per phase Hardwired SPS is strongly advised 

    SPC LOCK/REINITSPC giving order to unlock or reinit AR.Cannot be configured if SPS LOCK/REINIT exists.

    DPS on/off ctrlDPS giving order to activate/deactivate AR Cannot be configured if DPC on/off ctrl exists 

    DPC on/off ctrlDPC giving order to activate/deactivate AR Cannot be configured if DPS on/off ctrl exists