CPX-AP-I-EC-M12EtherCAT interface
80997392019-11[8099741]
Instructions | Operat-ing
Translation of the original instructions
EtherCAT® is a registered trademark of its respective trademark holder in certain countries.
2 Festo — CPX-AP-I-EC-M12 — 2019-11
3Festo — CPX-AP-I-EC-M12 — 2019-11
1 About this document................................................................................................... 4
1.1 Applicable documents.................................................................................................. 4
1.2 Product version............................................................................................................ 4
1.3 Product labelling.......................................................................................................... 4
1.4 Specified standards...................................................................................................... 5
2 Safety........................................................................................................................... 5
2.1 Safety instructions........................................................................................................ 5
2.2 Intended Use................................................................................................................ 5
2.3 Training of qualified personnel..................................................................................... 5
3 Additional information................................................................................................ 5
4 Service..........................................................................................................................5
5 Product overview......................................................................................................... 6
5.1 Function....................................................................................................................... 6
5.2 Configuration................................................................................................................ 7
5.2.1 Product design........................................................................................................7
5.2.2 LED displays........................................................................................................... 8
5.2.3 Control elements.....................................................................................................8
5.2.4 Connecting elements.............................................................................................. 9
6 Assembly..................................................................................................................... 10
7 Installation.................................................................................................................. 10
8 Commissioning............................................................................................................ 10
9 Parameterisation......................................................................................................... 11
9.1 Object directory............................................................................................................ 13
9.1.1 EtherCAT General Objects....................................................................................... 13
9.1.2 EtherCAT Modular Device Profile............................................................................ 17
10 Diagnostics and Fault Clearance................................................................................. 20
10.1 Diagnostics options...................................................................................................... 20
10.2 Diagnostic Messages.................................................................................................... 20
10.3 LED displays................................................................................................................. 26
10.4 Diagnostics via EtherCAT.............................................................................................. 31
10.4.1 Diagnostics via SDO access.................................................................................... 31
10.4.2 Diagnostics via diagnostics history.........................................................................31
10.4.3 Emergency message............................................................................................... 34
11 Disposal........................................................................................................................35
12 Technical Data............................................................................................................. 35
Table of contents
1 About this document
1.1 Applicable documents
All available documents for the product è www.festo.com/pk.
Document Contents
Instruction manual for automation systemCPX-AP
Instruction manual and important information onassembly, electrical installation and maintenancetasks as well as description of the automationsystem CPX-AP
Tab. 1 Applicable documents
1.2 Product versionThis document refers to the following product versions:
Product Version
CPX-AP-I-EC-M12 EtherCAT interface CPX-AP-I-EC-M12 revision 1 or later
Tab. 2 Product version
The product version can be determined using the product label.
There may be an updated version of this document for these or later product versionsè www.festo.com/sp.
1.3 Product labellingThe product labelling is located on the right-hand side of the module. The Data Matrix code is on theconnection side. Scanning the printed Data Matrix Code with an appropriate device opens the FestoSupport Portal with the information appropriate for the product. Alternatively, the Product Key(11-digit alphanumeric code on the product labelling) can be entered in the search field of the SupportPortal è www.festo.com/sp.
About this document
Festo — CPX-AP-I-EC-M12 — 2019-114
1.4 Specified standards
Version
IEC 60204-1:2016-10 ISO/IEC 8802-3:2000-10
IEC 61158:2014-07 EN 60204-1:2018-09
IEC 61784:2014-08 EN 60529:1991-10
IEC 61918:2013-08 –
Tab. 3 Standards specified in the document
2 Safety
2.1 Safety instructions– Take into consideration the legal regulations for the respective destination.– Use the product only within the defined values è 12 Technical Data.– Observe labelling on the product.– Observe further applicable documents.– Store the product in a dry, UV- and corrosion-protected environment.– Before working on the product:
Switch off the power supply and secure it against being switched on again.
2.2 Intended UseThe product described in this document is intended only for use as an interface between an automa-tion system CPX-AP and a higher-order controller through integration in a EtherCAT network.Use the product only as follows:– Use only in an industrial environment. Outside industrial environments, e.g. in commercial and
residential/mixed-use areas, it may be necessary to take measures to suppress radio interference.– Use only in combination with modules and components that are permissible for the respective
product variant è www.festo.com/catalogue.– Only use the product if it is in perfect technical condition.
2.3 Training of qualified personnelInstallation, commissioning, maintenance and disassembly should only be conducted by qualified per-sonnel. The qualified personnel must be familiar with installation of electrical control systems.
3 Additional information– Accessories è www.festo.com/catalogue.
4 ServiceContact your regional Festo contact person if you have technical questions è www.festo.com.
Safety
5Festo — CPX-AP-I-EC-M12 — 2019-11
5 Product overview
5.1 FunctionThe product, as a station in an EtherCAT network, establishes the connection between a higher-ordercontroller and the modules of an automation system CPX-AP.
Device Description FileA device description file (ESI file) is used for project engineering in the EtherCAT interface of thehigher-order controller software.It contains all the information required to configuration of the automation system CPX-AP via controlsoftware.
The current device description file is available on the Festo Support Portal è www.festo.com/sp.
Crossover detection (auto MDI/MDI-X)The product supports crossover detection (auto MDI/MDI-X), which means that there is the option ofusing patch cables or crossover cables.
Distributed ClocksThe product supports the "Distributed Clocks" function for precise synchronisation of stations in anEtherCAT® network. Applications that require simultaneously coordinated actions can therefore beimplemented.
Product overview
6 Festo — CPX-AP-I-EC-M12 — 2019-11
5.2 Configuration
5.2.1 Product design
1 Mounting interface connection side top
2 Rotary switch cover
3 Network connection EtherCAT [OUT X2]
4 Connection for system communication [XF21]
5 Connection for voltage forwarding [XD2]
6 Mounting interface connection side bottom andconnection functional earth FE
7 Mounting interface, lateral bottom and connection forfunctional earth FE
8 Connection for power supply [XD1]
9 Connection for system communication [XF20]
10 Network connection EtherCAT [IN X1]
11 Screw Cover Rotary switch
12 Inscription label (optional)
13 Mounting interface, lateral top
Fig. 1 Product design
Product overview
7Festo — CPX-AP-I-EC-M12 — 2019-11
5.2.2 LED displays
1 System diagnostics [SD] (green/red)
2 Maintenance [MT] (yellow)
3 EtherCAT error [ERR] (red)
4 Network connection [LA X2] (green)
5 Network connection [LA X1] (green)
6 EtherCAT operating status [RUN] (green)
7 Performance level [PL] (green/red)
8 Module diagnostics [MD] (green/red)
Fig. 2 LED displays
5.2.3 Control elements
NOTICE!
Damage to internal electronics.Damage to at-risk components due to electrostatic discharge.• Ensure your body is electrostatically discharged before activating the rotary switch.
Rotary switch Function
The 3 rotary switches are used to set the EtherCAT "Explicit DeviceID" of the interface in hexadecimal code.Possible settings:– 0 = stored EtherCAT address, no "Explicit Device ID" assigned– 1 … 4095 (1h … fffh) = permissible address rangeIf set to 0, the address of the interface is automatically assigned bythe EtherCAT master (autoincrement).Factory setting: 0
Tab. 4 Rotary switch
Changes to the rotary switches only take effect following a restart of the interface.
Product overview
8 Festo — CPX-AP-I-EC-M12 — 2019-11
5.2.4 Connecting elements
Connection for power supply [XD1]
Plug M8, 4-pin, A-coded Signal
1 +24 V DC logic supply PS
2 0 V DC load supply PL
3 0 V DC logic supply PS
4 +24 V DC load supply PL
Tab. 5 Connection for power supply
Connection for voltage forwarding [XD2]
Socket M8, 4-pin, A-coded Signal
1 +24 V DC logic supply PS
2 0 V DC load supply PL
3 0 V DC logic supply PS
4 +24 V DC load supply PL
Tab. 6 Connection for voltage forwarding
Connection for system communication [XF20], [XF21]
Socket M8, 4-pin, D-coded Signal
1 RX– Received data –
2 TX+ Transmitted data +
3 RX+ Received data +
4 TX– Transmitted data –
Tab. 7 Connection for system communication
Connection for EtherCAT network [IN X1]
Socket M12, 4-pin, D-coded Signal
1 TD+ Transmitted data +
2 RD+ Received data +
3 TD– Transmitted data –
4 RD– Received data –
Thread Shield Functional earth
Tab. 8 Connection for EtherCAT network [IN X1]
Product overview
9Festo — CPX-AP-I-EC-M12 — 2019-11
Connection for EtherCAT network [OUT X2]
Socket M12, 4-pin, D-coded Signal
1 RD+ Received data +
2 TD+ Transmitted data +
3 RD– Received data –
4 TD– Transmitted data –
Thread Shield Functional earth
Tab. 9 Connection for EtherCAT network [OUT X2]
6 Assembly• Assemble the module as outlined in the “Instruction manual for automation system
CPX-AP"è 1.1 Applicable documents.
7 Installation• Carry out the installation according to the "Instruction manual for automation system
CPX-AP"è 1.1 Applicable documents.• EtherCAT Use network cables as described in the cable specification è 12 Technical Data.
8 CommissioningNOTICE!
Unauthorised access to the device can cause damage or malfunctions.When connecting the device to a network, protect the network from unauthorised access.Measures to protect the network include: • Firewall• Intrusion prevention system (IPS)• Network segmentation• Virtual LAN (VLAN)• Virtual private network (VPN)• Security at physical access level (port security)Further information è Directives and standards for security in information technology,e.g. IEC 62443, ISO/IEC 27001.
NOTICE!
Malfunction due to switching on the higher-order controller and automation system CPX-AP in theincorrect order.• Switch on the higher-order controller and automation system CPX-AP according to the preset
order of the network used.
1. Using the appropriate software, set up an automation project for the higher-order controller.
Assembly
10 Festo — CPX-AP-I-EC-M12 — 2019-11
2. Import the device description file into the software è www.festo.com/sp.3. Configure the automation system CPX-AP in the software:
– System structure– Network addressing– Address assignment of modules è Instruction manual for automation system CPX-AP
4. Transfer the automation project to the higher-order controller.
Behaviour of the display components of the module after error-free commissioning
[MD] [SD] [PL] [MT]
Illuminated green Illuminated green Illuminated green Off
Tab. 10 Behaviour of the display components after error-free commissioning
[LA X1], [LA X2] [RUN] [ERR]
Illuminated green Illuminated green Off
Tab. 11 Behaviour of the display components after error-free commissioning
Information on troubleshooting in the event of incorrect behaviour:è Instruction manual for automation system CPX-APè 10 Diagnostics and Fault Clearance
9 ParameterisationVarious parameters are available for reading out information about the modules in an automation sys-tem CPX-AP and adapting the modules to the application situation.Every configured or connected module also provides some of its parameters as network parameters.These are then displayed in the objects 0x2000 … 0x2FFF.
ID Parameter Instance-s
Datatype
Access1) Arraysize
246 Fieldbus serial number 1 UINT32 ro –
791 Product key 1 CHAR ro 12
960 Firmware version 1 CHAR ro 40
20000 Module code 1 UINT32 ro –
Parameterisation
11Festo — CPX-AP-I-EC-M12 — 2019-11
ID Parameter Instance-s
Datatype
Access1) Arraysize
20022 Configuration of voltage monitoring loadsupply PL– 0: load voltage monitoring inactive– 1: load voltage monitoring active, with
suppression of diagnostics at switch-off (factory setting)
– 2: load voltage monitoring active
1 UINT8 rw –
20059 AP Sync operating mode 1 ENUM_ID ro –
20085 Measured value temperature AP-ASIC [°C] 1 INT16 ro –
20087 Current measured value of logic supply PS[mV]
1 UINT16 ro –
20088 Current measured value of load supply PL[mV]
1 UINT16 ro –
20092 Operating time [s] 1 UINT32 ro –
20093 Hardware version 1 UINT8 ro –
20196 Diagnostic status– Index 0: diagnostic status of the entire
automation system CPX-AP– Index 1: diagnostic status of module 1
(address 1)– Index 2: diagnostic status of module 2
(address 2)– ...Each entry is of the data type UINT8 withthe following meaning:– Bit 0: degree of severity information (1)– Bit 1: degree of severity maintenance
(1)– Bit 2: degree of severity warning (1)– Bit 3: degree of severity error (1)– Bit 4, 5: reserved– Bit 6: module present (1), module lost
(0)– Bit 7: reservedBit 6 is not valid for index 0.
1 UINT8 ro Numberof mod-ules + 1
1130125 Bootloader version 1 CHAR ro 40
1) ro = read only; rw = read write
Tab. 12 Parameter
Parameterisation
12 Festo — CPX-AP-I-EC-M12 — 2019-11
9.1 Object directory
9.1.1 EtherCAT General Objects
Index Sub-index
Description Data type Access1) Value
0x1000 0 Device type U32 ro Bit 0 …15: device profile usedBit 16 …31: further information on thedevice profile used
0x1001 0 Error register U32 ro Bit 0: generic errorBit 1: current errorBit 2: voltage errorBit 3: temperature errorBit 4: communication errorBit 5: device-profile-specific errorBit 6: reservedBit 7: manufacturer-specific error
0x1008 0 Device name VISIBLE_STRING
ro CPX-AP-I-EC-M12
0x1009 0 Hardware version VISIBLE_STRING
ro
0x100A 0 Software version VISIBLE_STRING
ro
Identity object 0x1018
0 Number of entries U8 ro 4
1 Vendor ID U32 ro 0x0000001D
2 Product code U32 ro 0x007B6451
3 Revision number U32 ro
0x1018
4 Serial number U32 ro
Error settings object 0x10F1
0 Number of entries U8 ro 2
1 Local error reaction U32 rw 0 = PDO status1 = deactivate SyncManager2 = device-specific status
0x10F1
2 Sync error counterlimit
U16 rw
Diagnosis history object 0x10F3
0x10F3 0 Number of entries U8 ro 5 … 255
Parameterisation
13Festo — CPX-AP-I-EC-M12 — 2019-11
Index Sub-index
Description Data type Access1) Value
1 Maximum mes-sages
U8 rw 250
2 Newest message U8 ro Subindex of latest message (6 …255)Factory setting = 0
3 Newest acknow-ledged message
U8 rw Factory setting = 0
4 New messagesavailable
BOOL ro p Overwrite Mode:0 = latest message read1 = latest message not readAcknowledge Mode:0 = no acknowledgeable messagesavailable1 = acknowledgeable messages avail-able
Bit 0: send from Emergency messages0 = do not send messages as Emer-gency message (factory setting)1 = send messages as Emergency mes-sage
Bit 1: information messages0 = store information messages in dia-gnostic memory (factory setting)1 = do not store information messagesin the diagnostic memory
Bit 2: warning messages0 = store warning messages in diagnost-ic memory (factory setting)1 = do not store warning messages inthe diagnostic memory
Bit 3: error messages0 = store error messages in diagnosticmemory (factory setting)1 = do not store error messages in thediagnostic memory
0x10F3
5 Flags U16 rw
Bit 4: operating mode0 = Overwrite Mode1 = Acknowledge Mode
Parameterisation
14 Festo — CPX-AP-I-EC-M12 — 2019-11
Index Sub-index
Description Data type Access1) Value
Bit 5: Overwrite/Discard InformationOverwrite mode:1 = overwrite unacknowledged mes-sagesAcknowledge Mode:1 = discard new messages if diagnosticmemory full with unacknowledged mes-sages
5 Flags U16 rw
Bit 6 … 15: reserved
0x10F3
6…
255
Diagnosis message OCTET_STRING
ro Diagnostic message 1…
Diagnostic message 250è Tab. 27 Structure of diagnosticmessages
Timestamp object (0x10F8)
0x10F8 0 Timestamp object U64 ro p Specified in [ns]
Receive PDO Mapping (0x1600 ... 0x17FF)
0 Number of objectsin this PDO
U8 rw 0 … 254
1 First output objectto be mapped
U32 rw
… … … …
0x1600…
0x17FF
n Last output objectto be mapped
U32 rw
Bit 0 … 7: length of the objectBit 8 … 15: subindex of the objectBit 16 … 31: index of the object
Transmit PDO Mapping (0x1A00 ... 0x1BFF)
0 Number of objectsin this PDO
U8 rw 0 … 254
1 First input object tobe mapped
U32 rw
… … … …
0x1A00…
0x1BFF
n Last input object tobe mapped
U32 rw
Bit 0 … 7: length of the objectBit 8 … 15: subindex of the objectBit 16 … 31: index of the object
Sync Manager Communication Type (0x1C00)
0x1C00 0 Number of usedSync Managerchannels
U8 ro 4
Parameterisation
15Festo — CPX-AP-I-EC-M12 — 2019-11
Index Sub-index
Description Data type Access1) Value
1 CommunicationtypeSync Manager 0
U8 ro
2 CommunicationtypeSync Manager 1
U8 ro
3 CommunicationtypeSync Manager 2
U8 ro
0x1C00
4 CommunicationtypeSync Manager 3
U8 ro
0 = not used1 = receive mailbox2 = send mailbox3 = process data output4 = process data input
Sync Manager PDO Assignment (0x1C12 ... 0x1C13)
0 Number ofassigned[RT] x PDOs
U8 rw 0 … 2540x1C12…
0x1C13
1 … n PDO mappingobject index ofassigned PDO
U16 rw 0x1600: RxPDO 10x1601: RxPDO 2…
0x17FF: RxPDO 512or:0x1A00: TxPDO 10x1A01: TxPDO 2…
0x1BFF: TxPDO 512
Sync Manager Synchronization (0x1C32 ... 0x1C33)
0x1C32…
0x1C33
0 Number of syn-chronization para-meters
U8 ro 0 … 3
0x1C32…
0x1C33
1 Synchronizationtype
U16 rw 0: not synchronised1: synchronised2: DC Sync03: DC Sync132: SyncSm033: SyncSm1…
Parameterisation
16 Festo — CPX-AP-I-EC-M12 — 2019-11
Index Sub-index
Description Data type Access1) Value
63: SyncSm31
2 Cycle time U32 rw Specified in [ns]
0x1C32…
0x1C333 Shift time U32 rw Specified in [ns]
1) ro = read only; rw = read write; ro p = read only (PDO mappable)
Tab. 13 EtherCAT General Objects
9.1.2 EtherCAT Modular Device Profile
Index Description Value
0x2000…
0x2FFF
Manufacturer specific area Network parameters of the respective mod-ules based on the APDD
0x6000…
0x6FFF
Input data object area Input objects (TxPDOs)
0x7000…
0x7FFF
Output data object area Output objects (RxPDOs)
0x9000…
0x9FFF
Information data object area Module informationè Tab. 15 Information data object area
0xF000 Modular device profile object è Tab. 16 Modular device profile object
0xF030…
0xF03F
Configured module ident list è Tab. 17 Configured module ident list
0xF050…
0xF05F
Detected module ident list è Tab. 18 Detected module ident list
Tab. 14 EtherCAT Modular Device Profile
Information data object area (0x9000 … 0x9FFF)
Index Sub-index
Description Data type Access1) Value
1 Address of themodule
U16 ro Module address0x9000…
0x9FFF2 Type string VISIBLE_
STRINGro Module description
Parameterisation
17Festo — CPX-AP-I-EC-M12 — 2019-11
Index Sub-index
Description Data type Access1) Value
3 Name string VISIBLE_STRING
ro Module name
4 Device type U32 ro Type of equipment
5 Vendor ID U32 ro Manufacturer ID
6 Product code U32 ro Product code
7 Revision number U32 ro Revision number
8 Serial number U32 ro Serial number
9 Module PDO group U16 ro
10 Module ident U32 ro Module ID
11 Slot U16 ro Slot number
12 Slot group U16 ro Slot group
13…
29
reserved
30 Network segmentaddress
OCTET_STRING[6]
ro Network address
31 Network port U32 ro Network connection
32 Festo product key STRING(12)
ro Festo Product Key
33 Festo part number U32 ro Festo part number
34 Firmware version STRING(34)
ro Firmware version
0x9000…
0x9FFF
35…
255
Vendor/profilespecific
ro Manufacturer/profile-specific informa-tion
1) ro = read only; rw = read write; ro p = read only (PDO mappable)
Tab. 15 Information data object area
Parameterisation
18 Festo — CPX-AP-I-EC-M12 — 2019-11
Modular device profile object (0xF000)
Index Sub-index
Description Data type Access1) Value
0 Number of entries U8 ro
1 Index distance U16 ro Factory setting: 0x10
2 Maximum numberof modules
U16 ro Maximum number of modules
3 General configura-tion
U32 ro Factory setting: 0
0xF000
4 General informa-tion
U32 ro General information
1) ro = read only; rw = read write; ro p = read only (PDO mappable)
Tab. 16 Modular device profile object
Configured module ident list (0xF030 … 0xF03F)
Index Sub-index
Description Data type Access1) Value
1 Module ident ofthe module con-figured at position1
U32 ro Module ID of the module configured atposition 1
2 Module ident ofthe module con-figured at position2
U32 ro Module ID of the module configured atposition 2
… … … … …
0xF030…
0xF03F
255 Module ident ofthe module con-figured at position255
U32 ro Module ID of the module configured atposition 255
1) ro = read only; rw = read write; ro p = read only (PDO mappable)
Tab. 17 Configured module ident list
Parameterisation
19Festo — CPX-AP-I-EC-M12 — 2019-11
Detected module ident list (0xF050 … 0xF05F)
Index Sub-index
Description Data type Access1) Value
1 Module ident ofthe module detec-ted on position 1
U32 ro Module ID of the module detected atposition 1
2 Module ident ofthe module detec-ted on position 2
U32 ro Module ID of the module detected atposition 2
… … … … …
0xF050…
0xF05F
255 Module ident ofthe module detec-ted on position 255
U32 ro Module ID of the module detected atposition 255
1) ro = read only; rw = read write; ro p = read only (PDO mappable)
Tab. 18 Detected module ident list
10 Diagnostics and Fault Clearance
10.1 Diagnostics optionsDiagnostics via LED displaysThe system and network status and errors are displayed directly on the module via LED indicatorsè 10.3 LED displays.
Diagnostics via EtherCATDiagnostics as part of EtherCAT functions via control software over the networkè 10.4 Diagnostics via EtherCAT.
10.2 Diagnostic Messages
Only the diagnostic messages of the interface are listed in the following table.Module-specific diagnostic messages è Instructions for the respective module
ID hex (dec) Message Description
Overvoltage of the logic supply PS 24 V DC was detected.
Remedy – Check logic supply PS.
02 | 01 | 0017(33619991)
Overvoltage in logicsupply PS 24 V DC
Diagnost-ic status
Error
Diagnostics and Fault Clearance
20 Festo — CPX-AP-I-EC-M12 — 2019-11
ID hex (dec) Message Description
Undervoltage in the load supply PL 24 V DC was detected.
Remedy – Check load supply PL.
02 | 01 | 0105(33620229)
Undervoltage in loadsupply PL 24 V DC
Diagnost-ic status
Error
A switch-off of the load supply PL was detected. The causecan be a deliberate shutdown by the emergency stop.
Remedy – Check if the emergency stop was activ-ated.
– Check load supply PL.
02 | 01 | 0106(33620230)
Switch-off load supplyPL 24 V DC
Diagnost-ic status
Information
Overvoltage load supply PL 24 V DC
Remedy – Check load supply PL.
02 | 01 | 013F(33620287)
Overvoltage load sup-ply PL 24 V DC
Diagnost-ic status
Error
The startup parameter specified in the AP device descrip-tion does not exist in the device or deviates from the spe-cification.
Remedy – Check firmware version.
06 | 00 | 0109(100663561)
Startup parameterrejected by device
Diagnost-ic status
Error
The length of the start-up parameter in the device differsfrom the specified length in the AP device description.
Remedy – Check firmware version.
06 | 00 | 010A(100663562)
Start-up parameterdeviation in length
Diagnost-ic status
Error
No check of the target slot configuration for the actual slotconfiguration.
Remedy – Download slot configuration.
06 | 00 | 0188(100663688)
Module identificationcheck skipped
Diagnost-ic status
Warning
Module identification failed for Slot %u (Detected %u -Configured %u).
06 | 00 | 0189(100663689)
Module identificationcheck failed
Remedy – Download current slot configuration.
Diagnostics and Fault Clearance
21Festo — CPX-AP-I-EC-M12 — 2019-11
ID hex (dec) Message Description
06 | 00 | 0189(100663689)
Module identificationcheck failed
Diagnost-ic status
Error
Transferred device address is invalid.
Remedy – Check address configuration. Is the con-figuration set via software or hardware(DIL switch)?
– Check the assigned address for thedevice.
– Check multiple address assignment.– Check the DIL-switch setting.
08 | 00 | 012E(134218030)
Device addressinvalid
Diagnost-ic status
Warning
Calculate bus cycle time failed (local timer too slow).
Remedy – Increase cycle time.
08 | 00 | 0192(134218130)
Invalid cycle time
Diagnost-ic status
Error
The communication to the AP Master is aborted.
Remedy – Restart AP Master.– Check communication cable (AP).
08 | 01 | 0124(134283556)
AP Master lost
Diagnost-ic status
Error
The AP system communication to a module is aborted.
Remedy – Restart AP system.– Check the cable.
08 | 01 | 0127(134283559)
Communication to APmodule interrupted
Diagnost-ic status
Error
Output process data Watchdog of the AP module expired.
Remedy – Match cycle time and watchdog paramet-ers.
– Restart AP system.– Check the cable.
08 | 01 | 0130(134283568)
Output process dataWatchdog of the APmodule expired
Diagnost-ic status
Error
Diagnostics and Fault Clearance
22 Festo — CPX-AP-I-EC-M12 — 2019-11
ID hex (dec) Message Description
Input process data Watchdog of the AP module expired.
Remedy – Match cycle time and watchdog paramet-ers.
– Restart AP system.– Check the cable.
08 | 01 | 0131(134283569)
Input process dataWatchdog of the APmodule expired
Diagnost-ic status
Error
The process data watchdog for the output data in theinterface has expired.
Remedy – Match cycle time and watchdog paramet-ers.
– Restart AP system.– Check the cable.
08 | 01 | 0132(134283570)
Output process dataWatchdog of the inter-face expired
Diagnost-ic status
Error
The process data watchdog for the input data in the inter-face has expired.
Remedy – Match cycle time and watchdog paramet-ers.
– Restart AP system.– Check the cable.
08 | 01 | 0133(134283571)
Input process dataWatchdog of the inter-face expired
Diagnost-ic status
Error
A module has not mirrored the toggle bit in the processdata.
Remedy – Match cycle time and toggle timeout para-meters.
– Restart AP system.– Check the cable.
08 | 01 | 0134(134283572)
AP Master Toggle biterror
Diagnost-ic status
Error
Status change request from: %d to: %d.
Remedy –
08 | 04 | 0191(134480273)
Status changerequest
Diagnost-ic status
Error
Diagnostics and Fault Clearance
23Festo — CPX-AP-I-EC-M12 — 2019-11
ID hex (dec) Message Description
Sync Manager %d invalid address (%d).
Remedy – Set correct Sync Manager address.
08 | 04 | 0193(134480275)
Sync Manager invalidaddress
Diagnost-ic status
Error
Sync Manager %d invalid I/O size (%d).
Remedy – Correct I/O size.
08 | 04 | 0194(134480276)
Sync Manager invalidI/O size
Diagnost-ic status
Error
Sync Manager %d invalid configuration (%d).
Remedy – Check and correct configuration.
08 | 04 | 0195(134480277)
Sync Manager invalidconfiguration
Diagnost-ic status
Error
DC activation register invalid
Remedy – Correct DC activation register.
08 | 04 | 0196(134480278)
DC activation registerinvalid
Diagnost-ic status
Error
The configured SyncType (0x1C32.1 or 0x1C33.1) is notsupported.
Remedy – Check DC registers and supported synctypes (0x1C32.4 and 0x1C33.4).
08 | 04 | 0197(134480279)
Sync Type not suppor-ted
Diagnost-ic status
Error
The system starts.
Remedy –
0B | 00 | 0140(184549696)
System start
Diagnost-ic status
Information
Firmware invalid
Remedy – Repeat transmission of firmware package.
0B | 04 | 00B7(184811703)
Firmware invalid
Diagnost-ic status
Error
The version of the Diagnostic Full Image is not supported.0B | 08 | 018F(185074063)
Unsupported Full Dia-gnostic Image version Remedy – Check and adjust firmware versions of
master and devices.
Diagnostics and Fault Clearance
24 Festo — CPX-AP-I-EC-M12 — 2019-11
ID hex (dec) Message Description
0B | 08 | 018F(185074063)
Unsupported Full Dia-gnostic Image version
Diagnost-ic status
Error
The diagnostic version is not supported.
Remedy – Check and adjust firmware versions ofmaster and devices.
0B | 08 | 0190(185074064)
Unsupported dia-gnostic version
Diagnost-ic status
Error
The device description file stored in the device at the fact-ory is invalid or missing.
Remedy – Restart device.– Check AP system communication.– Check firmware version.– In the event of repeated errors, contact
Festo Service.
0B | 09 | 0128(185139496)
APDD invalid
Diagnost-ic status
Error
The start-up device description file stored in the device atthe factory is invalid or missing.
Remedy – Restart device.– Check AP system communication.– Check firmware version.– In the event of repeated errors, contact
Festo Service.
0B | 09 | 0129(185139497)
Start-up APDD invalid
Diagnost-ic status
Error
Tab. 19 Diagnostic Messages
Diagnostics and Fault Clearance
25Festo — CPX-AP-I-EC-M12 — 2019-11
10.3 LED displays
Module diagnostics [MD]
LED (red,green)
Meaning Remedy
Off
Logic supply PS not available. Check connection of logic supply PS.
Illuminatedgreen
No module diagnostics active –
Flashes green
Module diagnostics activeDegree of severity "Information"e. g. switching off load supply PL
–
Flashes red
Module diagnostics activeDegree of severity "Warning"e. g. parameterisation error
Take appropriate remedial action, e. g. check parameterisation.
Illuminated red
Module diagnostics activeDegree of severity "Error"e. g. undervoltage in load supply PL
Take appropriate remedial action, e. g. check load supply PL.
LED flashesred quickly
Module ramp-up not yet completed.System communication not yet initial-ised.
–
Flashes quicklygreen
Module identification (service function) –
Tab. 20 LED module diagnostics [MD]
Diagnostics and Fault Clearance
26 Festo — CPX-AP-I-EC-M12 — 2019-11
System diagnostics [SD]
LED (red,green)
Meaning Remedy
Off
Logic supply PS not available. Check connection of logic supply PS.
Illuminatedgreen
No system diagnostics active –
Flashes green
System diagnostics activeDegree of severity "Information"e. g. load supply PL to a module notavailable or firmware update in a moduleactive.
–
Flashes red
System diagnostics activeDegree of severity "Warning"e. g. e.g. parameterisation error in amodule.
Illuminated red
System diagnostics activeDegree of severity "Error"e. g. sensor supply short circuit in amodule.
Flashes quicklygreen
Module identification (service function) –
Tab. 21 LED system diagnostics [SD]
Diagnostics and Fault Clearance
27Festo — CPX-AP-I-EC-M12 — 2019-11
Load supply [PL]
LED (red,green)
Meaning Remedy
Illuminatedgreen
Load supply PL available. –
Flashes green
Load supply PL not available. Check load supply PL.
Flashes red
Load supply PL outside the tolerancerange.
Check load supply PL.
Tab. 22 LED load supply [PL]
Maintenance [MT]
LED (yellow) Meaning Remedy
Off
No maintenance needed. –
Illuminated
Maintenance required in at least onemodule in the automation systemCPX-AP.
Carry out the necessary remedial meas-ures è Instructions on the respectivemodule.
Tab. 23 LED maintenance [MT]
Diagnostics and Fault Clearance
28 Festo — CPX-AP-I-EC-M12 — 2019-11
EtherCAT operating status [RUN]
LED (green) Meaning Remedy
Illuminated
OperationalNormal operating status
–
Flashing
Pre-operationalConfiguration of EtherCAT network
–
flashes 1xbriefly
Safe operationalOnly the input signals are updated. Theoutputs retain their current status.
–
flickers
BootstrapThe interface is receiving a firmwareupdate.
–
Off
InitialisationNormal status after switching on or aftera restart
–
Tab. 24 LED EtherCAT operating status [RUN]
Diagnostics and Fault Clearance
29Festo — CPX-AP-I-EC-M12 — 2019-11
EtherCAT error [ERR]
LED (red) Meaning Remedy
Illuminated
serious communication errorPossible causes:– Application controller not respond-
ing– Watchdog timeout due to ESC
Contact Festo Service è www.festo.com.
Flashing
Configuration error, no network connec-tionPossible causes:– Line interrupted– No connection to master– Master is not active
Check network connections.Check the configuration and addressingof the interface.
flashes 1xbriefly
EtherCAT state change from Operationalto Safe-Operational due to synchronisa-tion error
–
flashes 2xbriefly
Application watchdog timeoutWatchdog timeout due to sync manager
–
flickers
Booting errorError (checksum) in application control-ler flash memory
–
Off
No error –
Tab. 25 EtherCAT error [ERR] LED
Diagnostics and Fault Clearance
30 Festo — CPX-AP-I-EC-M12 — 2019-11
Connection status [LA X1], [LA X2]
LED (green) Meaning Remedy
Off
No network connection. Check network connection.
flickers
Network connection OK.Data traffic activity.
–
Illuminated
Network connection OK.No data traffic.
–
Tab. 26 LED connection status [LA X1], [LA X2]
10.4 Diagnostics via EtherCAT
The availability of diagnostic information via the EtherCAT network depends on the parameterisation.
10.4.1 Diagnostics via SDO accessDiagnostic information can be requested from the higher-order controller through SDO accessè 9.1 Object directory.
10.4.2 Diagnostics via diagnostics historyThe diagnostic messages of the EtherCAT Interface are stored in the diagnostic history. Via the dia-gnostic object 0x10F3 (from subindex 6) the last 250 diagnostic messages of the EtherCAT interfacecan be displayed è 9.1 Object directory.An error message referenced with a code is displayed for every event (warning, error, information).The diagnostic messages are translated using the device description file (ESI file) and can be readfrom the controller software in this way.
Operating modes of diagnostic messagesThere are two operating modes for handling diagnostic messages. The operating mode can be definedvia object 0x10F3 (subindex 5, bit 4):– Overwrite Mode:
When the number of diagnostic messages reaches 250, old diagnostic messages are overwritten.– Acknowledge Mode:
A diagnostic message must first be acknowledged before it can be overwritten with a new dia-gnostic message. When the number of unacknowledged diagnostic messages reaches 250, newdiagnostic messages will not be saved and will be lost.
Diagnostics and Fault Clearance
31Festo — CPX-AP-I-EC-M12 — 2019-11
Map "New message available" messageFor simplification of the diagnostic evaluation, the module offers the option of signalling the existenceof a new diagnostic message through the process data. To do this, the "New message available"object can optionally be mapped to the process data.
Deactivate/activate Emergency messageThe sending of one Emergency message can be deactivated and activated via object 0x10F3 (subindex5, bit 0).
Structure of diagnostic messages
Parameter Data type Description
Bit 0 … 15 Bit 16 … 31
0x0000 …0xDFFF Not used
0xE000 Error number of the diagnosticsIDè Tab. 19 Diagnostic Messagese.g.: 0x | 02 |01 |0017 (33619991)– 02 = main group– 01 = sub-group– 0017 = error number
0xE001 … 0xE7FF Not used
0xE800 Emergency Error Code as definedin DS301 or DS4xxx
0xE801 … 0xEDFF reserved
0xEE00 … 0xEFFF profile-specific
Diagnostic code U32
0xF000 … 0xFFFF Not used
Bit 0 … 3 Diagnostic status0 = Information message1 = warning message2 = error message
Bit 4 Local timestamp
Bit 5 … 7 reserved
Flags U16
Bit 8 … 15 Number of parameters in this dia-gnostic message
Text ID U16 0 = no text ID1 … 65535 = text ID
Time stamp U64 0 = no time stamp
Diagnostics and Fault Clearance
32 Festo — CPX-AP-I-EC-M12 — 2019-11
Parameter Data type Description
Bit 12 … 15 Bit 0 … 11
0 Data type Parameter 10x0001 = BOOL0x0002 = INT80x0003 = INT160x0004 = INT320x0005 = U80x0006 = U160x0007 = U32
1 BYTE ARRAY size [Byte]
2 ASCII string size [byte]
3 UNICODE-STRING Size [Byte]
4 Size Parameter 1 [Byte]
FlagsParameter 1
U16
5 … 15 reserved
Parameter 11)
Value of parameter 1
FlagsParameter 2
U16 è flags parameter 1
Parameter 22)
Value of parameter 2… … …
1) depending on flags parameter 12) depending on flags parameter 2
Tab. 27 Structure of diagnostic messages
Diagnostics and Fault Clearance
33Festo — CPX-AP-I-EC-M12 — 2019-11
10.4.3 Emergency messageThe automation system CPX-AP sends a Emergency message. For this the sending of the data Emer-gency message via object 0x10F3 (subindex 5, bit 0) must be activated.The Emergency message is structured as follows:
Byte
0 1 2 3 4 5 6 7
Emergency error codeè Tab. 29 Emergencyerror code
Errorregisterè 0x1001
Error number of thediagnostics IDè Tab. 19 DiagnosticMessages
Module number Channelnumber
Tab. 28 Structure of the Emergency message
Emergencyerror code
Category
0x2081 1 Current
0x3082 2 Voltage
0x4083 3 Temperature
0xF084 4 Pressure
0xF085 5 Motion
0x6386 6 Configuration/parameterisation
0x8087 7 Monitoring
0x8188 8 Communication
0xF089 9 Safety engineering
0x508A 10 Internal hardware
0x608B 11 Software
0xF08C 12 Maintenance
0xFF8D 13 Various
0xFF8E 14 Device-specific
0xFF8F 15 Customer-specific
0x9090 16 External device
0xF091 17 Security (data)
0x7092 18 Encoder
Tab. 29 Emergency error code
Diagnostics and Fault Clearance
34 Festo — CPX-AP-I-EC-M12 — 2019-11
11 DisposalENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accordance with the currentregulations è www.festo.com/sp.
12 Technical Data
General technical data
General technical datafor automation systemCPX-AP
Instruction manual for automation system CPX-APè 1.1 Applicable documents
Dimensions(length × width ×height)
[mm] 170 × 45 × 35
Product weight [g] 190
Ambient temperature [°C] –20 … +50
Storage temperature [°C] –40 … +70
Storage time [years] 2 (max.)
Humidity(non-condensing)
[%] 5 … 95
Assigned addressspace (inputs/outputs)
[Bytes] 2048/2048 (max.)
Module code (hex/dec) 0x2084/8324d
Module identification CPX-AP-I-EC-M12
Degree of protection inaccordance withEN 60529
IP65/IP67(if lines are connected and connections that are not required areclosed with a cover cap)
Protection against elec-tric shock (protectionagainst direct andindirect contact inaccordance withIEC 60204-1)
through the use of SELV/PELV circuits(safe extra-low voltage/protected extra-low voltage)
Electromagnetic com-patibility
See declaration of conformity è www.festo.com
Mounting position Any
Tab. 30 General technical data
Disposal
35Festo — CPX-AP-I-EC-M12 — 2019-11
Power supply
Logic supply PS [V DC] 24 _ 25 %
Intrinsic current con-sumption at nominaloperating voltage 24 Vfrom PS
[mA] 84
Reverse polarity pro-tection 24 V PS against0 V PS
Yes
Diagnostic message,overvoltage in logicsupply PS
[V DC] ³ 31
Mains buffering time,logic supply PS
[ms] 10
Load supply PL [V DC] 24 ± 25 %
Intrinsic current con-sumption at 24V atnominal voltage 24 Vfrom PL
[mA] Typ. 5
Reverse polarity pro-tection 24 V PL against0 V PL
Yes
Diagnostic message,undervoltage in loadsupply PL
[V DC] £ 17
Diagnostic message,overvoltage in loadsupply PL
[V DC] ³ 31
Capacitive load at load supply PL
24 V PL to 0 V PL [nF] Typ. 35
24 V PL to FE [nF] Typ. 35
0 V PL to FE [nF] Typ. 20
Tab. 31 Power supply
Technical Data
36 Festo — CPX-AP-I-EC-M12 — 2019-11
Network-specific data
Protocol EtherCAT(based on the Ethernet protocol IEEE 802.3)
Specification Standards and norms with reference to EtherCAT:IEC 61158IEC 61784IEC 61918ISO/IEC 8802-3
Transmission rate [Mbps] 100
Crossover Detection Auto-MDI/MDI-X
Cable length persegment
[m] 100 (max.)
Cable specification
Cable type Ethernet twisted pair cable, shielded
Transmission class Category Cat 5 or higher
Cable diameter [mm] 6 … 8
Wire cross section [mm2] 0.14 … 0.75AWG 22 (required for maximum connection length between net-work participants)
Tab. 32 Network-specific data
Technical Data
37Festo — CPX-AP-I-EC-M12 — 2019-11
© 2019 all rights reserved to Festo SE & Co. KG
Copyright:Festo SE & Co. KG Ruiter Straße 82 73734 Esslingen Germany
+49 711 347-0
www.festo.comInternet:
Phone: