IMAX XTRA EL1090kW
•Simplecontrolinterfacewithlargebacklitdisplay
•Voltfreecontacts
•0-10VBMSoperationstandard
•Robustaluminiumsiliconalloyheatexchanger
•Suitableforsingleormultipleinstallations
•Upto109.8%partloadat30%output
•NOx<40mg/kWh
•NaturalGas
•BuildingRegulationPartL2compliant
FEATURES & BENEFITS
BOILER DIM A DIM B DIM C
1090 1674 1567 1685
Thefollowingminimumclearancesmustbemaintainedforoperationandservicing:
TheImaxXtraELrangeofcondensingboilersisavailablein10modelswithoutputsfrom320to1240kW.Suitableforfloorstandingapplicationsineithersingleormultipleinstallations.
All dimensions in mm
A
B
C
DIMENSIONS & CLEARANCES
TOP:700mm
RIGHT SIDE:700mm
FRONT:700mm
LEFT SIDE: 700mm
REAR: 1000mm†
†Frombackofboiler
A
B
C
TECHNICAL SPECIFICATIONSIMAX XTRA EL 1090kW
W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060
GET A QUOTE
*2yearwarrantysubjecttoTermsandConditions.2yearspartsandlabourwarrantyavailablesubjecttobeingcommissionedbyIdealBoilers.
DryWeight KG 1066
BoilerDimensions mm 1567(H)x1674(W)x1685(D)
BoilerClearances mm Front:700LeftSide:700RightSide:700Top:700Rear:1000
SeasonalEfficiency(BuildingRegsL2) % 96.9
Min/MaxGaspressure(NatGas) mbar 15-20
Fuel (TypeG20) NaturalGas
FuelConsumption(NatGas) m³/h 109.8
FlameProtection Ionisation
Ignition Spark
BoilerOutput(Mean70°C) kW 201.4-1017.2
BoilerOutput(Mean40°C) kW 226-1105.4
BoilerInput(Grosscv) kW 1152
GasInletSize 2xG2”
NOxRating/emissionsat0%O2
mg/kWh Class6(38.7)
HydraulicResistance(11°C∆T) mbar 320
HydraulicResistance(20°C∆T) mbar 97.65
NominalFlowRate(11°C∆T) l/s 23.7
NominalFlowRate(20°C∆T) l/s 13
MinFlowRate(20°C∆T)(MAXMOD) l/s 2.6
MinFlowTemperature °C 30
MaxFlowTemperature °C 90
MinWorkingPressure bar 1
MaxWorkingPressure bar 6
MaxStaticHeadOfWater metres 61
CondensateConnection mm 21.5x2
HighLimitSetPoint °C 100flow,100return105H/Ex
Flow&ReturnSize 2xG3”
WaterContent litres 130.6
FlueSize mm 350
FlueGasVolume m³/h 1609.4
Min-MaxFlueGasTemperature80/60 °C 50-63
MaxFlueResistance Pa 100
ElectricalSupply 230/240V50Hz1Ph
Current(MaxNoPump) amp 2x2.71
PowerConsumption watt 1250
ModulatingInput V/dc 0-10V
FuseRating amp 2x7
ControlsVoltage V 24or240
InsulationClassIP IP20
On/Off0-10VDC Yes
OpenTherm Yes
HighLimitProtection Yes
LowWaterProtection Yes
VoltFreeCommonAlarm Yes
BoilerRunIndication Yes
ModulatingSequencerKit,includingDHWTankKit,PlantRoomSensorKit,6ZoneExpansionKit
Yes
ProgrammableRoomThermostatKits Yes
OutsideSensorKit Yes
DHWTankSensorKit Yes
SafetyInterlockKit Yes
BACNetGatewayKit Yes
LONWorksGatewayKit Yes
MODBusGatewayKit Yes
RemoteAccessKit Yes
SealedSystemServicesFlowManifoldKit Yes
InletAirFilterKit Yes
CondensatePumpKit Yes
RoomSealedAirDuctKit Yes
HeaderKit(flow/return) Yes
HeaderKit(gas) Yes
HeaderKit(air) Yes
GENERAL FLUE/AIR INLET
ELECTRICAL
CONTROL OPERATION
OPTIONAL EXTRAS
BURNER PRE MIX
HYDRAULICS
SUGGESTED ENGINEERING SPECIFICATIONIMAX XTRA EL 1090kW
Pleasenotethattheaboveinformationiscorrectattimeofpublication.IdealCommercialHeatingLimitedhasapolicyofcontinuousdevelopmentandthereforereservestherighttoalterspecificationswithoutpriornotification. 211328
OVERVIEW
Theboilersmustbefullyautomaticallycontrolled,floorstanding,fanned,super-efficientcondensingappliancesutilisinganaluminiumsiliconalloyheatexchangerandbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.
CONTROLS
ThecondensingboilersmusthaveconnectivityforallcommontypesofBMSintegrationincluding0-10v,voltfreeandOpenThermconnections.AdditionalmodulesmaybeusedforBACnet,LONWorksandMODBusgateways.WherenoBMSispresentamodulatingsequencermustbeavailable.
Theboilermustbefullymodulatingwitha5:1turndownratioandincludecontrolfeaturesenablingsetpointadjustment,heatingcircuitcontrolofoneconstanttemperatureandoneDHWcircuitor2constanttemperaturecircuits,andsafetylockoutparametersincludingfaultdiagnosisforbothboilerandexternalcomponentssuchassensorsorpumps.
Boilercapabilitiesmustinclude,withtheuseofexternalcomponents,frostprotection,weatherorroomcompensationandsystempumpcontrol.
FLUE
ThecondensingboilersmustbesuitableforusewitharoomsealedflueoropenflueapplicationsincludingC13,C33andB23classifications.Theflueoutletandairinletmustbesituatedattherearoftheboiler.
HYDRAULIC
Thecondensingboilermustbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.Allhydraulicconnectionsincludingflowreturnandcondensatedrainmustbelocatedontherearoftheboiler.Hydraulicconnectionsmustbeuniformacrosstheoutputsavailableintherangetoensureeaseofinstallationandmaintenance.
Theboilermusthaveamaximumoperatingpressureof6barandbesuitableforheatingandindirecthotwatersystems.
DIMENSIONS
Thecondensingboilermustfitwithinmaximumpermittedfloorspaceof1.41m²(320–620kWmodels)or2.82m²(715–1240kWmodels).
MOUNTING / POSITIONING
Thecondensingboilerswillbefloorstanding.
EFFICIENCY
Thecondensingboilersarecapableofhighseasonalefficiencieswithaminimumrequirementof96.8%andlowNOxemissionsnogreaterthan38.7mg/kWH.
APPROVALS
TheboilersmustbetestedandcertifiedbyBSItoEN15502forusewithNaturalGas.
BoilersarecertifiedtomeettherequirementsoftheECGasApplianceDirective,BoilerEfficiencyDirective,EMCandLowVoltageDirective.
ThemanufacturermustbeISO9001accredited.
SPECIFICATION
Theboilerwillbecapableofflowratesforcommonsystemsusing11°Cto20°Ctemperaturedifferentials.
SOURCING
ThecondensingboilermustbemanufacturedorfinallyassembledintheUnitedKingdom.
WARRANTY
Theboilermustbeavailablewitha2yearwarranty.