HVX 12-17.5-24kV User Guide

48
HVX 12-17.5-24kV Embedded pole vacuum circuit-breaker Medium Voltage Switching Device Technical Instruction NO.AVXN00726-02-02 2011/08

description

Schneider MV SWGR Manual

Transcript of HVX 12-17.5-24kV User Guide

Page 1: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

Medium Voltage Switching Device

Technical Instruction

NO.AVXN00726-02-022011/08

Page 2: HVX 12-17.5-24kV User Guide

Global specialist in energy management, Schneider Electric is the world's 100 countries and provide total solutions, including in energy and infrastructure, industrial processes, building automation and data center networks, as is the world leader in residential applications has a strong Market power. Committed to providing customers safe, reliable, efficient energy, Schneider Electric in 2009 to 15.8 billion euros in sales, with more than 100,000 employees. Schneider Electric to help you - make the best use of its efficiency, enjoy the energy!

In 1987, Schneider Electric was established in the first joint venture plant in Tianjin Merlin Gerin, the circuit breaker technology to China, to replace the traditional fuse, making China the safety of users of electricity has greatly increased, and the establishment of standards for the circuit breaker has made outstanding Contribution. Early 90s, winning odd brand of Schneider Electric's first switch panel into China, the Chinese ended the era of using the light cord switch.

Schneider Electric's strong support for the high investment in China's economic construction and to provide Chinese customers with advanced technical and product support and improve Technical services, the low-voltage electrical appliances, converter, contacts and other industrial products, extensive use of economic construction in China, promoting China's industrial Of the process.

Currently, Schneider Electric China had established 77 offices, 26 factories,6 logistics centers, 1 learning institute, 3 R & D center, 1 laboratory, 500 distributors and sales network all over the country. Schneider Electric China has nearly 22,000 employees. By working with partners and the cooperation of a large number of dealers, Schneider Electric China has created tens of thousands of jobs.

With its deep understanding of the five markets, the careful care of corporate clients, as well as in the field of energy management experience, Schneider Electric from a good supplier of products and equipment have grown to a total solution provider. This year, the first integration of Schneider Electric in construction of buildings, IT, security, power and industrial processes and equipment, and other five major areas of expertise and experience, its high quality products and solutions integrated in a unified framework, through the standard Interface for various industries to provide an open, transparent,energy saving and efficient Energy management platform for enterprise customers to save up to

30% of investment costs and operational costs.

Schneider Electric Energy Efficiency Management Platform

Schneider Electric in China

施耐德电气

善用其效 尽享其能

Page 3: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker Content

1

1 Regulations and Provisions ..............................2

1.1 Technical Instruction .........................................21.2 Terms and symbols used ......................................2

1.3 Use condition .............................................3

1.4 Applied standards ..........................................3

1.5 Safety provisions ...........................................4

1.6 Disposal after the end of service life ..............................4

2 Technical data ..........................................5

2.1 Type designation ...........................................5 2.2 Technical data .............................................6 2.3 Control and operating devices ..................................6

3 Variants ................................................9

4 Delivery, storage and transport ......................... 10

4.1 Delivery ............................................... 10 4.2 Storage ............................................... 11 4.3 Transport .............................................. 11

5 Assembly ............................................. 12

5.1 Instructions for assembly .................................... 12 5.2 HVX-E Mechanical assembly with panel .......................... 13 5.3 Connecting the control lines.................................. 13

6 Commissioning ....................................... 15

6.1 HVX-E (withdrawable unit) ................................... 15

7 Operation ............................................ 16

7.1 Control elements and operator interface .......................... 16 7.2 Interlocks .............................................. 17 7.3 Actuate withdrawable unit (only HVX-E) .......................... 18 7.4 Charging the energy storing device ............................. 18 7.5 Switching operations....................................... 19

8 Servicing ............................................. 20

8.1 Servicing schedule ........................................ 20 8.2 Safety provisions ......................................... 20 8.3 Cleaning insulating components ............................... 21 8.4 Corrosion protection ....................................... 21 8.5 Avoid condensation ....................................... 22 8.6 Lubrication instructions ..................................... 22 8.7 Admissible numbers of breaking operations of vacuum chamber .......... 25

9 Annex ............................................... 26

9.1 Accessories ............................................. 26 9.2 Auxiliary products ........................................ 26 9.3 Screw fastenings ......................................... 26 9.4 Treatment of firmly screw-connected contact surfaces ................ 27

10 Drawing.. ........................................... 28

10.1 Outline ............................................... 28 10.2 Recommend dimension of HVX-E VCB assembly with panel ............ 34 10.3 Wiring diagram ......................................... 38

Page 4: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

2

1 Regulations and provisions

1.1 Remarks on this Technical Instruction

As our products are subject to continuous

1.2 Terms and symbols used

further development, we reserve the right to changes regarding standards, illustrations and technical data.

All dimensions not specified in detail are in millimeters.

This Technical Instruction uses certain terms and symbols. They warn about dangers or provide important information which must be complied with at all costs so as to avoid danger and damage:

WARNING:This symbol warns of dangerous electrical voltage. Contact with voltage may result in fatal injury!

WARNING:This symbol is used for instructions non-compliance with which may result in serious injury, death or serious material damage.

Important:This symbol is used for information which is important to avoid damage.

This Technical Instruction describes transport, assembly, operation, handlingand maintenance of the series HVX vacuum service breakers.

It must be stored so that it is at any time readily accessible for and can be used by persons who are to work on the switchgear.

When re-selling the circuit-breaker or the switchgear with circuit-breaker,make sure that this Technical Instruction is transmitted as well.

The following additional documentsmust be observed for this circuit

breaker:

● Purchase agreement containing the stipulations on the specific equipment of the

circuit-breaker and the legal details.

● Project notes regarding the HVX circuit breaker

● For assembly and operation of the circuit-breaker, the operating manual of the

switchgear in which it is operated must be complied with.

Page 5: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

3

1 Regulations and provisions

1.3 Use in line with the intended purpose

1.4 Application standards

IMPORTANT:

Disclaimer of liability

The HVX vacuum circuit-breaker is intended exclusively as a switching unit in air-

insulated medium-voltage switchgear. It may only be used in the scope of the specified

standards and the switchgear-specific technical data. Any other use constitutes

improper use and may result in dangers and damage.

Operating reliability and service life depend on correct operation.

The manufacturer shall not be held responsible for damage which

occurs if:

● Instructions in this Technical Instruction are not complied with,

● The circuit-breaker is not opera¬ted according to its intended use (see above),

● The circuit-breaker is assembled, connected or operated impro¬perly,

● Accessories or spare parts are used which have not been approved by the

manufacturer,

● The circuit-breaker is converted without the manufacturer's approval, or if

inadmissible parts are attached.

● The three-pole FP SF6 gas insulation circuit-breaker:

● corresponds to the requirements for AC switchgear for voltages above 1 kV acc. to

IEC 62271-100;

● complies with Chinese Standard / T 11022-1999 DL / T 402-1999.

Environmental and operating conditions

HVX circuit-breakers may only be operated under normal operating conditions acc. to

IEC 60694.

Operation under conditions deviating from these is only admissible upon consultation

and with the written approval of the manufacturer.

Ambient conditions

Temperature class

"minus 5 indoors"1)

Ambient temperature

min./max

Average value over 24

hours(max)

Max.installation alti-

tude above sea level

1)higher values on request

1000m1)

35˚C1)

-5/40˚C1)

Page 6: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

4

1 Regulations and provisions

1.5 Safety provisions

Applicable standards and regula¬tions:

The work described in this Technical Instruction may only be performed by specialist

electricians who have pro¬ved their experience with the HVX circuit-breaker and the

EN 50110-1 standard.

● The locally applicable accident prevention, operating and work instructions must

be complied with.

● Installation: IEC 61936-1/HD 637 S1

● Operation of electrical equipment: EN 50110-1

Read these instructions carefully be¬fore you work on the circuit-breaker, and perform

the work detailed in it according to the descriptions. Do not perform any work on the

circuit-breaker which is not described in this Technical Instruction.

WARNING:Before starting work on the circuit-breaker, de-energize the system, verify

it for zero voltage and earth the system according to the applicable safety

rules pur¬suant to EN50110-1.

WARNING:Before performing work on the circuit-breaker, switch off the auxiliary

voltage and prevent it from reclosing.

WARNING:There is a risk of injury when working on the drive mechanism. Before

commencing work, re¬lease the energy-storing device by performing the

operating se¬quence OFF-ON-OFF.

1.6 Disposal after the end of service life

A manual on disposal after the end of the service life is available for disposal of the HVX

vacuum circuit breaker.

Disposal at the end of the service life is performed as a service by the Service Center at

the manufacturer's which is subject to a fee.

Page 7: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

5

2 Technical data

2.1 Type designationThe type designation on the rating plate (Fig. 2.1) specifies essential technical data. The

type designation is broken down in this example.

Fig. 2.1

Example of rating plate

1 Type designation

2 Serial numbers

3 Year of construction

4 Technical data

Phase spacing(mm)

Installation: E is withdrawable, F is Fixed

Rated current(A)

Rated short-circuit breaking current(kA)

Rated voltage(kV)

Basic type

HVX

Type HVX12-31-12E210 NO. 10-00272/02/01

Ur 12 kV

1 2

4

3

Fr 50 HzIr 1250 A

0-0.3s-CO-3min-CO

GB1984-2003 Date:2010.07IEC62271-100/2008

Up 75 kV Motor 220AC/DCUOp 220 VDC

Isc 31.5 kA tk 4 s Ic 25 A

Schneider Electric Huadian Switchgear Xiamen CO., Ltd

Page 8: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

6

The drive mechanism is designed on principle for manual charging of the energy storing device (closing spring).

The drive can be equipped with additional operating and control devices.

● for charging the energy-storing device (spiral spring)

● 3 each max.

Closing release

● 1 each

Blocking coil

● Blocking coils prevent the circuit breaker from being closed and opened via the push-buttons "ON" or "OFF", as

well as manual actuation of the withdraw able unit.

● If the rated auxiliary voltage has fallen or is shut off, all blocking coils are in "blocked" position.

Push switches ● are snap-action switches on the drive and are installed depending on the customized design.

2.2 Technical data

2.3 Control and operating devices

2.4 Component fitting options:

Motor

Opening release

Under voltage release ● 1 each

2 Technical data

Rated voltage [kV]1 12 17.5 24

Rated lightning impulse

withstand voltage[kV] 75

42

630,1250,1600

2000,2500,3150,4000*

25,31.5,10,50

25,31.5,40,50 25,31.5,40,50

25,31.5,40,50 25,31.5,5.5,40

25,31.5,40

505050

630,1250,1600

2000,2500,3150,4000*

630,1250,1600,2000,

2500,3150*,4000*

38 65

95 125

[kV]

[kA]

[kA]

[Hz]

[A]Rated current lr

Rated short-circuit

breaking current

Rated frequency fr

Rated short-time current

lk/4s

Rated power frequency

withstand voltage Ud

Page 9: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

7

Technical data, auxiliary switch

Power consumption, solenoids and motor

Operating times*

Information about the power consumption of solenoids and the motor is available from the manufacturer. The auxiliary voltage data is

required to this effect.

*Rated frequency according to specification on rating plate (50/60 Hz)

2 Technical data

-

-

Rated auxiliary voltage

Switching capacity [A] 10 3,8 2 10

[A] 15

[ms] 10 20

250A/3s

Time factor T=L/R

Rated short-time current

Rated continuous current

[V]

DC[V]

≤48 125 220 120 230

AC [V]

solenoids/motor

Closing release

Minimum command time "OFF" el.tripping [ms] 20

[ms] 20

[s] ≤12

Minimum command time "ON" el.tripping

Motor charging time

≤250

Opening release ≤250

Undervoltage release approx.12

approx.100Motor for energy-storage device

power consumption[W]

DC[W] AC 50/60 Hz[VA]

Times for solenoids and motor

Page 10: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

8

Auxiliary switches

Anti-pumping relay

Operating counter

Auxiliary switches are always actuated directly by the switch shaft via an intermediate

linkage. Their position always corresponds to that of the main contacts. As standard,

the circuit-breaker is equipped with two auxiliary switches with 8 contact elements

each.

The switching functions have been set in the factory according to the wiring diagram.

If an ON and OFF command is

simultaneously and permanently present at the circuit-breaker, the latter returns to its

initial position after closing. It remains in this initial position until the ON command is

issued anew. This prevents continuous closing

and opening ("pumping").

● The operating counter indicates the number of switching operations.

2 Technical data

Page 11: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

9

12 kV≤U≤24 kV

1250 A≤I≤3150 A

25 kA≤Isc≤50 kA

3 Variants

1 Conductor bar terminal /moving contact

2 Circuit-breaker poles

3 Rating plate

4 Operator interface

5 Secondary terminal

6 Drive housing

7 Rollers

8 Withdrawable unit

9 Insertion opening for crank to move the circuit-

eaker into its disconnected/service position /

manually

10"IP" protection sheet

11 Shutter rail

12 Secondary terminal locking rail

12&17.5kV

24kV

Fig. 3.1

Vacuum circuit-breaker HVX-E - withdraw able unit with secondary terminal

HVX model for the following technical data (Fig. 3.1):

Page 12: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

4.1 Delivery

10

4 Delivery, storage and transport

● Handle shipping units carefully when unloading and unpacking them.

● Shipping units must be unpacked immediately after receipt. Any damage occurred

in transit must be recorded and reported immediately to the manufacturer.

● On delivery, the consignment must be checked for completeness.

● The supplier must be notified in writing about any discrepancies.

Fig.4.1

shipping unit

Page 13: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

4.2 Storage

11

Storage unit should not be shipping unit.Circuit breaker storage with transportation of

packaging that appears the question belongs to the consignee's responsibility.

Guide values without packaging

● Only transport the circuit-breaker within its shipping unit on a pallet.

4.3 Transport

● Use the hanging holes to maintain the circuit breaker roughly in horizontal position

when hanged.

● No other hanging point allowed.

Transport using a forklift truck:

Transport without pallet:

Weights[kg]

4 Delivery, storage and transport

Type HVX-E withdrawable Unit

Rated

voltage [kV] 12&17.5

≤1600

120 220 180 230 279

≤1250 ≤2000 ≤3150≤3150

24

Rated current[A]

Weights[kg]

Make sure the rope or strap is strong enough to bear the weight of the

circuit- breaker and do not touch the circuit-breaker.

Remove the lifting brackets before entering in cubicle.

WARNING:

WARNING:

Page 14: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

12

5 Assembly

5.1 Instructions for Assembly

● Dimension drawings are made available on request.

● Check technical data on rating plate.

● Check auxiliary voltage of the control and operating devices installed.

● The circuit-breaker is supplied in position "OFF" and with the energy storing device

"released".

Fig. 5.1

Move the circuit-breaker in front of the panel

The energy storing device must not be charged until assembly is finished.

Risk of injuries.

The safety provisions of chapter 1.5 must be observed.

WARNING:

WARNING:

Page 15: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

13

5 Assembly

5.2 HVX-E Mechanical assembly Mounting the transport truck

5.3 Connecting the control lines

A transport truck (optional) is used to rack the circuit-breaker into the switchgear panel (Fig. 5.1). For the design and

method of operation of the transport truck used, please refer to the instructions for the panel in question.

When performing the following assembly steps, observe and comply with the instructions given for the

panel used.

The control lines are connected, depending on design, via control connectors (Fig. 5.2).

The control lines are wired in the circuit-breaker up to the control connector or up to the terminal strip.

Single-wire conductors or strands can be connected

● Place the circuit-breaker on the transport truck rails.

● Lock the circuit-breaker on the transport truck.

○ Make sure that the lifting brackets are removed.

○ Grease the disconnecting fingers (fig. 8.3).

● Couple the transport truck to the panel.

● Unlock the circuit-breaker from the transport truck.

● Push the circuit-breaker into the panel until it is engaged in the interlock rocker.

● Release the transport truck from the panel.

● to terminal strip up to 2.5 mm2

● in control connector up to 1.5mm2

Placing circuit-breaker on transport truck and racking it into the switchgear

IMPORTANT:

Fig. 5.2

Control connector 1 Insert control connector

Page 16: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

14

Terminal with control connector

Connection to terminal strip

IMPORTANT:

Push the control connector onto the pin right-angle plug-and socket connector of the cubicle and lock it(Fig. 5.9).

Remove the cover plate.

Connect external control lines via the terminal strip.

The specific circuit diagram valid for the unit in question has been enclosed with each circuit-breaker. If additional

control lines are placed in the drive casing, leave a sufficient distance from the movable parts of the drive.

After connecting the external control line, mount the cover plate.

Comply with the Tightening torques specified for crew fastening (refer to Annex).

5 Assembly

Page 17: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

15

Perform functional tests:

6.1 HVX-E (withdrawable unit)

IMPORTANT:

IMPORTANT:

IMPORTANT:

Observe the operating and locking conditions (Chapter 7).

The energy storing device of motorized circuit-breakers is charged

automatically once the auxiliary voltage is applied.

Under voltage releases / blocking coils (optional) enable switching tests

only to be performed with the auxiliary voltage applied.

6 Commissioning

● Check circuit-breaker for external damage.

● Make sure that there are no external parts in the circuit-breaker

compartment.

● Check surface of insulating components for impurities. If necessary, clean

(see Chapter 8).

● Check whether the transport securing devices have been removed (see

Chapter 5.2).

● Charge energy-storing device using the crank (Fig. 9.1 rep. 2). Check the spring

position indicator.

● Switch circuit-breaker on and off several times by hand. Check position indicator.

● Move the withdrawable unit to its service and disconnected position via the crank

handle (Fig. 9.1 rep. 3).

○ Check mechanical interlocks between the HVX-E and the cell. Check

position indication. ● Check electrical functions of control and operating devices. Apply auxiliary voltage.

Actuate the releases to perform switching operations and check functions / interlocks.

Watch position indicators.

● Racking the circuit-breaker in and out. At the same time, check the position

indicators and the interlocks in the circuit-breaker and with regard to other devices.

Page 18: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

16

7.1 Control elements and operator interface

7 Operation

Fig. 7.1

Operator interface of HVX circuit-breaker

Fig. 7.2

Control elements for the circuit-breaker HVX-E

1 closed door of switchgear panel

2 ON/OFF operating rod

3 Spring charging crank for spring operating mechanism

4 Moving crank handle (only in case of HVX-E)

OFF button(rocker"0")orpushbutton"0"

ON button(rocker"1")orpushbutton"1"

Rating pale

Operations counter

posit ion indicator of circuit-breaker

posit ion indicator of closing spring

I n s e r t i o n o p e n i n g f o r charging the closing spring

Page 19: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

17

Position indicators on circuit-breaker and possible operating sequences

Mechanical interlocks

Electrical interlocks

WARNING:

7.2 Interlocks(where applicable)

C = Switching ON O = Switching OFF

The HVX switch features basic interlocks to prevent operating errors.

have been designed according to the circuit diagram.

You must be familiar with these interlocks before operating the circuit-breaker

7 Operation

Item

1 released OFF none

charged OFF c-o

released ON o

charged ON o-c-o

2

3

4

Position indicatorEnergy-storing device(closing spring)

Position indicatorON/OFFSwitch position

Position operatingsequence(mechanical)

Interlock

Between the withdraw unit and

earthing switch

The withdrawable unit cannot be racked in while the

earthing switch of the swit¬chgear panel is in "ON"

position

Insert the crank handle, it can’t be twirled after 1/

2 circle in clockwise.

Insert the crank handle, it can’t be twirled after 1/

2 circle in clockwise/ anticlockwise.

The circuit-breaker cannot be swit¬ched on by

manual operation or power-driven.

Ccrank handle of earthing switch can’t operate

while Operating hole of earthing switch is close.

Do not apply force!

The earthing switch cannot be switched on as soon as

the withdrawable unit has left its disconnected position

The withdrawable unit cannot be racked in or out while

the circuit-breaker is switched on

The circuit-breaker cannot be switched on unless

- the withdrawable unit is completely in its disconnected

or service position

Between the withdrawable unit and

the operating state of the circuit-

breaker

Function of interlock Method of operation of interlock

Page 20: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

18

7.3 Actuate withdrawable unit (only HVX-E)

○ Insert crank handle (Fig. 7.3) and move it clockwise to its stop or until blocking; the circuit-breaker is

racked into its service position. Observe the position indicator on the switchgear panel.

○ Insert crank handle (Fig. 7.3) and move it counter-clockwise to its stop; the circuit-breaker is racked

into its disconnected position.

○ Observe the position indicator on the switchgear panel.

○ Remove crank handle.

○ Remove crank handle.

Initial situation: ● Circuit-breaker OFF

● Earthing switch OFF

Initial situation: ● Circuit-breaker OFF

Move circuit-breaker from disconnected into service position by hand:

Move circuit-breaker from service into disconnected position by hand:

7 Operation

Fig. 7.3

Crank handle to rack the circuit-breaker in and out

Fig. 7.4

Charge the energy storing device

IMPORTANT:

Observe interlock conditions(see chapter 7.2).

Page 21: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

19

● Move circuit-breaker in "ready-foreclosing" position.

○ Insert crank into opening for tensioning the energy storing device (Fig. 7.4)

○ Charge the spiral spring using the spring charging crank. As soon as the spiral spring is charged, the

spring charging mechanism is decoupled and the position indicator signals "charged":

ˉ If the motor starts during this process, this does not constitute a risk.

○ Remove crank. The circuit-breaker is ready for closing (Table, Chapter 7.1, item 2).

● Push button "ON" - or actuate closing release electrically.

● The position indicator shows the switch position "ON" (Table, Chapter 7.1, item 3).

● The position of the auxiliary switch has changed. The energy storing device can be charged

immediately after switching ON (by hand or by motor). If voltage is applied to the motor, charging is

performed automatically.

● The position indicator shows the energy storing device position "charged" (Table, Chapter 7.1, item 4).

● Push button "OFF" - or switch off via opening release, under voltage release or secondary coil.

● The position indicator shows the switch position "OFF" (Table, Chapter 7.1, item 1 or2).

● The position of the auxiliary switch has changed.

7.4 Charging the energy storing device

Manually

7 Operation

Via motor

Closing (ON)

Opening (OFF)

7.5 Switching operations

The energy storing device of motorized circuit-breakers is charged automatically as soon as the auxiliary voltage is

applied.

Page 22: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

8 Servicing

8.1 Servicing schedule

8.2 Safety provisions

20

Series HVX vacuum circuit-breakers require regular inspections. The intervals depend on the strain to which the

switches are subject during operation, and on the operating conditions.

In case of frequent condensation or air pollution (dust, smoke or corrosive gases), the maintenance intervals must be

adapted to the actual conditions.

The circuit-breaker operating company is responsible for complying with the specified maintenance

intervals and for performing maintenance according to the actual operating and ambient conditions.

In case of queries or ambiguities, please contact the manufacturer.

The safety provisions of Chapter 1.5 must be observed.

The circuit-breaker must not be disassembled for maintenance work (see Disclaimer of liability,section

1.3).

Only specialist electricians certified by the manufacturer for maintenance work regarding series HVX vacuum circuit-

breakers and who have the

required knowledge regarding operation of medium-voltage switchgear are permitted to perform maintenance and

cleaning work.

IMPORTANT:

WARNING:

Safety provisions

On principle, the 5 safety rules applicable for electrical engineering must be complied with

before maintenance work on the circuit-breaker is started:

Maintenance intervals(ambient condi-

tions according to IEC 60 694)

Every 4 years

After 20 years

Once the summation current limit has

been reached(refer to Chapter 8.7)Replace circuit-breaker pole Manufacturer's Service Center

● Check for contamination/condensa-tion and damage

● if necessary, clean circuit-breaker(see sect ion 8.3)and perform seve-ral switching tests

● Clean,grease circuit-breaker(see chapter 8.3 and 8.6)and perform several switching tests

● Cheak releases and blocking coilsfor proper working ordeer

Staff qualified accordingly for

the work to be done

Maintenance work Q u a l i f i c a t i o n / p o s i t i o n

perfor-ming the work

Page 23: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

8 Servicing

8.3 Cleaning insulatingComponents

8.4 Corrosion protection

21

● Isolate switchgear from power Supply

● Prevent it from reclosing

● Verify it for zero voltage

● Earth and short-circuit it

● Cover or bar off adjacent live components.

Switch off the auxiliary voltage for the circuit-breaker drive and secure it against reclosing.

Release the energy-storing device by performing the corresponding operating sequence on the circuit-breaker. ON - OFF - ON(see Chapter 7)

Use a dry cleaning cloth for slight soiling:

Use cleaning agents for severe soiling:

WARNING:

These rules apply for the upper and lower circuit-breaker terminals alike.

To ensure the specified insulating level, the insulating components must be clean.

On principle, general cleanliness of the circuit-breaker or of its external parts should be

ensured.

The use of other cleaning agents is not admissible.

Clean by means of a dry, lint-free cloth. Depending on dirt collected, replace cloth as

often as necessary.

Drive mechanisms and covers have a long-term protection against corrosion.

Any damage to the paint, scratches and other damage must be repaired immediately

to avoid corrosion.

Contact the manufacturer's Service Center.

Cleaning agent, 1 liter can (see Chapter 9.2)

● Wear protective gloves ● Use cleaning agent according to manufacturer's instructions ● Soak the cloth thoroughly and wipe the insulating components. Keep duration of

exposure as short as possible. ● Expose the cleaned surface to the air for at least two hours.

Page 24: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

8.5 Avoid Condensation

8.6 Lubrication instructions

Preparations

Lubricants

WARNING:

IMPORTANT:

Lubrication procedure

WARNING:

To ensure the specified insulating level, the circuit-breaker - especially its insulating

components - must not be

exposed to condensation.

Measures to take in case of condensation:

● If condensation of the circuit breaker is detected, the switching device

must be cleaned, according to section 8.3.

● Installation or inspection of the appropriate heating. It must provide

a sufficient heating performance to prevent condensation on the circuit-

breaker.

22

8 Servicing

Comply with safety Provisions (Chapter 1.5).

Circuit-breakers and drives must not be disassembled for service and

maintenance work (see Disclaimer of liability, section 1.3).

Only approved Lubricants may be used (section 9.2).

● Clean the points of lubrication (Fig. 8.1 to 8.3) using a lint-free cotton

cloth; in case of serious contamination, use a cleaning agent (see section 8.3).

● Apply a thin coat of lubricant, using e.g. a paintbrush.

ˉ Cryogenic grease

ˉ High-pressure grease

ˉ Contact lubricant Kontasynth

Remove the withdrawable unit from the switchgear cubicle for inspection (see

instructions for the panel concerned).

Remove the cover plate of the circuit-breaker drive.

Page 25: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

Points of lubrication

IMPORTANT:

23

8 Servicing

The following elements must not be lubricated:

● Points of lubrication on the drive (Fig. 8.1):

All metallic surfaces sliding up oneach other, especially cam discs, cogwheels and ratchet levers.

Fig. 8.1

Circuit-breaker drive mechanism

□ High-pressure grease O Cryogenic grease

ˉ Motor

ˉ Electric releases

ˉ Push switches

ˉ Blocking coils

ˉ Auxiliary switches

ˉ Ball bearings

Page 26: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

24

● Spindle of withdrawable unit mechanism(Fig. 8.2, item 1).

● Moving contacts (Fig. 8.3).

8 Servicing

Fig. 8.2

Rack-in mechanism

Fig. 8.3

Moving contacts

∆ Contact lubricant Kontasynth

○ High-pressure grease

1 Spindle

1

Page 27: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

25

Final steps

8.7 Admissible numbers of breaking operations of vacuum chamber

Re-mount the cover plate and insert the circuit-breaker in the panel (see section 5).

Check circuit-breaker according to section 6 "Commissioning".

The diagram defines exclusively the admissible summation current limit. It is a guide as

to whether the vacuum interrupter chambers/pole sections need to be replaced or not.

For the data regarding the rated normal current Ir and the short-circuit breaking

current Isc, please refer to the rating plate (Fig. 8.4).

Ir = Rated (normal) current [A]

Isc = Short-circuit breaking current [kA]

Fig. 8.4

Data for rated normal current Ir

(1) and short-circuit breaking current Isc

(2) on the rating plate

8 Servicing

Type HVX12-31-12E210 NO. 10-00272/02/01

Ur 12 kV

1 2

4

3

Fr 50 HzIr 1250 A

0-0.3s-CO-3min-CO

GB1984-2003 Date:2010.07IEC62271-100/2008

Up 75 kV Motor 220AC/DCUOp 220 VDC

Isc 31.5 kA tk 4 s Ic 25 A

Schneider Electric Huadian Switchgear Xiamen CO., Ltd

Page 28: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

26

9.1 Accessories

9.2 Auxiliary products

9.3 Screw fastenings

Fig. 9.1

Accessories for HVX circuit-breaker

The accessories depend on the panel type used, and must be enquired about if

necessary.

1 ON/OFF operating rod

2 Spring charging crank for spring operating mechanism

3 Moving crank handle (in case of HVX-E only)

4 Lifting bracket (x2)

5 Lifting beam

6 Transport truck (optional)

Only the following auxiliary products may be used, which are available from AREVA.

The use of other auxiliary products is not admissible.

● Screws and bolts: ○ Grade ≥ 8.8

● Nuts: ○ Grade 8.

The following elements must be used for all metal screw couplings:

9 Annex

Designnation

Contact lubricant Kontasynth,0.5kg can S 008167

High-pressure grease,0.3 liter can ST 312-101-001

ST 312-105-001Cryogenic grease,0.3 liter can

Cleaning agent,1 liter can S 008152

Order no.

1 2 3 4

Page 29: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

27

9.4 Treatment of firmly screw-connected contact surfaces

Table 1:

Hex. Bolts and socket-head cap screws

(except slotted screws) and nuts (except self-

locking nuts)

Contact surfaces must be subjected to preliminary treatment before screw-fastening.

ˉ use a lint-free cloth,

ˉ in case of severe contamination: ˉ use detergent.

ˉ use emery cloth (grainsize 100 or finer)

ˉ or use a steelbrush which is only used for copper

ˉ use emery cloth (grainsize 100 or finer)

ˉ or use a steelbrush which is only usedfor aluminium

ˉ remove any existing passivation using a steel brush which is only used for steel.

Clean

Polish to achieve a bright surface:

Table 2:

Screw coupling between switching device

and conductor bar with copper as conductor

material.

9 Annex

Threadsize

Threadsize

Tightening torque[Nm]

Tightening torque[Nm]

min.

7

16

36

63

min.

5.5

15

30

60

M6

M8

M10

M12

M6

M8

M10

M12

max.

9

24

44

77

max.

7.5

19

40

76

Material of contactsurfaces

Copper, silver-plated -

A

-

B

C

Copper

Aluminium,silver-plated

Aluminium

Steel or steel,galvanized

Pre-treat-ment

Immediately after cleaning the material metallically bright, coat it with lubricant KL so that the space between the contact surfaces is completely filled once the screws have been fastened.

Page 30: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

28

10 Drawings

10.1 Outline Embeded pole HVX-F Fixed circuit breaker(12&17.5kV≤1250A≤ 31.5kA)

A Typec B Typec

D

E

P±2

51

480

427.5

406.5

112

217

205

P±2

254

153

55 55

54

103

119

4430

8

3044

40

79

410.5

438.

5

250

389.5

95

53

11

22

11

22

2-M10 H20

4-M10 H25

M12 H25Ø45

A

B

1:1 1:1

630 2531.5

210275

576706

520650520650

576706

210275

2531.5

1250

Rated short

clrclut currentP D E

Rated

current

Page 31: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

HVX-F Fixed circuit breaker (12&17.5kV ≤4000A ≤50 KA)

29

10 Drawings

44 44 3030

119

E

40

103 15

3

254

55 55

5479

51

8

664

720

310

237

53 250

95

389.5

410.5

112

427.5

438.

5

P± 2 P± 2

599

D20

40

40

4-M12

M16

4-M12

15

30

15

30

4-M12

M16

B

1:2

1:2

注1

C向 1:2

A/C

A TypecB Typec

1600 2000

1250 1600 2000

1250 1600 2000

2500 3150 4000*

25 31.5

40 50

25 31.5

40 50

210

275

576

704

520

650

P D ERated

current

Rated short

clrclut current

Page 32: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

HVX-E Draw-out circuit breaker (12&17.5kV≤1250A≤31.5 KA)

30

10 Drawings

A

P±2

E

297

19630 44

54

55

L

13.5

79

51

8

43

628.5

624.5

12

8635

622

523

260

±1.5

205

±1.5

Ø93

13.5

P±2

55

55

146

83

3044

19

296 ±2313 ±2

437

383

370

32025

154

76

C

D

200 0-3 50

4

16

8

Ø35

630 1250 25 31.5

502650

150210

457605

492640

503653

494638

801 836 853 844850275

Rated short

clrclut currentAP C D E E

Rated

current

Page 33: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

31

10 Drawings

HVX-E Draw-out circuit breaker (12&17.5kV≤4000A≤50 KA)

NOTE1:For rated current≤2000A

NOTE2:For rated current≤2500A

NOTE3:Hear sink for rated current≥2500A

NOTE4:For rated current≤2000A

NOTE1:The rated current 4000A is guarantied

with force cooling in panel

A

P±2

16

P±2

16

8.5

55

C

D

E 13.513.5

83

146 19

6

119

297

55 55

5479

51

4430 44 30

43

L

310

280

ØM

ØW

707H

602

606.5

35 86

25 320

370

383

359

293 ±2 296

76

165

200 0

-3 50

4

8

注1

注2

注3

1600 2000

1250 1600 2000

1250 1600 2000

1600 2000

1250 1600 2000

2500 3150 4000*

2500 3150 4000*

1250 1600 2000

2500 3150 4000*

25 31.5

40

50

25 31.5

40

25

31.5 40

50

50

210

210

275

275

275

275

275

582

582

777

777

777

777

777

640

640

836

836

836

836

836

653

653

853

853

853

853

853

638

638

844

844

844

844

844

118

128

118

148

148

128

158

79

79

79

79

109

79

109

691.5

691.5

729.5

729.5

729.5

729.5

729.5

Rated

current

Rated short

clrclut current

650

650

850

850

850

850

850

P A C D E L H M W

Page 34: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawings

HVX-E Draw-out circuit breaker (24kV≤1250A≤31.5 KA)

32

P A C D E L

Rated

current

A

Rated short-circuit

breaking current

kA

PD

mm

Dimension

mm

630 1250 25 31.5

HVX 24 Vacuum circuit breaker Rated Voltage: 24KV Rated short-circuit breaking current: 25KA,31.5KARated current: 630A,1250A

210

275

650

850

606

796

646

836

653

853

648

844

13.5E

A

PP

CD

L

296.

519

5.5

148

82.5

5555

4430

8

3044

51

18

43

306441 ±2

49.5

447

32031

032

5

167

775

+3 0

Ø93

Ø74

76

787

38300

0-3

4 18

50

128-10mm

54.5

8

1195479

Ø35

25383

Page 35: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

33

10 Drawings

HVX 24 Vacuum circuit breaker Rated Voltage: 24KV Rated short-circuit breaking current: 25KA,31.5KARated current: 1600A,2000A ,2500A,3150A*

HVX-E Draw-out circuit breaker (24kV≤3150A≤40 KA)

Note:3150A is guaranted by fored cooling in panel

1)Heat sink for current≥2500A

13.5853

275850

275

844

51

14882

.5 148

195.

529

6.5

3030 4444

8

5555

18

43

815 31

032

5

306

383447

827

ØM

76

167

37025 320

22.5

12

NOTE1

8-10mm

8

54.5

796836

1195479

ØW

300 0-3 50

3849.5

44

431 ±2

Rated current (A) 4000* 3150* 2500 2000 1600

ΦM mm 167 167 135 135 135

ΦW mm 109 109 79 79 79

Page 36: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawings

10.2 Recommend dimensions of HVX-E vacuum circuit breaker assembly with panel

Assemble schematic diagram of 12&17.5kV HVX(≤1250 A ≤31.5kA) and panel(650、800、

1000) Fig.1

Fig.1 Assemble dimensions of HVX-E vacuum circuit breaker and panel(1)

34

Page 37: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

35

10 Drawings

Assemble schematic diagram of 12&17.5kV HVX(≤4000 A ≤50kA) and panel(800、1000) Fig.2

Rated current(A)

Rated short-circuit

breaking current(kA)

Fixed contact(mm)

1250

40、50

φ79 φ109

4000*1600、2000

…50

2500、3150

…50 …50

The rated current 4000A is guarantied with force cooling in panel

Fig.2 Assemble dimensions of HVX-E vacuum circuit breaker and panel(2)

Page 38: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawings

Assemble schematic diagram of 24kV HVX(≤1250 A≤25kA) and panel(800、1000) Fig.3

Fig.3 Assemble dimensions of 24kV HVX-E vacuum circuit breaker and panel (1)

36

Page 39: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

37

10 Drawings

Assemble schematic diagram of 12&17.5kV HVX(≤4000 A≤50kA) and panel(800、1000) Fig.2

Fig.4 Assemble dimensions of 24kV HVX-E vacuum circuit breaker and panel (2)

Page 40: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawings

10.3Wiring diagram

Fixed type

1. This wcircuit diagram (ASX000525-03) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order

ˉ M1 Motor for energy storing device

ˉ S11/12 Auxiliary switch position indicator

ˉ S2 Micro switch for motor control

ˉ S6 Micro switch for blocking magnet

ˉ Y1 Blocking magnet for closing(option)

ˉ F11 1.Auxiliary opening release

ˉ F12 2.Auxiliary opening release(option)

ˉ F2 Auxiliary closing release

ˉ F3 Indirect overcurrent release(option)

ˉ F4 Undervoltage release(option)

ˉ K01 Anti-pumping-relay

38

Drawing number:ASX000525-03

Page 41: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

1. This circuit diagram (ASX000525-04) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order

ˉ M1 Motor for energy storing device

ˉ S11/12 Auxiliary switch position indicator

ˉ S2 Micro switch for motor control

ˉ S6 Micro switch for blocking magnet

ˉ Y1 Blocking magnet for closing(option)

ˉ F11 1.Auxiliary opening release

ˉ F12 2.Auxiliary opening release(option)

ˉ F2 Auxiliary closing release

ˉ F3 Indirect overcurrent release(option)

ˉ F4 Undervoltage release(option)

ˉ K01 Anti-pumping-relay

39

10 Drawings

Fixed type

Drawing number:ASX000525-04

Page 42: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawingshand trolley type

40

1. This circuit diagram (ASX000525-01) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order ˉ M1 Motor for energy storing device ˉ S11/12 Auxiliary switch position indicator ˉ S2 Micro switch for motor control ˉ S6 Micro switch for blocking magnet ˉ Y1 Blocking magnet for closing(option) ˉ F11 1.Auxiliary opening release ˉ F12 2.Auxiliary opening release(option) ˉ F2 Auxiliary closing release ˉ F3 Indirect overcurrent release(option) ˉ F4 Undervoltage release(option) ˉ K01 Anti-pumping-relay ˉ Q1 Units incorporated in the switchgear truck in compliance with order ˉ S8 Test position switch ˉ S9 Service position switch ˉ Y0 Blocking magnet blocking for trolley(option)

Drawing number:ASX000525-01

Page 43: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

41

10 Drawingshand trolley type

1. This circuit diagram (ASX000525-02) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order ˉ M1 Motor for energy storing device ˉ S11/12 Auxiliary switch position indicator ˉ S2 Micro switch for motor control ˉ S6 Micro switch for blocking magnet ˉ Y1 Blocking magnet for closing(option) ˉ F11 1.Auxiliary opening release ˉ F12 2.Auxiliary opening release(option) ˉ F2 Auxiliary closing release ˉ F3 Indirect overcurrent release(option) ˉ F4 Undervoltage release(option) ˉ K01 Anti-pumping-relay ˉ Q1 Units incorporated in the switchgear truck in compliance with order ˉ S8 Test position switch ˉ S9 Service position switch ˉ Y0 Blocking magnet blocking for trolley(option)

Drawing number:ASX000525-02

Page 44: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

10 Drawings

Electric hand trolley

42

1. This circuit diagram (ASX000525-05) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

4. If circuit breaker without blocking manget for trolley Y0, circuit diagram according to showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order ˉ M1 Motor for energy storing device ˉ S11/12 Auxiliary switch position indicator ˉ S2 Micro switch for motor control ˉ S6 Micro switch for blocking magnet ˉ Y1 Blocking magnet for closing(option) ˉ F11 1.Auxiliary opening release ˉ F12 2.Auxiliary opening release(option) ˉ F2 Auxiliary closing release ˉ F3 Indirect overcurrent release(option) ˉ F4 Undervoltage release(option) ˉ K01 Anti-pumping-relay ˉ Q1 Units incorporated in the switchgear truck in compliance with order ˉ S8 Test position switch ˉ S9 Service position switch ˉ Y0 Blocking magnet blocking for trolley(option) ˉ M2 Motor for control trolley

Drawing number:ASX000525-05

Page 45: HVX 12-17.5-24kV User Guide

HVX 12-17.5-24kVEmbedded pole vacuum circuit-breaker

43

10 Drawings

Electric hand trolley

1. This circuit diagram (ASX000525-06) shows the maximum switchgear equipment.The standard equipment doesn't include option items,if

the customer requires option items,please state it when placeing the order.

2. Circuit breaker is in discharge and open position,trolley is in service position.

3. If Circuit breaker without blocking manget for closing Y1, circuit dragram according to dash ¢Ù showing.

4. If circuit breaker without blocking manget for trolley Y0, circuit diagram according to showing.

ˉ Q0 Units incorporatrd in the circuit breaker in compliance with order ˉ M1 Motor for energy storing device ˉ S11/12 Auxiliary switch position indicator ˉ S2 Micro switch for motor control ˉ S6 Micro switch for blocking magnet ˉ Y1 Blocking magnet for closing(option) ˉ F11 1.Auxiliary opening release ˉ F12 2.Auxiliary opening release(option) ˉ F2 Auxiliary closing release ˉ F3 Indirect overcurrent release(option) ˉ F4 Undervoltage release(option) ˉ K01 Anti-pumping-relay ˉ Q1 Units incorporated in the switchgear truck in compliance with order ˉ S8 Test position switch ˉ S9 Service position switch ˉ Y0 Blocking magnet blocking for trolley(option) ˉ M2 Motor for control trolley

Drawing number:ASX000525-06

Page 46: HVX 12-17.5-24kV User Guide

Note:

Page 47: HVX 12-17.5-24kV User Guide

Note:

Page 48: HVX 12-17.5-24kV User Guide

Manufac turer:

Schneider Electric Huadian Switchgear(Xiamen)

co.,Ltd

No. 22 Huo Ju bei lu,Xiamen

361006,china

Tel: +86(0)592-5775316

Fax: +86(0)592-5775319

As standards, specifications and designs change from time to time, please

ask for confirmation of the information given in this publication.

© 2

01

1 Schneid

er Electric - A

ll rights reserved

This document has been printed

on ecological paper

Publishing: Schneider Electric

Design: Schneider Electric

Printing:

2011.11