SRI LANKA TELECOM
TTEECCHHNNIICCAALL
SSPPEECCIIFFIICCAATTIIOONNSS
Surge Protection Devices (SPD)
with Enclosure
-
7/27/2019 L~0742~2013_[2] Specification
2/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 1 of 1
1. Requirement Introduction
Surge Protection Device (SPD) connected in the mains power supply, needed to protect the
electrical and electronic equipment, should be able to withstand maximum of 100 kA per mode
(10/350sec).As per IEC 62305-1, LPL 1 (Lightning Protection Level) maximum expectedlightning current is 200 kA. As explained in IEC 62305,100 kA will be dissipated in earth and
the balance 100 kA will reach the electrical supply lines. Power Line SPDs are to be connected at
the mains incoming panel and in addition Distribution Boards which are more than 15 meters
away from the incoming panel. DBs which is feeding power to critical and sophisticatedelectronic equipment. SPDs must be installed ignoring the cable distance. Suitable SPDs also tobe used in all Telecommunication, Signaling, automation and instrumentation equipment
according to the Zonal concept explained in IEC 62305 for a perfect protection of complete
electronic installations. All SPDs should be tested and ensure performance requirements
according to IEC 61643
2 Scope
-
7/27/2019 L~0742~2013_[2] Specification
3/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 2 of 1
3.1.5. Offered equipment shall be capable of operating and delivering the expected
performances without degrading the specified performances under the
environmental conditions mentioned above.
4. Technical requirement
4.1. Mechanical Construction
4.1.1. The entire surge carrying connections shall be of bolted connections.
4.1.2. The mechanical Dimensions & weight shall be specified in schedule of
requirement.4.1.3. Powder coating shall be applied for the Enclosure.
4.1.4. Enclosure shall be design so that input power cable and output power cable
separate with considerable distance to avoided surge interference to the output.
4.1.5. Plastic Cable glands (Polyamide) shall be provided with the enclosure to fix the
input and output cable. The class of the gland should be IP 67
4 2 Ele t i l S e ifi ti
-
7/27/2019 L~0742~2013_[2] Specification
4/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 3 of 1
5. Design Characteristics
5.1. Option I5.1.1. The design characteristics of the power line protector shall be fully complied &
tested for / with relevant international standards and specifications which is IEC
61643 for providing required protection to sensitive telecommunication
equipment.
5.1.2. The offered protector shall be a modular design.
5.1.3. The Surge protective device shall protect the system for both Common Mode and
Transverse mode Surges, transients coming from Commercial Power lines.Protection modes shall be clearly specified.
5.1.3.1. Line Neutral : Encapsulated/Non-exhausting Spark Gap
5.1.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap
5.1.4. Protector shall Type 1 (Class B ) protector which can be used between LPZ 0 and
LPZ 1 (LPZ-Lightning Protection Zone) specified in international standard IEC
62305-4
5 1 5 Th it f th T 1(Cl B) SPD h ll b
-
7/27/2019 L~0742~2013_[2] Specification
5/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 4 of 1
5.2. Option II
5.2.1. The design characteristics of the power line protector shall be fully complied &
tested for / with relevant international standards and specifications which is IEC61643 for providing required protection to sensitive telecommunication
equipment.
5.2.2. The offered protector shall be a modular design
5.2.3. The Surge protective device shall protect the system for both Common mode and
Transverse mode Surges, transients coming from Commercial Power lines.
Protection modes shall be clearly specified.
5.2.3.1. Line Neutral : MOV with built in thermal fuse5.2.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap
5.2.4. Protector shall Type1+2 (Class B+C ) protector which can be used between LPZ 0
(Lightning Protection Zone) and LPZ 2 specified in international standard IEC
62305-4
5.2.5. The capacity of the Type 1 + 2 (Class B + C) SPD shall be,
5.2.5.1. Impulse current (Iimp) between Line to Neutral shall be 7 kA at 10/350 s
i l
-
7/27/2019 L~0742~2013_[2] Specification
6/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 5 of 1
5.2.11. Provisions shall be made for extension of alarm condition mentioned on clause
5.2.9 to a distant location via potential free contact.
5.3. Option III
5.3.1. The design characteristics of the power line protector shall be fully complied &
tested for / with relevant international standards and specifications which is IEC
61643 for providing required protection to sensitive telecommunication
equipment.
5.3.2. The offered protector shall be a modular design
5.3.3. The Surge protective device shall protect the system for both Common Mode andTransverse mode Surges, transients coming from Commercial Power lines.
Protection modes shall be clearly specified.
5.3.3.1. Line Neutral : MOV with built in thermal fuse
5.3.3.2. Neutral Ground : Encapsulated/Non-exhausting Spark Gap
5.3.4. Protector shall Type 2 (Class C ) protector which can be used between LPZ 1
(Lightning Protection Zone) and LPZ 2 specified in international standard IEC
62305 4
-
7/27/2019 L~0742~2013_[2] Specification
7/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 6 of 1
5.3.10. The offered protector shall not induce fire hazard either in an event of diverting
any power line surges or in an event of sustaining over voltage.
5.3.11. Provisions shall be made for extension of alarm condition mentioned on clause5.3.9 to a distant location via potential free contact.
6. Standards
Offered manufacture or (and) product shall complied to the following standards
6.1. ISO 9001-2008 & ISO 14001 - 2009
6.2. UL listed
6.3. IEC 62305 & 61643EN
7. Installation Materials
The installation materials needed for installation of the protective device shall be supplied
with the protective device.
8. Spare parts
8 1 S li h ll t th l f ll t f f i t f t l t t
-
7/27/2019 L~0742~2013_[2] Specification
8/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 7 of 1
10.3. One set of each above literature (comprehensive technical hand book) should be
provided with the bidding documents, for the evaluation purpose of the Technical
Evaluation Committee.
11. Training
11.1. Supplier shall arrange the local training for technical officers of SLT from foreign or
local qualified trainer.
11.2. Supplier shall provide the details of the resource person for such training along with
the bids.
11.3. The training program shall include11.3.1. IEC 62305
11.3.2. Physics of lightening
11.3.3. Characteristics of protectors and parameters
11.3.4. Protection of telecommunication systems against lightening
11.3.5. EMC: how these effects on systems and possible ways of avoiding damages
11.3.6. Characteristics of offered arresters theoretical data sheets
11.3.7. Correct installation and maintenance methods11 3 8 E thi & I t f th d h i l thi
-
7/27/2019 L~0742~2013_[2] Specification
9/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 8 of 1
Technical Description
Complied(C)/
Not complied(NC) Remarks
1 Requirement Introduction
2 Scope
2.1 This specification covers for Type I, II & III (Class B, C
& D) Surge Protection Devices (SPD). Bidders shall quote
for the tender accordingly for the given specifications /
options only.2.2 Whole unit shall be design as one unit within single metal
/ Self-extinguishing high quality Polycarbonate enclosure
and shall be able to mount to wall without any
modification to the enclosure.
3 Environmental & Operating Conditions
3.1 The equipment shall be constructed in such a manner to
t ti f t il i t i l diti t ith t d
-
7/27/2019 L~0742~2013_[2] Specification
10/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 9 of 1
Technical Description
Complied(C)/
Not complied
(NC)
Remarks
4.1.4 Enclosure shall be design so that input power cable and
output power cable separate with considerable distance to
avoided surge interference to the output.
4.1.5 Plastic Cable glands (Polyamide) shall be provided with
the enclosure to fix the input and output cable. The class
of the gland should be IP 67
4.2 Electrical Specification4.2.1 All component of the panel shall be compatible to the
following characteristics of the main supply.
4.2.1.1 Nominal Voltage: 400V (line to line) 20.0%; 3, 4
wire. TT System
4.2.1.2 Nominal Voltage: 230V (line to Neutral)
4.2.1.3 Frequency: 50Hz 2 Hz.
4 2 1 4 E i ti di t ib ti t i TT t h
-
7/27/2019 L~0742~2013_[2] Specification
11/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 10 of 1
Technical Description
Complied(C)/
Not complied
(NC)
Remarks
be fully complied & tested for / with relevant international
standards and specifications which is IEC 61643 for
providing required protection to sensitive
telecommunication equipment.
5.1.2 The offered protector shall be a modular design.
5.1.3 The Surge protective device shall protect the system for
both Common Mode and Transverse mode Surges,transients coming from Commercial Power lines.
Protection modes shall be clearly specified.
5.1.3.1 Line Neutral :Encapsulated/Non-exhausting Spark Gap
5.1.3.2 Neutral Ground :Encapsulated/Non-exhausting Spark
Gap
5.1.4 Protector shall Type 1 (Class B ) protector which can be
d b t LPZ 0 d LPZ 1 (LPZ Li ht i
-
7/27/2019 L~0742~2013_[2] Specification
12/21
-
7/27/2019 L~0742~2013_[2] Specification
13/21
-
7/27/2019 L~0742~2013_[2] Specification
14/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 13 of 1
Technical Description
Complied(C)/
Not complied
(NC)
Remarks
5.3.3.2 Neutral Ground : Encapsulated/Non-exhausting Spark
Gap
5.3.4 Protector shall Type 2 (Class C ) protector which can be
used between LPZ 1 (Lightning Protection Zone) and LPZ
2 specified in international standard IEC 62305-4
5.3.5 The capacity of the Type 2 (Class C) SPD shall be,
5.3.5.1 Nominal current (In) between Line to Neutral shall be 20kA at 8/20 s
5.3.5.2 Maximum discharge current (Imax)between Line to Neutral
shall be 40 kA at 8/20 s
5.3.5.3 Nominal current (In) between Neutral to Ground shall be
50 kA at 8/20 s
5.3.5.4 Maximum discharge current between Neutral to Ground
h ld b 50 kA t 8/20
-
7/27/2019 L~0742~2013_[2] Specification
15/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 14 of 1
Technical Description
Complied(C)/
Not complied
(NC)
Remarks
6 Standards
6.1 ISO 9001-2008 & ISO 14001 - 2009
6.2 UL listed
6.3 IEC 62305 & 61643EN
7 Installation Materials
8 Spare parts
8.1 Supplier shall guarantee the supply of all types of sparesof equipment for at least ten (10) years from the date of
purchase of equipment.
8.2 List of spares and annual price variation for each spare
part for ten (10) years period shall be provided with the
submission
9 Samples
10 D i lit t h d b k & d t ti
-
7/27/2019 L~0742~2013_[2] Specification
16/21
Clause by Clause compliance sheet
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 15 of 1
Technical Description
Complied(C)/
Not complied
(NC)
Remarks
11.3.3 Characteristics of protectors and parameters
11.3.4 Protection of telecommunication systems against
lightening
11.3.5 EMC: how these effects on systems and possible ways of
avoiding damages
11.3.6 Characteristics of offered arresters theoretical data sheets
11.3.7 Correct installation and maintenance methods
11.3.8 Earthing & Improvements of earth and chemical earthing
11.3.9 Related Surge Protection and earthing standards
11.3.10 Installation Practices of the offered product
11.3.11 Periodical Maintenance Practices of the offered product
11.4 Supplier shall provide the details of the training schedule
and the place within two weeks period after issuing Letter
of Intent (LI)
-
7/27/2019 L~0742~2013_[2] Specification
17/21
Schedule of Requirement
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 15/08/2013Revision No : 02
Date of Revision : 15/08/2013
Page : Page 1 of 1
ITEM DESCRIPTION
NO
1 Manufacture details
1.1 Brand/Trade Name
1.2 Country of Origin
1.3 Country of Manufacture / Assemble
1.4 Name of Manufacturer
1.5 Factory Address
-
7/27/2019 L~0742~2013_[2] Specification
18/21
Drawings
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 18/08/2013Revision No : 02
Date of Revision : 18/08/2013
Page : Page 1 of 1
SPD
1
P
D
2
L
N
F2
F1
Connection dia ram for SPD for 1 hase network
-
7/27/2019 L~0742~2013_[2] Specification
19/21
Drawings
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 18/08/2013
Revision No : 02
Date of Revision : 18/08/2013
Page : Page 2 of 1
IncomingACB/MCCB/SFU
Backupfuse/MPCB/MCBforSurgeArrester
RYB
andN
Busbarorlooping
aftertheincomer
EarthBusbarinthepanel
SurgeArrestertoconnectbetweenLineandNeutral
SPD
toconnectbetweenNeutralandEarth
.
SPD
1
R
Y
B
N
F4 F5 F6
F1
F2
F3
SPD
2
SPD
3
Connection dia ram for SPD for 3 hase 4 wire
-
7/27/2019 L~0742~2013_[2] Specification
20/21
Previous Local Experience
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 18/08/2013
Revi si on No : 02
Date of Revision : 18/08/2013
Page : Page 1 of 1
1
. .
Name & Signature of the Tenderer Date Official Frank
Client Name & address TypeCapacity Qty
Contact person Contact No.Cost of thecontract
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
-
7/27/2019 L~0742~2013_[2] Specification
21/21
Price Schedule
Three Phase Surge Protection Devices (SPD) with Enclosure
No: PACS SPC 706
Issue No : 002
Date of Issue : 18/08/2013
Revi si on No : 02
Date of Revision : 18/08/2013
Page : Page 1 of 1
1
(A) FOR LOCAL SUPPLIERS
Description Qty Unit Price (Rs.)[Excluding Taxes]
Total Cost (Rs.)[Excluding Taxes]
Total VAT(Rs.)
Total OtherTaxes (Rs.)
Grand Total (Rs.)[Including Taxes]
1 Three Phase Surge Protection Devices (SPD)
with Enclosure
2 Others (Please Specify)
(B) FOR FOREIGN SUPPLIERS
Description Qty Country of Origin FOB Unit PriceTotal FOB
Cost
Total
Insurance
Total Freight Total CIF Cost
1 Three Phase Surge Protection Devices (SPD)
with Enclosure
2 Others (Please Specify)
I / We agree to supply, install & commission the above mentioned items as per quoted price to Sri Lanka Telecom as per the
Clause No 32 of General Conditions of tender.
. ..
Name & Signature of the Tenderer Date Official Frank
Note :
Part (A) for local suppliers and Part (B) for foreign suppliers only
All details shall be filled and submitted with the offer. Incomplete offers will be rejected.
All applicable taxes should be clearly indicated in this form.
Any other charges should be clearly included