How to Specify the Right Motor Control Center for the Job
-
Upload
fcof1232374 -
Category
Documents
-
view
225 -
download
0
Transcript of How to Specify the Right Motor Control Center for the Job
8/3/2019 How to Specify the Right Motor Control Center for the Job
http://slidepdf.com/reader/full/how-to-specify-the-right-motor-control-center-for-the-job 1/4
advanced search
power quality design / engineer ing ops & maintenance market t rends produc t depot light ing voice / data / video const ruc tion grounding NEC tra ining
It’s no surprise that as the interrupting rating of a device
increases, so does its cost. This chart gives you a simple view as
to how much it increases.
How to Specify the Right Motor Control
Center For the JobJun 1, 2005 12:00 PM, By Patrick Daley, P.E., Devon Engineering
When purchasing a new or replacement MCC be sure to address a few important
items in your specification
Motor control centers (MCCs) were first introduced in 1937 as a way to conserve wall
and/or floor space in industrial facilities. Before 1960, wall-mounted motor starters were
used even if only a few motors were involved. Relays were housed in separate controlcabinets. Today, even if a few motor starters are needed, they're typically installed within
a standardized vertical enclosure with all the required relays, instruments, and controls.
Overall, the same requirement today often dictates the use of MCCs in new installations.
However, unlike the '50s, when the vast majority of loads served by MCCs were electric
motors with across-the-line starters, today's MCCs can accommodate a wide variety of
different devices required in modern facilities. But specification of this popular piece of
equipment shouldn't be taken for granted. A few key line items in your spec, including
ampacity, bussing material, and feeder cables, could mean the difference between a
long, reliable service life and an early, abrupt failure.
Ampacity. One of the first items to be determined is the ampacity of the MCC. Basically,
the ampacity is the maximum amount of current that the main horizontal bus can
accommodate without overheating. The minimum ampacity of an MCC main horizontal
bus is 600A. Smaller sizes are generally not available and are considered “special
order” items. Often, these special order MCCs with smaller bus ampacity simply contain
600A bussing with a revised nameplate.
Following the horizontal bus ampacity is the specification of the vertical bus ampacity.
The minimum ampacity of a vertical bus is 300A. For most manufacturers, the maximumampacity of an MCC horizontal bus is 2,000A and the maximum ampacity of a vertical
bus is 1,600A, although some manufacturers claim an ampacity up to 5,000A for a
horizontal bus. Generally, if a group of loads requires more than 2,000A, then it would be
best to use two separately fed MCC line-ups as opposed to one.
Another issue to
consider when
specifying an MCC is
the available fault
current levels on the
power distribution
system. T he
available fault
current is simply the
amount of electric
current that would
flow if a direct short
were to occur
between phases or
from phase toground (enclosure)
within the MCC.
A couple of
definitions are in order at this point. The interrupting rating of an electrical device applies
primarily to circuit breakers and fuses and other devices designed to interrupt the flow of
current during a ground fault and/or a short circuit. This rating signifies that the current
interrupting device will open and break the flow of current to the piece of equipment it's
protecting without rupturing and damaging nearby equipment or personnel. The short-
circuit rating of electrical equipment is the maximum fault current that the device can
handle without extensive damage to the electrical components of the circuit.
Per 110.10 of the 2005 NEC, “Listed products applied in accordance with their listing
shall be considered to meet the requirements of this section.” Although an MCC may
have a nameplate that indicates the short-circuit withstand rating as 42,000A, for
example, the overall short-circuit rating of an MCC is based on the installed circuit
interrupting device with the lowest current-interrupting rating.
The amount of current available varies from installation to installation, depending on the
impedance of the electric source. For example, if the available fault current isdetermined to be 12,000A, the MCC must be rated to withstand 12,000A of fault current
during the time it takes the overcurrent protective device (OCPD) immediately upstream
of the fault to open and clear the fault. Fault-current ratings of electrical devices are
available in semi-standard ratings. Some typical ratings are 10,000A, 14,000A, 18,000A,
and 22,000A.
The fault current withstand rating of an MCC is determined by the lowest rated device
in this issue
Power
Monitoring
Equipment
Trends
Electricians in
Antarctica
Heat Tracing
More from this issue
Subscribe to Digital Edition
advertisement
what's wrong here?
What's Wrong
Here?Oct 20, 2011 11:38 AM
What's Wrong
Here?Oct 6, 2011 11:46 AM
What's Wrong
Here?Sep 22, 2011 4:58 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
Light tower diffuser Oct 28, 2011 7:00 AM
View all 2011 Product Spotlights
Free Product Info
Our Product Information site is the
ultimate online resource for products
and services offered by Advertisers
featured in our Magazine. Thisservice is provided as a quick and
easy way to request Product
Information online. Get FREE
product information now.
More...
advertisement
Arlington CP9000
Arlington's new 9"
diameter ceiling cover
plate is the neatest way to
cover unused "high hat"
cans. With no tools
needed, installation
couldn't be faster!...
Arlington Gangable
Boxes
Designed for new or
retrofit applications, these
snap-together gangable
plastic boxes eliminate the
need to construct a
multiple-gang steel box outof several individual
ones...
advertisement
2008 NEC Books
2011 NEC Books
Technical Books
About Us Contact Us Subscribe Advertise Login Classifieds
Home > Magazine Articles
09Share 0 2 0Digg
w to Specify the Right Motor Control Center For the Job http://ecmweb.com/mag/electric_specify_right_motor/
4 28/10/2011 22:0
8/3/2019 How to Specify the Right Motor Control Center for the Job
http://slidepdf.com/reader/full/how-to-specify-the-right-motor-control-center-for-the-job 2/4
within the MCC. If an MCC bus structure is rated to withstand 42,000A and a circuit
breaker is installed with a fault-withstand rating of 18,000A, then the entire MCC
assembly is rated 18,000A. Bear in mind that most NEMA class motor contactors are
rated for a fault-current withstand of 5,000A; some are rated for 10,000A. In order to
account for the lower fault-current withstand rating of motor contactors (and avoid costly
fault damage), a current-limiting motor protector circuit breaker or current-limiting fuses
should be considered.
Bear in mind that the higher the interrupting rating of a device, the higher the cost
(Figure on page 18). Therefore, significant cost savings can be obtained by doing a
short-circuit analysis of an electric power circuit.
Bussing material. The material used for the electrical bussing within the MCC is
another item you should carefully consider during specification.
The most common type of bus material is copper. Aluminum can be used to reducecosts, but aluminum has its own set of problems. For example, its expansion and
contraction is much greater than copper, which can result in the gradual loosening of
bolts and other fasteners. To account for this effect, special washers with spring-type
tensioning are used to connect the aluminum bus to the insulated bus supports. These
fasteners must be properly torqued per the manufacturer's recommendations, or the
spring effect will be lost and subsequent loosening of the fasteners will occur over time.
Also, due to its lower conductivity than copper, aluminum bus must be larger to handle
the same level of current.
Copper bus, on the other hand, can be bolted tightly to the bus supports, and fasteners
seldom loosen over time. However, copper does have its own shortcomings. Some
environments may present a corrosive atmosphere to the copper bussing, which will
lead to eventual MCC failure. For example, ammonia gas, which is often used in
refrigerant or large chiller loops, will attack copper. It will also cause stress corrosion
cracking of copper alloys.
It's possible to protect the copper bussing from corrosion by coating the bus with tin.
Although a tin coating will corrode, the corrosion products of tin are relatively thin and
friable and will break down mechanically, allowing for a continuously reliable metal-
to-metal connection. Tin is also anodic with respect to copper. In other words, if atin-coated copper bus is scratched and the underlying copper is exposed, the tin will
corrode while the copper bus won't. Other examples of corrosive industrial environments
that you should pay attention to are pulp plants, wastewater treatment facilities, fossil
fuel-based power generating plants, and marine environments.
Coating copper bus with silver is effective in some environments, but it can form
relatively thick, insulating layers of silver sulfide (tarnish). It can also be aggressively
attacked by chloride sources. Copper is also anodic to silver, meaning that given a
copper/silver metallic junction, the copper will corrode while the silver wont.
Feeder cables. One of the commonly overlooked issues involved in specifying and
purchasing an MCC is how the main feeder cables will enter the MCC. You typically
have two choices: overhead or underground. Due to the fact that the electric power
cables that feed an MCC are typically numerous and large, knowing beforehand how an
MCC will be fed will eliminate difficult wire bends and/or costly field changes required to
properly terminate an awkward cable feed. One can specify an MCC that will
accommodate both types of feeds, but again, costs will increase and some MCC space
will be wasted.
If automatic controls are going to be implemented for operation of the motor loads, thenthe type of control wiring should be indicated. The various types of control wiring
available are as follows:
Type A — No terminal blocks within the MCC. Only wiring on the motor starter itself is
required. No wiring external to the control device.
Type B — Control wiring to terminal blocks within motor starter buckets while user field
load wiring terminates to the device adjacent to the vertical wire-way.
Type B-D — For Size 3 and smaller starters, field load wiring connects directly to the
device terminals.
Type B-T — For Size 3 and smaller starters, field load wiring connects to factory-wired
power terminal blocks located in or adjacent to each unit.
Type C — Same as B except all factory-wired to master terminal boards at the top or
bottom of the MCC.
Class I — Doesn't include interwiring or interlocking between units or to remotely
mounted devices. Doesn't include control system engineering diagrams if individual units
are supplied. Types A, B, or C wiring available.
Class II — Factory-wired controls and interlocks. Full wiring diagrams are provided,
factory system engineering. Types B or C. Class II type C wiring is expensive and
requires a longer lead time.
By no means are the preceding items meant to be an all-encompassing list of
specifications necessary to successfully purchase or spec an MCC for a specific
application. However, it's a good starting point. Other issues that must be considered
when specifying an MCC include:
Enclosure type: indoor (NEMA 1) or outdoor (NEMA 3R)
Ground-fault detection
Metering
Wire marking
Indication lights
Hands-off auto switches
Voltage rating
Additional help is available through a review of pre-written specifications. However, the
selected document will need to be carefully reviewed and possibly altered in order toproduce the specification that will meet you and your client's specific needs. If the task
seems time consuming or difficult, it's recommended that the services of a professional
engineer be sought for expertise in this area. The MCC will be in service for the next 25
to 30 years, so such an investment will be well worth the effort.
Daley is an electrical engineer with Devon Engineering in Colorado Springs, Colo.
More...
Recent Comments
More...
Case Studies
The Backup Plan
Lessons Learned from
Large-Scale Fire Alarm
Installation at Two California
Hospitals
Century Aluminum Saves
Thousands with Upgrade to LED
Obstruction Lights
1capybara all equipment shall be
installed as the manufacturer
intends. in the specs of the
disconnect it...
Stumped by the Code? June
2011 6 days ago
Matrk03 Was looking at moving
violations #10 .wouldn't the
installation be exempt from the
NEC if it was...
Whats Wrong Here? 1 week ago
Gordon Tesch I would request to
have it removed and probably
going to have to replace every
thing before there...
Whats Wrong Here? 1 week ago
Pjbeacom18 where in the code
book can I find out about the law
of two wires under a single lug on
load side...
Stumped by the Code? June
2011 1 week ago
Tlcgizer Per National Electric
Code, what is the maximum
allowable non-fire rated (outdoor)
cable length...
Stumped by the Code?
September 2011 1 week ago
Social Media
More ways to stay informed...
More...
More...
Moving Violations 10 Moving Violations 9
Understanding NEC
Requirements for Solar
Photovoltaic Systems
During this session, Mike Holt will
address possible conflicts or confusing NEC
requirements, provide tips on proper electrical
installation techniques, and discuss the dangers
related to improper installations. View this On Demand
Webinar!
Top Code Changes: 2011 NEC
EC&M has partnered with NEC
expert Mike Holt to present a one
hour Webinar covering the top 2011
NEC Code Changes. This event will
be broadcast live on the Web with
streaming audio and PowerPoint slides allowing the
audience to have real-time interaction with the guest
speaker, Mike Holt. View this On Demand Webinar!
resources
product info
tradeshow
research
industry links
rss
w to Specify the Right Motor Control Center For the Job http://ecmweb.com/mag/electric_specify_right_motor/
4 28/10/2011 22:0
8/3/2019 How to Specify the Right Motor Control Center for the Job
http://slidepdf.com/reader/full/how-to-specify-the-right-motor-control-center-for-the-job 3/4
Latest Articles
European Green Building Space to
Almost Quadruple by 2016Oct 28, 2011 2:34 PM
Nonresidential Building
Construction Spending Inches
UpwardOct 28, 2011 2:13 PM
North American Business
Conditions Improve in October Oct 28, 2011 2:01 PM
Trending Articles
Insulation Resistance
Testing: How and Why?
Electrical connections
using threaded couplings or
threaded hubs on
Like
Want to use this article? Click here for options!
© 2011 Penton Business Media, Inc.
Acceptable Use Policy
Add New Comment
Showing 0 comments
Sort by Subscribe by email Subscribe by RSS
Trackback URL
blog comments powered by DISQUS
Back to Top
Browse Back Issues
October 2011 September 2011 August 2011 July 2011 June 2011 May 2011 April 2011 March 2011
Browse Back Issues
0
1 person liked this.
Type your comment here.
Image
Siemens answers www.siemens.com/answers
The intelligent factory Answers for industry.
Motor Control Tutorials www.Galilmc.com
Free Web Tutorials from Galil, The World Leader inMotor Control.
Eaton Circuit Breakers www.PocoSales.com
In stock for fast delivery specs, drawings, designguides
National Electrical Code NFPA.org/NationalElectricalCode
2011 National Electrical Code (NEC) Order now for safety & compliance.
9Share 0 2 0Digg
w to Specify the Right Motor Control Center For the Job http://ecmweb.com/mag/electric_specify_right_motor/
4 28/10/2011 22:0
8/3/2019 How to Specify the Right Motor Control Center for the Job
http://slidepdf.com/reader/full/how-to-specify-the-right-motor-control-center-for-the-job 4/4
Archives | SubscribeView Sample | Subscribe
View Sample | SubscribeArchives | Subscribe View Sample | Subscribe
Archives | Subscribe
View Sample | Subscribe
Home Contact Us E-mail Webmaster For Advertisers For Search Partners Privacy Statement Terms of Use
browse e-newsletters
© 2011 Penton Business Media, Inc.
w to Specify the Right Motor Control Center For the Job http://ecmweb.com/mag/electric_specify_right_motor/
4 28/10/2011 22 0