Test Procedures for Fire Fighting SystemProject Name :
Site Name :
Room Name :
Date :
Fire Panel MRP-2002 Test Sheet
System Trouble Test
Power Supply Test
Mains Test (AC 220 v.)
Disconnect the 220 AC volt
Green AC Power LED LABLE OFF
The LCD Display will indicate AC FAULT
Yellow Trouble LED LABLE ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
Battery Test
Disconnect the Battery
Green AC Power LED ON
The LCD Display will indicate NO BATTERY
Yellow Trouble LED ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
Earth Fault Test
Connect any cable to a steel conduit
Green AC Power LED ON
Yellow System Trouble LED ON Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
8/6/2019 HPCO2 Test Sheet
http://slidepdf.com/reader/full/hpco2-test-sheet 2/6
Initiating Zones Trouble Test
Disconnect any detector from its base, disconnect any wire from zone 1 or 2
Green AC Power LED ON
The LCD Display will indicate OPEN FAULT(Open 2- wire smoke)
Yellow Trouble LED ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
Manual Release Trouble Test
Disconnect Manual Release from zone 3
Green AC Power LED ON
LCD Display will indicate OPEN FAULT (Open Rel)
Yellow Trouble LED ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
Abort Release SW Trouble Test
Disconnect Manual Release from zone 4
Green AC Power LED ON LCD Display will indicate OPEN FAULT (Open Abort Rel SW)
Yellow Trouble LED ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
Notification Appliance Trouble Test
Disconnect the Bell or Siren from its base, disconnect any wire from O/P 1&2
Green AC Power LED ON
LCD Display will indicate OPEN FAULT (Open NAC 1&2)
Yellow Trouble LED ON Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
8/6/2019 HPCO2 Test Sheet
http://slidepdf.com/reader/full/hpco2-test-sheet 3/6
Releasing Circuits Trouble Test
Disconnect any wire from O/P 3&4
Green AC Power LED ON
LCD Display will indicate OPEN FAULT (Open NAC 3&4)
Yellow Trouble LED ON
Circuit Trouble LED ON
Internal Buzzer Sound
Press ACK/STEP Button to mute internal buzzer
-------------------------------------------------------------- System Alarm & Releasing Test
Disconnect the Electric Actuator from the cylinder valve
Test Zone 1 or Zone 2 (Alarm Test)
Test any Detector from zone 1 or zone 2 using recommended test magnet
Green AC Power LED ON
LCD Display will indicate ALARM 2-Wire Smoke
Internal Buzzer Sound
1-st Alarm Notification Circuit Activated (BELL) O/P1
Press ACK/STEP Button to mute internal buzzer
Press Alarm Silence Button to Silence the Bell
Press Rest Button to Rest the system
Test Zone 1 and Zone 2 (Releasing Test)
Test any Detector from zone 1 and zone 2 using recommended test magnet
Green AC Power LED ON
LCD Display will indicate ALARM 2-Wire Smoke
Internal Buzzer Sound
1-st Alarm Notification Circuit Activated (BELL) O/P1 2-nd Alarm Notification Circuit Activated (SIREN) O/P2
Releasing Circuit Activated After The Delay Time O/P3
Check the operation of the Electric Actuator.
Press ACK/STEP Button to mute internal buzzer
Press Alarm Silence Button to Silence the Bell and the Siren
Press Rest Button to Rest the system
8/6/2019 HPCO2 Test Sheet
http://slidepdf.com/reader/full/hpco2-test-sheet 4/6
Test Zone 1 and Zone 2 (Releasing Test with Abort)
Test any Detector from zone 1 and zone 2 using recommended test magnet
Green AC Power LED ON
LCD Display will indicate ALARM 2-Wire Smok
Internal Buzzer Sound
1-st Alarm Notification Circuit Activated (BELL) O/P1
2-nd Alarm Notification Circuit Activated (SIREN) O/P2
Press and Hold the Abort switch for 2 sec.
Releasing Circuit Activated After The Delay Time (FROM 30Sec to 20MIN)
Check the operation of the Electric Actuator.
Press ACK/STEP Button to mute internal buzzer
Press Alarm Silence Button to Silence the Bell and the Siren
Press Rest Button to Rest the system
Manual Release Test (Releasing Test)
Push In and Pull Down the manual gas release
Green AC Power LED ON
Internal Buzzer Sound
2-nd Alarm Notification Circuit Activated (SIREN) O/P2
Releasing Circuit Activated Immediately O/P3
Press ACK/STEP Button to mute internal buzzer
Press Alarm Silence Button to Silence the Bell
Press Rest Button to Rest the system
-------------------------------------------------------------------------------------------
8/6/2019 HPCO2 Test Sheet
http://slidepdf.com/reader/full/hpco2-test-sheet 5/6
Pipes Pneumatically Test Sheet
Refer to NFPA2001 to test the
6-3.2.1 High Pressures system
All piping from the carbon dioxide supply to the nozzle shall be subjected to a
minimum pressure of 600 psig (4137 Kpa). The leakage during a 2-mintee period
shall not exceed a pressure drop of 10 percent
Duration:
Start time: Pressure bar
End time: Pressure bar
----------------------------------------------
---------------------------------------------
Signatures:
Owner Representative.
Consultant Representative.
Contractor Representative.
Supplier Representative.