    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)

    5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points 18

    OPC Client

    1

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.

    1

    3

    RemarksSoftware

    Integration

    7

    Required Points

    1 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    2/40

    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    Integration

    Required Points

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    1 Through OSP/BACnet Connection3

    Total Point List-Through OSP/BACnet connection (cont.) 0

    2 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    3/40

    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    Integration

    Required Points

    FAHU( CAV )

    1 Supply Air Temperature 1

    2 Outside Air Temperature 1

    3 Chilled water supply temperature 1

    4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1

    6 Final Filter Status 1

    7 Pre Filter Status 1

    8 Supply Fan Status 1

    9 Supply fan air flow status 1

    10 Supply Fan Trip 1

    11 Supply Fan Auto / Manual 1

    12 Fresh air Damper Open / Close Feedback 1

    13 Smoke Detector 1

    14 2-Way Cooling Valve Control 1

    15 Supply Fan Start/Stop 1

    16 Fresh air Damper open / close Command 1

    Total per Unit 5 8 1 2

    Total for all Units 5 8 1 2

    Total AHU (CAV) Points

    1

    16

    3 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    4/40

    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    Integration

    Required Points

    AHU( CAV ) with Electric Heater

    1 Space Temperature 0

    2 Return Air Temperature 1

    3 Return Air Humidity 1

    4 Return Air Carbon Dioxide 1

    5 Mixed Air Temperature 1

    6 Supply Air Temperature 1

    7 Outside Air Temperature 1

    8 Chilled water supply temperature 1

    9 Chilled water return temperature 1

    10 2-Way Cooling Valve Position feedback 1

    11 Final Filter Status 1

    12 Pre Filter Status 1

    13 Supply Fan Status 1

    14 Supply fan air flow status 1

    15 Supply Fan Trip 1

    16 Supply Fan Auto / Manual 1

    17 Fresh air Damper Open / Close Feedback 1

    18 Return air Damper Open / Close Feedback 1

    19 Smoke Detector 1

    20 2-Way Cooling Valve Control 1

    21 Supply Fan Start/Stop 1

    22 Fresh air Damper open / close Command 1

    23 Return air Damper open / close Command 1

    24 Electric Heater Status 4

    25 Electric Heater Current Switch 4

    26 Electric Heater Auto / Manual 4

    27 Electric Heater Start / Stop 4

    Total per Unit 9 21 1 7

    Total for all Units 27 63 3 21

    Total AHU (CAV) Points 114

    3

    4 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    5/40

    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    Integration

    Required Points

    Fan Coil Units (FCU)

    1 Return Air Temperature 1

    2 Air Flow Filter Status 1

    3 Supply Fan Status 1

    4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    Total per Unit 1 4 0 2

    Total for all Units 5 20 0 10

    Total Fan Coil Units (FCU) Points

    Exhaust Fans1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 16 0 4

    TOTAL EXHAUST FANS POINTS 20

    35

    4

    5

    5 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    6/40

    Project : ITTC - MOSQUE

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    Integration

    Required Points

    Impulse Fans

    1 Start/Stop Control 0 1 0 0

    2 Contactor Status 1

    3 Air Flow Monitoring 1

    4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1

    Total for all Units 0 30 0 10

    Total Impulse fans points

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points

    3

    1

    40

    10

    6 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    7/40

    Project : ITTC - COMM . STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)

    5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    Software

    Integration

    7

    18

    Item Point DescriptionQty.

    1

    RemarksOPC Client

    1

    Required Points

    3

    BACnet

    Network

    Thermostat

    7 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    8/40

    Project : ITTC - COMM . STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationItem Point DescriptionQty. RemarksOPC Client

    Required Points BACnetNetwork

    Thermostat

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    Through OSP/BACnet Connection13

    0Total Point List-Through OSP/BACnet connection (cont.)

    8 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    9/40

    Project : ITTC - COMM. STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationItem Point DescriptionQty. RemarksOPC Client

    Required Points BACnetNetwork

    Thermostat

    AHU( CAV ) with Electric Heater

    1 Space Temperature 0

    2 Return Air Temperature 1

    3 Return Air Humidity 1

    4 Return Air Carbon Dioxide 1

    5 Mixed Air Temperature 1

    6 Supply Air Temperature 1

    7 Outside Air Temperature 1

    8 Chilled water supply temperature 1

    9 Chilled water return temperature 1

    10 2-Way Cooling Valve Position feedback 1

    11 Final Filter Status 1

    12 Pre Filter Status 1

    13 Supply Fan Status 1

    14 Supply fan air flow status 1

    15 Supply Fan Trip 1

    16 Supply Fan Auto / Manual 1

    17 Fresh air Damper Open / Close Feedback 1

    18 Return air Damper Open / Close Feedback 1

    19 Smoke Detector 1

    20 2-Way Cooling Valve Control 1

    21 Supply Fan Start/Stop 1

    22 Fresh air Damper open / close Command 1

    23 Return air Damper open / close Command 1

    24 Electric Heater Status 4

    25 Electric Heater Current Switch 4

    26 Electric Heater Auto / Manual 4

    27 Electric Heater Start / Stop 4

    Total per Unit 9 21 1 7

    Total for all Units 18 42 2 14

    Total AHU (CAV) Points

    2

    76

    9 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    10/40

    Project : ITTC - COMM. STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationItem Point DescriptionQty. RemarksOPC Client

    Required Points BACnetNetwork

    Thermostat

    FAHU( CAV ) with Exhaust Air Fan

    1 Supply Air Temperature 1

    2 Outside Air Temperature 1

    3 Chilled water supply temperature 1

    4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1

    6 Final Filter Status 1

    7 Pre Filter Status 1

    8 Supply & Exhaust Fan Status 2

    9 Supply & Exhaust fan air flow status 2

    10 Supply & exhaust Fan Trip 2

    11 Supply & Exhaust Fan Auto / Manual 2

    12 Fresh air Damper Open / Close Feedback 1

    13 Exhaust air Damper Open / Close Feedback 1

    14 Smoke Detector 1

    15 2-Way Cooling Valve Control 1

    16 Supply & Exhaust Fan Start/Stop 2

    17 Fresh air Damper open / close Command 1

    18 Exhaust air Damper open / close Command 1

    Total per Unit 5 13 1 4

    Total for all Units 5 13 1 4

    TOTAL AHU (CAV) with Return Fan Points 23

    1

    10 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    11/40

    Project : ITTC - COMM. STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationItem Point DescriptionQty. RemarksOPC Client

    Required Points BACnetNetwork

    Thermostat

    Fan Coil Units (FCU) with Electric Heater

    1 Return Air Temperature 1

    2 Air Flow Filter Status 1

    3 Supply Fan Status 14 Supply Fan Auto / Manual 1

    5 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    8 Electric Heater Status 1

    9 Electric Heater Current Switch 1

    10 Electric Heater Auto / Manual 1

    11 Electric Heater Start / Stop 1

    Total per Unit 1 7 0 3

    Total for all Units 68 476 0 204

    Total Fan Coil Units (FCU) with Electric Heater Points

    Exhaust Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 16 0 4

    TOTAL EXHAUST FANS POINTS

    Pressurization Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Air Flow Status 1

    5 Air Damper Open / Close Feedback 1

    6 Air Damper Open / Close Command 1

    Total per Unit 0 5 0 1

    Total for all Units 0 10 0 2

    Total Pressurization Fans Points

    748

    68

    2

    12

    4

    20

    11 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    12/40

    Project : ITTC - COMM . STORES

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationItem Point DescriptionQty. RemarksOPC Client

    Required Points BACnetNetwork

    Thermostat

    Impulse Fans

    1 Start/Stop Control 0 1 0 0

    2 Contactor Status 1

    3 Air Flow Monitoring 1

    4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1

    Total for all Units 0 24 0 8

    Total Impulse fans points

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points

    3

    1

    32

    8

    12 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    13/40

    Project : ITTC - COMM . CENTER

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)

    5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    3

    7

    18

    1

    1

    OPC ClientRequired Points BACnet

    Network

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    13 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    14/40

    Project : ITTC - COMM. CENTER

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    Required Points BACnetNetwork

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3Total Point List-Through OSP/BACnet connection (cont.)

    3

    0

    1 Through OSP/BACnet Connection

    14 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    15/40

    Project : ITTC - COMM. CENTER

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    Required Points BACnetNetwork

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    AHU( CAV ) with Electric Heater

    1 Space Temperature 0

    2 Return Air Temperature 1

    3 Return Air Humidity 1

    4 Return Air Carbon Dioxide 15 Mixed Air Temperature 1

    6 Supply Air Temperature 1

    7 Outside Air Temperature 1

    8 Chilled water supply temperature 1

    9 Chilled water return temperature 1

    10 2-Way Cooling Valve Position feedback 1

    11 Final Filter Status 1

    12 Pre Filter Status 1

    13 Supply Fan Status 1

    14 Supply fan air flow status 1

    15 Supply Fan Trip 1

    16 Supply Fan Auto / Manual 1

    17 Fresh air Damper Open / Close Feedback 1

    18 Return air Damper Open / Close Feedback 1

    19 Smoke Detector 1

    20 2-Way Cooling Valve Control 1

    21 Supply Fan Start/Stop 1

    22 Fresh air Damper open / close Command 1

    23 Return air Damper open / close Command 1

    24 Electric Heater Status 4

    25 Electric Heater Current Switch 4

    26 Electric Heater Auto / Manual 4

    27 Electric Heater Start / Stop 4

    Total per Unit 9 21 1 7

    Total for all Units 54 126 6 42

    Total AHU (CAV) Points 228

    6

    15 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    16/40

    Project : ITTC - COMM. CENTER

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    Required Points BACnetNetwork

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    FAHU( CAV ) with Exhaust Air Fan

    1 Supply Air Temperature 1

    2 Outside Air Temperature 1

    3 Chilled water supply temperature 1

    4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1

    6 Final Filter Status 1

    7 Pre Filter Status 1

    8 Supply & Exhaust Fan Status 2

    9 Supply & Exhaust fan air flow status 2

    10 Supply & exhaust Fan Trip 2

    11 Supply & Exhaust Fan Auto / Manual 2

    12 Fresh air Damper Open / Close Feedback 1

    13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1

    15 2-Way Cooling Valve Control 1

    16 Supply & Exhaust Fan Start/Stop 2

    17 Fresh air Damper open / close Command 1

    18 Exhaust air Damper open / close Command 1

    Total per Unit 5 13 1 4

    Total for all Units 5 13 1 4

    TOTAL AHU (CAV) with Return Fan Points

    1

    23

    16 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    17/40

    Project : ITTC - COMM. CENTER

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    Required Points BACnetNetwork

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    Fan Coil Units (FCU) with Electric Heater

    1 Return Air Temperature 1

    2 Air Flow Filter Status 1

    3 Supply Fan Status 14 Supply Fan Auto / Manual 1

    5 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    8 Electric Heater Status 1

    9 Electric Heater Current Switch 1

    10 Electric Heater Auto / Manual 1

    11 Electric Heater Start / Stop 1

    Total per Unit 1 7 0 3

    Total for all Units 110 770 0 330

    Total Fan Coil Units (FCU) with Electric Heater Points

    Exhaust Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 48 0 12

    TOTAL EXHAUST FANS POINTS

    Pressurization Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Air Flow Status 1

    5 Air Damper Open / Close Feedback 1

    6 Air Damper Open / Close Command 1

    Total per Unit 0 5 0 1

    Total for all Units 0 10 0 2

    Total Pressurization Fans Points

    110

    12

    60

    1210

    2

    12

    17 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    18/40

    Project : ITTC - COMM . CENTER

    Subject : BMS Input / Output List

    AI DI AO DOOPC Client

    Required Points BACnetNetwork

    Thermostat

    RemarksSoftware

    IntegrationItem Point DescriptionQty.

    Impulse Fans

    1 Start/Stop Control 0 1 0 0

    2 Contactor Status 1

    3 Air Flow Monitoring 1

    4 Motor Fail/Trip 1 Relay Output From BMSTotal per Unit 0 3 0 1

    Total for all Units 0 36 0 12

    Total Impulse fans points

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points

    12

    1

    48

    3

    18 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    19/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    Software

    Integration

    7

    18

    1

    OPC Client

    3

    BACnet

    Network

    Thermostat

    Remarks

    1

    Required PointsItem Point DescriptionQty.

    19 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    20/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    Through OSP/BACnet Connection3

    Total Point List-Through OSP/BACnet connection (cont.)

    1

    0

    20 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    21/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    AHU( CAV ) with Electric Heater & Return Air Fan

    1 Space Temperature 0

    2 Return Air Temperature 1

    3 Return Air Humidity 1

    4 Return Air Carbon Dioxide 15 Mixed Air Temperature 1

    6 Supply Air Temperature 1

    7 Outside Air Temperature 1

    8 Chilled water supply temperature 1

    9 Chilled water return temperature 1

    10 2-Way Cooling Valve Position feedback 1

    11 Final Filter Status 1

    12 Pre Filter Status 1

    13 Supply & Return Fans Status 2

    14 Supply & Return fans air flow status 2

    15 Supply & Return Fans Trip 2

    16 Supply & Return Fans Auto / Manual 2

    17 Fresh air Damper Open / Close Feedback 1

    18 Return air Damper Open / Close Feedback 1

    19 Exhaust air Damper Open / Close Feedback 1

    20 Smoke Detector 1

    21 2-Way Cooling Valve Control 1

    22 Supply & Return Fans Start/Stop 2

    23 Fresh air Damper open / close Command 1

    24 Return air Damper open / close Command 1

    25 Exhaust air Damper open / close Command 1

    26 Electric Heater Status 4

    27 Electric Heater Current Switch 4

    28 Electric Heater Auto / Manual 4

    29 Electric Heater Start / Stop 4

    Total per Unit 9 26 1 9

    Total for all Units 18 52 2 18

    TOTAL AHU (CAV) with Return Fan Points

    2

    90

    21 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    22/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    FAHU( CAV ) with Exhaust Air Fan

    1 Supply Air Temperature 1

    2 Outside Air Temperature 1

    3 Chilled water supply temperature 1

    4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1

    6 Final Filter Status 1

    7 Pre Filter Status 1

    8 Supply & Exhaust Fan Status 2

    9 Supply & Exhaust fan air flow status 2

    10 Supply & exhaust Fan Trip 2

    11 Supply & Exhaust Fan Auto / Manual 2

    12 Fresh air Damper Open / Close Feedback 1

    13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1

    15 2-Way Cooling Valve Control 1

    16 Supply & Exhaust Fan Start/Stop 2

    17 Fresh air Damper open / close Command 1

    18 Exhaust air Damper open / close Command 1

    Total per Unit 5 13 1 4

    Total for all Units 20 52 4 16

    TOTAL AHU (CAV) with Return Fan Points

    4

    92

    22 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    23/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    AHU( VAV )

    1 Return Air Temperature 1

    2 Return Air Humidity 1

    3 Return Air Carbon Dioxide 1

    4 Mixed Air Temperature 15 Supply Air Temperature 1

    6 Supply Duct static pressure 1

    7 Outside Air Temperature 1

    8 2-Way Cooling Valve Position feedback 1

    9 Chilled water supply temperature 1

    10 Chilled water return temperature 1

    11 Supply Fan VFD Feedback 1

    12 Supply Fan status 1

    13 Supply fan air flow status 114 Supply Fan Auto / Manual 1

    15 Supply Fan General Alarm 1

    16 Fresh air Damper Open / Close Feedback 1

    17 Return air Damper Open / Close Feedback 1

    18 Smoke Detector 1

    19 Supply fan VFD control 1

    20 2-Way Cooling Valve Control 1

    21 Supply Fan Start/Stop 1

    22 Final Filter Status 1

    23 Pre Filter Status 1

    24 Fresh air Damper open/close Command 1

    25 Return air Damper Open / Close Command 1

    Total per Unit 11 9 2 3

    Total for all Units 55 45 10 15

    Total AHU (VAV) Points 125

    5

    23 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    24/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    AHU( VAV ) with Return/Exhaust Air Fan

    1 Return Air Temperature 1

    2 Return Air Humidity 1

    3 Return Air Carbon Dioxide 1

    4 Mixed Air Temperature 15 Supply Air Temperature 1

    6 Supply Duct static pressure 1

    7 Outside Air Temperature 1

    8 2-Way Cooling Valve Position feedback 1

    9 Chilled water supply temperature 1

    10 Chilled water return temperature 1

    11 Supply Fan VFD Feedback 1

    12 Supply Fan status 1

    13 Supply fan air flow status 1

    14 Supply Fan Auto / Manual 1

    15 Supply Fan General Alarm 1

    16 Fresh air Damper Open / Close Feedback 1

    17 Return air Damper Open / Close Feedback 1

    18 Smoke Detector 1

    19 Supply fan VFD control 1

    20 2-Way Cooling Valve Control 1

    21 Supply Fan Start/Stop 1

    22 Final Filter Status 1

    23 Pre Filter Status 1

    24 Fresh air Damper open/close Command 1

    25 Return air Damper Open / Close Command 1

    26 Return Fan VFD Feedback 1

    27 Return Fan status 1

    28 Return fan air flow status 1

    29 Return Fan Auto / Manual 1

    30 Return Fan General Alarm 1

    31 Return fan VFD control 1

    32 Return Fan Start/Stop 1

    33 Exhaust air Damper Open / Close Feedback 1

    34 Exhaust air Damper open/close Command 1

    Total per Unit 12 14 3 5

    Total for all Units 12 14 3 5

    Total AHU (VAV) with Return Air Fan Points

    1

    34

    24 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    25/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    Fan Coil Units (FCU)

    1 Return Air Temperature 1

    2 Air Flow Filter Status 1

    3 Supply Fan Status 1

    4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    Total per Unit 1 4 0 2

    Total for all Units 25 100 0 50

    Total Fan Coil Units (FCU) Points

    Fan Coil Units (FCU) with Electric Heater

    1 Return Air Temperature 12 Air Flow Filter Status 1

    3 Supply Fan Status 1

    4 Supply Fan Auto / Manual 1

    5 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    8 Electric Heater Status 1

    9 Electric Heater Current Switch 1

    10 Electric Heater Auto / Manual 1

    11 Electric Heater Start / Stop 1

    Total per Unit 1 7 0 3

    Total for all Units 13 91 0 39

    Total Fan Coil Units (FCU) with Electric Heater Points

    175

    25

    143

    13

    25 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    26/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    VAV Box with Electric Heater

    1 Space Temperature sensor with set point with fan speed selector 1

    Space Temperature Sensor with set point and fan

    speed selector

    2 Damper Actuator modulate 1 0-10v Signal to Damper Actuator

    3 Enable/Disable Stages of Electric Heater 1 Relay Output From BMS

    Total per Unit 1 0 1 1

    Total for all Units 28 0 28 28

    Total VAV Box with Electric Heater points

    Exhaust Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 24 0 6

    TOTAL EXHAUST FANS POINTS

    Pressurization Fans

    1 Fan Status 12 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Air Flow Status 1

    5 Air Damper Open / Close Feedback 1

    6 Air Damper Open / Close Command 1

    Total per Unit 0 5 0 1

    Total for all Units 0 15 0 3

    Total Pressurization Fans Points

    3

    30

    18

    6

    28

    84

    26 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    27/40

    Project : ITTC - SPORTS CLUB

    Subject : BMS Input / Output List

    AI DI AO DO

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    RemarksRequired Points

    Item Point DescriptionQty.

    Impulse Fans

    1 Start/Stop Control 0 1 0 0

    2 Contactor Status 1

    3 Air Flow Monitoring 1

    4 Motor Fail/Trip 1 Relay Output From BMS

    Total per Unit 0 3 0 1

    Total for all Units 0 30 0 10

    Total Impulse fans points

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points

    3

    10

    1

    40

    27 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    28/40

    Project : ITTC - SCHOOL

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    RemarksSoftware

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.

    1

    Required Points

    7

    18

    1

    3

    28 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    29/40

    Project : ITTC - SCHOOL

    Subject : BMS Input / Output List

    AI DI AO DORemarks

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.Required Points

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -

    5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    Through OSP/BACnet Connection13

    Total Point List-Through OSP/BACnet connection (cont.) 0

    29 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    30/40

    Project : ITTC - SCHOOL

    Subject : BMS Input / Output List

    AI DI AO DORemarks

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.Required Points

    FAHU( CAV ) with Exhaust Air Fan

    1 Supply Air Temperature 1

    2 Outside Air Temperature 1

    3 Chilled water supply temperature 1

    4 Chilled water return temperature 15 2-Way Cooling Valve Position feedback 1

    6 Final Filter Status 1

    7 Pre Filter Status 1

    8 Supply & Exhaust Fan Status 2

    9 Supply & Exhaust fan air flow status 2

    10 Supply & exhaust Fan Trip 2

    11 Supply & Exhaust Fan Auto / Manual 2

    12 Fresh air Damper Open / Close Feedback 1

    13 Exhaust air Damper Open / Close Feedback 114 Smoke Detector 1

    15 2-Way Cooling Valve Control 1

    16 Supply & Exhaust Fan Start/Stop 2

    17 Fresh air Damper open / close Command 1

    18 Exhaust air Damper open / close Command 1

    Total per Unit 5 13 1 4

    Total for all Units 5 13 1 4

    TOTAL AHU (CAV) with Return Fan Points

    1

    23

    30 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    31/40

    Project : ITTC - SCHOOL

    Subject : BMS Input / Output List

    AI DI AO DORemarks

    Software

    IntegrationOPC Client

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.Required Points

    Fan Coil Units (FCU)

    1 Return Air Temperature 1

    2 Air Flow Filter Status 1

    3 Supply Fan Status 1

    4 Supply Fan Auto / Manual 15 Supply Fan Air Flow Switch 1

    6 Supply Fan Start / Stop 1

    7 2- Way Control Valve Open / Close Command 1

    Total per Unit 1 4 0 2

    Total for all Units 35 140 0 70

    Total Fan Coil Units (FCU) Points

    Exhaust Fans1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 16 0 4

    TOTAL EXHAUST FANS POINTS

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points 1

    245

    35

    20

    3

    4

    31 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    32/40

    Project : ITTC- ETS ROOM FOR VILLAS

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor

    3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    1

    Required Points

    7

    18

    1

    3

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    32 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    33/40

    Project : ITTC- ETS ROOM FOR VILLAS

    Subject : BMS Input / Output List

    AI DI AO DO

    Required Points BACnetNetwork

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -

    5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -

    14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    3

    0Total Point List-Through OSP/BACnet connection (cont.)

    Through OSP/BACnet Connection1

    33 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    34/40

    Project : ITTC- ETS ROOM FOR VILL AS

    Subject : BMS Input / Output List

    AI DI AO DO

    Required Points BACnetNetwork

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Fan Coil Units (FCU) @ Tenants Area

    1 1 BACnet Network Thermostat

    Total per Unit 0 0 0 0 1

    Total for all Units 1

    Exhaust Air Fans

    1 Fan Status 1

    2 Fan Trip 1

    3 Fan Auto/Manual 1

    4 Fan Start/Stop 1 Relay Output From BMS

    5 Fan Air Flow Status 1

    Total per Unit 0 4 0 1

    Total for all Units 0 4 0 1

    Total Exhaust Air Fans Points

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points

    5

    3

    1

    1

    34 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    35/40

    Project : ITTC - APARTMENT TYPES (C,D,E,F& H) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor 3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 12 12 6 6

    Total Tertiary Chilled Water System points

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.

    1

    2

    RemarksSoftware

    IntegrationOPC Client

    6

    Required Points

    7

    36

    35 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    36/40

    Project : ITTC - APARTMENT TYPES (C,D,E,F&H ) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Required Points

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -

    5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -

    14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 6

    6

    16

    Total Point List-Through OSP/BACnet connection (cont.)

    Through OSP/BACnet Connection

    0

    36 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    37/40

    Project : I TTC - APARTMENT TYPES (C,D,E,F& H) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Required Points

    Fan Coil Units (FCU) @ Tenants Area

    1 1 BACnet Network Thermostat

    Total per Unit 0 0 0 0 1

    Total for all Units 1

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points 1

    3

    37 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    38/40

    Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    Energy transfer Station (ETS)

    1 Chilled Water Meters 1 1 Water Flow Meter

    2 Differential Pressure Transmitter 1 Liquid Differential Pressure Sensor

    3 Motorized Valve (HX) 1 VFC from Valve Limit Switch (valve by others)

    4 By-Pass Motorized Valve 1 VFC from Valve Limit Switch (valve by others)5 Pressure Indicator 1 Liquid Pressure Sensor

    6 Temperature Indicator 1 Immersion Temperature Sensor

    Total per Unit 3 1 3 0

    Total for all Units 3 1 3 0

    Total ETS Points

    Tertiary Chilled Water System

    1 Tertiary Common Chilled Water Supply Temperature 1 Immersion Temperature Sensor

    2 Tertiary commom Chilled Water Return Temperature 1 Immersion Temperature Sensor 3 Tertiary Chilled Water Flow 0 Flow Meter(By Others)

    5 Tertiary Loop Chilled Water Differential Pressure in Loop 1 Liquid Differential Pressure Sensor

    Total per Unit 3

    Tertiary Chilled Water Pump VFD Feedback 1 0-10V From Pump VFD Control Panel

    6 Tertiary Chilled Water Pump Run Status 0 VFC From Pump Control Panel

    7 Tertiary Chilled Water Pump VFD Trip 1 VFC From Pump Control Panel

    8 Tertiary Chilled Water Pump VFD Auto / Manual 1 VFC From Pump Control Panel

    9 Tertiary Chilled Water Pump VFD Control 1 0-10V DC Signal From BMS

    10 Tertiary Chilled Water Pump Enable / Disable 1 Relay Output From BMS

    Total per Unit 1 2 1 1

    Total for all Units 6 6 3 3

    Total Tertiary Chilled Water System points

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty.

    1

    1

    RemarksSoftware

    IntegrationOPC Client

    3

    Required Points

    7

    18

    38 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    39/40

    Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Required Points

    Point List - Through OSP/BACnet connection (cont.)

    1 Frequency Output (in Hz) -

    2 Percent Output -

    3 Speed (in RPM) -

    4 Current (in Amps) -

    5 Torque (in %) -

    6 Power(in %) -

    7 Run Time hours -

    8 Run/Stop Status -

    9 VSD Fault Alarm -

    10 Current Limit(in %) -

    11 Accel Time (in sec) -

    12 Decel Time(in sec) -

    13 VSD speed modulate -

    14 start/stop command -

    Total per Unit 0 0 0 0 1

    Total for all Units 0 0 0 0 3

    3

    13

    Total Point List-Through OSP/BACnet connection (cont.)

    Through OSP/BACnet Connection

    0

    39 of 40

  • 7/27/2019 Itcc Bms Io Hvac

    40/40

    Project : ITTC - APARTMENT TYPES (A&B) ETS ROOM

    Subject : BMS Input / Output List

    AI DI AO DO

    BACnet

    Network

    Thermostat

    Item Point DescriptionQty. RemarksSoftware

    IntegrationOPC Client

    Required Points

    Fan Coil Units (FCU) @ Tenants Area

    1 1 BACnet Network Thermostat

    Total per Unit 0 0 0 0 1

    Total for all Units 1

    Closed Expansion Tanks

    1 1 Tank Pressure 3 Air Pressure Sensor

    Total per Unit 3 0 0 0

    Total for all Units 3 0 0 0

    Total Closed Expansion Tanks Points

    Air Separator

    1 1 Pressure 1 Air Pressure Sensor

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Air Separator Points 1