GP Dimming Panels: 120/277 V

38
GP Dimming Panels GRAFIK Systems Power Equipment 369401f 1 09.01.17 SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: GP dimming panels provide power and dimming for up to 144 load circuits and control any light source, including full-conduction, non-dimming. Models available with: • 120 V~ and 277 V~ input power. • 3 to 144 circuits. • Different feed types and breakers. GP Dimming Panels work with: • GRAFIK Eye 4000 Control Units. • GRAFIK 5000, GRAFIK 6000, GRAFIK 7000 Systems and Quantum Systems. • LP Dimming Panels. • XP Softswitch Panels. • DMX512 dimming systems via the 2LINK option. GP Dimming Panels: 120/277 V~ GP3/4 Mini-Size Panels GP8-24 Standard-Size Panels GP36 Large-Size Panels GP48-144 Large-Size Panels

Transcript of GP Dimming Panels: 120/277 V

Page 1: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 1 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GP dimming panels provide power and dimming for up to 144 load circuits and control any light source, including full-conduction, non-dimming.Models available with:

•120V~and277V~ input power.•3to144circuits.•Differentfeedtypesandbreakers.

GP Dimming Panels work with:•GRAFIKEye4000ControlUnits.•GRAFIK5000,GRAFIK6000,GRAFIK7000SystemsandQuantumSystems.

•LPDimmingPanels.•XPSoftswitchPanels.•DMX512dimmingsystemsviathe2LINKoption.

GP Dimming Panels: 120/277 V~

GP3/4 Mini-Size Panels

GP8-24 Standard-Size Panels

GP36 Large-Size Panels

GP48-144 Large-Size Panels

Page 2: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f209.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GP dimming panels provide power and dimming for up to 24loadcircuitsandcontrolanylightsource,includingfull-conduction, non-dimming.Models available with:

•230V~ input power.•3to24circuits.•Differentfeedtypesandbreakers.

GP Dimming Panels work with:•GRAFIKEye4000ControlUnits.•GRAFIK5000,GRAFIK6000,GRAFIK7000SystemsandQuantumSystems.

•LPDimmingPanels.•XPSoftswitchPanels.•DMX512dimmingsystemsviathe2LINKoption.

GP3/4 Mini-Size Panels

GP8-24 Standard-Size Panels

GP Dimming Panels: 230 V~ (CE)

Page 3: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 3 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GP dimming panels provide power and dimming for up to 24loadcircuitsandcontrolanylightsource,includingfull-conduction, non-dimming.Models available with:

•220–240V~ input power.•3to24circuits.•Differentfeedtypesandbreakers.

GP Dimming Panels work with:•GRAFIKEye4000ControlUnits.•GRAFIK5000,GRAFIK6000,GRAFIK7000SystemsandQuantumSystems.

•LPDimmingPanels.•XPSoftswitchPanels.•DMX512dimmingsystemsviathe2LINKoption.

GP3/4 Mini-Size Panels

GP8-24 Standard-Size Panels

GP Dimming Panels: 220– 240 V~ (non-CE)

Page 4: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 4 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Standards•ULRListed(Reference:ULFileE42071).•ComplieswithCSAorNOM(whereappropriate).•CaliforniaEnergyCommissionListed•SeismicCertified(TestMethodAC156.ReferenceOSHPDPreapprovalOSP-0215-10).

Power•Inputpower:120V~and277V~,50/60Hz,phase-

to-neutral.•BranchCircuitCapacity:–120V~(upto2000W/VA)–277V~(4500W/VA)–Minimumload:0W

•NumberofCircuits:3–144•BranchCircuitBreakers:ULR rated thermal magnetic. AICratings(otherratingsavailable):–120V~(10,000A)–277V~(14,000A)

•Lightningstrikeprotection:MeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto6000 V~andcurrentsurgesofupto3000A.

•10-yearpowerfailurememory:Automaticallyrestoreslighting to scene selected prior to power interruption.

Sources/Load TypesOperatesthesesourceswithasmoothcontinuousSquareLawdimmingcurveoronafull-conduction,non-dimmingbasis:

•Incandescent(Tungsten)/Halogen•MagneticLow-VoltageTransformer•LEDdriversspecifiedbythemanufacturertowork

with forward-phase dimming controls. *•Electroniclow-voltagetransformersspecifiedbythemanufacturertoworkwithforward-phasedimmingcontrols.

•LutronElectronicFluorescentDimmingBallasts•MagneticFluorescentLampBallasts•Optionalmodulesallowforcontrolof0–10V-,DSI,andPWMloadtypes.

•OperatesHIDsourcesonafull-conduction,non-dimmingbasis.

Wiring•Internal:Pre-wiredbyLutron.•Systemcommunications:Low-voltageIECPELV/NEC® Class2wiringconnectsdimmingpanelstoothercomponents.

•Line(mains)voltage:Feed,load,andcontrolcircuitwiringonly;nootherwiringorassemblyrequired.

Filter Chokes•Loadcurrentrisetimeismeasuredata90-degree

conduction angle.•10–90%ofload-currentwaveform:–350µSecrisetimeat50%dimmercapacity.–400µSecrisetimeat100%dimmercapacity.

•0–100%ofload-currentwaveform:–525µSecrisetimeat50%dimmercapacity.–600µSecrisetimeat100%dimmercapacity.

•Atnopointinthewaveformcantherateofcurrentchangeexceed300mAperµSec.

•ConsultLutronforhigherrisetimeoptions.

Dimming Cards•Panelcurrentratingsarelistedforcontinuousoperation;UL®listedspecificallyforeachlightsource.

•RTISSfiltercircuittechnologycompensatesforincominglinevoltagevariations;novisibleflickerwith+/–2%changeinRMSvoltage/cycleand+/–2% Hzchangeinfrequency/second.

•Arclessrelayair-gapOFFswitches(oneperloadcircuit)ensureopenloadcircuitswhenOFFfunctionis selected; eliminate arcing at mechanical contacts when loads are switched.

Physical Design•Enclosure:NEMA-Type1(Type2availableonrequest);IP-20protection;16U.S.GaugeSteel;indooruseonly.

•Weight:30to1300lb(14to590kg).•Mounting:Surface-mountonly.Allowspacefor

ventilating.•SeismicCertificationLimits:SDS=2.5 g,z/h=1.0,IP=1.5forwallorwall/floormountedpanels.SDS=1.5 gforfloor-mountpanelsonly.ContactLutronfordetails.

Environment / Heat Dissipation•Patented,ribbedaluminumheatsinkbasecoolspanelbyconvection;nofans.

•32°F–104°F(0°C–40°C);relativehumiditylessthan90%,non-condensing.

Specifications: 120/277 V~

continued on next page…* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistof

compatibleproducts.

Page 5: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f509.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Short Circuit Current Ratings(otherratingsavailable)

Panel Type Voltage Std. Min. SCCR RatingGPMainLug(standard-andlarge-size) 120V~;277V~ 25,000A

GPMainBreaker(standard-size)120V~ 10,000A277V~ 18,000A

GPMainBreaker(large-size)120V~ 25,000A277V~ 25,000A

GPMini-Size120V~ 10,000A277V~ 14,000A

GPMini-Size(feed-through)120V~ 10,000A277V~ 14,000A

Specifications: 120/277 V~(continued)

Page 6: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 6 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring•Internal:Pre-wiredbyLutron.•Systemcommunications:Low-voltageIECPELV/NEC® Class2wiringconnectsdimmingpanelstoothercomponents.

•Line(mains)voltage:Feed,load,andcontrolcircuitwiringonly;nootherwiringorassemblyrequired.

Filter Chokes•Loadcurrentrisetimeismeasuredata90-degreeconductionangle,with120V~ input power.

•10-90%ofloadcurrentwaveform:–350µSecrisetimeat50%dimmercapacity.–400µSecrisetimeat100%dimmercapacity.

•0–100%ofloadcurrentwaveform:–525µSecrisetimeat50%dimmercapacity.–600µSecrisetimeat100%dimmercapacity.

•Atnopointinthewaveformcantherateofcurrentchangeexceed300mAperµSec.

•ConsultLutronforhigherrisetimeoptions.

Dimming Cards•Panelcurrentratingsarelistedforcontinuous

operation.•RTISSfiltercircuittechnologycompensatesforincominglinevoltagevariations;novisibleflickerwith+/–2%changeinRMSvoltage/cycleand+/–2%Hzchangeinfrequency/second.

•Arclessrelayair-gapOFFswitches(oneperloadcircuit)ensureopenloadcircuitswhenOFFfunctionis selected; eliminate arcing at mechanical contacts when loads are switched.

Physical Design•Enclosure:NEMA-Type1(Type 2availableonrequest),IP-20protection;16U.S.GaugeSteel;indooruseonly.

•Weight:30to175lb(14to80kg).•Mounting:Surface-mountonly;allowspacefor

ventilating.

Environment/Heat Dissipation•Patented,ribbedaluminumheatsinkbasecoolspanelbyconvection;nofans.

•32°F–104°F(0°C–40°C);relativehumiditylessthan90%,non-condensing.

Standards•ComplieswithCE.

Power•Inputpower:230V~50/60Hz,phase-to-neutral.•BranchCircuitCapacity:10A–Minimumload:0W

•NumberofCircuits:3–24•BranchCircuitBreakers:IEC-ratedthermalmagnetic.AICrating(otherratingsavailable):6000A

•Lightningstrikeprotection:MeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto6000V~andcurrentsurgesofupto3000A.

•10-yearpowerfailurememory:Automaticallyrestoreslighting to scene selected prior to power interruption.

Sources/Load TypesOperatesthesesourceswithasmoothcontinuousSquareLawdimmingcurveoronafullconduction,non-dimmingbasis:

•Incandescent(Tungsten)/Halogen•MagneticLow-VoltageTransformer•LEDdriversspecifiedbythemanufacturertowork

with forward-phase dimming controls. *•Electroniclow-voltagetransformersspecifiedbythemanufacturertoworkwithforward-phasedimmingcontrols.

•LutronElectronicFluorescentDimmingBallasts•MagneticFluorescentLampBallasts•Optionalmodulesallowforcontrolof0–10V-,DSI,andPWMloadtypes.

•OperatesHIDsourcesonafull-conduction,non-dimmingbasis.

Specifications: 230 V~ (CE)

* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistofcompatibleproducts.

Page 7: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 7 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring•Internal:PrewiredbyLutron.•Systemcommunications:Low-voltageIECPELV/NEC® Class2wiringconnectsdimmingpanelstoothercomponents.

•Line(mains)voltage:Feed,load,andcontrolcircuitwiringonly;nootherwiringorassemblyrequired.

Filter Chokes•Loadcurrentrisetimeismeasuredata90-degreeconductionangle,with120V~ input power.

•10–90%ofloadcurrentwaveform:–350µSecrisetimeat50%dimmercapacity.–400µSecrisetimeat100%dimmercapacity.

•0–100%ofloadcurrentwaveform:–525µSecrisetimeat50%dimmercapacity.–600µSecrisetimeat100%dimmercapacity.

•Atnopointinthewaveformcantherateofcurrentchangeexceed300mAperµSec.

•ConsultLutronforhigherrisetimeoptions.

Dimming Cards•Panelcurrentratingsarelistedforcontinuous

operation.•RTISSfiltercircuittechnologycompensatesforincominglinevoltagevariations:Novisibleflickerwith+/–2%changeinRMSvoltage/cycleand+/–2%Hzchangeinfrequency/second.

•Arclessrelayair-gapOFFswitches(oneperloadcircuit)ensureopenloadcircuitswhenOFFfunctionis selected; eliminate arcing at mechanical contacts when loads are switched.

Physical Design•Enclosure:NEMA-Type1(Type 2availableonrequest),IP-20protection;16U.S.GaugeSteel;indooruseonly.

•Weight:30to175lb(14to80kg).•Mounting:Surface-mountonly;allowspacefor

ventilating.

Environment/Heat Dissipation•Patented,ribbedaluminumheatsinkbasecoolspanelbyconvection;nofans.

•32°F–104°F(0°C–40°C);relativehumiditylessthan90%,non-condensing.

Power•Inputpower:220–240V~50/60Hz,

phase-to-neutral.•BranchCircuitCapacity:16Aor10A–Minimumload:0W

•NumberofCircuits:3–24•BranchCircuitBreakers:IEC-ratedthermalmagnetic.AICrating(otherratingsavailable):6000A

•Lightningstrikeprotection:MeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto6000V~andcurrentsurgesofupto3000A.

•10-yearpowerfailurememory:Automaticallyrestoreslighting to scene selected prior to power interruption.

Sources/Load TypesOperatesthesesourceswithasmoothcontinuousSquareLawdimmingcurveoronafull-conduction,non-dimmingbasis:

•Incandescent(Tungsten)/Halogen•MagneticLow-VoltageTransformer•LEDdriversspecifiedbythemanufacturertowork

with forward-phase dimming controls. *•Electroniclow-voltagetransformersspecifiedbythemanufacturertoworkwithforward-phasedimmingcontrols.

•LutronElectronicFluorescentDimmingBallasts•MagneticFluorescentLampBallasts•Optionalmodulesallowforcontrolof0–10V-,DSI,andPWMloadtypes.

•OperatesHIDsourcesonafull-conduction,non-dimmingbasis.

Specifications: 220 – 240 V~ (non-CE)

* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistofcompatibleproducts.

Page 8: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f809.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Prefix•GP:GPDimmingPanel

Number of Load Circuits•Indicatesnumberofloadcircuitsinthepanel

Voltage•120:120V~•277:277V~

Feed Type•2:1-phase,2-wire•3:1-phase,3-wire(splitphase)•4:3-phase,4-wire

Panel Feed•ML:MainLugsonly•Mxx:MainBreakerwithxx=breakersizeinAmps

Branch Circuit Breakers•20:20Abranchcircuitbreakers•15:15Abranchcircuitbreakers

Custom Panel Suffix•Indicatespanelwithspecialoptions

How to Build a GP Model Number: 120/277 V~

Prefix Feed Type

Number of Load Circuits

Voltage Panel Feed

Branch Circuit

Breakers

Custom Panel Suffix

G P 12 – 120 4 ML – 20 – CGP–XXX

Page 9: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 9 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Prefix•GP:GPDimmingPanel

Number of Load Circuits•Indicatesnumberofloadcircuitsinthepanel

Voltage•230:CE

Feed Type•2:1-phase,2-wire•4:3-phase,4-wire

Panel Feed•IS:IsolatorSwitch

Branch Circuit Breakers•10:10Abranchcircuitbreakers

Region Suffix•CE:230V~

Custom Panel Suffix•Indicatespanelwithspecialoptions

How to Build a GP Model Number: 230 V~

Prefix Feed Type

Number of Load Circuits

Voltage Panel Feed

Branch Circuit

Breakers

Custom Panel Suffix

G P 12 – 230 4 IS – 1 0 CE – CGP–XXXRegion Suffix

Page 10: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 10 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Prefix•GP:GPDimmingPanel

Number of Load Circuits•Indicatesnumberofloadcircuitsinthepanel

Voltage•240:220–240V~

Feed Type•2:1-phase,2-wire•4:3-phase,4-wire

Panel Feed•IS:IsolatorSwitch

Branch Circuit Breakers•16:16Abranchcircuitbreakers•10:10Abranchcircuitbreakers

Region Suffix•AU:220–240V~

Custom Panel Suffix•Indicatespanelwithspecialoptions

How to Build a GP Model Number: 220 – 240 V~

Prefix Feed Type

Number of Load Circuits

Voltage Panel Feed

Branch Circuit

Breakers

Custom Panel Suffix

G P 12 – 240 4 IS – 1 6 AU – CGP–XXXRegion Suffix

Page 11: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 11 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 120/277 V~

GP3/4 Mini-Size Models 1

120 V~ PowerPanel Branch Ratings

Number of Circuits Feed Type Maximum

FeedCircuit Breakers 2

Maximum Dimmed Hot Load 3

GP3

1-phase,2-wire40A 15A 1500W/VA

40A 20A 2000W/VA

1-phase, 3-wire30A 15A 1500W/VA

40A 20A 2000W/VA

3-phase, 4-wire15A 15A 1500W/VA

20A 20A 2000W/VA

GP4 Feed-through20A 15A4 1500W/VA

20A 20A4 2000W/VA

277 V~ PowerPanel Branch Ratings

Number of Circuits Feed Type Maximum

FeedCircuit Breakers 2

Maximum Dimmed Hot Load 3

GP31-phase,2-wire 40A 20A 4500W/VA

3-phase, 4-wire 20A 20A 4500W/VA

GP4 Feed-through 20A 20A4 4500W/VA

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.2 20/16A,15/12Acontinuousloadrating.3 Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.4 Breakerslocatedindistributionpanelsuppliedbyothers.

continued on next page…

Page 12: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f1209.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 120/277 V~(continued)

GP8 – 24 Standard-Size Models 1

120 V~ PowerPanel Branch Ratings

Number of Circuits Feed Type Panel Feed Maximum

FeedCircuit Breakers 2

Maximum Dimmed Hot Load 3

GP8

1-phase,2-wire MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

1-phase, 3-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

60AMainBreaker 60A 15A 1500W/VA

80AMainBreaker 80A 20A 2000W/VA

3-phase, 4-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

50AMainBreaker 50A 15A 1500W/VA

60AMainBreaker 60A 20A 2000W/VA

GP12

1-phase, 3-wire MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

3-phase, 4-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

60AMainBreaker 60A 15A 1500W/VA

80AMainBreaker 80A 20A 2000W/VA

GP16

1-phase, 3-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

125AMainBreaker 125A 15A 1500W/VA

175AMainBreaker 175A 20A 2000W/VA

3-phase, 4-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

100AMainBreaker 100A 15A 1500W/VA

125AMainBreaker 125A 20A 2000W/VA

GP20 3-phase, 3-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

110AMainBreaker 110A 15A 1500W/VA

150AMainBreaker 150A 20A 2000W/VA

GP24 3-phase, 4-wire

MainLugsOnly175A 15A 1500W/VA

175A 20A 2000W/VA

125AMainBreaker 125A 15A 1500W/VA

175AMainBreaker 175A 20A 2000W/VA

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.2 20/16A,15/12Acontinuousloadrating.3 Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.

continued on next page…

Page 13: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 13 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 120/277 V~(continued)

GP8 – 24 Standard-Size Models 1(continued)277 V~ Power

Panel Branch Ratings

Number of Circuits Feed Type Panel Feed Maximum

FeedCircuit Breakers

Maximum Dimmed Hot Load 2

GP8

1-phase,2-wire MainLugsOnly 175A 20A 4500W/VA

3-phase, 4-wireMainLugsOnly 175A 20A 2000W/VA

60AMainBreaker 60A 20A 2000W/VA

GP12 3-phase, 4-wireMainLugsOnly 175A 20A 2000W/VA

80AMainBreaker 80A 20A 2000W/VA

GP16 3-phase, 4-wireMainLugsOnly 175A 20A 2000W/VA

125AMainBreaker 125A 20A 2000W/VA

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.2 Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.

continued on next page…

Page 14: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 14 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 120/277 V~(continued)

GP36 – 144 Large-Size Models 1

120 V~ PowerPanel Branch Ratings

Number of Circuits Feed Type Panel Feed Maximum

FeedCircuit Breakers 2

Maximum Dimmed Hot Load 3

GP36 3-phase, 4-wire

MainLugsOnly750A 15A 1500W/VA

750A 20A 2000W/VA

200AMainBreaker 200A 15A 1500W/VA

250AMainBreaker 250A 20A 2000W/VA

GP48 3-phase, 4-wire

MainLugsOnly750A 15A 1500W/VA

750A 20A 2000W/VA

250AMainBreaker 250A 15A 1500W/VA

350AMainBreaker 350A 20A 2000W/VA

GP60 3-phase, 4-wire

MainLugsOnly750A 15A 1500W/VA

750A 20A 2000W/VA

300AMainBreaker 300A 15A 1500W/VA

400AMainBreaker 400A 20A 2000W/VA

GP72 3-phase, 4-wire

MainLugsOnly750A 15A 1500W/VA

750A 20A 2000W/VA

350AMainBreaker 350A 15A 1500W/VA

400AMainBreaker 400A 20A 2000W/VA

GP96-144 3-phase, 4-wire MainLugsOnly750A 15A 1500W/VA

750A 20A 2000W/VA

277 V~ PowerPanel Branch Ratings

Number of Circuits Feed Type Panel Feed Maximum

FeedCircuit Breakers 2

Maximum Dimmed Hot Load 3

GP36 3-phase, 4-wireMainLugsOnly 750A 20A 4500W/VA

250AMainBreaker 250A 20A 4500W/VA

GP48 3-phase, 4-wireMainLugsOnly 750A 20A 4500W/VA

350AMainBreaker 350A 20A 4500W/VA

GP60 3-phase, 4-wireMainLugsOnly 750A 20A 4500W/VA

400AMainBreaker 400A 20A 4500W/VA

GP72 3-phase, 4-wireMainLugsOnly 750A 20A 4500W/VA

400AMainBreaker 400A 20A 4500W/VA

GP96-144 3-phase, 4-wire MainLugsOnly 750A 20A 4500W/VA

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.2 20/16A,15/12Acontinuousloadrating.3 Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.

Page 15: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f1509.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 230 V~

GP3/4 Mini-Size Models 1

230 V~ (CE) PowerNumber of Circuits Feed Type Maximum

FeedPanel Feed / Branch Circuit Breakers

GP31-phase,2-wire 30A 10A

3-phase, 4-wire 10A 10A

GP4 Feed-through 10A 10A2

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.2 Breakerslocatedindistributionpanelsuppliedbyothers.

GP8 – 24 Standard-Size Models 1

230 V~ (CE) PowerNumber of Circuits Feed Type Panel Feed Maximum

Feed Branch Circuit Breakers

GP81-phase,2-wire IsolatorSwitch 125A 10A

3-phase, 4-wire IsolatorSwitch 125A 10A

GP12 3-phase, 4-wire IsolatorSwitch 125A 10A

GP16 3-phase, 4-wire IsolatorSwitch 125A 10A

GP20 3-phase, 4-wire IsolatorSwitch 125A 10A

GP24 3-phase, 4-wire IsolatorSwitch 125A 10A

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.

Page 16: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 16 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Ratings: 220 – 240 V~

GP3/4 Mini-Size Models 1

220 – 240 V~ PowerNumber of Circuits Feed Type Maximum

FeedPanel Feed / Branch Circuit Breakers

GP3

1-phase,2-wire48A 16A

30A 10A

3-phase, 4-wire16A 16A

10A 10A

GP4 Feed-through16A 16A

10A 10A

GP8 – 24 Standard-Size Models 1

220 – 240 V~ PowerNumber of Circuits Feed Type Panel Feed Maximum

Feed Branch Circuit Breakers

GP8

1-phase,2-wire IsolatorSwitch 125A16A

10A

3-phase, 4-wire IsolatorSwitch 125A16A

10A

GP12 3-phase, 4-wire IsolatorSwitch 125A16A

10A

GP16 3-phase, 4-wire IsolatorSwitch 125A16A

10A

GP20 3-phase, 4-wire IsolatorSwitch 125A16A

10A

GP24 3-phase, 4-wire IsolatorSwitch 125A16A

10A

1 Onlystandardpanelslisted.ConsultLutronforfurtheroptions.

Page 17: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 17 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Dimensions: GP3/4 Mini-Size PanelsAlldimensionsshownas:in(mm)

Top View

11 (279)

61⁄4 (160)

35 ⁄8(92)51⁄8 (130)

15⁄8(41)

7/8in(22mm)diameterIECPELV/NEC®Class 2wiring only.

Left-Side View

18(457)

191⁄2 (495)

211⁄8 (537)

11 (279)95⁄8 (244)

Front View

Keyholesaccept1/4in(6 mm)mountingbolts,maximum.#10M6recommended.

Right-Side View

23⁄4(70)

51⁄4(133)

11⁄8(29)

13⁄16(30)

Bottom View

Loadcircuitwiring Feedwiring

23⁄4(70)

11⁄2(38)

51⁄2(140)

11⁄2(38)

11 (279)

Page 18: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f1809.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Dimensions: GP8 – 24 Standard-Size PanelsAlldimensionsshownas:in(mm)

Bottom View

Top View

28(711)

12(304)

4(100) Suggestedloadwiring entries.

Suggestedfeedwiring entry.

2(50)2(50)

13 (330)

12(304)

Right-Side View

Removabletop cover

7/8in(22mm)diameterIECPELV/NEC® Class 2wiringonly.

2(50)

Left-Side View

33 (838)

35(889)

Front View

28(711)

12(304)

37 (940)

Keyholesaccept5/16in(8 mm)mountingbolts,maximum.1/4in(M8)recommended.

Page 19: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 19 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Dimensions: GP36 Large-Size PanelsAlldimensionsshownas:in(mm)

* Availabletopunchforalternatefeedwiring.**Availabletopunchforalternateloadcircuitwiring.

Top View

261⁄8(653)

23(580)

141⁄8 (360) 6(150)

51⁄2(140)

Suggestedloadandfeed wiring entry.

Back View261⁄8(653)251⁄16(627)

17⁄8(47)

9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

91⁄2 (237)

545 ⁄16 (1358)

80(2000)

113⁄4 (294)

Right-Side View

6in(150mm)diameter*

3/4in(20mm)diameterIECPELV/NEC® Class 2wiringonly.

Left-Side View

101⁄2 (263)

141⁄8 (353)

87(2175)

843⁄4 (2120)

86(2170)

541⁄2 (1363)

301⁄2 (763)

61⁄2 (163)

4in(100mm)diameter**

Bottom View

241⁄14(633)235 ⁄16(583)

261⁄8(653)

23⁄16(55)2(50)17⁄8(47)11⁄8(28)

9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

3in(75mm)squarearea*

8(200)

15⁄16(33)

11 (275)

1115 ⁄16 (298)

141⁄8 (353)

Page 20: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2009.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Dimensions: GP48/60/72 Large-Size PanelsAlldimensionsshownas:in(mm)

* Availabletopunchforalternatefeedwiring.**Availabletopunchforalternateloadcircuitwiring.

525 ⁄16(1308)23(580) 23(580)

141⁄8 (360) 6(150)

51⁄2(140)

Top View

Suggestedloadandfeed wiring entry.

511⁄8(1278)271⁄4(681)

251⁄16(627) 17⁄8(48)

50(1250)

Back View9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

91⁄2 (237)

545 ⁄16 (1358)

80(2000)

113⁄4 (294)

Right-Side View

6in(150mm)diameter*

3/4in(20mm)diameterIECPELV/NEC® Class 2wiringonly.

101⁄2 (263)

141⁄8 (353)

Left-Side View

87(2175)

843⁄4 (2120)

86(2170)

541⁄2 (1363)

301⁄2 (763)

61⁄2 (163)

4in(100mm)diameter**

Bottom View507⁄16(1261)

497⁄16(1236)

245 ⁄16(633)

2815 ⁄16(723)

235 ⁄16(583)

28(700)23⁄16(55)

17⁄8(48)

8(200)

15⁄16(33)

11 (275)

1115 ⁄16 (298)

141⁄8 (353)

9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

3in(75mm)squarearea*

Page 21: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2109.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Dimensions: GP96 – 144 Large-Size Panels(twounitsinstalledback-to-back)Alldimensionsshownas:in(mm)

* Availabletopunchforalternatefeedwiring.**Availabletopunchforalternateloadcircuitwiring.

525 ⁄16(1308)23(580) 23(580)

281⁄4 (720)

141⁄8 (360)

6(150)

51⁄2(140)

Top View

Suggestedloadandfeed wiring entry.

511⁄8(1278)271⁄4(681)

251⁄16(627) 17⁄8(48)

50(1250)

Back View of One Unit9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

87(2175)

843⁄4 (2120)

86(2170)

541⁄2 (1363)

301⁄2 (763)

61⁄2 (163)

101⁄2 (263)

141⁄8 (353)

Left-Side View

4in(100mm)diameter**

3/4in(20mm)diameterIECPELV/NEC® Class 2wiringonly.

Bottom View507⁄16(1261)

497⁄16(1236)

245 ⁄16(633)

2815 ⁄16(723)

235 ⁄16(583)

28(700)23⁄16(55)

17⁄8(47)

3in(75mm)squarearea*

8(200)

15⁄16(33)

11 (275)

115 ⁄16 (298)

141⁄8 (353)

9/16in(14mm)diametermountinghole.Use1/2in(13mm)hardware.

91⁄2 (237)

545 ⁄16 (1358)

80(2000)

113⁄4 (294)

Right-Side View

6in(150mm)diameter*

3/4in(20mm)diameterIECPELV/NEC® Class 2wiringonly.

Page 22: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2209.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Surfacemountindoors.•Panelgeneratesheat.Mountonlywhereambienttemperaturewillbe0–40°C(32–104°F).

•Thisequipmentisaircooled.Donotblockventsorwarrantywillbevoid.Leave12in(310mm)clearancesabove,below,andinfrontofpanel.Noclearancenecessary on sides.

•Reinforcewallstructureforweightandlocalcodes.

Panel Maximum BTUs/Hour

Weight (without packaging)

GP3/4 685 30lb(14kg)

•Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudiblenoiseisacceptable.

•Mountpanelssoline(mains)voltagewiringisatleast6ft(1.8m)fromsoundorelectronicequipmentandwiring.

•GPpanelsmustbemountedwithin7°oftruevertical.•Formaximumfeedandwiresizes,consultWiring

Overview page.Note:Waterdamagespanels.Installwheretheywillnot get wet.

Mounting: GP3/4 Mini-Size Panels

Front View

IECPELV/NEC® Class2wiring

Terminalblocksfor load circuits

Branchcircuitbreakers

Feedwiring

Loadcircuitwiring

Raceway

Side View

12in(310mm)minimum

12in(310mm)minimum

IECPELV/NEC® Class2wiring

12in(310mm)minimum

Wall

Page 23: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2309.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Surfacemountindoors.•Panelgeneratesheat.Mountonlywhereambienttemperaturewillbe32–104°F(0–40°C).

•Thisequipmentisaircooled.Donotblockventsorwarrantywillbevoid.Leave12in(310mm)clearancesabove,below,andinfrontofpanel.LeaveclearanceonsidesforIECPELV/NEC®Class2wiring.

•Reinforcewallstructureforweightandlocalcodes.

Panel Maximum BTUs/Hour

Weight (without packaging)

GP8 1365 115lb(52kg)GP12 2045 130lb(59kg)GP16 2725 145lb(66kg)GP20 3405 160lb(73kg)GP24 4085 175lb(80kg)

•Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudiblenoiseisacceptable.

•Mountpanelssoline(mains)voltagewiringisatleast6ft(1.8m)fromsoundorelectronicequipmentandwiring.

•GPpanelsmustbemountedwithin7°oftruevertical.•Formaximumfeedandwiresizes,consultWiring

Overview page.Note:Waterdamagespanels.Installwheretheywillnot get wet.

Mounting: GP8 – 24 Standard-Size Panels

Front View

Ceiling

Raceway

Feedwiring

Loadcircuitwiring

Terminalblocksfor load circuits

IECPELV/NEC® Class2wiring

Mainlugsormainbreaker

Side View

12in(310mm)minimum

12in(310mm)minimum

IECPELV/NEC® Class2wiring

Airflow

12in(310mm)minimum

Wall

Page 24: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2409.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Atleast8.67ft(2650mm)betweenthefloorandthesuspendedceilingisrequiredforthislayout.Note:Waterdamagespanels.Installwheretheywillnot get wet.

Mounting One Panel Above Another

* 6in(160mm)minimumapprovedforthislayoutonly.

Side View(GP8–24)

Suspendedceiling depth

Mountingholes

IECPELV/NEC® Class2wiring

Airflow

Mountingholes

Wall

Front View(GP8–24)

Ceiling

Raceway

Loadcircuitwiring

Feedwiring

Mainlugsormainbreaker

IECPELV/NEC® Class2wiring

12 in(310 mm)minimum

8.67 ft(2650 mm)minimum

7.5 ft(2280 mm)

6.5 ft(1950 mm)

3 ft 45⁄8 in (1030 mm)

6 in(160 mm)minimum*

12 in(310 mm)minimum

Page 25: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2509.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Surfacemountindoors.•Panelgeneratesheat.Mountonlywhereambienttemperaturewillbe32–104°F(0–40°C).

•Thisequipmentisaircooled.Donotblockventsorwarrantywillbevoid.Leave12in(310mm)clearancesaboveandinfrontofpanel.LeaveclearanceonsidesforIECPELV/NEC®Class 2wiring.

Panel Maximum BTUs/Hour

Weight (without packaging)

GP36 4350 325lb(147kg)GP48 5800 550lb(250kg)GP60 7250 600lb(273kg)GP72 8700 650lb(295kg)

•Mountpanelonfloorandagainstawall.Use1/2in(13 mm)mountingbolts.

•Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudiblenoiseisacceptable.

•Mountpanelssoline(mains)voltagewiringisatleast6ft(1.8m)fromsoundorelectronicequipmentandwiring.

•GPpanelsmustbemountedwithin7°oftruevertical.

GP36-72 MountingGP36consistsoftherightsidemoduleonly.Mountasshown.

Alternate Conduit Locations•Runfeedwiringinfrombottom.•Runloadcircuitwiringinfromleftside.

Note:Waterdamagespanels.Installwheretheywillnot get wet.

Mounting: GP36 – 72 Large-Size Panel

Side View

12in(310mm)minimum

3ft(930mm)minimum

IECPELV/NEC® Class2wiring

Airflow

Wall

Front View

Ceiling

Raceway

Feedandloadcircuit wiring

Mainlugsormainbreaker

IECPELV/NEC® Class2wiring

Terminalblocksfor load circuits

GP36

GP48–72

Page 26: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2609.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Surfacemountindoors.•Panelgeneratesheat.Mountonlywhereambienttemperaturewillbe32–104°F(0–40°C).

•Thisequipmentisaircooled.Donotblockventsorwarrantywillbevoid.Leave12in(310mm)clearancesaboveandinfrontofpanel.LeaveclearanceonsidesforIECPELV/NEC®Class 2wiring.

Panel Maximum BTUs/Hour

Weight (without packaging)

GP96-144 17400 1300lb(590kg)

•Mountpanelonfloorandagainstawall.Use1/2in(13 mm)mountingbolts.

•Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudiblenoiseisacceptable.

•Mountpanelssoline(mains)voltagewiringisatleast6ft(1.8m)fromsoundorelectronicequipmentandwiring.

•GPpanelsmustbemountedwithin7°oftruevertical.

GP96-144 Mounting•Allowairflowand3ft(92cm)clearancefromfronts/

sides of panel as shown.•NotetheextraIECPELV/NEC®Class 2wiring.

Alternate Conduit Locations•Runfeedwiringinfrombottom.•Runloadcircuitwiringinfromleftside.

Note:Waterdamagespanels.Installwheretheywillnot get wet.

Mounting: GP96 – 144 Large-Size Panel

Front View

Ceiling

Raceway

Feedandloadcircuit wiring

Mainlugsormainbreaker

IECPELV/NEC® Class2wiring

Terminalblocksfor load circuits

Side View

12in(310mm)minimum

3ft(930mm)minimum

IECPELV/NEC® Class2wiring

Airflow

Wall

Page 27: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2709.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wire Sizes120/277 V~

•PowerFeed:14 AWG(2.0 mm2)to8 AWG(6.0 mm2)•NeutralFeed:14 AWG(2.0 mm2)to6 AWG(10.0 mm2)•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to6 AWG(10.0 mm2)

230 V~ (CE), 220 – 240 V~

•PowerFeed:18 AWG(1.0 mm2)to4 AWG(25.0 mm2)•NeutralFeed:14 AWG(2.0 mm2)to6 AWG(10.0 mm2)•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to6 AWG(10.0 mm2)

Wiring TipsWireGP3Mini-Sizepanelssimilarlytoalighting distributionpanel:

•Runfeedandloadwiring;nootherwiringorassemblyrequired.

•Commonneutralsarenotpermitted.Runseparate neutrals for each load circuit.GP3 panels can provide temporary lighting.

•Wireallloads.•Donotremovethebypassjumpersthatprotectthe

dimming modules.•Usebranchcircuitbreakerstoswitchlightsonandoff.

Wiring Overview: GP3 Mini-Size Panels(120/277V~,230V~[CE],220–240V~)

SH1

H1

DH2

SH2

DH3

SH3

DH1

H2

H3

SL1

L1

DL2

SL2

DL3

SL3

DL1

L2

L3

IECPELV/NEC® Class2wiring

Terminalblock

Ground

PanelFeedWiring

PowerFeed(Line/Hot)

NeutralFeed

SH1

H1

DH2

SH2

DH3

SH3

DH1

H2

H3

SL1

L1

DL2

SL2

DL3

SL3

DL1

L2

L3

Load

Bypassjumpers(Donotremove)

TypicalLoadCircuit

DimmedLine/Hot

LoadNeutral

120/277 V~SH1

H1

DH2

SH2

DH3

SH3

DH1

H2

H3

SL1

L1

DL2

SL2

DL3

SL3

DL1

L2

L3

Load

Bypassjumpers(Donotremove)

TypicalLoadCircuit

DimmedLine/Hot

LoadNeutral

230 V~ (CE), 220 – 240 V~

OR

Page 28: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2809.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wire Sizes•PowerFeed:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•NeutralFeed:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)

Wiring TipsWireGP4Mini-Sizepanelssimilarlytoalightingdistributionpanel:

•Runfeedandloadwiring;nootherwiringorassemblyrequired.

•Commonneutralsarenotpermitted.Runseparateneutrals for each load circuit.GP4 panels can provide temporary lighting.

•Wireallloads.•Donotremovethebypassjumpersthatprotectthe

dimming modules.

Wiring Overview: GP4 Mini-Size Panels(120/277V~,230V~[CE],220–240V~)

PanelFeedWiring

PowerFeed(Line/Hot)

NeutralFeed

DH1

SH1

H1

N1

N1

DH2

SH2

H2

N2

N2

IECPELV/NEC® Class2wiring

Terminalblock

Ground

DH1

SH1

H1

N1

N1

DH2

SH2

H2

N2

N2

Load

Bypassjumpers(Donotremove)

TypicalDimmingLeg

DimmedLine/Hot

LoadNeutral

Page 29: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f2909.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wire Sizes•PowerFeedStandardMainLugs:14 AWG(2.0 mm2)to2/0 AWG(70.0 mm2)•PowerFeedDual-TapMainLugs:6 AWG(10.0 mm2)to4/0 AWG(120 mm2)•NeutralFeed:6 AWG(10.0 mm2)to350 mcm(177.0 mm2)•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to6 AWG(10.0 mm2)

Wiring TipsWireGP8–24Standard-Sizepanels similarly to a lighting distributionpanel:

•Runfeedandloadwiring;nootherwiringorassemblyrequired.

•Commonneutralsarenotpermitted.Runseparateneutralsforeachloadcircuit.GP8–24panelscanprovidetemporary lighting.

•Wireallloads.•Donotremovethebypassjumpers

that protect the dimming modules.•Usebranchcircuitbreakerstoswitch

lights on and off.

Wiring Overview: GP8 – 24 Standard-Size Panels(120/277V~)

DH1

SH1

H1

DH1

SH1

PanelFeedWiringPowerFeed

(Line/Hot)NeutralFeed

DH1

SH1

H1

DH1

SH1

TypicalLoadCircuit

Load

Bypassjumpers(Donotremove)

LoadNeutral

DimmedLine/Hot

Terminalblock

Branchcircuitbreakers

IECPELV/NEC® Class2wiring

Page 30: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 30 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wire Sizes•PowerFeed:14 AWG(2.0 mm2)to2 AWG(35.0 mm2)•NeutralFeed:14 AWG(2.0 mm2)to2 AWG(35.0 mm2)•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)

Wiring TipsWireGP8–24Standard-Sizepanels similarly to a lighting distributionpanel.

•Runfeedandloadwiring;nootherwiringorassemblyrequired.

•Commonneutralsarenotpermitted.Runseparateneutralsfor each load circuit.GP8–24panelscanprovidetemporary lighting.

•Wireallloads.•Donotremovethebypassjumpers

that protect the dimming modules.•Usebranchcircuitbreakersto

switch lights on and off.

Wiring Overview: GP8 – 24 Standard-Size Panels(230V~[CE],220–240V~)

DL1

SL1

L1

DL2

SL2

L2

N1

N1

PanelFeedWiringPowerFeed

(Line/Hot)NeutralFeed

DL1

SL1

L1

DL2

SL2

L2

N1

N1

TypicalLoadCircuit

Load

Bypassjumpers(Donotremove)

DimmedLive

LoadNeutral

Terminalblock

Branchcircuitbreakers

IECPELV/NEC® Class2wiring

Page 31: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 31 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wire Sizes•PanelFeedWiring:–Mainlugsonly:Parallel4 AWGto500 kcmil(mcm)–200 Ato400 Amainbreakers:1/0 AWG(50 mm2)to600 kcmil(mcm)

•DimmedLine/Hot:14 AWG(2.0 mm2)to10 AWG(4.0 mm2)•LoadNeutral:14 AWG(2.0 mm2)to6 AWG(10.0mm2)

Wiring TipsWireGP36–144Large-Sizepanelssimilarlytoalightingdistributionpanel:

•Runfeedandloadwiring;nootherwiringorassemblyrequired.

•Commonneutralsarenotpermitted.Runseparateneutrals for each load circuit.GP36–144panelscanprovidetemporarylighting.

•Wireallloads.•Donotremovethebypassjumpersthatprotectthe

dimming modules.•Usebranchcircuitbreakerstoswitchlightsonandoff.

Wiring Overview: GP36 – 144 Large-Size Panels(120/277V~)

* VariesdependingonMBorMLO.Seemodelnumberspage.

DH SH H DH SH

PanelFeedWiringPowerFeed(Line/Hot)*

NeutralFeed*

DH SH H DH SH

TypicalLoadCircuit

Load

Bypassjumpers(Donotremove)

LoadNeutral

DimmedLine/Hot

Branchcircuitbreakers

IECPELV/NEC®Class2wiring

Terminalblock

Page 32: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f3209.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Allloadcircuitwiringis14 AWG(2.0 mm2)to10 AWG(4.0 mm2).•SwitchedHot(SH)mustbeusedfor3-wirecontrolledloadsonly;usetheDimmedHot(DH)forallnon-dimload

types.•ConsultWiring Overview page for appropriate neutral location.

Load Circuits: 120/277 V~(GP3–144)

Wiring for Lutron Hi-lume A-Series L3D drivers, and Lutron Hi-lume fluorescent dimming ballasts

SH1

H1

DH1

N

GPDimmingPanel

LoadTerminals

Lutron3-WireBallastorLED

DriverLoad

Neutral(White) Red

Red

Blue

Blue

Ground

DimmedHot(Orange)

SwitchedHot(Black)

Bypassjumpers(Donotremove)

Wiring for 2-Wire Load Types

N

SH1

H1

DH1

GPDimmingPanel

LoadTerminals

LoadNeutral(White)

DimmedHot(Orange)

Bypassjumpers(Donotremove)

LutronHi-lume120V~ dimmingballastshown.

Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types

1

+

_

1

2

+

_

2L1

N1

DL1

L2

N2

DL2

GPDimmingPanel

H +

N −

GRX-TVMTerminalBlock

Load

Neutral(White)

DimmedLive(Orange)

Bypassjumpers(Donotremove)

Page 33: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 33 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Allloadcircuitwiringis14 AWG(2.0 mm2)to10 AWG(4.0 mm2).•UsetheDimmedLive(DL)forallnon-dimloadtypes.•ConsultWiring Overview page for appropriate neutral location.

Load Circuits: 230 V~ (CE)(GP3–24)

Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types

1

+

_

1

2

+

_

2L1

N1

DL1

L2

N2

DL2

GPDimmingPanel

H +

N −

GRX-TVMTerminalBlock

Load

Neutral(White)

DimmedLive(Orange)

Bypassjumpers(Donotremove)

Wiring for 2-Wire Load Types

SL1

L1

N1

DL1

GPDimmingPanel

LoadTerminals

LoadNeutral(White)

DimmedLive(Orange)

Bypassjumpers(Donotremove)

Page 34: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 34 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

•Allloadcircuitwiringis14 AWG(2.0 mm2)to10 AWG(4.0 mm2).•SwitchedLive(SL)mustbeusedforHi-lumeFDBorEco-10loadsonly;usetheDimmedLive(DL)forallnon-dim

load types.•ConsultWiring Overview page for appropriate neutral location.

Load Circuits: 220 – 240 V~(GP3–24)

Wiring for Lutron Hi-lume or Eco-10(ECO-Series)Fluorescent Dimming Ballasts

SL1

L1

N1

DL1

GPDimmingPanel

LoadTerminals

Lutron3-WireBallastorLED

DriverLoad

Neutral(White) Red

Red

Blue

Blue

Ground

DimmedLive(Orange)

SwitchedLive(Black)

Bypassjumpers(Donotremove)

Wiring for 2-Wire Load Types

SL1

L1

N1

DL1

GPDimmingPanel

LoadTerminals

LoadNeutral(White)

DimmedLive(Orange)

Bypassjumpers(Donotremove)

LutronHi-lume 220–240V~ dimming ballastshown.

Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types

1

+

_

1

2

+

_

2L1

N1

DL1

L2

N2

DL2

GPDimmingPanel

H +

N −

GRX-TVMTerminalBlock

Load

Neutral(White)

DimmedLive(Orange)

Bypassjumpers(Donotremove)

Page 35: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f3509.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Low-Voltage IEC PELV/NEC® Class 2 Wiring (AllModels)•Systemcommunicationsuseslow-voltageIECPELV/NEC®Class2wiring.•Wiringmustbedaisy-chained.•Wiringmustrunseparatelyfromline(mains)voltage.

GRAFIK Eye 4000 System•IECPELV/NEC®Class2wiringlinkrequires:–Two12AWG(2.5mm2)conductorsforcontrolpower.–Onetwisted,shieldedpairof18AWG(1.0mm2)fordatalink.–One18AWG(1.0mm2)conductorforemergency(essential)senseline,frompaneltopanel.

•Totallengthofcontrollinkmaybenomorethan2000ft(610m).•Approvedlow-voltagecableisavailablefromLutron1andBelden.Theseareapprovedwith22AWG(0.5mm2)datalinkwires.

Quantum System•IECPELV/NEC®Class2wiringlinkrequires:–Two12AWG(2.5mm2)conductorsforcontrolpower.–Onetwisted,shieldedpairof22AWG(0.5mm2)fordatalink.–One18AWG(1.0mm2)conductorforemergency(essential)senseline,frompaneltopanel.

•Totallengthofcontrollinkmaybenomorethan2000ft(610m).•IfMUX-RPTRinterface2andGRX-CBL-46Lcable1isused,lengthmaybeupto4000ft(1219m).•Maximumof32circuitselectorsperlinkor512switchlegs(controllableoutputs)perlink.•ItisnotnecessarytopositiontheQuantumpanelattheendofthelink;itmaybeinthemiddle.

1 GRX-CBL-46LIECPELV/NEC®Class2wiringcableisavailablefromLutronandcontains: Two12AWG(2.5mm2)conductorsforcontrolpower. Onetwisted,shieldedpairof22AWG(0.5mm2)fordatalink. One18AWG(1.0mm2)conductorforemergency(essential)senseline.

2 OnlytheMUX-RPTRinterfacecanonlybeusedtoextendthelengthofapowerpanellinkinQuantum.ToextendaQSwallstationlink,aQSPS-P1-10-60mustbeused.

3 Linkterminators(LT-1)arerequiredatthebeginningandENDofeverypowerpanellink.

DimmingPanel

ControlUnitControlInterface

Wallstations

DimmingPanelQuantum Processor

RefertoQuantumSpecification

ControlUnitControlInterface

Wallstations

PowerPanelLink3

Page 36: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 36 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

* Emergencypower:Theadditional18AWG(1.0 mm2)wireisa“sense”linefromterminal5ofanotherpanel.Thissenselineallowsanemergency(essential)lightingpanelto“sense”whennormal(non-essential)powerislost.Ifmorethanoneemergencylightingpanelneedstosensefromaspecificnormalpanel,adedicatedwirebetweeneachpairofnormal(non-essential)andemergency(essential)panelsmayberequired.

† Shield/Drain:Connectshieldingasshown.Donotconnecttoground(earth)orcircuitboardofcircuitselector.Connectthebaredrainwiresandcutoffthe outside shield.

IEC PELV/NEC® Class 2 Terminal Connections: GRAFIK SystemsTM

EachLow-VoltageIECPELV/NEC®Class2terminalcanacceptonlytwo18AWG(1.0mm2)wires.Two 12 AWG(2.5mm2)conductorswillnotfit.Connectasshown,using appropriate wire connectors.

IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: GRAFIK Systems (AllModels)

SELECT CIRCUIT

Data A OK Power Data B OK

1 2 3 4 D 5

1 2 3 4 D 5 C D

Co

mm

on

Co

mm

on

+24

VF

W

Sen

se

MU

X

MU

X

Dra

in

Dra

in

MU

X

MU

X

Circuit

1

2

Link

ALink

BSELECT CIRCUIT

Data A OK Power Data B OK

1 2 3 4 D 5

1 2 3 4 D 5 C D

Co

mm

on

Co

mm

on

+24

VF

W

Sen

se

MU

X

MU

X

Dra

in

Dra

in

MU

X

MU

X

Circuit

1

2

Link

ALink

B

ControlWiring(2)12AWG(2.5mm2)1:Common2:24VFW

Toadditional power panels

Dimming Panel 1 Dimming Panel 2

Tolightingcontrols or processors

Shield/Drain† Shield/Drain†

(1)18AWG(1.0mm2)5:SenseLine*

DataLink(1)shielded,twistedpair22AWG(0.5mm2)3:MUX4:MUX

1

2

3, 4

5

1

2

3, 4

SELECT CIRCUIT

2

1

Circuit

Data A OK Power

1 2 3 4 5D

Co

mm

on

24V

FW

MU

X

MU

X

Dra

inS

ense

1 2 3 4 D 5

Data B OK

B Co

mm

Dra

in

MU

X

MU

X

C D

Link

ALink

(4)12AWG(2.5mm2)

Page 37: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f 37 09.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

* Emergencypower:Theadditional18AWG(1.0 mm2)wireisa“sense”linefromterminal5ofanotherpanel.Thissenselineallowsanemergency(essential)lightingpanelto“sense”whennormal(non-essential)powerislost.Ifmorethanoneemergencylightingpanelneedstosensefromaspecificnormalpanel,adedicatedwirebetweeneachpairofnormal(non-essential)andemergency(essential)panelsmayberequired.

† Shield/Drain:Connectshieldingasshown.Donotconnecttoground(earth)orcircuitboardofcircuitselector.Connectthebaredrainwiresandcutoffthe outside shield.

** 24V-:OnlyconnectPin2(24V-)betweenpowerpanelsandLUT-ELI-3PHunits.Pin2shouldnotbeconnectedtotheQuantumprocessoronthelink.

IEC PELV/NEC® Class 2 Terminal Connections: QuantumEachLow-VoltageIECPELV/NEC®Class2terminalcanacceptonlytwo18AWG(1.0mm2)wiresorone 12 AWGto22AWG(2.5mm2to0.5mm2)wire.Connectasshown, using appropriate wire connectors.

IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: Quantum

SELECT CIRCUIT

Data A OK Power Data B OK

1 2 3 4 D 5

1 2 3 4 D 5 C D

Co

mm

on

Co

mm

on

+24

VF

W

Sen

se

MU

X

MU

X

Dra

in

Dra

in

MU

X

MU

X

Circuit

1

2

Link

ALink

BSELECT CIRCUIT

Data A OK Power Data B OK

1 2 3 4 D 5

1 2 3 4 D 5 C D

Co

mm

on

Co

mm

on

+24

VF

W

Sen

se

MU

X

MU

X

Dra

in

Dra

in

MU

X

MU

X

Circuit

1

2

Link

ALink

B

ControlWiring(2)12AWG(2.5mm2)1:Common2:24VFW

Toadditional power panels

Dimming Panel 1 Dimming Panel 2

Tolightingcontrols or processors

Shield/Drain† Shield/Drain†

(1)18AWG(1.0mm2)5:SenseLine*

DataLink(1)shielded,twistedpair22AWG(0.5mm2)3:MUX4:MUX

1

2**

3, 4

5

1

2

3, 4

SELECT CIRCUIT

2

1

Circuit

Data A OK Power

1 2 3 4 5D

Co

mm

on

24V

FW

MU

X

MU

X

Dra

inS

ense

1 2 3 4 D 5

Data B OK

B Co

mm

Dra

in

MU

X

MU

X

C D

Link

ALink

(4)12AWG(2.5mm2)

Page 38: GP Dimming Panels: 120/277 V

GP Dimming PanelsGRAFIK Systems Power Equipment

369401f3809.01.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Custom Options

Option Description ApplicationCustomMainBreaker Panelfeaturesacustommainbreakersize Jobswithspecialloadrequirements.DualTapLugSet Panelacceptsupto225Afeed AsinglefeedwithmultipleGPDimming

Panelsisrequired.BranchCircuitProtection

BranchCircuitBreakerswithhigherAICratingsorspecialbreakertypessuchasGFI(GroundFaultInterrupt) —

LutronTen-VoltModule(TVM)

AllowspaneltooperatefluorescentballaststhatmeetIEC929standardsfor0–10V-controlincluding:•LutronTVEballasts•0–10V- neon•PWMfluorescent•Tridonic®DSI(DigitalSerialInterface).TheTVMcansinkorsource50mA(typically25–50ballasts)on each circuit

Jobswithfluorescentballaststhatrequire0–10V-,PWM,orDSIcontrol

MRI PaneldimsDC(DirectCurrent)lightinginMagneticResonanceImaging(MRI)facilities.

MRIfacilitiesorsoundstudioswherestandardlighting-controlequipmentwon'tworkbecauseofRFIandEMI.

LockingCover •Preventsaccidentalswitchingofcircuitbreakers.•Addsanadditional2.25in(57.2mm)tothefrontofthepanel.•AvailableforGP8–GP24only.

Servicecorridorsandpublicareas.

2Link •AllowsaDMX512theatricalconsoletooperatetheloadcircuits in the dimming panel.

•AllowsaGRAFIKEye4000Systemtohandle128zones(twolinksof64zones)

•AllowstwoGRAFIKEye4000Systemstosharethesamedimming panel.

•ControlofarchitecturallightingfromDMX512theatricalconsoleisrequired.

•Amixofarchitecturalandtheatricallightingexistsonthejob.

•Multiplesystemswherespaceforpanels is limited.