Fire Alarm Control Panel Operating Manual

Transcript of Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring...

Page 1: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

Fire Alarm Control Panel

Operating Manual

Page 2: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

I

AH-02412 FAMILY

ITEM

Introduction and Characteristics Fire Alarm System Assembly Diagram Fire Alarm Signal Flow Chart Panel Descriptions Standard Detector Wiring Method Method of Wiring Wiring Principle Operating Instructions

1.Fire Surveillance 2.Fire Alarm 3.Reset 4.Fault Alarm 5.Standby Power 6.Alarm Relay Output 7.Fault Relay Output 8.Control Board LED Test 9.Occurrence of Alarm Signal during Testing 10.The Display Module LCD (AH-02412L) 11.Extinguishing Facility (AH-02412E)

Installation Location Important Notes On Maintenance

1.Normal State of Control Panel 2.Maintenance of Devices 3.Overall Maintenance

Trouble Shooting 1.Malfunction of Zone Indicator & Combination PBL Box 2.Functions of Fuses 3.Causes of Burnt Fuses & Inspection Guidelines 4.Combination PBL Fire Indicating Lamp & Alarm Bell malfunction 5.Zone “ Fault/Disable ” Indicator & “ Fault ” Indicator light up 6.AC Power Fault 7.Standby Power Fault 8.PCB Connection Fault 9.Ground Fault 10.Zone “Alarm” Indicator & Fire “Alarm” In dicator light up

Main Specifications

CONTENTS

1223-567,89

1010101111111111111112

131313

141414151515

1616

Page

13

161616

Page 3: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E11

AH-02412 FAMILY

Due to the creativity and progress of fire fighting technology among highly developed countries, we never give up any chance to upgrade our new generation fire alarm control panel. We are not only pursuing higher technology level, but also compact design to meet national quality standard.

..

This digital control panel primary uses processor to handle relevant signal, which improve most weak points of traditional control panel. See below for more details. (1)The use of microprocessor has improved the unit's correctness that used to be affected by bad characteristic of traditional devices. (2)Uses digital mode to transmit and control signal process, which highly increase the precision of signal. (3)Internal control voltage uses 5V that prevent burning circuit caused by traditional high voltage. (4)Module type design simplified entire system, function up-grade just has to change related module and no need big work to complete it. Thus, users are able to save big bucks on up-grade or repair cost. (5)Microprocessor can be revised according to user's request, its expand ability has much greater than traditional ones. (6)Shortage of terminal has not seen on this unit, up to four sets of signal transfer contacts (relay outputs) are added for new design. (7)Zone isolating button and control board switches are electronic-type and used digital 0 and 1 signals for switch control signal. Also they will not damaged by abnormal high voltage because of undirected control high voltage and interfered by dust, this phenomenon usually happened on mechanical-type switch.

Introduction and Characteristics

Introduction

Characteristics

Page 4: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Fire Alarm System Assembly Diagram

2

AH-02412 FAMILY

Fire Alarm System Assembly Diagram

Fire Alarm Signal Flow Chart

1-Heat Detector2-Smoke Detector3-Gas Detector4-Flame Detector5-Alarm Bell6-Indicating Lamp7-Manual Call Point8-Annunciator9-Extinguishing Device10-Control Panel

1.Occurrence of fire

2-1.Detector

2-2.Manual Call Point

3.Control Panel

4-1.Alarm Bell

4-2.Indicating Lamp

4-3.Annunciator

Page 5: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Panel Description(AH-02412)

3

AH-02412 FAMILY

Description

1.Zone Alarm LED2.Zone Fault/Disable LED3.Zone Disable4.Silence Sounders5.Mute Internal Buzzer6.Lamp Test7.Reset8.Fire Alarm LED

9.Fault LED10.System Normal LED11.System Fault LED12.Supply Fault LED13.Sounder Fault LED14.CPU Fault LED15.Disable LED16.Key Switch

Dimensions and Specifications

130 mm

Page 6: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Panel Description(AH-02412E)

4

AH-02412 FAMILY

Description

Dimensions and Specifications

Nac

Active

Trouble

(Nac)

3

1718

19

1.Zone Alarm LED2.Zone Fault / Disable LED3.Nac Active LED4.Nac Fault LED5.Zone Disable6.Nac7.Silence Sounders8.Mute Internal Buzzer9.Lamp Test10.Reset

11.Fire Alarm LED12.Fault LED13.System Normal LED14.System Fault LED15.Supply Fault LED16.Sounder Fault LED17.CPU Fault LED18.Disable LED19.Key Switch

130 mm

Page 7: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Panel Description(AH-02412L)

5

AH-02412 FAMILY

Description

Dimensions and Specifications

1.Fire Alarm LED2.Zone Alarm LED3.Zone Fault/Disable LED4.Zone Disable 5.Silence Sounders6.Mute Internal Buzzer7.Lamp Test8.Reset9.Supply Fault LED

10.Sounder Fault LED11.CPU Fault LED12.Disable LED13.Fault LED14.System Normal LED15.System Fault LED16.LCD Display17.Numeric Key

Fire Alarm Control Panel

FaultAlarm System Normal System Fault

Supply Fault

CPU Fault

Disable

Sounder Fault

Alarm

Fault /Disable

s c ACK

AH-02412L

Page 8: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Standard Detector Wiring Method

6

AH-02412 FAMILY

Standard Detector Wiring Method

Common Line(Zn-)

Circuit Line(L)

Connectto ControlPanel

Detector at theend of everyCircult is installed withone terminalresistor 4.7k1/4W

ControlPanel

Terminal Resistor4.7K 4.7K 4.7K

(C) 1.6mmx1Indicating Lamp 1.6mmx1Alarm Bell 1.6mmx1

(L)Diameter of Circuit line be 1.0mm~1.2mm(C)Common line 1.2~1.6mm.Limited to seven Circuit lines per wire (according to regulation)

Symbols

ControlPanel

Rate of RiseDetector

Fixed Temp.Detector

SomkeDetector

CombinationP.B.L.Box

ManualCall Point

Alarm Bell

IndicatingLamp

Page 9: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Method of Wiring

7

AH-02412 FAMILY

Method of wiring

AC110V/220V

Stand byPower

Sounder 1

Sounder 2

AC 110/220V 50Hz/60Hz

DC 24V/A accroding to number of zone

Max. connection =no. of zone x 1.2

Terminal device4.7k

4.7k

Fire RelayOutput Of Contact Point

Fault Relay Output of Contact point

Zone

AC Power

Indicating Lamp

24V DCOutput Wiring

Max. connection =no. of zone x 1.2

Max. connection =no. of zone x 1.2

Detector

Detector

To Relay Output Device

To Relay Output Device

220

Z1

Z2

Z8

.....

Page 10: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Method of Wiring

8

AH-02412 FAMILY

Signal Transfer(Voltage Free Contacts)

Method of Wiring

Reset 24V

To Relay Output Device

E1

To Relay Output DeviceE2

To Relay Output Device

E8

Gas Relay

To Gas Release EquipmentS1

To Gas Release EquipmentS4

AnnunciatorControl Panel

E1

E2

E8

DC

1

2

3

4

8

9

Page 11: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E19

AH-02412 FAMILYWiring Principle

Wiring Principle

1. Wiring Material Table (longer distance excluded; please refer to your local regulation)

1.0 ~ 1.2M/M N

1.2 ~ 1.6M/M N

1.2 ~ 1.6M/M 21.2 ~ 1.6M/M 21.0 ~ 1.2M/M

1.0 ~ 1.6M/M 11.2 ~ 2.0M/M 2

2.

3. Wire-Point Labels and Joint ClipsInside the Control Panel and every Wire Connection Box, the wire points are to be attached to Label Covers or Label Stickers and then connected to the Y-clip.

4.Wiring MethodPlease refer to Page 6 ~ 8 of this handbook for the wiring of safetyequipment.

5. Terminal Resistor Connecting MethodEvery end of a Detector zone shall be fitted with a resistor (not more than one).

6. Wiring RecordOnce the external wiring is laid, a record of the detailed external wiring diagram shall be kept for future inspection and repair.

Item

Detector Zone

Zone Common Line

Alarm BellFire Indicating LampManual Call PointEarthAC Power

Specification QuantityDepends on zone device, basically 1/zone.No more than 7 zones percommon line.

Parallel connect with detectors.

Dependents on panel's load.

Wire Connection BoxIn order to facilitate inspection, maintenance and repair, every flooror appropriate area should install a Wire Connection Box in whichconnecting joints are provided. The Box case shall be waterproof and the wording “Fire Fighting Only” should labeled on an aluminum plate.

Page 12: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Operating Instructions

10

AH-02412 FAMILY

Operating Instructions

1. Fire SurveillanceAfter installed system devices into the panel, connect with AC supply source and the "System Normal" indicators will lighten up. Fire Indicating Lamp of the combination PBL box light up and surveillance begins.

2. Fire Alarm When detector has detected a signal of fire, the Fire "Alarm" Indicator(red) and the related zone indicator will lighten up simultaneously. The Main Bell and Alarm Bell will also sound. The Fire Indicating Lamp of the combination PBL box will blink. These activities indicate that the fire alarm is valid

(1) Main Bell Disable To stop the Main Bell from sounding, press "Mute Internal Buzzer" button the sounding stop immediately. It will resound when next alarm is issued.

(2) Alarm Bell Disable (SND1 & SND2) To stop the Alarm Bell from sounding, press "Silence Sounder"button the sounding stop immediately. It will resound when next alarm is issued.

3. ResetOnce the fire alarm is activated, the Fire "Alarm" Indicator and the Zone "Alarm"Indicator will remain lighten. If the control panel requires starting the surveillance again after the previous fire situation has been resolve, just depress the "Reset" button and wait 5 seconds. However, if detectors have been burnt or the MCP press-down not recovered, reset cannot be activated. For this matter, repair should be completed first, then depress the "Reset"button to reset the system.

(3) Single Zone Relay Output Disable (optional)To stop any zone relay output during alarm, press "Z1 ~Z8" button then the zone alarm LED will off, and the zone fault LED will blink. Press again to start relay output.

(4) Gas Release Disable (optional)To stop gas release output after cross-zone action just press "Nac" button. When the "Nac Active" LED turns on means gas release output has completed. Note that you have to switch off the AC & DC power and switch them back on to clear this feature.

Page 13: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Operating Instructions

11

AH-02412 FAMILY

4.Fault Alarm The panel is equipped with "Auto Fault Indication/ Release"function. Should there be a Circuit Break in certain areas, or detachment of the terminal resistor, the "Fault"indicator and the related Zone"Fault/ Disable"indicator will lighten up simultaneously. The internal beeper will sound. Upon repair of the circuit, the mentioned situation above will cease. (1) Disable Fault Sound To stop the fault sound, press"Mute Internal Buzzer"button. When new fault alarm received, it will resound.5.Standby Power The control panel is equipped with automatic rechargeable batteries the stand-by power source (24VDC) shall be installed during operation. When the Main power source has been terminated, the "System Normal" indicator will light off and the"Fault" indicators will light up. If the standby power is in trouble, the "Supply Fault"indicator will also turn on.

6.Alarm Relay Output One 'A' contact (24V/3A) for alarm output when any zone in alarm condition.7.Fault Relay Output One 'A' contact (24V/3A) for alarm output when any zone in fault condition.8.Control Board LED Test Press the "Test" button, all LED on board will light up and buzzer will sound and reset automatically after 5 sec.9.Occurrence of Alarm Signal during Testing If there is an alarm signal in any Circuit other than those under testing , the test must be end immediately and handle the alarm signal Circuit first.10.The Display Module LCD (optional) The LCD is only comes with model AH-02412L and has a backlight display with 2 rows of 20 characters each. By means of the 12 buttons on right side, it is possible to obtain detailed information for the warning signaled LED's on the front panel and set up the security code for protection purpose. A.Input 4-digits security code (xxxx) and then press ACK button to start.

Page 14: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

Operating Instructions

12

AH-02412 FAMILY

B.12 buttons including 10 numeric,1 select/clear and 1 acknowledge.C.Use S/C for displayed heading selection and information clear, the " " and " " buttons scroll of the manual headings.D.Original screen: first line shows Alarm= 000 Fault= 000 (note: 0 means normal condition); second line shows current date & time (yr/mo/day/hr/min/sec).E.For inconsecutive alarm signal, screen will show 000 but fire indicator will remain ON. For inconsecutive fault signal, screen will show 000 and zone fault indicator will OFF.F.Features as follow: 1.Time setting: After correct time is set up, press "ACK" for completion. 2.Zone status display: a.Display current zone status, at normal condition it will show 'No Signal'; press "ACK" and back to last screen. b.Display any alarm, disconnection or short; the first line shows event #, zone # and event status. The second line shows the date and time of the event. Press "ACK" and back to last screen. 3.Memory data display: a.255 events memory and display with capital M. b.Record all kind of status; the first line shows event #, zone # and event status. The second line shows the date and time of the event. Press "ACK" and back to last screen. 4.Memory data delete: By input access code, memory data will clear automatically and then back to last screen. 5.Access code setting: First enter original code (0000) then enter the access code. To return the original code, press '5' and short the two pins on the right of PCB 528D inside the panel. 6.System information: It shows model #, zone # and version; press "ACK" will back to original screen.

> >

11. Extinguishing Facility (AH-02412E only) The extinguishing system will be activated after fire alarm has issued for 0 ~ 60 seconds with adjustable timer (please refer to the logic switch located on main board, single digit on the right and decimal digit on the left) and gas discharge will automatically turned off after 10 seconds or by pushing the "Nac" button. While activated, the LED (Active) on the panel will be ON until the system's supply power was turned OFF and ON again. When user intends to stop the extinguishing process just press the "Nac" button. The extinguishing facility is only activated when both zone in same area have issued fire alarm.

Page 15: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

13

AH-02412 FAMILY

Please refer to your local regulation for installation details.

..

Installation Location

Installation Location

Important Notes On Maintenance 1.Normal State of Control Panel (1)Normal Condition (Fire Surveillance Alert) Under normal conditions, the "System Normal" indicator should light up. All other indicators should be OFF for ready status and Fire Indicating Lamp on the Combination PBL Box should light up. (2)Power Failure When there is a power failure, the "System Normal" indicator should light off and the "System Fault" indicators will light up. 2.Maintenance of Devices (1)If maintenance may cause disturbances to public, appropriate co-ordination must be made before. (2)Priority should be given to those faulty devices in the area. (3)Maintenance should be scheduled at least twice a year and must include both physical and functional inspections. 3.Overall Maintenance Annual overall inspection should carry out by the professional institution or the original equipment manufacturer. Inspection records must be tabulated and kept by a responsible person or the department concerned, to ensure the public safety. (1)Power Supply Check whether the external wiring of the panel its power consumption are within the safety regulation, whether the standby power conforms to specifications and whether the duration of power supply is within the safety regulation. (2)Detectors To perform a site test for the detectors in order to check whether they are functioning properly and also to check the condition of detector's Indicating LED (on the detector's base). (3)Insulation Test The insulation between power terminal of control panel and earth shall have a value of 250V 20M and above.

Page 16: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

14

AH-02412 FAMILY Trouble Shooting

Trouble Shooting The Control Panel is produced with an advanced technology and delicate design that is easy to assemble. It requires no special skills to trouble-shoot a malfunction, thus avoiding any teething problems that might be encountered during maintenance. 1.Malfunction of Zone Indicator & Combination PBL Box The system devices are assembled with many single units (refer page 2), either the 'Detectors', 'Circuits' or 'Combination PBL Box ' become defective, it will affect the functionality of the Control Panel. (1)Measure terminal "AC" with a Multi-meter for any voltage. (2)Check whether the "System Normal" indicator is functioning properly. The system should specify 24V DC. (3)Check whether fuses are in good condition. (4)Check whether the external devices and wiring conform to specifications, as stated in this handbook. 2.Function of Fuses The Control Panel has fuses, each fuse with individual protection function. It must not be replaced with fuses that do not conform to specifications or are of bad quality; otherwise we will not be liable for any damage. Burnt fuses are probably caused by external wiring error, short circuit or faulty external devices. (1)AC: Fuse for power source AC. (2)BATT: Fuse for standby power source. (3)SND1,SND2: Fuse for alarm bell. (Resettable type) (4)AUX: Fuse for Combination PBL Fire Indicating Lamp. (Resettable type) (5)DC24V: Fuse for direct current source 24VDC. (Resettable type) 3.Causes of Burnt Fuses & Inspection Guidelines (1)AC Fuse Burnt a.It could be due to excessive voltage supply that causes the AC Fuse to be burnt. b.Conformance of Specification (lower-rated fuse may be burnt by a surge of current). (2)BATT Fuse Burnt a.Check whether the standby power polarity '+' and '-' have been in reversed position. b.Similar to inspection guidelines for AC Fuse, the standby power supply will pass through BATT Fuse when power supply from the Main Source has been cut-off.

Page 17: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

15

AH-02412 FAMILY Trouble Shooting

4.Combination PBL Fire Indicating Lamp & Alarm Bell Malfunction (1)Remove the external wiring of the Fire Indicating Lamp and Alarm Bell. (2)Measure the ( '+' and '-' ) outlet of Fire Indicating Lamp with a multi-meter and Check whether it is read DC24V. Then perform a fire test. Reset after it is completed. (3)Measure the ( '+' and '-' ) outlet of the Alarm Bell with multi-meter. It should not have any voltage supplied. Then perform a fire test and a DC24V voltage should be recorded. Reset after the test. (4)When the test results conform to (2) and (3), it indicates that the control panel is functioning properly. The wires should only be connected after the external wiring have been repaired. 5.Zone "Fault" Indicator & "Fault/Disable" Indicator light up When one or several "Fault/Disable" Indicator and "Fault" Indicator light up simultaneously, it should be regarded as a signal of circuit break. In this instance, inspection and repairs should be carried out in the following manner: (1)Check for any loops in the control panel not use End-of-line resistor. (2)Remove the circuit that in trouble; the disconnection signal should immediately go off. (3)If test results conform to (2), it indicates that the control panel is functioning properly. The wire shall only be connected after the external wiring has been repaired. (4)Inspect the external circuit to check whether last detector has been installed one End of Line Resistor, or improperly installed. (5)Check for any break in the external wiring as well as any dislocation of detectors. (6)Set the multi-meter to mode and measure the malfunction circuit resistance value. The resistance value between the zone line and common line should 4.7k . (7)After removal of the circuit line, there should not be any voltage between the zone line and zone common line. The wire shall only be connected after the external wiring has been repaired. 6.AC Power Fault When AC power is too high, "Fault" & "System Fault" indicators will light up. When AC power is too low, "Fault" & "CPU Fault" indicators will light up.

Page 18: Fire Alarm Control Panel - Horing · PDF fileStandard Detector Wiring Method Method of Wiring ... our new generation fire alarm control panel. ... 10-Control Panel 1.Occurrence of

AH-02412 FAMILYC 2005-04E1

16

AH-02412 FAMILY Trouble Shooting

7.Standby Power Fault When there is any problem on Battery, the "Fault" indicator & "Supply Fault" indicator will on and sound.8.PCB Connection Fault When there is any disconnection between PCBs, the "Fault" indicator will light up & "System Fault" indicator will blink every 0.5 sec.9.Ground Fault When there is any external wiring has short circuit with earth, the "Fault" indicator will light up & "System Fault" indicator will blink every 0.2 sec.10.Zone "Alarm" Indicator & Fire "Alarm" Indicator light up When one or more zone "Alarm" indicators and Fire "Alarm" Indicator lighten up simultaneously, it should be regarded as a fire alarm signal. The inspection and repair guidelines are as follows: (1)Remote the circuit that in trouble. Measure between the loop line and loop common line to check for short circuit or resistance value is normal (normal value=4.7k ). (2)After remote the circuit that in trouble, the control panel must be reset. At this moment, the zone indicator should carry a circuit break signal. After repairing the circuit line, re-connect the external circuit line. (3)Check for presence of any short circuit of the external wiring, or any defective detectors.

Main Specification

Descriptions RemakersPowerVoltage rangeStandby powerCharging voltage,current

Exterior resistance# of heat detectorconnected# of smoke detectorconnected# of fire indicating lampconnected# of alarm bell connectedDigital SwitchEnd of line resistorMaterialColorAccessory functions

220VAC 50/60HzNominal voltage 15%24VDC 4Ah

24VDC;short circuit under5V 30mARound-trip under 50

# of loop x 1.2500000 cycle Min. reliability4.7k1.2mm steel plateIvory whiteAux. Contacts for signal transfer and computermonitor, MCP contact andphone Jack

26VDC 100mA ~ 400mA

Loop voltage,current

Max. 30 per loop

Max. 30 per loop

# of loop x 1.2

Others also avilable

With auto adjustmentfunction

Mechanic type hasno limit

One per loop

Others also avilable

Optional selections

+-