Handbook on Lead Acid Cell for Railway signaling

download Handbook on Lead Acid Cell for Railway signaling

of 32

Transcript of Handbook on Lead Acid Cell for Railway signaling

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    1/32

    CAMTECH/S/2005/LAC/2.0 1

    LEAD ACID CELL

    1. Introduction

    Two different types of lead acid cells are

    manufactured by the industry and depending on

    the application, these are normally referred to as

    mobile or stationary. These are also called

    Accumulators or storage cells.

    This document includes instructions, which are

    applicable for the installation and maintenance

    of stationary secondary lead acid cells or

    batteries.

    2. Parts of Lead Acid Cell

    Parts of Lead acid cell are shown in figurebelow.

    Figure - 1

    Lead Acid Cell March2005

    Ver 2.0

    1. Level indicator

    2. Vent plug

    3. Terminal ports

    4. Cover

    5. Separator guard

    6. Positive plate7. Separator

    8. Negative plate

    9. Container

    10. Plate rest

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    2/32

    CAMTECH/S/2005/LAC/2.0 2

    Level indicator and Vent plug.

    For all capacities of lead acid cell vent/float plug

    shall be of threads M27x3 pitch is provided. The

    dimension of vent cum float guide plug are shown in

    figure below:

    Red mark

    Green mark

    Plug

    Threads(M27x3 Pitch)

    Transparent

    Indicator

    Float at greenmark level

    mark levelFloat at red

    Figure - 2

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    3/32

    CAMTECH/S/2005/LAC/2.0 3

    Plastic Skirtingof suitablecolour fireretardant

    Microporous body

    Plug

    Suitable anti splasharrangement for

    eelctrolyte so thatgasses can pass

    Threads M 27x3 pitch

    Body

    25x10 approx8 windows of size

    Figure 3

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    4/32

    CAMTECH/S/2005/LAC/2.0 4

    6 or 8 holes 0 2

    for releasing gas

    Figure - 4

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    5/32

    CAMTECH/S/2005/LAC/2.0 5

    Plates

    The plates, which are actual electrodes, are:

    Spongy Lead

    Lead Peroxide

    The plates will usually be plante or faure types.

    In the plante type the plates are solid type and of

    wed construction. Where as, in faure type a plategrid of antimony alloy is used with the lead peroxide

    or spongy lead in a powdered from secured inside a

    bay made of this grid.

    Separators

    The separators act as insulating piecesbetween the different plates.

    separators are made of either specially

    treated wood, perforated rubber, celluloid or

    rubber fabric made porous by thick cotton

    threads or glass wool.

    The common separator is wood, since it

    is the cheapest of all separators.

    Container

    The container is made of vulcanised

    rubber, pitch celluloid or glass.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    6/32

    CAMTECH/S/2005/LAC/2.0 6

    Celluloid or glass containers are

    normally used for light duty work and celluloid

    container for portable work.

    Plate rest

    The plate rest or bottom blocks are raised

    ribs either fitted in the bottom of the jar or made

    in the jar itself so that the plates do not touch the

    bottom and the tope portion is kept at the correctlevel.

    These also form a receptacle to collect

    the sludge formed during its period of active life.

    Terminal ports

    All the positive plates are welded to one

    bar and all the negative plates to another

    common bar.

    There is always one more negative plate

    then the positive to provide equal working area,

    on all sides of the positive plates.

    The outside plates are, therefore, always

    negative plates.

    The terminal posts are upward extensionsof connecting bars. This forms the terminal post

    and passes through the cover to enable external

    connections to be made.

    Cover

    The covers are generally of vulcanized

    rubber or pitch.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    7/32

    CAMTECH/S/2005/LAC/2.0 7

    A hole is provided for pouring the

    electrolyte and this can be closed by a screwed

    cap. The cap is provided with minute holes

    for gases to escape.

    This is also known as Vent Cap

    3. Brief description and working

    A lead acid battery consists of positive and

    negative electrodes immersed in an electrolytekept in sealed container. The material of the

    positive electrode is lead dioxide (PbO2) and

    that the negative electrode is spongy lead (Pb).

    These electrode are electrically insulated from

    each other using separators. The electrolyte is a

    suitable mixture of sulfuric acid and distilled

    water.

    When the battery is fully charged, the negativeelectrode remains as Lead, the positive electrode

    as lead dioxide and the concentration of sulfuric

    acid solution (specific gravity is between 1200-

    1220).

    As the battery discharges, the positive and

    negative electrodes convert chemically in to lead

    sulfate. The chemical reaction consumes the acidand finally releases water in the electrolyte

    solution, thereby reducing the specific gravity.

    Capacity V/S Discharge rate

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    8/32

    CAMTECH/S/2005/LAC/2.0 8

    The capacity of the battery is the amount of

    electricity that can be obtained from it. It can be

    rated in two ways.

    Ampere-hour rating

    Watt-hour rating.

    The ampere-hour rating is always given with the

    specified discharge rate, that is.

    a) 100 AH at 10 A rate

    b) 150 AH at 15 A rate.

    In(a)the maximum discharge current should not

    exceed 10 Amps, and the period of discharge at this

    rate is 10 hours.

    Similarly, for (b) maximum rate is 15 Amps and

    period is 10 hours.

    This is also sometimes expressed as hour rate for

    example 100 Amps. @ 5 hours rate worked, mean

    that the maximum discharge current is 20 Amps.

    and the period of discharge is 5 hours. The capacity

    always reduces with increase in discharge rate so

    that the actual ampere-hour capacity obtained is

    usually 80 to 90% of the rated value.

    Efficiency of a secondary cell

    The efficiency of a secondary cell is

    defined as the ratio of output of a cell to the

    input required to restore the initial state of

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    9/32

    CAMTECH/S/2005/LAC/2.0 9

    charge under specified conditions of

    temperature, current rate and final voltage.

    Generally the efficiency is expressed inthree ways:

    Ampere-hour efficiency.

    Volt efficiency.

    Watt-hour efficiency.

    Ampere-hour efficiency is the ratio of the

    ampere hours output to the ampere hours of therecharge.

    The ampere-hour loss, which determines

    ampere hour efficiency during cycle of charge

    and discharge is principally that due to gassing.

    Local action is responsible of certain

    amount, but unless the test is spread over a long

    period of time or the battery is in a veryunhealthy condition this loss may be

    disregarded. Since gassing is due to charging

    current in excess of the utilised in charging the

    active material, ampere hour efficiency can be

    increased by controlling the charging current to

    keep it below the value, which will produce

    excessive gassing, but such careful control of the

    charging rate, and especially if the cycle ofcharge and discharge did not involve bringing

    the battery to an absolutely fully charged

    condition, an ampere hour efficiency of nearly

    100% can be obtained.

    Under commercial service conditions

    including frequent cycles of charge and

    discharge involving nearly the full capacity of

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    10/32

    CAMTECH/S/2005/LAC/2.0 10

    the battery, an ampere hour efficiency between

    85 to 90% may be obtained.

    4. Unpacking and storing

    Carefully unpack the cells received from trade

    (rough handling could damage them) and check

    all the components including the vent plugs, vent

    cum float guide, inter cell connectors, nuts and

    bolts.

    Inspect the sides and the bottom of the batterypacking case for any wet spots, which indicate

    broken jars/containers. These might have been

    broken during handling and transportation.

    Cracked and broken batteries may be rejected

    and details may be brought to the notice of the

    supplier for replacement.

    The battery must be stored in clean, cool and dry

    room protected from sun, rain and dust.

    5. Location and Installation

    Mount the batteries in well-ventilated, clean and

    dry rooms.

    For small battery installations, natural

    ventilation through windows and doors maynormally be sufficient. However, for larger

    battery installation (more than 12 cells). Forced

    ventilation methods using exhaust fans must be

    provided.

    Separate battery room are necessary to avoid the

    adverse effect of fumes on other interlocking

    and power equipment as well as to provide free

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    11/32

    CAMTECH/S/2005/LAC/2.0 11

    access to the maintenance staff (battery rooms

    are not double locked.).

    The battery room shall be provided with acidproof flooring and acid proof tiles on walls up to

    suitable height.

    Wherever, batteries are kept in field inside the

    location boxes, suitable openings/holes are

    necessary for ventilation.

    Where batteries are housed in location boxes,

    these housings shall be painted with acidresistant paint.

    In some applications, where a few cells are

    required to be kept in offices, equipment rooms,

    residence etc. they may be housed in wooden

    boxes proved with enough holes for ventilation.

    Locate the batteries away from direct Sunrays

    and heat emitting system.

    Place the batteries on rugged wooden racks of

    sufficient height so that it is possible to inspect

    and maintain them properly.

    Two or more coats of acid resistant paint of

    approved type shall protect the racks.

    The racks shall be level and mounted on

    approved type of insulators.

    A typical arrangement is shown in figure below.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    12/32

    CAMTECH/S/2005/LAC/2.0 12

    Connector

    Insulator

    Connector

    Centre of cells

    Connector

    + + -

    SINGLE/DOUBLE ROW SINGLETIER WOOD ON RACK

    Figure - 5

    InsulatorConnector

    Connector Connector

    SINGLE/DOUBLE ROW DOUBLETIER WOOD ON RACK

    Centre of Cells

    + - +

    Figure - 6

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    13/32

    CAMTECH/S/2005/LAC/2.0 13

    Lead acid cells of an approved type shall be used

    and shall conform to specification no. IRS: S

    88/93 for low maintenance lead acid cells. The cells shall be installed as per approved

    drawings.

    At the time of installation, capacity test shall be

    done and record shall be maintained.

    Insulate the cells from the floor and from each

    other using insulators. Place wooden planks

    under the batteries wherever the cells are kept onmasonry racks and floors, metallic frames and

    location boxes.

    Keep the individual batteries properly aligned

    and leveled to avoid stresses on the

    connectors/cable. Keeping battery insulator

    block under the battery is desirable.

    Ensure proper clearance between adjacent cells

    for connecting the battery terminal connectors

    and between adjacent rows from the angle of

    maintenance.

    Wooden battery racks must be protected against

    decay by painting them using acid resistance

    paint (Type 2 of IS 158-68).

    On receipt of charged secondary cells, the vent

    plugs shall be removed and the height of theelectrolyte shall be noted, if it is below the

    prescribed level, the loss may be due to spillage

    during transit. The level of the electrolyte can be

    restored by adding battery grade acid of

    recommended specific gravity.

    6. Initial Charging

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    14/32

    CAMTECH/S/2005/LAC/2.0 14

    Unless, good facilities are available in the Chief

    Signal/Telecom Inspectors depot for chargingsecondary lead acid cells and their subsequent

    handling and transportation to actual site of

    installation it is advisable to do the initial

    charging at site.

    Initial charging of the batteries shall be done as

    per instructions of the manufacturer and the date

    of charging shall be suitable painted on thebatteries, or on a separate board kept near the

    batteries.

    The procedure given below, however, generally

    applies for initial charging to all makes of lead

    acid batteries.

    Ensure that all the cells in the battery set are of

    the same type and capacity. Charging individual

    cells separately is not advisable.

    Battery grade dilute sulfuric acid conforming to

    IS 266 and distilled or de-mineralized water

    conforming to IS 1069 shall only be used as

    electrolyte

    A glass, porcelain, rubber or any other acid

    proof container shall only be used for mixing

    acid and water. Always acid shall be added to water.

    During mixing, the solution must be stirred

    constantly so that its temperature does not

    exceed 50 C.

    Ratio in which sulfuric acid and distilled water

    must be mixed is given in the table 1.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    15/32

    CAMTECH/S/2005/LAC/2.0 15

    Specific

    Gravityof the

    original

    Acid

    Specific

    Gravityof the

    solution

    required

    Distillwater

    Sulfuricacid

    1825 1400 11 7

    1825 1190 5 1

    1400 1190 6 5

    Table-1

    While preparing electrolyte, the solution should

    be continuously stirred using a glass or wooden

    rod.

    The temperature of the same should not be

    allowed to exceeds the limit, then allow it to

    cool.

    Allow it to cool for at least 10 to 12 hours and

    see that the specific gravity is between 1190 and

    1200.

    Since, specific gravity varies with the

    temperature a correction must be applied to

    arrive at the correct value.

    For temperature > 27 C 0.0007 per CFor temperature < 27 C -0.0007 per C

    Clean all the new cells for the battery set with

    distilled water and fill all of them with this

    electrolyte which will ensure uniform specific

    gravity.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    16/32

    CAMTECH/S/2005/LAC/2.0 16

    The level of the electrolyte should be about 12 to

    15 mm above the plate.

    Check either the red mark indicated on the ventfloat or use a glass tube to see the level.

    The charger output terminals must be correctly

    connected to the battery set i.e. + to + and to -.

    Ensure that all electrical connections between

    the charger and the battery are tight and offer

    good conductivity.

    Apply charge for 35 hours at the starting currentrate given by the empirical formula/ thumb rule,

    where the starting charging current is taken as

    4% of the ampere hours (AH) value of the cells.

    Starting Current = 0.04 x AH value

    (For initial charging)

    Check specific gravity and voltage reading every

    8 hours. Apply temperature correction on thespecific gravity readings.

    Stop charging when the specific gravity becomes

    12105.

    If the specific gravity of the cell/cells after

    charging does not improve to its normal value, a

    small quantity of electrolyte is taken out and

    replaced by solution of higher specific gravity

    (1400). A fresh charging cycle must then begiven for two hours to ensure mixing.

    Discharge the battery through a suitable load

    (lamps) till the specific gravity reduces to

    between 1180 and 1190 and the voltage of cells

    to 1.85 V.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    17/32

    CAMTECH/S/2005/LAC/2.0 17

    Repeat the cycle of charge and discharge once

    again and then charge finally for use.

    Ensure that the battery is charged optimally andno over charging, over gassing or heating takes

    place.

    Apply a coat of petroleum jelly or non-oxidizing

    grease on the battery connectors to avoid

    corrosion.

    Close all the vent caps and ensure that the floats

    are in position. If after charging, the battery are not put up in use

    for 15 days they should be given as equalizing

    charge to bring specific gravity of all the cells to

    12105.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    18/32

    CAMTECH/S/2005/LAC/2.0 18

    7. Maintenance and Inspection

    Maintenance tests and repair work on the cell,which may interfere with safe operation of

    trains, shall not be started until movements are

    fully protected.

    Temporary repairs or adjustments shall be made

    in such a manner that safety of train operation is

    not impaired when repairs and or adjustments

    are made. After the maintenance and repair work

    (Including temporary repair) are completed tests

    shall be immediately carried out to ensure that

    the connected apparatus functions satisfactorily.

    Battery charger used shall be as per specification

    no. IRS: S 86/2000 for battery charger self

    regulating.

    Float and boost mode shall be adjusted to 2.15Volt/cell and 2.4 Volt/cell

    The battery room and location boxes shall be

    kept well ventilated, free from water, oil or dust

    surroundings and batteries shall be kept clean.

    Connecting cables shall be flexible and

    sufficiently long to prevent strain on the battery

    terminals.

    The electrical connection shall always be kept

    tight.

    The terminals and connections shall be coated

    with pure Vaseline or petroleum jelly to prevent

    corrosion.

    Grease shall not be used.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    19/32

    CAMTECH/S/2005/LAC/2.0 19

    The electrolyte shall be maintained at the correct

    level by topping up as often as necessary with

    distilled or demineralised water. Electrolyte lost due to spillage shall be replaced

    with proper amount of electrolyte of the same

    specific gravity as that of other cells of the

    battery.

    Electrolyte shall not be added in any other

    circumstances.

    Each cell shall be tested periodically and itscleaning and charging arranged so that its

    voltage and specific gravity are within specified

    limits.

    Test results and dates of cleaning and charging

    adjustments shall be recorded on the Battery

    History Card.

    A separate card shall be maintained for each

    battery set. The voltage of individual cell shall not fall

    below 1.85 Volts.

    7.1 Precautions

    Checks / tests on battery and general cleaning

    normally do not affect the circuit it is feeding.

    However, care must be taken to ensure that the

    working circuits do not get affected.

    For maintenance and repair works (including

    temporary repairs) which may require

    disconnecting or recharging or replacement of

    the battery, disconnection notice must be issued

    to the ASM on duty and work commenced after

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    20/32

    CAMTECH/S/2005/LAC/2.0 20

    the same is allowed and necessary precautions

    have been taken. This will ensure safety in train

    operation. Always use suitable goggles and rubber gloves

    and wears an apron while working with battery

    electrolyte.

    7.2 General Cleaning

    Check each cell of the battery set once everyfifteen days. Ensure that all connections are

    tight. Remove dust or dirt from the battery top

    and connections. Wipe the battery using a wet

    cloth piece and allow it to dry.

    At least once in three months, neutralize the acid

    on the battery covers and terminals with either

    ammonia or sodium bicarbonate solution in

    water before cleaning. Keep terminals and metalparts free of corrosion.

    7.3 Electrolyte

    Distilled water (IS 1069) should be used to top

    up the cells at regular intervals to maintain the

    recommended electrolyte level. The level goesdown on account of evaporation, the electrolyte

    level should never drop below the top of the

    plates.

    Do not let it spill out to avoid electrolyte loss

    and corrosion. Add distilled water only when the

    battery is charging or gassing.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    21/32

    CAMTECH/S/2005/LAC/2.0 21

    Electrolyte lost due to spillage should be

    replaced with proper amount of electrolyte of the

    same specific gravity as that of other cells of the battery. Under no other circumstances should

    electrolyte be added.

    7.4 Voltage and Specific Gravity.

    The specific gravity and the terminal voltage of

    batteries should be checked.

    Measurements must be taken after switchingOFF the charger of at least one hour.

    It is a good practice to switch off the charger of

    at least one or two battery sets for 4 hours or

    based on the battery set condition during

    inspection and maintenance trips to the station.

    This helps in not only accessing the condition of

    the battery but also provides a discharge cycle. Keep accurate records of the battery voltages

    and sp. gravity as these are extremely important.

    They provide a detail history of the performance

    of each cell. Variations observed from normal

    values pin point the degradation in battery

    condition which can be promptly corrected.

    In case, in a particular battery set, the specific

    gravity of individual cells are observed to bevarying considerably, the electrolyte must be

    exchanged / balanced between cells with higher

    value of specific gravity for those having lower

    value. This will also ensure uniform gravity in

    all of them. Balancing of electrolyte has to be

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    22/32

    CAMTECH/S/2005/LAC/2.0 22

    done for individual cell after taking out from the

    set.

    Records must include in the following proforma.

    Form - S&T/BCP

    ______Railway______Division

    Station_________

    Signal and Telecommunication Department

    SECONDARY BATTERY HISTORY CARDNo. of Cells: Installation date:

    Capacity (AH): Circuit reference:

    Battery Set no.: Charging current:

    Battery set voltage: Charger make:

    Battery make : Charger capacity:

    Cell no.

    Workdon

    eand

    remarks

    Signature

    Date

    Param

    eter

    1 2 - 10 - 15

    Specific

    gravity

    Cell

    voltage

    Specific

    gravity1220

    Cell volts

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    23/32

    CAMTECH/S/2005/LAC/2.0 23

    When the charge in the battery set has gone down

    considerably, recharging must be done at a

    current equal to 10% of the AH value until thespecific gravity of the cell came to 12105.

    7.5 Cable and connections

    Connectors and connecting cable should be

    flexible and sufficiently long to prevent strain on

    the battery terminals. The connecting cablesshould have lead coated eyelets/lugs for

    connections.

    Electrical connection should always be kept

    tight. Loose connections get heated up leading to

    failure.

    Terminals and connections should be coated

    with pure Vaseline or petroleum jelly or non

    oxidizing grease to prevent corrosion. Ifcorrosion occurred, it should be removed by

    wiping clean with a solution of washing soda

    and water (or dilute ammonia) taking care that

    the solution does not enter the cells.

    Grease shall not be used.

    7.6 Equalizing charge

    The battery, which is continuously used in Float

    Service should be given equlising charge to

    compensate for low/ uneven specific gravity of

    cells. Equilsing charge is given to cells once in a

    three months at fixed current (normally 1/10 th of

    AH capacity). The charging should be continued

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    24/32

    CAMTECH/S/2005/LAC/2.0 24

    till the voltage and specific gravity in all cell

    have remains constant for three consecutive half

    hourly readings.

    7.7 Miscellaneous

    The vent plugs should be kept in position and

    tight. If a vent plug is lost, it should be replaced

    early to prevent spillage of electrolyte.

    Defective cells should be disconnected andreplaced. Batteries showing irregularities, which

    can not be corrected, should be taken out of

    service and report made to proper authority.

    Only approved hydrometer and voltmeter should

    be used for recording observations. It is

    recommended that :

    Voltmeter should be of an accuracy class

    not inferior to 1.0 in accordance withIS:1248-68. The resistance of the voltmeter

    must be at least 1000 Ohms per Volt.

    7.8 Periodicity

    The periodicity of maintenance, will generally

    be as given below, except otherwise modified bythe concerned Railway.

    Maintainer Period

    ESM/WTM Weekly

    JE/SE Monthly

    SSE Every quarter

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    25/32

    CAMTECH/S/2005/LAC/2.0 25

    8. Trouble shooting

    Sr. Cause Remedy

    1. Battery does not charge.

    1.1 Disconnection in the

    charging circuit.

    Check the circuit

    and rectify.

    1.2 Blowing OFF of charger fuse

    AC or DC side

    Check the fuse

    and rectify

    1.3 Loose connections or highresistance at terminals

    Check theconnection, clean

    and tighten them.

    1.4 Defective charger not

    feeding current

    Replace the

    charger

    1.5 Wrong connections Check the

    connections and

    rectify

    2. Battery takes more time to charge2.1 Loose connection or higher

    resistance at terminals

    Open the

    connections and

    clean and the

    reconnect

    2.2 Charger not able to feed

    enough charging current

    Replace the

    charger

    2.3 Excessive discharge Charge thebattery separately

    2.4 Wrong connection Check the

    connection and

    rectify.

    2.5 The charger out put Voltage Adjust the

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    26/32

    CAMTECH/S/2005/LAC/2.0 26

    Sr. Cause Remedy

    may be less than 2.5 Volt percell.

    charger outputvoltage.

    2.6 Number of cells use may be

    more than the charger

    capacity.

    Adjust number of

    cells as per 2.15

    volt per cell

    3. Battery does not last for long

    3.1 Low electrolyte level Maintain the

    level properly3.2 Uneven specific gravity and

    voltage of the cells

    Equalize the

    specific gravity

    of each cell with

    the electrolyte

    3.3 Not properly or full charge Recharge again

    3.4 Leakage in some cells Replace them

    3.5 Reverse polarity on some

    cells

    Remove the

    reverse polaritycell from the set.

    3.6 Inadequate number of cells

    or load current is more.

    Installed the cells

    as per the load

    3.7 Low specific gravity Add the solution

    of higher specific

    gravity.

    3.8 Charger output voltage orcharging current may not be

    adequate

    Adjust the outputvoltage and

    charging current.

    3.9 Batter charger may not be

    adequate for charging battery

    of given AH

    Replace the

    charger with

    adequate capacity

    4. Battery over heats during charge or discharge

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    27/32

    CAMTECH/S/2005/LAC/2.0 27

    Sr. Cause Remedy

    4.1 Charging current very high,especially at the finish.

    Make propercharging current

    4.2 Charger voltage high. Check the voltage

    and adjust

    properly.

    4.3 Charged for longer period. Discharge the

    battery with

    suitable load.4.4 Over discharged or excessive

    load current

    Adjust the load

    current

    4.5 Poor ventilation or

    temperature is high

    Make proper

    ventilation

    4.6 Internal short circuit Replace the

    battery

    4.7 More sediment material inthe cell, old/worn out cells

    Replace the cell

    4.8 Low level of electrolyte Add the distilled

    water as per

    requirement

    5. Low electrolyte level

    5.1 Broke/cracked container of

    cell

    Replace the cell.

    5.2 Distilled water not recouped

    regular.

    Add the distilled

    water as per

    requirement

    5.3 Excessive charging Adjust the

    charger current

    5.4 Excessive heat Provide

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    28/32

    CAMTECH/S/2005/LAC/2.0 28

    Sr. Cause Remedy

    ventilation5.5 Vent caps missing Provide new vent

    caps

    6. Voltage and specific gravity of cells unequal

    6.1 Internal short circuit or

    leakage

    Replaced the cell.

    6.2 Leakage of electrolyte

    through crack cell, sealingcompound and covers

    Replaced the cell

    6.3 Dirty terminals of cell top Clean the

    terminals.

    6.4 Used with low electrolyte

    level

    Use proper

    electrolyte

    6.5 Sedimentation high inside

    the battery

    Replace the

    battery

    6.6 Plates worn out Replace the

    battery

    6.7 Impure electrolyte Replace the

    electrolyte and

    recharge the

    battery.

    7. Specific gravity is higherthen normal during float

    charging due to float voltage

    is high.

    Adjust floatvoltage.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    29/32

    CAMTECH/S/2005/LAC/2.0 29

    9. Spare parts

    The following spare parts and consumables willbe necessary.

    Acid resistance paint IS158-68

    Sulfuric acid IS-266

    Distilled water IS-1069

    Ammonia

    Sodium bicarbonate (washing soda) Petroleum jelly or Vaseline or non-oxidizing

    grease

    Cloth for cleaning

    Nuts and bolts

    Connectors and cables

    Cotton waste grade A

    Vent cum float guide plugs Floats

    Rubber gloves.

    10. Tools and measuring equipment

    Following tools and measuring equipment will

    be necessary:

    For measuring voltage, DC voltmeter ranges

    0 volts to 200 volts

    DC ammeter ranges 0 amps to 50 amps

    Syringe type hydrometer

    Crocodile clips

    Wires or cables of adequate current capacity

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    30/32

    CAMTECH/S/2005/LAC/2.0 30

    Battery charger with controls for charging

    current

    Spanner set

    Battery shunt meter

    Thermometer C range 0-80C

    Glass tube (20 to 30 cms long)

    Glass or PVC or porcelain or rubber

    container

    Glass rod (30 to 40 cms long )

    Nylon brush with tough bristles.

    11. Dos and Donts

    11.1 Dos

    Ensure that the positive and negative wires are

    connected to positive and negative terminalsrespectively, while connecting the charger to the

    batteries.

    If the batteries not in use, keep the battery in full

    charge condition by given an equalizing charge

    atleast once every month.

    Ensure that the float indicator is available and in

    working order.

    Electrolyte is highly corrosive and should be

    handled carefully to avoid injury to person or

    damage to clothing or equipment. If the

    electrolyte is accidentally spilled, it should be

    flushed with plenty of water immediately, after

    treating with washing soda solution.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    31/32

    CAMTECH/S/2005/LAC/2.0 31

    After the failure of power supply battery should

    be charged on boost mode i.e. load plus three

    ampere, preventing the battery from buckling of battery due to rising temperature and

    evaporation of distilled water.

    Ensure that charger float and boost voltages has

    been adjusted to 2.15 Volt per cell and 2.4 Volt

    per cell respectively.

    Ensure that charger is suitable for charging the

    AH capacity of battery used.

    11.2 Donts

    Do not allow over charging, excessive gassing

    and heating

    Do not allow the batteries to get fully discharge.

    Do not allow open flame smoking near the

    batteries to eliminate danger from explosion or

    fire.

    Extreme care must be exercised to avoid a spark

    or flash when changing connections or working

    on or near the battery.

    Battery lead should first be disconnected at a

    point remote from the battery set.

    Metal jugs should not be used for carrying waterrequired for topping up.

    Do not miss handle the cells, specially during

    transportation.

    Do not hold the cells by the electrode terminals.

    Lead Acid Cell March2005

    Ver 2.0

  • 8/14/2019 Handbook on Lead Acid Cell for Railway signaling

    32/32

    CAMTECH/S/2005/LAC/2.0 32