Fan Coil Unit Product Line-up. FCU Home Application Show.

32
Fan Coil Unit Fan Coil Unit Product Line-up Product Line-up

Transcript of Fan Coil Unit Product Line-up. FCU Home Application Show.

Page 1: Fan Coil Unit Product Line-up. FCU Home Application Show.

Fan Coil Unit Fan Coil Unit

Product Line-upProduct Line-up

Page 2: Fan Coil Unit Product Line-up. FCU Home Application Show.

FCU Home Application Show

Page 3: Fan Coil Unit Product Line-up. FCU Home Application Show.

How to Read the Model No.?

I F --Function controlR Remote control RA Remote control with heaterE with electric heater

Nominal Air Volume (CFM)

H High Static Pressure __ Normal Static Pressure

Type CodesC4 Cassette 4

Way C1 Cassette 1 Way

CC Cassette Compact

H1 Duct TypeH2 2nd

Generation Duct TypeH3 Duct Type

High StaticF1 Floor Open

Side Intake F2 Floor Open Bottom Intake

F3 Floor Concealed

MW Mid-Wall TypeChilled Water fan Coil Unit

Page 4: Fan Coil Unit Product Line-up. FCU Home Application Show.

All Series (Present Product)

4 way Cassette

Compact 4 way

cassette

Series Model

IFC4-xxHRN4

ModelAir Volume

(CFM)Series

Air Volume

(CFM)

600~1500

IFCC-xxHRN4 300~500

One 1 Cassette

IFC1-xxxHRN4 300~600

Floor Standing

IFC1-xxHRN4

IFC2-xxHRN4 150~1000

Floor Standing

IFC3-xxHRN4 150~1000

Duct 2-rows

IFH2-XHRN4

IFH2H-xHRN4200~1400

Duct 4-rows

IFH1-xxHRN4

IFH1-xHNR4300~2000

Page 5: Fan Coil Unit Product Line-up. FCU Home Application Show.

All Series (New Products)

New 4 way Cassette

New Compact 4 way

cassette

Series Model

IFC4-xxxR/RA

With Auxiliary

Electrical Heater

ModelAir Volume

(CFM)Series

Air Volume

(CFM)

600~1500

IFCC-xxxR/RA

With AEH300~500

New 1 way Cassette

IFC1-xxxR/RA

With AEH300~400

Wall mounted

Duct 2-rows IFH2-xxxE

IFH2H-xxxE

With AEH &

Plenums

200~1400

High Static

Pressure IFH3H

IFH3H-xxxE

With AEH

800~2200

800~2200

Duct 4-rows IFH1-xxxE

With AEH &

Plenum

250~600

300~2000

200~1200

Mass

production on

June 1st, 2008

Duct New 3-rows

IFMW

Page 6: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

2-Rows2-RowsIFH2 IFH2 SeriesSeriesAir volume: 200-1400 CFMAir volume: 200-1400 CFMAir return plenums and air filter are optionalAir return plenums and air filter are optionalIFH2 static pressure is 12PaIFH2 static pressure is 12PaIFH2H static pressure is 30Pa, and 50Pa can IFH2H static pressure is 30Pa, and 50Pa can be customized.be customized.

2-Rows2-RowsIFH2-XXXEIFH2-XXXE Series (With Auxiliary Electrical Heater) Series (With Auxiliary Electrical Heater)Air volume: 200-1400 CFMAir volume: 200-1400 CFMAir return plenums and air filter are standardAir return plenums and air filter are standardIFH2-xxxE static pressure is 12PaIFH2-xxxE static pressure is 12PaIFH2H-xxxE static pressure is 30Pa, and 50Pa IFH2H-xxxE static pressure is 30Pa, and 50Pa can be customized. can be customized.

Page 7: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

NewNew 3-Rows3-Rows

Air volume: 200-1200 CFMAir volume: 200-1200 CFM

Air return plenums and air filter are optionalAir return plenums and air filter are optional

The working static pressure of standard series is The working static pressure of standard series is 12 Pa, and which of high static series is 30Pa. 12 Pa, and which of high static series is 30Pa. Also 50Pa can be customized.Also 50Pa can be customized.

Page 8: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

4-Rows4-RowsIFH1IFH1 Series SeriesAir volume: 300-2000 CFMAir volume: 300-2000 CFMAir return plenums and air filter are optionalAir return plenums and air filter are optionalstatic pressure is 12Pastatic pressure is 12Pa

4-Rows4-RowsIFH1-XXXEIFH1-XXXE Series (With Auxiliary Electrical Heater) Series (With Auxiliary Electrical Heater)Air volume: 300-2000 CFMAir volume: 300-2000 CFMAir return plenums and air filter are standardAir return plenums and air filter are standardstatic pressure is 12Pastatic pressure is 12Pa

Page 9: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Elegance and prestige----Concealed installation makes the conditioned space more concordant.

Low thickness for easy installation and maintenance.

Low noise fan direct driven by 1 phase and 4 speed setting motor, so there are more choices for variable applications.

The plenum and the air filter are standard, so it is very easy to install.

The auxiliary electrical heater and the new electronics thermostat are standard. And the heater can be controlled independently.

Features

Page 10: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

L

490

240

(mm)

Connection from right side

Note:1. Only 1400CFM type is 3 rows;2. Pipe connection way can be selected

from left or right.3. IFH2 Pressure is 12 Pa 4. IFH2H pressure is 30 pa, and 50Pa

can be customized.

L CFMdB (A)

770 200 39

827 300 41

937 400 43

1140

500 48

600 48

800 51

1546 1000 51

18351200 53

1400 55

Page 11: Fan Coil Unit Product Line-up. FCU Home Application Show.

Model CFMCooling Capacity

Heating Capacity

Power Input

Static Pressure

Electrical Heater

IFH2(H)-200(E) 200 2003 W 3210 W 43 W 12(30) Pa 500W

IFH2(H)-300(E) 300 2710 W 4310 W 59 W 12(30) Pa 650W

IFH2(H)-400(E) 400 3605 W 5410 W 72 W 12(30) Pa 1000W

IFH2(H)-500(E) 500 4500 W 6800 W 84 W 12(30) Pa 1000W

IFH2(H)-600(E) 600 5410 W 8100 W 105 W 12(30) Pa 1500W

IFH2(H)-800(E) 800 7195 W 11000 W 150 W 12(30) Pa 2000W

IFH2(H)-1000(E) 1000 9000 W 13500 W 172 W 12(30) Pa 2000W

IFH2(H)-1200(E) 1200 11000 W 16500 W 210 W 12(30) Pa 3000W

IFH2(H)-1400(E) 1400 13000 W 19500 W 250 W 12(30) Pa 3000W

Specifications

Duct Type

Page 12: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

L490(590)

240(340)

(mm)

Note:1. Pipe connection way can be

selected from left or right.2. Pressure is 12 Pa 3. Available for 50Hz & 60 Hz

L CFMdB (A)

874 300 41.2

1185

400 40.0

450 39.4

500 43.2

600 46.2

1369

750 46.2

850 46.7

950 51.61369×340×49

0 1200 51.6

1369×340×590

1500 51.4

2000 58.4

Page 13: Fan Coil Unit Product Line-up. FCU Home Application Show.

Model CFMCooling Capacity

Heating Capacity

Power Input

Static Pressure

Electrical Heater

IFH1-300 300 2700 W 3510 W 43 W 12 Pa 600W

IFH1-400 400 3600 W 4680 W 44 W 12 Pa 1500W

IFH1-450 450 4050 W 5260 W 55 W 12 Pa 1500W

IFH1-500 500 4500 W 5850 W 60 W 12 Pa 1500W

IFH1-600 600 5400 W 7020 W 105 W 12 Pa 1500W

IFH1-750 750 6800 W 8840 W 119 W 12 Pa 2000W

IFH1-850 850 7600 W 9880 W 124 W 12 Pa 2000W

IFH1-950 950 8400 W 10900 W 162 W 12 Pa 2000W

IFH1-1200 1200 10800 W 14000 W 175 W 12 Pa 2400W

IFH1-1500 1500 13500 W 17550 W 236 W 12 Pa 2400W

IFH1-2000 2000 18000 W 23400 W 360 W 12 Pa 3000W

Specifications

Duct Type

Page 14: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Optional Accessories

Air return plenums, electrical heaters, 3-way valves, thermostat.

For the units without Electrical

Heater

Page 15: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Optional Accessories

New electronic thermostat especially for the units with electrical heater.

For the units with Electrical

Heater

Page 16: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Typical Installation 1

Installation

Page 17: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Typical Installation 2

Installation

Page 18: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Installation

Typical installation sketch(With 2-way valve)

Page 19: Fan Coil Unit Product Line-up. FCU Home Application Show.

Duct Type

Installation

Typical installation sketch(With 3-way valve)

Page 20: Fan Coil Unit Product Line-up. FCU Home Application Show.

High Static Pressure Duct Type

800, 1000, 1200, 1400

1600, 2000, 2200

IFH3H SeriesAir volume: 800-2200 CFMAir volume: 800-2200 CFMAir return plenums and air filter are includedAir return plenums and air filter are includedFor 800 to 1400 CFM unit, the working static pressure is 70PaFor 1600 to 2200 CFM units, the working static pressure is 100Pa

Page 21: Fan Coil Unit Product Line-up. FCU Home Application Show.

High Static Pressure Duct Type

IFH3H-xxxE SeriesAir volume: 800-2200 CFMAir volume: 800-2200 CFMAir return plenums and air filter included as well as Auxiliary Air return plenums and air filter included as well as Auxiliary Electrical Heater Electrical Heater For 800 to 1400 CFM unit, the working static pressure is 70PaFor 1600 to 2200 CFM units, the working static pressure is 100Pa

800, 1000, 1200, 1400

1600, 2000, 2200

Page 22: Fan Coil Unit Product Line-up. FCU Home Application Show.

High Static Pressure Duct Type

Features• High air volume, high static pressure, high capacity

• Easy to clean or change the air filter

• Extra drain pan to protecting your ceiling

• Includes air plenum, air filters.

Page 23: Fan Coil Unit Product Line-up. FCU Home Application Show.

High Static Pressure Duct Type

Model CFMCooling Capacity

Heating Capacity

Power Input

Static Pressure

Electrical Heater

IFH3H- 800 5275 W 5860 W 350 W 70 Pa 3000W

IFH3H- 1000 7030 W 7910 W 350 W 70 Pa 3000W

IFH3H- 1200 8790 W 9670 W 350 W 100 Pa 3000W

IFH3H- 1400 10550 W 10550 W 350 W 100 Pa 3000W

IFH3H- 1600 12310 W 13480 W 650 W 100 Pa 10 kW

IFH3H- 2000 14070 W 15530 W 1020 W 100 Pa 10 kW

IFH3H- 2200 17585 W 19340 W 1140 W 100 Pa 10 kW

Specifications

Page 24: Fan Coil Unit Product Line-up. FCU Home Application Show.

New Cassette Type

Body Dimensions (mm)

:850×235×400

Panel Dimensions (mm):1050×18×470

CFMCooling Capacity

dB (A)

Electrical Heater

300 3040 W 41.8 1000 W

400 3790 W 43.7 1000 W

IFCC-xxxR/RA Series

R means normal models

RA means the models with auxiliary electrical heater

Page 25: Fan Coil Unit Product Line-up. FCU Home Application Show.

New Cassette Type

Dimension (mm):

580×254×580

Panel Dimension (mm):

650×30×650

Dimension (mm):

840×240×840

840×310×840

Panel Dimension (mm):

950×40×950

Compact type

IFCC-xxxR/RA

Common type

IFC4-xxxR/RA

CFMCooling Capacity

dB (A)

Electrical Heater

300 3000 W 38.8 1000 W

400 3780 W 40.1 1000 W

450 4050 W 40.8 /

500 5480 W 42.5 /

CFMCooling Capacity

dB (A)

Electrical Heater

600 5720W 44.6 2100 W

750 6990W 45.1 2100 W

850 7270 W 45.8 2700 W

950 8220W 47.7 2700 W

1200 10390 W 49.5 2700 W

1500 12870 W 51.8 2700 W

Page 26: Fan Coil Unit Product Line-up. FCU Home Application Show.

New Cassette Type

Built-in body design, integrative design with the ceiling, makes the installation room more concordant;

Built-in high head drain pump can lift the condensate water up to 500 mm and drain out smoothly;

New designed coils makes the water pressure drop decrease and makes the capacity higher;

4-speed motor gives you more choices.

Brand new appearance of common 4-way cassette.

Features

Page 27: Fan Coil Unit Product Line-up. FCU Home Application Show.

Floor-standing Type

Dimension (mm):

550×212×545

750×212×545

950×212×545

1250×212×545Concealed type

IFF3

Dimension (mm):

880×225×626

1000×225×626

1200×225×626

1500×225×626

Exposed type

IFF1 air return from side

IFF2 air return from bottom

CFMCooling Capacity

Heating Capacity

dB (A)

150 1150 W 2540 W 32

250 1870 W 4170 W 35

300 2530 W 5640 W 37

400 3270 W 7220 W 39

450 3970 W 8850 W 41

500 4850 W 10280 W 43

600 5640 W 12240 W 44

800 6520 W 15350 W 46

900 7850 W 18200 W 48

Page 28: Fan Coil Unit Product Line-up. FCU Home Application Show.

Floor-standing Type

Available now!

New grill

Exposed type

IFF4

IFF5

Special designSpecial design

Page 29: Fan Coil Unit Product Line-up. FCU Home Application Show.

Floor-standing Type

Features

All metal parts are made of commercial grade galvanized steel, providing maximum protection against corrosion.

Soft, streamlined appearance.

Air filter is easily removed and cleaned.

Low noise fan direct driven by single phase and 3 speed setting motor

If cooperate with the newly designed thermostat- KJR-15B/E(P), when the inlet water temperature is higher than 20 in cooling mode or lower ℃than 35 in heating mode, the fan will be shut down automatically to ℃maintain the comfort.

Page 30: Fan Coil Unit Product Line-up. FCU Home Application Show.

Floor-standing Type

Features Thermostat and 3-way valve are optional

Page 31: Fan Coil Unit Product Line-up. FCU Home Application Show.

Wall-mounted Type

Air volume range: 250, 300, 400, 500 and 600 CFM. The appearance is the same as wall mounted indoor unit for MDV

NEW

IFM

W

Serie

s!

Page 32: Fan Coil Unit Product Line-up. FCU Home Application Show.

Thank You!