Gas-insulated switchgear NXPLUS C (single-busbar)...Gas-insulated switchgear NXPLUS C...

3
Gas-insulated switchgear NXPLUS C (single-busbar): More Info: info@rabanalsafina.com Description: Up to 15 kV, 31.5 kA, 2500 A busbar, 2500 A feeder Up to 24 kV, 25 kA, 2500 A busbar, 2000 A feeder Metal-enclosed Single-busbar Gas-insulated Hermetically enclosed Factory-assembled, type-tested switchgear according IEC 62 271-200 Customer's Benefit: - Environmental Independence - Compactness - Maintenance-free Design - Personal Safety - Security of Operation, Reliability - Cost-efficient, Ecological Technical Data: Rated voltage kV 7.2 12 15 17.5 24 Rated frequency Hz 5060/ 5060/ 5060/ 5060/ 5060/ Rated short-duration power- kV 20 28* 36 38 50

Transcript of Gas-insulated switchgear NXPLUS C (single-busbar)...Gas-insulated switchgear NXPLUS C...

Page 1: Gas-insulated switchgear NXPLUS C (single-busbar)...Gas-insulated switchgear NXPLUS C (single-busbar): More Info: info@rabanalsafina.com Description: Up to 15 kV, 31.5 kA, 2500 A

Gas-insulated switchgear NXPLUS C (single-busbar):

More Info: [email protected]

Description:

Up to 15 kV, 31.5 kA, 2500 A busbar, 2500 A feederUp to 24 kV, 25 kA, 2500 A busbar, 2000 A feeder

Metal-enclosedSingle-busbar Gas-insulated Hermetically enclosedFactory-assembled, type-tested switchgearaccording IEC 62 271-200

Customer's Benefit:- Environmental Independence- Compactness- Maintenance-free Design- Personal Safety- Security of Operation, Reliability- Cost-efficient, Ecological

Technical Data:Rated voltage kV 7.2 12 15 17.5 24

Rated frequency Hz 5060/ 5060/ 5060/ 5060/ 5060/

Rated short-duration power- kV 20 28* 36 38 50

Page 2: Gas-insulated switchgear NXPLUS C (single-busbar)...Gas-insulated switchgear NXPLUS C (single-busbar): More Info: info@rabanalsafina.com Description: Up to 15 kV, 31.5 kA, 2500 A

More Info: [email protected]

Technical Data:Rated voltage kV 7.2 12 15 17.5 24

frequency withstand voltage

Rated lightning impulse

withstand voltage

kV 60 75* 95 95 125

Rated peak withstand current kA 8082/ 8082/ 8082/ 6365/ 6365/

Rated short-circuit making current kA 80 80 80 63 63

Rated short-time withstand current, 3 s kA 31.5 31.5 31.5 25 25

Rated short-circuit breaking current kA 31.5 31.5 31.5 25 25

Rated normal current of busbar A 2500 2500 2500 2500 2500

Rated normal current of feeder A 2500 2500 2500 2000 2000

Degree of protection - Primary part

Degree of protection - Secondary part

IP65

IP3XD

IP65

IP3XD

IP65

IP3XD

IP65

IP3XD

IP65

IP3XD

Dimensions

- Width **

- Depth without rear duct

- Depth with rear duct

- Height 600 mm panels

- Height 900 mm panels (with hood)

mm

mm

mm

mm

mm

600

1100

1225

2250

2550

600

1100

1225

2250

2550

600

1100

1225

2250

2550

600

1100

1225

2250

2550

600

1100

1225

2250

2550

* 42 kV / 95 kV according to some national standards

** at 2000 A / 2500 A rated normal current: 900 mm

Page 3: Gas-insulated switchgear NXPLUS C (single-busbar)...Gas-insulated switchgear NXPLUS C (single-busbar): More Info: info@rabanalsafina.com Description: Up to 15 kV, 31.5 kA, 2500 A

More Info: [email protected]

Technical Data:Classification according to IEC 62271 -200

Partition Class: PM (metallic partition)

Loss of service continuity

category panels:

- with HV HRC fuses

- without HV HRC fuses

LSC 2

LSC 2

Accessibility of Compartments (enclosure):

- Busbar compartment:

- Switching device compartment:

- Low-voltage compartment:

- Cable compartment:

without HV HRC fuses

with HV HRC fuses

tool-based

non accessible

tool-based

tool-based

Interlock-controlled

and tool-based

Internal arc classification

Designation of internal arc classification IAC for

- Wall-standing arrangement

7.2 kV, 12 kV, 15 kV: IAC A FL 31.5 kA, 1 s

17.5 kV, 24 kV:

- Free-standing arrangement

7.2 kV, 12 kV, 15 kV:

17.5 kV, 24 kV:

I AC A FL 25 kA, 1 s

IAC A FLR 31.5 kA, 1 s

IAC A FLR 25 kA, 1 s

Type of accessibility A Switchgear in closed electrical