    Fire Protection Pumps

    Prepared by

    Eng.Humaid Abu Humaid

    A Fire Pump is:

  • 7/31/2019 Fire Protection Pump

    2/8

    -2-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    any device that takes water from any source, such as public or private mains, tanks, ponds, or

    reservoirs and increasing the pressure of water for the purpose of supplying the necessary flow

    to any fire protection system such as sprinkler standpipes, water spray or foam system.

    Types of Pumps: (According to Purpose)

    1. Suction Pump : Is a type of fire pump that supply the necessary flow and pressure ofwater for fire fighting system from water reservoirs , ponds ,well and river.

    2. Booster Pump: Is a type of fire pump that increase the water pressure, which is drawnfrom a public service main or private-use water system.

    3. Jockey Pump: Is a type of fire pump that maintain system pressure without turning onthe fire pump.

  • 7/31/2019 Fire Protection Pump

    3/8

    -3-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    Types of Pumps (According to Operation Method)

    1 .Centrifugal Pump: It is used for stand pipe, sprinkler and spray nozzles system.

    Centrifugal pump components:

    Section of Horizontal Split Case Pump

    Impeller

    CasingShaft Sleeve

    Packing

    Lubrication

    Purges

    Bearing

    Ball

    Eye

    Shaft

    A- Impeller

    B- Eye

    C- Shaft

    D- Packing

    E- Casing

    ( Bronze)

    Stainless-steel

    Packed gland

    Cast iron

    F-Shafts leave Bronze

  • 7/31/2019 Fire Protection Pump

    4/8

    -4-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    2 .Positive Displacement Pump: It is used on fire trucks, water mist system

    that require very big pressure and as a foam concentrate pump in foam/water system

    Types of Centrifugal PumpsThe pumps divide into two types according to shaft position, pump divide to:

    a- Horizontal:

    a. End Suctionb. Horizontal split case pump

    It is not used for suction lifts from water reservoir (NFPA) but it is used for NPSH not

    more than 5.38m and suction head 3.7m and it need a priming tank capacity 100-500 liters

    (LPC).

    b- Vertical

  • 7/31/2019 Fire Protection Pump

    5/8

    -5-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    Fire Pump Installation

    a- Horizontal split case fire pump

    b- Vertical shaft turbine type pump.

    1- Installation in a well

    2- Installation in wet pit

  • 7/31/2019 Fire Protection Pump

    6/8

    -6-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    Rated Pump Capacitygpm L/min gpm L/min gpm L/min

    25 95 400 1514 2000 7570

    50 189 450 1703 2500 9462

    100 379 500 1892 3000 11355

    150 568 750 2839 3500 13247

    200 757 1000 3785 4000 15140

    250 946 1250 4731 4500 17032

    300 1136 1500 5677 5000 15925

    Notes:

    1- pumps for rating over5000 Gpm are subject to individual review by civil defence2- A centrifugal fire pump shall be selected in the range of operation from 90% to 150 % of it

    is rate capacity

    Fire Pump Application

    a. According to NFPA the fire pump are used for sprinklers and hydrants system

    b. According to BS5306 part 2 (LPC) there are two sets of pump one for sprinklersystem and other for hydrant system

  • 7/31/2019 Fire Protection Pump

    7/8

    -7-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    Shop Test : Each individual pump shall be tested at the factory to provide detailedperformance data and to demonstrate its appliance with specification.

    1- Rated flow2- rated pressure

    3- brake horse power

    4- efficiency

    5- NPSH

    6- Shaft rotation

    Operating Range of Fire Pump

    The relation between flow and pressure shaft as follows:

    Rated Pump Capacity as Follows:

    Situation Flow

    (gpm)

    Percent % Pressure Psi Percent

    %

    Accepted

    ratio %

    a. Pump rating 1500 100 % 80 100 % 100 %

    b. No flow (churn) 0 0 % 90 112.5 % 65 %

    Operating Range of Fire Pump

    - Flow Curve :

    Flow % Pressure %

    0% Not more than 140%

    100% 100%

    150% Not less than 65%

  • 7/31/2019 Fire Protection Pump

    8/8

    -8-

    Tel : 0795670677

    E-mail : [email protected]

    Eng.Humaid Abu Humaid

    Types of Driver

    a. Electric Motor

    b. Diesel Enginec. Steam Turbine

    Minim

    um

    Pipe