FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU...

33
Data Sheet FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 1 Fan Coil Unit - EC Fan - Waterside 4 Pipe and 2 raise/lower (floating point) valves. The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan, in response to a thermistor temperature sensor with a local setpoint knob and a local switch input (window contact, pushbutton, or Passive Infra Red movement detector input). The WR4 strategy is for waterside 4 pipe units controlling 2 raise/lower (floating point) valve actuators. The strategy is designed to work with TB/TS Trend Thermistor Room Sensors. The strategy supports the fitting of a WMB Room Display module without further configuration. The strategy is designed for use with an IQeco31 and is part of the Plus library. Order code: IQE31/[y]/BAC/ECFANWR4P/[p] where [y] is unit type F = fixed, P = programmable and [p] is the voltage option. The strategy will also fit IQeco35 and IQeco38 and can be field downloaded to suitable controllers using SET and the standard solutions. Inputs The following real sensors and digital inputs are connected to the input channels and their values can be monitored by text comms (including IC Comms): Real Sensors IN 1: "Local Discharge Air Temp" (S21), the thermistor temperature sensor for the discharge air. IN 2: "Local Space Temperature" (S22), the thermistor temperature sensor for the space. IN 3: "Local Setpoint Adjust" (S23), the local setpoint adjustment potentiometer (scaled in the range -0.5 to +0.5). This generates a setpoint trim in the range -1°C to +1°C or -1°F to +1°F when the knob ‘Offset Range’ (K3) value is set to 2. Real Digital Inputs IN 4: "Window Pushbutton PIR" (I24) this input can be either a window contact which opens, or a pushbutton, or PIR (passive infra red occupation detector) which closes when the occupation override is required. The type of input is defined by switches ‘Window Mode 1=Enabled’ (W41) and ‘0=Pushbutton 1=PIR’ (W42). Outputs

Transcript of FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU...

Page 1: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

Data Sheet

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 1

Fan Coil Unit - EC Fan - Waterside 4 Pipe and 2 raise/lower (floating point) valves. The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan, in response to a thermistor temperature sensor with a local setpoint knob and a local switch input (window contact, pushbutton, or Passive Infra Red movement detector input). The WR4 strategy is for waterside 4 pipe units controlling 2 raise/lower (floating point) valve actuators. The strategy is designed to work with TB/TS Trend Thermistor Room Sensors. The strategy supports the fitting of a WMB Room Display module without further configuration. The strategy is designed for use with an IQeco31 and is part of the Plus library. Order code: IQE31/[y]/BAC/ECFANWR4P/[p] where [y] is unit type F = fixed, P = programmable and [p] is the voltage option. The strategy will also fit IQeco35 and IQeco38 and can be field downloaded to suitable controllers using SET and the standard solutions. Inputs

The following real sensors and digital inputs are connected to the input channels and their values can be monitored by text comms (including IC Comms): Real Sensors IN 1: "Local Discharge Air Temp" (S21), the thermistor temperature sensor for the discharge air. IN 2: "Local Space Temperature" (S22), the thermistor temperature sensor for the space. IN 3: "Local Setpoint Adjust" (S23), the local setpoint adjustment potentiometer (scaled in the range -0.5 to +0.5). This generates a setpoint trim in the range -1°C to +1°C or -1°F to +1°F when the knob ‘Offset Range’ (K3) value is set to 2. Real Digital Inputs IN 4: "Window Pushbutton PIR" (I24) this input can be either a window contact which opens, or a pushbutton, or PIR (passive infra red occupation detector) which closes when the occupation override is required. The type of input is defined by switches ‘Window Mode 1=Enabled’ (W41) and ‘0=Pushbutton 1=PIR’ (W42). Outputs

Page 2: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20 May 2011 2

OUT 1: "Occupation Relay" (D1), this output is used to switch power to the fan controller. OUT 5,6: "Heating Valve" (D5), these outputs are connected to a raise/lower (floating point) actuator to raise (open) and lower (close) respectively. OUT 7,8: "Cooling Valve" (D7), these outputs are connected to a raise/lower (floating point) actuator to raise (open) and lower (close) respectively. OUT 9: "EC Fan" (D9), this is connected to the speed input on the EC fan controller. Default Operation The behaviour of the strategy before any configuration of knobs as switches is as follows: The default occupancy state of the strategy is unoccupied. In most cases when the controller is powered on the fan outputs will not operate as the space temperature used for control will be within the deadband for the unoccupied state. There are 3 ways to take the strategy out of the unoccupied state: 1. Set Knob "Remote Occupancy" (K11) to 0. 2. Using a pushbutton connected to IN4. Press the pushbutton once; this should place the unit into bypass. The bypass state is active until another press of the pushbutton or timeouts after 30 minutes. 3. Use the service button to put the unit into occupied. Details are in "Service Button - Occupancy" section of the strategy datasheet. The fan output may not be operating for the following reasons: a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes. b. Changes to the knobs and switches from the defaults are overriding the fan control. c. The occupancy state is unoccupied. Knobs Switches <21 The following knobs and switches are grouped by the role they are intended to play within the strategy. They can be monitored and changed by text comms (including IC Comms). Some can be monitored using display and directory modules (e.g. using IQView): Modules Role 1-10 Adjustments - Items the users may want to change. 11-20 Remote Control - Items that are expected to receive IC Comms e.g. frost protection. 21-30 Overrides - Items that enable control to be overridden e.g. heating override. 31-40 Settings - Items that should be set up during commissioning. 41-50 Options - Items that select an option or behaviour e.g. serial parallel fan. 51-60 Energy - Items related to energy. Adjustments K1 ‘Pushbutton PIR Timeout’, this knob defines the time in minutes for which the activation of the pushbutton/PIR input overrides the unit into the occupied state. The default value is 30 minutes. K2 ‘Setpoint Adjust Timeout’, this knob defines the time in minutes for which any setpoint trim will be applied to the setpoint. The default value is 30 minutes. K3 ‘Offset Range’, this knob is used to define the range of ‘Local Setpoint Adjust‘ (S23). The ‘Local Setpoint Adjust‘ (S23) is scaled to give a range of -0.5 to +0.5; this is multiplied by the ‘Offset Range’ to give the setpoint trim which is applied to the ‘Remote Setpoint’(K14) to produce the ‘Setpoint’ (S3). The default value is 2°C or 2°F producing a value between -1°C to +1°C or -1°F to +1°F. K4 ‘OCC Deadband’, this knob defines the difference between the heating and cooling setpoints during occupation. The default value is 1°C or 2°F. K5 ‘NOCC Deadband’, this knob defines the difference between the heating and cooling setpoints during non-occupation. The default value is 12°C or 22°F. K6 ‘Standby Deadband’, this knob defines the difference between the heating and cooling setpoints during standby. The default value is 2°C or 4°F. K7 ‘Heating Setpoint’, this knob defines the heating setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint 1=Separate’ (W36). The default value is 19.5°C or 67°F. K8 ‘Cooling Setpoint’, this knob defines the cooling setpoint when separate setpoints are selected using switch ‘HeatCool Setpoint 1=Separate’ (W36). The default value is 20.5°C or 69°F. W1 ‘Unit Bypass Request 1=Active’, this switch is set to ON if the unit is in bypass and can be used to put the unit into or out of bypass. The default state is OFF.

Page 3: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3

Remote Control K11 ‘Remote Occupancy’, this knob defines unit’s occupancy state: 0(Occupied), 1(Unoccupied), 2(Bypass), 3(Standby). It can be overridden into bypass (equivalent to Occupied within the unit) from any occupation state by the pushbutton or from standby by the PIR. The state is overridden to unoccupied by the switch ‘Remote Shutdown 1=Shutdown’ (W11) or the window contact (IN24). The definition of the occupancy states are detailed below under Occupancy States. The default value is 1(Unoccupied). K12 ‘Remote Space Temperature‘, this knob is used instead of input ‘Local Space Temperature’ (S22) when the input has an out of limits or read alarm. It can also be used by setting switch ‘Temperature Select 1=Remote’ (W34) to ON. The default value is 20°C or 68°F. K13 ‘Remote Setpoint Offset‘, this knob is used instead of input ‘Local Setpoint Adjust’ (S23) to provide the setpoint trim. It is added to the ‘Remote Setpoint’ (K14) when the input (S23) has an out of limits or read alarm. It can also be used by setting switch ‘SP Offset Select 1=Remote’ (W35). The default value is 0°C or 0°F. K14 ‘Remote Setpoint‘, this knob is combined with the setpoint trim to provide the ‘Setpoint’ (S3). The default value is 20°C or 68°F. K15 ‘Remote Fan Speed‘, this knob is used to set the fan speed in the range of range: 0 (off), 1 (low), 2 (medium), 3 (high), or 4(auto). To ensure that the 'Remote Fan Speed' value is used when sensor ‘Local Fan Speed’ (S27) is fitted the switch 'Fan Speed Select 1=Remote' (W39) must set to ON. The fan will be switched off during non-occupation unless there is heating demand (fabric protection) which selects low fan speed. The default value is 4(auto). K17 ‘Heating Flow Temperature’, this knob sets the temperature used to calculate the energy consumption of the unit when in heating mode. The default value is 80°C or 176°F. K18 ‘Cooling Flow Temperature’, this knob sets the temperature used to calculate the energy consumption of the unit when in cooling mode. The default value is 6°C or 43°F. W11 ‘Remote Shutdown 1=Shutdown’, this switch when set to ON forces the unit into the unoccupied state, disables cooling, only allows sub-zero heating, and disables fabric protection during non-occupation. The default state is OFF. W12 ‘Frost Condition 1=Frost’, this switch when set to ON forces the unit into a frost condition during non-occupation. During the frost condition the heating demand is fixed at 98%. The default state is OFF. Knobs Switches 21 - 40 Overrides K21 ‘Heating Override Value’, this knob sets the value used to drive the heating output when switch ‘Heating Override 1=Enabled’ (W21) is enabled. The default value is 0%. K22 ‘Cooling Override Value’, this knob sets the value used to drive the cooling output when switch ‘Cooling Override 1=Enabled’ (W22) is enabled. The default value is 0%. K28 ‘Fan Speed Override Value EC’, this knob sets the value used to drive the fan speed output when switch ‘Fan Override 1=Enabled’ (W27) is enabled. The analogue value 0 is OFF and 100 is full speed. The default value is 50. W21 ‘Heating Override 1=Enabled’, this switch when set to ON enables heating override and the heating valve output is set to the value on the knob ‘Heating Override Value’’ (K21). The default state is OFF. W22 ‘Cooling Override 1=Enabled’, this switch when set to ON enables cooling override and the cooling valve output is set to the value on the knob ‘Cooling Override Value’’ (K22). The default state is OFF. W27 ‘Fan Override 1=Enabled’, this switch when set to ON enables fan to be overridden and the fan outputs are set to the speed selected on the knob ‘Fan Speed Override Value EC’ (K28). The default value is OFF. W28 ‘Water Balance 1=Enabled’, this switch when set to ON forces all valve outputs to 100%. The default state is OFF. Settings K31 ‘Fan Anti Cycle Time’, this knob defines the time in minutes that the fan must be OFF before restarting to ensure maximum number of starts per hour is not exceeded. The default value is 5 minutes (maximum of 12 starts per hour). K39 ‘Minimum Fan Speed Setpoint’, this knob defines the minimum speed permitted by the EC fan. The default value is 37%. K40 ‘Maximum Fan Speed Setpoint’, this knob defines the maximum speed permitted by the EC fan. The default value is 70%. W31 ‘Service Button Mode 1=Enabled’, this switch when set to ON allows the service button to be used as an input into the strategy. The default state is ON. W32 ‘Overrides 0=Disabled 1=Enabled’, this switch when set to ON allows the strategy overrides to be used. The default state is ON. W34 ‘Temperature Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Space Temperature‘ (K12) and not sensor ‘Local Space Temperature’ (S22). The default state is OFF. W35 ‘SP Offset Select 1=Remote’, this switch when set to ON forces the control to use the value from knob ‘Remote Setpoint Offset‘ (K13) and not sensor ‘Local Setpoint Adjust’ (S23). The default state is OFF. W36 ‘HeatCool Setpoint 1=Separate’, this switch when set to ON enables the control to use separate setpoints for heating and cooling use knobs ‘Heating Setpoint’ (K7) and ‘Cooling Setpoint’ (K8). The default state is OFF. W37 ‘Pushbutton TETS KO 1=Fitted’, this switch when set to ON allows the control to utilise the override pushbutton operation of the TB/TS/KO range of thermistor room temperature sensors. The default state is OFF. W39 ‘Fan Speed Select 1=Remote’, this switch when set to ON forces the strategy to use the value from knob ‘Remote Fan Speed‘ (K15) and not sensor ‘Local Fan Speed’ (S27). The default state is OFF. Knobs Switches >41 Options W41 ‘Window Mode 1=Enabled’, this switch when set to ON forces the control to treat the digital input ‘Window Pushbutton PIR’ (I24) as a window contact. W42 ‘0=Pushbutton 1=PIR ‘, this switch is only used when switch ‘Window Mode 1=Enabled’ (W41) is set to OFF. Then the switch when set to ON treats the digital input ‘Window Pushbutton PIR’ (I24) as a passive infrared detector and when set to OFF treats the input as a pushbutton. The default state is OFF. W45 ‘Fan Off at Setpoint 1=Enabled’, this switch when set to ON will disable the fan when the unit is at setpoint and there is no heating or cooling demand. The default state is OFF. Energy

Page 4: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20 May 2011 4

K51 ‘ECO Mode Deadband Increase’, this knob defines the value that will be added to the existing deadbands when switch ‘Operating Mode 0=Comfort 1=ECO’ (W51) is set to ON. The default value is 4°C or 7°F. K52 ‘Power Conversion Factor’, this knob defines the scaling factor that will be multiplied with the heat meter module output to produce kW. 1kW = 0.948608 Btu/s. The default value is 1 when using kW and 0.948608 when using Btu/s. W51 ‘Operating Mode 0=Comfort 1=ECO’, this switch when set to ON enables the control to operate in eco mode and increase the deadband by the value on knob ‘ECO Mode Deadband Increase’ (K51). The default state is OFF. W52 ‘Energy Meter 1=Reset’, this switch when set to ON will reset the energy meter. Once set the control automatically resets the switch to OFF. The default state is OFF. Window PushbuttonPIR Operation The external digital Input ‘Window Pushbutton PIR’ can be used as either a window contact, PIR or Override Pushbutton and its type configured by Switches ‘0=Pushbutton 1=PIR’ and ‘Window Mode 1=Enabled’’. In window mode (Switch ‘Window Mode 1=Enabled’ set to ON) the Input ‘Window Pushbutton PIR’ is configured to be a window contact. When the window contact is open the control will override the unit into Unoccupied. In pushbutton mode (Switch ‘0=Pushbutton 1=PIR’ set to OFF) the Input ‘Window Pushbutton PIR’ forces the unit into Bypass from any state for the time set ON Knob ‘Pushbutton PIR Timeout’. In PIR mode (Switch ‘0=Pushbutton 1=PIR’ set to ON) the Input ‘Window Pushbutton PIR’ will override the unit from Occupied or Standby into Bypass for at least the time set ON Knob ‘Pushbutton PIR Timeout’. Within the unit, the Bypass condition is treated the same as Occupied so that although Sensor ‘Occupancy’ shows separate Occupied and Bypass states, if Bypass is set then Inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will both be set to ON. The Switch ‘Unit Bypass Request 1=Active’ can be used to stop or start the bypass condition. When Switch ‘Pushbutton TETS KO 1=Fitted’ is set to ON the external Sensor ‘Local Setpoint Adjust’ out of limits alarm is used to as the input for PIR or pushbutton override. Technical Description A single external digital Input ‘Window Pushbutton PIR’ is used as a window contact, PIR or Override Pushbutton to create a ‘PB PIR override active’ and ‘Unit interrupt’ digital signals. When used as a PIR or Pushbutton the input is only processed by the strategy at the rate of the counter module reschedule time. This is to ensure that only one press of the button is reacted to by the strategy. The strategy also supports the use of a TE/TS/KO for the override pushbutton using external Sensor ‘Local Setpoint Adjust’ and Switch ‘Pushbutton TETS KO 1=Fitted’. Commissioning Details 1. Configure strategy for the type of Input connected to Input ‘Window Pushbutton PIR’ using Switches ‘Window Mode 1=Enabled’ and ‘0=Pushbutton 1=PIR’. 2. If override is provided by TB/TS/KO set Switch ‘Pushbutton TETS KO 1=Fitted’ to 1. 3. Set the time of Knob ‘Pushbutton PIR Timeout’ for the length of the bypass period required. Tip. Input ‘Window Pushbutton PIR’ can be configured as a status monitoring input e.g. filter dirty by changing the E parameter on function module ‘Input active’ to 100 and setting Switch ‘Window Mode 1=Enabled’ to 0. Remember to change the label on the input to indicate its function. Occupancy State The unit operates in either Occupied, Unoccupied, Bypass, and Standby modes as determined by the ‘Remote Occupancy’ setting. Occupied: The unit is on for normal operation and controls to a user defined setpoint. Unoccupied: The unit is off, no fan, heating or cooling. The PIR has no effect although the override pushbutton will override the unit into bypass. Bypass: The unit has been put into occupation by the override pushbutton or the PIR (occupancy sensor). Standby: The unit is activated to reduce its energy consumption. In this mode either the override pushbutton or the PIR will put the unit back into occupied. Within the unit the Bypass condition is treated the same as Occupied but both inputs ‘Unit In Bypass’ and ‘Unit Occupied’ will be set to ON. When Switch ‘Remote Shutdown 1=Shutdown’ is set to ON it will override the unit into unoccupied. The same behaviour occurs if the unit is in window mode (Switch ‘Window Mode 1=Enabled’ set to ON) and the window contact on Input ‘Window Pushbutton PIR’ is not closed. Technical Description A single external digital Input ‘Window Pushbutton PIR’ is used as either a window contact, PIR or Override Pushbutton. The required occupancy states are decoded to digital signals. 0 = Occupied, 1 = Unoccupied, 2 = Bypass, 3 = Standby. The unit can also be put in to occupancy using the service pin. Discharge and Space Temp Technical Description With external sensor ‘Local Discharge Air Temp’ fitted the sensor value is gated through to internal sensors ‘Discharge Air Temperature’. The internal sensor 'Space Temperature' will use the value of either the external sensor 'Room Display Space Temp', when a Room Display module is fitted, or the value from external sensor ‘Local Space Temperature’, if fitted. If the external

Page 5: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 5

sensor has a ‘Read’ or ‘Out of limit’ alarm the value of input F on the respective gate module will be displayed on the internal sensor. Setting switch ‘Temperature Select 1=Remote’ to 1 forces the internal sensor ‘Space Temperature’ to use the value on input F of the gate module ‘Actual space temperature’. Heating Cooling Setpoints The heating and cooling setpoints can be configured to be separately adjusted or calculated. The selected setpoints have half the current deadband applied as defined by the occupation state. The value of the deadband is increased when not in occupation. The setpoint can also have an offset (trim) adjustment made locally, that will increase or decrease the required setpoint. Eco Features Local offset adjustment is valid for an adjustable time after which it is ignored until a change of the offset value is detected. The size of the deadband is increased when the unit is in ECO mode. Technical Description The setpoint is calculated from Knob ‘Remote Setpoint’ unless Switch ‘HeatCool Setpoint 1=Separate’ is set to 1 when Function ‘Selected heat setpoint’ and Function ‘Selected cool setpoint’ use Knobs ‘Heating Setpoint’ and ‘Cooling Setpoint’ respectively for they values. The ‘Heat setpoint’ is calculated by subtracting half the deadband, selected by the mode of occupation, from the value on Function ‘Selected heat setpoint’ and adding any value on Function ‘Setpoint offset’. The ‘Cool setpoint’ is calculated by adding half the deadband, selected by the mode of occupation, to the value on Function ‘Selected cool setpoint’ and adding any value on Function ‘Setpoint offset’. The ‘Heat setpoint’ and ‘Cool setpoint’ are each halved and combined to provide the ‘Setpoint’. The normal operation of ‘Setpoint offset’ with the external Sensor ‘Local Setpoint Adjust’ fitted is for the sensor value to be gated through Function ‘Selected setpoint offset’ and the value of Knob ‘Offset Range’ to be gated through Function ‘Selected offset range’. If the sensor has a ‘Read’ or ‘Out of limit’ alarm or Switch ‘SP Offset Select 1=Remote’ is set to 1 the strategy gates through the value of Knob ‘Remote Setpoint Offset’ on Function ‘Selected setpoint offset’ and a value of 1 through Function ‘Selected offset range’. If a Room Display module is fitted the strategy will automatically use the value on Knob 'Room Display Setpoint' to calculate any change in setpoint and feed this through as the offset value. Any change in the offset value is detected by the strategy and will start Logic timer ‘Adjustment active’. The offset value on Function ‘Selected setpoint offset’ is gated through Function ‘Active setpoint offset’ it is then scaled using the value on Function ‘Selected offset range’. Function ‘Setpoint offset’ value is added to the ‘Minimum setpoint’ and ‘Maximum setpoint’ to provide the ‘Heat setpoint’ and ‘Cool setpoint’ respectively and is set to 0 after the time set on Knob ‘Setpoint Adjust Timeout’ has expired. Heating Cooling Demands Heating and cooling demands are calculated by comparing the space temperature with the relevant setpoint. If the space temperature is below the heating setpoint a heating demand is created and if the space temperature is above the cooling setpoint a cooling demand is generated, the greater the different the larger the demand. To prevent hunting of the heating and cooling demands a deadband is employed to ensure a change equal to half the deadband is detected before a demand is generated or removed. When the heating or cooling demand reaches 100% the speed of the fan is increased. When a frost condition exists and the unit state is unoccupied the heating is enabled. Technical Description Both heating and cooling sides are controlled by different control loops. Heating and cooling loops are enabled whenever ‘Unit interrupt’ and 'Fan control off selected' are set to 0. The heating loop compares the "Actual space temperature" with the "Heating setpoint". The proportional + integral (P+I) loop will modulate the heating output to maintain a constant space temperature. As the temperature decreases below the heating setpoint the heating output will modulate open. The heating output will be modulated closed as the temperature increases above the heating setpoint. The loop output is limited to the range 0 to 100%. The cooling loop compares the "Actual space temperature" with the "Cooling setpoint". The proportional + integral (P+I) loop will modulate the cooling output to maintain a constant space temperature. As the temperature increases above the cooling setpoint the cooling output will be modulated open. The cooling output will be modulated closed as the temperature decreases below the cooling setpoint. The loop output is limited to the range 0 to 100%.

The integral time constant is the time for which the loop output will have added to it an amount equal to product of the error and the gain (i.e. equal to the proportional part) under conditions of constant error. If the error stays the same for the integral time constant, the loop output will double and will be 2G(E). The loops have the following default settings: heat loop gain = 20, cool loop gain = -20, both loop integral time constants = 10 minutes. These settings can be changed by text comms.

Page 6: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20 May 2011 6

The output from the loops (ignoring the integral action) is illustrated by the chart below:

The heating loop will not operate until the ‘Actual space temperature’ drops below the ‘Heating setpoint’ by half the deadband e.g. Setpoint 20°C (70°F) deadband 1° = 20-0.5 = 19.5°C (70-0.5 = 69.5°F) during occupation. Similarly for cooling it must rise above the ‘Cooling setpoint’ by half the deadband. The loop gains are set to ±20 by default which gives proportional bands of 5°C (°F) i.e. 100/20. When set to defaults, during occupation, this will give 100% heat and maximum fan speed at 12.5°C (64.5°F), and 100% cool and maximum fan speed at 25.5°C (75.5°F) ignoring the effect of the integral term. The loop outputs are added together and then split into separate heating and cooling outputs to prevent simultaneous heating and cooling. The separate demands are rescaled so the demand 0 to 50% drives the relevant valve output between 0 and 100% and the demand 50 to 100% increases the fan speed. When the heating or cooling demand is greater than 4.5% a respective ‘Heating required’ or ‘Cooling required’ signal will be set to 1. The ‘Heating required’ or ‘Cooling required’ signals are reset to 0 when the respective demand falls below 0.5%. The heating loop is overridden to 98% if the "Frost Condition 1=Frost" is set to 1 and "Unit - unoccupied" is set to 1. This will bring on the heating. Heating Cooling Valves The heating demand drives the heating valve. A demand of 100% opens the valve fully and a demand of 0% closes the valve. The cooling demand drives the cooling valve. A demand of 100% opens the valve fully and a demand of 0% closes the valve. Both the heating and cooling valves are fully opened when Switch ‘Water Balance 1=Enabled’ is ON. Technical Description The heating valve can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting switch ‘Heating Override 1=Enabled’ to 1 and adjusting Knob ‘Heating Override Value’ to the required value between 100 and 0. The cooling valve can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting switch ‘Cooling Override 1=Enabled’ to 1 and adjusting Knob ‘Cooling Override Value’ to the required value between 100 and 0. Overrides are ignored and the valves are fully opened when Switch ‘Water Balance 1=Enabled’ is 1. Commissioning Details 1. The heating valve drive time should be set to match the fitted actuator. 2. The cooling valve drive time should be set to match the fitted actuator. Fan Control - Variable Speed The fan is ON when the occupation state is occupied; bypass or standby and is OFF when unoccupied. The required speed of the fan is displayed on the sensor ‘Selected Fan Speed’ where 0 = OFF, 1 = Low, 2 = Medium, 3 = High and 4 = Auto. Low speed is the value set on knob 'Minimum Fan Speed Setpoint' and High speed is the values set on knob 'Maximum Fan Speed Setpoint'. Medium speed is the mid value between these two setpoints. If the ‘Selected Fan Speed’ is Auto, the fan will normally run at low speed, but as the fan demand increases, as a result of an increase in the heating or cooling demand, the fan speed will be increased to meet the demand, similarly the fan speed will be reduced as demand is met. The actual fan speed is displayed on the sensor ‘Actual EC Fan Speed’ and is a factor of 10 smaller than the demand i.e. Low = 'Minimum Fan Speed Setpoint' = 37 will display as 3.7. The fan has an anti cycling timer to protect it from excessive restarts. Eco Features The fan can be set to switch OFF whenever the unit is at setpoint i.e. no heating or cooling demand by setting Switch ‘Fan Off at Setpoint 1=Enabled’ to ON. The fan will restart when a heating or cooling demand exists. This is only applicable when the sensor ‘Selected Fan Speed’ is set to Auto (a value of 4). Technical Description

Page 7: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 7

The fan is enabled when the occupation state is occupied, bypass or standby and the unit interrupt signal is 0. The driver 'Occupation Relay' is enabled during occupation, time delayed based on the controller address, and is intended to be used to enable the fan controller. Automatic control is achieved by rescaling the fan demand set between the ‘Minimum Fan Speed Setpoint’ to the ‘Maximum Fan Speed Setpoint’. When the required to switch off the ‘Minimum Fan Speed Setpoint’ value is replaced with 0. The fan control can only be overridden when Logic ‘Unit - unoccupied’ is 0 by either Knob ‘Remote Fan Speed’ or the WMB Room Display module. The strategy selects the correct control depending on which items are present using the WMB Room Display module ‘I/O2 Failed status’ bit. The Knob ‘Remote Fan Speed’ is used when its value is less than 4 or when Switch ‘Fan Speed Select 1=Remote’ is set to 1. When used the knob has precedence over the external WMB Room Display module. The WMB Room Display module if fitted uses Knob ‘Room Display Fan Speed’ to display and adjust the speed. The fan control has an anti cycling timer that delays the time to restart after the fan stops thus preventing unwanted cycling of the fan. When electric heaters are included in the control the fan will run when Logic ‘Electric heat run on required’ is 1. The fan control can be overridden, providing Switch 'Overrides 0=Disabled 1=Enabled' is set to 1, by setting Switch ‘Fan Override 1=Enabled’ to 1 and adjusting Knob ‘Fan Speed Override Value EC’ to the required value. The anti cycle timer still operates under these circumstances. Commissioning Details 1. Set the ‘Minimum Fan Speed Setpoint’ 2. Set the ‘Maximum Fan Speed Setpoint’ 3. Confirm that Comparator 'Fan enabled' parameter E value is correctly set to indicate that the fan is enabled. 4. The Timer ‘Anti cycle active’ parameter F requires setting to ensure the minimum off time required for anti cycling the fan. 300 seconds = 5 minutes = 12 starts per hour. 5. The switch 'Fan Speed Select 1=Remote’ requires setting to 1 if the WMB Room Display is to be excluded from the control of the fan. Service Pin - Water balance Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to start and stop water balancing where all the valve outputs are set to 100% or 0% i.e. fully open or fully closed. The function is only available if Switch ‘Service Button Mode 1=Enabled’ is set to ON. For a full description of service pin mode refer to the Trend publication TE201089 IQeco Configuration Manual Issue 2 or greater. The service button press sequence for the required behaviour is as follows; Required Action Phase 1 Phase 2 Phase 3 Water Balance On for the Lan No Press No Press No Press Water Balance Off for the Lan Press No Press No Press Water Balance On for the Unit No Press Press No Press Water Balance Off for the Unit Press Press No Press Technical Description The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit. Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED (green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1. Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a ON condition is required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2. Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase 1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3. Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of the Exit stage. Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode will be automatically exited and the LED and service button return to their normal operation. Service Button - Occupancy

Page 8: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20 May 2011 8

Pressing the service button in a predefined sequence, when in service button mode, can initiate behaviour in the strategy to change the occupancy state to occupied or unoccupied. The function is only available if Switch ‘Service Button Mode 1=Enabled’ is set to ON. For a full description of service pin mode refer to the Trend publication TE201089 IQeco Configuration Manual Issue 2 or greater. The service button press sequence for the required behaviour is as follows; Required Action Phase 1 Phase 2 Phase 3 Occupied for the Lan No Press No Press Press Unoccupied for the Lan Press No Press Press Occupied for the Unit No Press Press Press Unoccupied for the Unit Press Press Press Technical Description The service button can be used to initiate behaviour designed in the strategy; to achieve this behaviour the controller must be put into service button mode. Service button mode has 5 stages Entry, Phase 1, Phase 2, Phase 3 and Exit. Entry - Press and hold the service button for 2 to 5 seconds. When the service button is released a rapidly flashing comms LED (green) for one second indicates entry into ‘service button mode’. When the flashing stops this indicates the start of Phase 1. Phase 1 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that an ON condition is required. If it is pressed then an OFF condition is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 2. Phase 2 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that the selection in Phase 1 should be applied to the LAN and if it is pressed then it will be applied to the UNIT. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of phase 3. Phase 3 - This stage lasts 3 seconds and during this time if the service button is not pressed it will mean that a Water Balance selection is required and if it is pressed then it will indicate that an Occupancy selection is required. At the end of this stage the comms LED (green) will flash once to confirm no press and twice to confirm a press. The end of the flashing indicates the start of the Exit stage. Exit - This stage lasts for 3 seconds and starts with a rapidly flashing comms LED (green). During this stage if the service button is not pressed then the service button mode will expire without any further action. The service button must be pressed to confirm the selections made in phases 1, 2 and 3. Once pressed the LED will go out for the remainder of the stage and the virtual input channel selected by the choices made during phases 1, 2 and 3 will go ON for one pass of the sequence table. The virtual input channel is allocated to a Digital Input module to make it available to be used by the strategy. At the end of this stage the service button mode will be automatically exited and the LED and service button return to their normal operation. Virtual Energy Meter An estimation of the unit’s energy consumption is calculated by the controller and can be viewed on Sensor ‘Unit Energy Meter’. The consumption is measured over a 30 minute period starting from 0 and increasing until the end of the period when the value is stored in the controller. The controller stores the last 200 values and these can be viewed from suitable displays or supervisory software e.g. IQView and 963. The calculation totals the estimated energy used by the heat exchangers and the energy consumed by the fan and by the loads switched by the relay output. The accuracy of the calculation depends on the values configured in the controller however the default values supplied provide for a like for like comparison between similar units. Technical Description The estimated calculations use the heat meter module for the power being provided by the heat exchangers. This power is then added to the power of the fan and using an integrator module the power consumed is calculated over the period of 15, 30 (default) or 60 minutes depending on the configuration of the strategy. Heat exchanger power estimation formula. Heating Power = (Heating medium temperature - Space temperature) * Coil duty * Valve position / 100 Power kW (D) = (Water Supply Temp DegC (E) - Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Water Supply Temp DegF (F) - Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Cooling Power = (Space temperature - Cooling medium temperature) * Coil duty * Valve position / 100 Power kW (D) = (Space Temp (E) - Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Space Temp DegF (E) - Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) To improve the accuracy of the estimation the following parameters should be configured with the correct value for the unit: Function module Parameter Units ‘Heating coil duty max speed’ F kW/degK (Btu/sDegF) ‘Cooling coil duty max speed’ F kW/degK (Btu/sDegF) ‘Fan duty max speed’ F kW ‘Occupation relay duty’ F kW The output 'Occupation Relay' is intended to be the relay that switches the power to the EC fan controller and the value of ‘Occupation relay duty’ is the duty when the fan controller is energised. The values calculated are linear and therefore are only an estimate.

Page 9: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 9

The period the integrator uses for the calculation can be changed by amending the arguments in parameter K on Logic module ‘Meter reset’: F = 15 minutes, G = 30 minutes and H = 60 minutes. If the Logic is changed then the period parameter P on plot module ‘Unit Energy Meter’ should also be changed to match: 1 = 15 minutes, 7 = 30 minutes and 0 = 60 minutes. Useful conversions: 1 kW = 0.948608 Btu/s 1 hp = 0.7074163 Btu/s 1 Btu/h/3600 = 1 Btu/s Commissioning Details 1. Set the values of the duty for the coils. 2. Set the values of the duty for the fan. 3. Set the value of the duty for the occupation relay. 4. Confirm the water flow temperatures are received from the main plant. IC Comms and Alarm Group Technical Description The IC Comms are configured for master slave operation directed to standard knobs and switches one or all of the following: Space Temperature, Setpoint, Occupancy and Fan Speed. The IC Comms modules use attribute 3 and to prohibit unwanted communications are, by default, disabled. One alarm group route and destination modules are configured to send Trend text alarms to address 1 on the local lan, this would normally be the IQ3/BINC VCNC port 10001. To prohibit unwanted alarms the route, by default, is disabled. Analogue node 99 is provided so a value can be placed in it to indicate the state of the unit during commissioning and witnessing. Digital Input 'Strategy Override 1=Active' when 1 indicates that one of the outputs is being overridden by the strategy and not in normal control. Commissioning Details 1. For master slave configuration configure attribute 3 and enabled IC Comms if master unit. 2. If alarms are required configure alarm destination address and enable alarm route.

Page 10: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

Please send any comments about this or any other Trend technical publication to [email protected] © 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems Limited Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend Control Systems USA 6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trendcontrols.com

Page 11: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

Trend Control Systems LtdAlbery Hoiuse,

Springfield Road

Horsham, West Sussex.

RH12 2PQ

UK

Telephone: +44 1403 211888

Fax: +44 1403 240271

Email: [email protected]

0 1 Original Issue All 18 May 2011 DRR Review

Issue Revision Project Change Note / Comments Pages Affected Date Approved Approved ByAddress ModuleIdentifier

Attribute F

Attribute G

Alarm Lan 0

Alarm Address 0

Controller Version

Serial Number

Strategy Name FCU EC Fan WR4

Product Order Code

SiteGUID:

Project:

Client:

Details:

Drawn By:

Engineer:

Controller Type:

Project Number:

Outstation: Lan:

Date:

Page:

{32C49D2B-FF61-4FE1-8E0C-2EF6803771B5}

IQeco Standard Strategies

New Product Development

Fan Coil Unit with EC Fan Waterside 4 Pipes with 2 raise/lower (floating point) Valves.

Brian Kirkdale

Brian Kirkdale

IQeco 31

May2011_v2

015 019

19/05/2011

01 of 17

Notes

The IQeco standard strategy controls a fan coil unit’s heat/cool outputs, and electronically commutated fan,

The control responses to a thermistor temperature sensor with a local setpoint knob and a local window contact input and a pushbutton, or Passive Infra Red movement detector input.

The WR4 strategy is for waterside 4 pipe units controlling 2 raise/lower (floating point) valve actuators.

The strategy supports the fitting of a WMB Room display module without further configuration.

Page 12: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

FCU EC Fan WR4

Strategy pages

Title Page 1Real Inputs 2Knobs Switches <21 3Knobs Switches 21 - 40 4Knobs Switches >41 5Window PushbuttonPIR Operation 6Occupancy State 7Discharge and Space Temp 8Heating Cooling Setpoints 9Heating Cooling Demands 10Heating Cooling Valves 11Fan Control - Variable Speed 12Fan Control - Variable page 2 13Service Pin - Water balance 14Service Button - Occupancy 15Virtual Energy Meter 16IC Comms and Alarm Group 17

Page 13: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-02 Real Inputs

0 - 01

May2011_v2

015

19/05/2011

02 of 17Trend Control Systems Ltd

Default Operation

The behaviour of the strategy before any configuration of knobs as switches is as follows:

The default occupancy state of the strategy is unoccupied.

In most cases when the controller is powered on the fan outputs will not operate as the space temperature used for control will be within the deadband for the unoccupied state.

There are 3 ways to take the strategy out of the unoccupied state:

1. Set Knob “Remote Occupancy” (K11) to 0.2. Using a pushbutton connected to IN4. Press the pushbutton once; this should place the unit into bypass. The bypass state is active until another press of the pushbutton or timouts after 30 minutes.3. Use the service button to put the unit into occupied. Details are in “Service Button - Occupancy” section of the strategy datasheet.

The fan output may not be operating for the following reasons:a. The fan anti cycling strategy is active. Once switched off the fan will not start for 5 minutes.b. Changes to the knobs and switches from the defaults are overriding the fan control.c. The occupancy state is unoccupied.

1Local Discharge Air Temp

S21

EXTERNAL

Vi0c1

DegC Units101 Type0 Offset50 High Alarm Limit-5 Low Alarm Limit600 High Alarm Delay600 Low Alarm Delay0 Out.Limits Delay0 Read Alarm DelayDisabled Read AlarmDisabled Out. Limits AlarmDisabled Low AlarmDisabled High Alarm

2Local Space Temperature

S22

EXTERNAL

Vi0c2

DegC Units101 Type0 Offset50 High Alarm Limit-5 Low Alarm Limit600 High Alarm Delay600 Low Alarm Delay0 Out.Limits Delay0 Read Alarm DelayDisabled Read AlarmDisabled Out. Limits AlarmDisabled Low AlarmDisabled High Alarm

3Local Setpoint Adjust

S23

EXTERNAL

Vi0c3

DegC Units102 Type0 Offset0.6 High Alarm Limit-0.6 Low Alarm Limit600 High Alarm Delay600 Low Alarm Delay0 Out.Limits Delay0 Read Alarm DelayDisabled Read AlarmDisabled Out. Limits AlarmDisabled Low AlarmDisabled High Alarm

Window Pushbutton PIR

I24

EXTERNAL

Sc4

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

10One shot switch reset

F1

COMPARATORD = 1 when F > E

E

FD

500

0

S21V

Local Discharge Air TempTo Page(s) 8,

S22V

Local Space TemperatureTo Page(s) 8,

S23V

Local Setpoint AdjustTo Page(s) 9,

I24S

Window Pushbutton PIRTo Page(s) 6,7,

F1D

One shot switch resetTo Page(s) 16,

Page 14: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-03 Knobs Switches <21

0 - 01

May2011_v2

015

19/05/2011

03 of 17Trend Control Systems Ltd

0 = Off1 = Low2 = Medium3 = High4 = Auto(1001-7)

Pushbutton PIR Timeout

K1KNOB

D30

min Units79 Pin Level1440 Top of Range0 Bottom of Range

Setpoint Adjust Timeout

K2KNOB

D60

min Units79 Pin Level1440 Top of Range0 Bottom of Range

Offset Range

K3KNOB

D2

DegC Units79 Pin Level10 Top of Range1 Bottom of Range

OCC Deadband

K4KNOB

D1

DegC Units60 Pin Level2 Top of Range0.5 Bottom of Range

NOCC Deadband

K5KNOB

D12

DegC Units60 Pin Level20 Top of Range8 Bottom of Range

Standby Deadband

K6KNOB

D2

DegC Units60 Pin Level3 Top of Range1 Bottom of Range

Heating Setpoint

K7KNOB

D19.5

DegC Units79 Pin Level24 Top of Range8 Bottom of Range

Cooling Setpoint

K8KNOB

D20.5

DegC Units79 Pin Level34 Top of Range18 Bottom of Range

Remote Space Temperature

K12KNOB

D20

DegC Units79 Pin Level30 Top of Range0 Bottom of Range

Remote Setpoint Offset

K13KNOB

D0

DegC Units79 Pin Level10 Top of Range-10 Bottom of Range

Remote Setpoint

K14KNOB

D20

DegC Units79 Pin Level24 Top of Range18 Bottom of Range

Heating Flow Temperature

K17KNOB

D80

DegC Units79 Pin Level0 Top of Range0 Bottom of Range

Cooling Flow Temperature

K18KNOB

D6

DegC Units79 Pin Level0 Top of Range0 Bottom of Range

Remote Shutdown 1=Shutdown

W11SWITCH

D0

79 Pin Level

Frost Condition 1=Frost

W12SWITCH

D0

79 Pin Level

Remote Fan Speed

K15KNOB

D4

enum Units79 Pin Level4 Top of Range0 Bottom of Range

K1D

Pushbutton PIR TimeoutTo Page(s) 6,

K2D

Setpoint Adjust TimeoutTo Page(s) 9,

K3D

Offset RangeTo Page(s) 9,

K5D

NOCC DeadbandTo Page(s) 9,

K6D

Standby DeadbandTo Page(s) 9,

K7D

Heating SetpointTo Page(s) 9,

K8D

Cooling SetpointTo Page(s) 9,

K12D

Remote Space TemperatureTo Page(s) 8,

K13D

Remote Setpoint OffsetTo Page(s) 9,

K14D

Remote SetpointTo Page(s) 9,

K17D

Heating Flow TemperatureTo Page(s) 16,

K18D

Cooling Flow TemperatureTo Page(s) 16,

W11D

Remote Shutdown 1=ShutdownTo Page(s) 7,

W12D

Frost Condition 1=FrostTo Page(s) 10,

K4D

OCC DeadbandTo Page(s) 9,

K15D

Remote Fan SpeedTo Page(s) 12,

W1D = 0Unit Bypass Request 1=Active

From Page 6W1D

Unit Bypass Request 1=ActiveTo Page(s) 3,

K11D = 1Remote Occupancy

From Page 7K11D

Remote OccupancyTo Page(s) 3,7,15,

Page 15: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-04 Knobs Switches 21 - 40

0 - 01

May2011_v2

015

19/05/2011

04 of 17Trend Control Systems Ltd

Heating Override Value

K21KNOB

D0

% Units60 Pin Level100 Top of Range0 Bottom of Range

Cooling Override Value

K22KNOB

D0

% Units60 Pin Level100 Top of Range0 Bottom of Range

Fan Anti Cycle Time

K31KNOB

D5

min Units79 Pin Level60 Top of Range0 Bottom of Range

Heating Override 1=Enabled

W21SWITCH

D0

60 Pin Level

Cooling Override 1=Enabled

W22SWITCH

D0

60 Pin Level

Temperature Select 1=Remote

W34SWITCH

D0

79 Pin Level

SP Offset Select 1=Remote

W35SWITCH

D0

79 Pin Level

HeatCool Setpoint 1=Separate

W36SWITCH

D0

79 Pin Level

Pushbutton TETS KO 1=Fitted

W37SWITCH

D0

79 Pin LevelFan Speed Override Value EC

K28KNOB

D50

% Units60 Pin Level100 Top of Range0 Bottom of Range

Minimum Fan Speed Setpoint

K39KNOB

D37

% Units79 Pin Level50 Top of Range0 Bottom of Range

Maximum Fan Speed Setpoint

K40KNOB

D70

% Units79 Pin Level100 Top of Range50 Bottom of Range

Fan Override 1=Enabled

W27SWITCH

D0

60 Pin Level

Service Button Mode 1=Enabled

W31SWITCH

D1

79 Pin Level

Fan Speed Select 1=Remote

W39SWITCH

D0

79 Pin Level

Overrides 0=Disabled 1=Enabled

W32SWITCH

D1

79 Pin Level

K21D

Heating Override ValueTo Page(s) 11,

K22D

Cooling Override ValueTo Page(s) 11,

K31D

Fan Anti Cycle TimeTo Page(s)

W21D

Heating Override 1=EnabledTo Page(s) 11,

W22D

Cooling Override 1=EnabledTo Page(s) 11,

W31D

Service Button Mode 1=EnabledTo Page(s) 14,15,

W34D

Temperature Select 1=RemoteTo Page(s) 8,

W35D

SP Offset Select 1=RemoteTo Page(s) 9,

W36D

HeatCool Setpoint 1=SeparateTo Page(s) 9,

W37D

Pushbutton TETS KO 1=FittedTo Page(s) 6,

K28D

Fan Speed Override Value ECTo Page(s) 13,

K39D

Minimum Fan Speed SetpointTo Page(s) 13,

K40D

Maximum Fan Speed SetpointTo Page(s) 13,

W27D

Fan Override 1=EnabledTo Page(s) 13,

W39D

Fan Speed Select 1=RemoteTo Page(s) 12,

W32D

Overrides 0=Disabled 1=EnabledTo Page(s) 11,13,

W28D

Water Balance 1=EnabledTo Page(s) 4,

W28D = 0Water Balance 1=Enabled

From Page 14

Page 16: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-05 Knobs Switches >41

0 - 01

May2011_v2

015

19/05/2011

05 of 17Trend Control Systems Ltd

ECO Mode Deadband Increase

K51KNOB

D4

DegC Units79 Pin Level6 Top of Range2 Bottom of Range

Operating Mode 0=Comfort 1=EC

W51SWITCH

D0

60 Pin Level

Window Mode 1=Enabled

W41SWITCH

D0

79 Pin Level

0=Pushbutton 1=PIR

W42SWITCH

D0

79 Pin Level

Fan Off at Setpoint 1=Enabled

W45SWITCH

D0

79 Pin Level

Power Conversion Factor

K52KNOB

D1

Units0 Pin Level0 Top of Range0 Bottom of Range

K51D

ECO Mode Deadband IncreaseTo Page(s) 9,

W51D

Operating Mode 0=Comfort 1=ECOTo Page(s) 9,

W41D

Window Mode 1=EnabledTo Page(s) 6,7,

W42D

0=Pushbutton 1=PIRTo Page(s) 6,

W45D

Fan Off at Setpoint 1=EnabledTo Page(s) 13,

K52D

Power Conversion FactorTo Page(s) 16,

W52D

Energy Meter 1=ResetTo Page(s) 5,

W52D = 0Energy Meter 1=Reset

From Page 16

Page 17: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-06 Window PushbuttonPIR Operation

0 - 01

May2011_v2

015

19/05/2011

06 of 17Trend Control Systems Ltd

Window Mode:Switch "Window Mode 1=Enabled" set to 1 Input "Window Pushbutton PIR" when open circuitwill force control to change to unoccupied.(1001-13)

PIR mode:Switch "0=Pushbutton 1=PIR" set to 1Control will change from standby to bypass upon movement being detected by the PIR for the amount of time determined by knob "Pushbutton PIR Timeout".(1001-11)

Pushbutton Mode:Switch "0=Pushbutton 1=PIR" set to 0Control will change from unoccupied to bypass for the amount of time determinedby knob "Pushbutton PIR Timeout"when the pushbutton is pressed. If the button is pressed whilst in bypassthe unit will be returned to unoccupied.(1001-12)

11Window Pushbutton PIR count

G1

COUNTER

S

A

R

M

I24S

F2D 9 9 9

1 Reschedule Time1 Scale Factor

12Input active

F2

COMPARATORD = 1 when F > E

E

FD

0.5

G1M

13KO Override Request

G2

COMB

E

F

G

H

D

S23o1S

0

W37D

G3D

J orK orL orM

E G h J Comb.K Comb.L Comb.M Comb.

14Pulse generator reset

G3

COMB

E

F

G

H

D

S23o1S

I24S

0

W41D

J orK orL orM

E J Comb.F H K Comb.

L Comb.M Comb.

15PIR request

G4

COMB

E

F

G

H

D

G20D

W42D

W41D

F2D

J orK orL orM

e F g H J Comb.K Comb.L Comb.M Comb.

16Pushbutton request

G5

COMB

E

F

G

H

D

F2D

W41D

W42D

G2D

J orK orL orM

E f g J Comb.H K Comb.

L Comb.M Comb.

18Pushbutton override active

G6

COMB

E

F

G

H

D

W1D

G8D

G5D

G7D

J orK orL orM

E f g h J Comb.e G K Comb.

L Comb.M Comb.

20PIR override active

G8

TIMER

S DG4D

0 On Delay0 Minimum OnF3D Off Delay

22Unit Bypass Request 1=Active

W1SWITCH

DG9D

60 Pin Level

21PB PIR override active

G9

COMB

E

F

G

H

D

W1D

G8D

G4D

G6D

J orK orL orM

H J Comb.F G K Comb.E F L Comb.

M Comb.

17Minutes to seconds

F3

MULTIPLYD=G*E*F

E

G

F

D

60

K1D

1

19Pushbutton override reset

G7

TIMER

S DG6D

F3D On Delay0 Minimum On0 Off Delay

W37D = 0Pushbutton TETS KO 1=Fitted

From Page 4

I24SWindow Pushbutton PIR

From Page 2

S23o1SOut - Local Setpoint Adjust

From Page 2

W41D = 0Window Mode 1=Enabled

From Page 5

W42D = 00=Pushbutton 1=PIR

From Page 5

G20DUnit - unoccupied

From Page 7

G9D

PB PIR override activeTo Page(s) 7,

K1D = 30Pushbutton PIR Timeout

From Page 3

I24SWindow Pushbutton PIR

From Page 2

W41D = 0Window Mode 1=Enabled

From Page 5

W42D = 00=Pushbutton 1=PIR

From Page 5

G8D

PIR override activeTo Page(s) 7,

W41D = 0Window Mode 1=Enabled

From Page 5I24N

Sts - Window Pushbutton PIRFrom Page 2

Page 18: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-07 Occupancy State

0 - 01

May2011_v2

015

19/05/2011

07 of 17Trend Control Systems Ltd

Unit interrupt:When in window mode and input"Window Pushbutton PIR" is 0 or theunit has been sent a shutdown commandcontrol is forced to unoccupied.(1001-14)

Unit Occupied is enabledwhen the zone is occupied.(1001-2)

Unit Unoccupied mode is activatedwhen the zone is unoccupiedfor longer periods of time.In this mode PIR has no effectalthough the Pushbutton willoverride the unit into bypass.(1001-3)

Unit Bypass mode is the occupiedstate used when the Pushbutton or PIR are activated.Bypass uses the same deadbandas occupied.(1001-4)

Unit Standby is activatedto reduce the energy consumptionof the zone. In this mode either the PIR if selected or the Pushbuttonwill put the zone back into occupied.(1001-5)

0 = Occupied1 = Unoccupied2 = Bypass3 = Standby(1001-1)

Window Mode:Switch "Window Mode 1=Enabled" set to 1 Input "Window Pushbutton PIR" when open circuitwill force control to change to unoccupied.(1001-13)

0 = Occupied1 = Unoccupied2 = Bypass3 = Standby(1001-1)

27Bypass request

G17

COMB

E

F

G

H

D

0

G9D

G8D

G20D

J orK orL orM

F g J Comb.F G h K Comb.

L Comb.M Comb.

28Bypass select

F6

GATED = F when B = 1

E

F

B

D

K11D

2

G17D

29Unoccupied select

F7

GATED = F when B = 1

E

F

B

D

F6D

1

G16D

30Occupancy decoder

F8

A TO D

G DF7D

a

b

c

d

e

f

g

h

32Unit - occupied

G18

COMB

E

F

G

H

D

F8a

F8b

G19D

0

J orK orL orM

e f J Comb.G K Comb.

L Comb.M Comb.

31Unit - bypass

G19

COMB

E

F

G

H

D

F8a

F8b

0

0

J orK orL orM

e F J Comb.K Comb.L Comb.M Comb.

33Unit - unoccupied

G20

COMB

E

F

G

H

D

F8a

F8b

0

0

J orK orL orM

E f J Comb.K Comb.L Comb.M Comb.

34Unit - standby

G21

COMB

E

F

G

H

D

F8a

F8b

0

0

J orK orL orM

E F J Comb.K Comb.L Comb.M Comb.

26Unit interrupt

G16

COMB

E

F

G

H

D

W41D

I24S

W11D

0

J orK orL orM

E f J Comb.G K Comb.

L Comb.M Comb.

35Occupancy

S10

INTERNALS

VF7D

enum Units4 High Alarm Limit-1 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

Unit Occupied

G18DI1INTERNAL

S

Hours RunStarts

Unit Unoccupied

G20DI2INTERNAL

S

Hours RunStarts

Unit In Bypass

G19DI3INTERNAL

S

Hours RunStarts

Unit In Standby

G21DI4INTERNAL

S

Hours RunStarts

39Remote Occupancy

K11KNOB

DF11D

enum Units79 Pin Level3 Top of Range0 Bottom of Range

36Unit not in occ mode

F9

COMPARATORD = 1 when F > E

E

FD

0.5

K11D

37Occ nocc select

F10

GATED = F when B = 1

E

F

B

D

1

0

F9D

38Occupancy value select

F11

GATED = F when B = 1

E

F

B

D

K11D

F10D

G75D

K11D = 1Remote Occupancy

From Page 7

G18D

Unit - occupiedTo Page(s) 9,

G19D

Unit - bypassTo Page(s)

G20D

Unit - unoccupiedTo Page(s) 6,10,13,

G21D

Unit - standbyTo Page(s) 9,

F7D

Unoccupied selectTo Page(s)

G9DPB PIR override active

From Page 6

G16D

Unit interruptTo Page(s) 10,13,

I24SWindow Pushbutton PIR

From Page 2

W41D = 0Window Mode 1=Enabled

From Page 5

W11D = 0Remote Shutdown 1=Shutdown

From Page 3

G8DPIR override active

From Page 6

K11D

Remote OccupancyTo Page(s) 3,7,15,

G75DService button occ active

From Page 15

F9D

Unit not in occ modeTo Page(s) 15,

Page 19: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-08 Discharge and Space Temp

0 - 01

May2011_v2

015

19/05/2011

08 of 17Trend Control Systems Ltd

41Discharge temp 0=Fitted

G26

COMB

E

F

G

H

D

S21r1S

S21o1S

0

0

J orK orL orM

E J Comb.F K Comb.

L Comb.M Comb.

42Actual discharge temp

F16

GATED = F when B = 1

E

F

B

D

S21V

0

G26D

43Discharge Air Temperature

S1

INTERNALS

VF16D

DegC Units40 High Alarm Limit10 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

45Select temperature 1=Remote

G27

COMB

E

F

G

H

D

S31r1S

S31o1S

S22r1S

S22o1S

J orK orL orM

e F J Comb.E G K Comb.E H L Comb.

M Comb.

46Selected space temperature

F17

GATED = F when B = 1

E

F

B

D

S31V

S22V

S31r1S

49Space Temperature

S2

INTERNALS

VF19D

DegC Units40 High Alarm Limit10 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

Space Temperature

P1SYNC

SS2V

15 Min Period100 Records

47Space temperature select

F18

GATED = F when B = 1

E

F

B

D

F17D

K12D

G27D

44Room Display Space Temp

S31

EXTERNAL

Vi2c1

DegC Units112 Type0 Offset50 High Alarm Limit-5 Low Alarm Limit600 High Alarm Delay600 Low Alarm Delay0 Out.Limits Delay0 Read Alarm DelayDisabled Read AlarmDisabled Out. Limits AlarmDisabled Low AlarmDisabled High Alarm

48Actual space temperature

F19

GATED = F when B = 1

E

F

B

D

F18D

K12D

W34D

S21o1SOut - Local Discharge Air Temp

From Page 2

S21r1SRd - Local Discharge Air Temp

From Page 2

S21VLocal Discharge Air Temp

From Page 2

F16D

Actual discharge tempTo Page(s)

S22VLocal Space Temperature

From Page 2

K12D = 20Remote Space Temperature

From Page 3F19D

Actual space temperatureTo Page(s) 10,

S22r1SRd - Local Space Temperature

From Page 2

S22o1SOut - Local Space Temperature

From Page 2

W34D = 0Temperature Select 1=Remote

From Page 4

K12D = 20Remote Space Temperature

From Page 3

Page 20: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-09 Heating Cooling Setpoints

0 - 01

May2011_v2

015

19/05/2011

09 of 17Trend Control Systems Ltd

62Deadband 0=NOCC 1=Standby

F29

GATED = F when B = 1

E

F

B

D

K5D

K6D

G21D

63OCC deadband select 1=0

F30

GATED = F when B = 1

E

F

B

D

K4D

0

W36D

64Deadband 1=OCC

F31

GATED = F when B = 1

E

F

B

D

F29D

F30D

G18D

65Selected heat setpoint

F32

GATED = F when B = 1

E

F

B

D

K14D

K7D

W36D

66Selected cool setpoint

F33

GATED = F when B = 1

E

F

B

D

K14D

K8D

W36D

52Select setpoint 1=Remote

G31

COMB

E

F

G

H

D

S23r1S

S23o1S

W35D

i2F

J orK orL orM

E H J Comb.F H K Comb.G L Comb.

M Comb.

53Selected setpoint offset

F22

GATED = F when B = 1

E

F

B

D

F21D

K13D

G31D

57Value changed

G32

COMB

E

F

G

H

D

F23D

i2F

G31D

F44D

J orK orL orM

e J Comb.f g h K Comb.

L Comb.M Comb.

58Adjustment active

G33

TIMER

S DG32D

0 On Delay0 Minimum OnF25D Off Delay

54Value has not changed

F23

PROXIMITYE +/- F

E

G

F

D

F24D

F22D

0.05

55Last change value

F24

GATED = F when B = 1

E

F

B

D

F22D

F24D

F23D

56Minutes to seconds

F25

MULTIPLYD=G*E*F

E

G

F

D

1

K2D

60

59Selected offset range

F26

GATED = F when B = 1

E

F

B

D

K3D

1

G31D 60Active setpoint offset

F27

GATED = F when B = 1

E

F

B

D

0

F22D

G33D

67Calculated deadband

F34

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F43D

1

1

F31D

71Minimum setpoint

F38

GATED = F when B = 1

E

F

B

D

F35D

F36D

F37D

72Maximum setpoint

F39

GATED = F when B = 1

E

F

B

D

F36D

F35D

F37D

73Heat setpoint

F40

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F38D

1

1

F28D

74Cool setpoint

F41

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F28D

1

1

F39D

75Actual setpoint

F42

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

0.5

0.5

F40D

F41D

76Setpoint

S3

INTERNALS

VF42D

DegC Units30 High Alarm Limit-30 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

68Heat setpoint - deaband

F35

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F34D

1

-0.5

F32D

69Cool setpoint + deadband

F36

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F34D

1

0.5

F33D

70Heat cool setpoint overlap

F37

COMPARATORD = 1 when F > E

E

FD

F36D

F35D

77Eco mode selected deadband

F43

GATED = F when B = 1

E

F

B

D

0

K51D

W51D

61Setpoint offset

F28

MULTIPLYD=G*E*F

E

G

F

D

1

F26D

F27D

51Selected setpoint adjustment

F21

GATED = F when B = 1

E

F

B

D

F48D

S23V

i2F

78Room Display Setpoint

K44KNOB

DF42D

DegC Units79 Pin Level24 Top of Range18 Bottom of Range

79Room display not changed

F44

PROXIMITYE +/- F

E

G

F

D

F42D

K44D

0.05

80Setpoint no offset

F45

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

0.5

0.5

F35D

F36D

83Room display offset value

F48

GATED = F when B = 1

E

F

B

D

F47D

F48D

F44D

82Room display calculated change

F47

DIVIDED=F(G/E)

E

G

F

D

F26D

F46D

1

81Room display changed value

F46

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

1

-1

K44D

F45D

K14D = 20Remote Setpoint

From Page 3

K4D = 1OCC Deadband

From Page 3

G18DUnit - occupied

From Page 7

K5D = 12NOCC Deadband

From Page 3

K6D = 2Standby Deadband

From Page 3

G21DUnit - standbyFrom Page 7

W36D = 0HeatCool Setpoint 1=Separate

From Page 4

K8D = 20.5Cooling Setpoint

From Page 3

K7D = 19.5Heating Setpoint

From Page 3

W35D = 0SP Offset Select 1=Remote

From Page 4

S23VLocal Setpoint Adjust

From Page 2

K13D = 0Remote Setpoint Offset

From Page 3

S23o1SOut - Local Setpoint Adjust

From Page 2

S23r1SRd - Local Setpoint Adjust

From Page 2

K3D = 2Offset RangeFrom Page 3

K2D = 60Setpoint Adjust Timeout

From Page 3

F41D

Cool setpointTo Page(s) 10,

F40D

Heat setpointTo Page(s) 10,

F42D

Actual setpointTo Page(s)

F43DEco mode selected deadband

From Page 9

K51D = 4ECO Mode Deadband Increase

From Page 5

W51D = 0Operating Mode 0=Comfort 1=ECO

From Page 5

F43D

Eco mode selected deadbandTo Page(s) 9,

F28D

Setpoint offsetTo Page(s) 9,

F28DSetpoint offset

From Page 9

F48D

Room display offset valueTo Page(s) 9,

F44D

Room display not changedTo Page(s) 9,

G31DSelect setpoint 1=Remote

From Page 9

F44DRoom display not changed

From Page 9

G31D

Select setpoint 1=RemoteTo Page(s) 9,i2F

I/O2 Failed Status

i2FI/O2 Failed Status

i2FI/O2 Failed Status

F48DRoom display offset value

From Page 9

Page 21: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-10 Heating Cooling Demands

0 - 01

May2011_v2

015

19/05/2011

10 of 17Trend Control Systems Ltd

88Heat loop

L1

LOOP

A

P

O

U

L

S

D

G36D

F19D

F40D

nul

98

G37D

5 Reschedule Time20 Gain10 Integral Time

Deadband

91Heat cool demand

F51

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

1

-1

L1D

L2D

Heating Demand

P2SYNC

SS11V

15 Min Period

98Heating below setpoint

F56

HYST BANDE=Level F=Band

E

G

F

D

F19D

F40D

1

99Heating required

G39

COMB

E

F

G

H

D

F56D

0

G36D

F54D

J orK orL orM

E G J Comb.g H K Comb.

L Comb.M Comb.

100Fan heat demand

F57

RSCL TOD=100(G-E)/(F-E)

E

G

F

D

50

F51D

100

102Fan demand

F59

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F57D

1

1

F58D

F19DActual space temperature

From Page 8

F59D

Fan demandTo Page(s) 13,

F78DFan control off selected

From Page 12

90Cool loop

L2

LOOP

A

P

O

U

L

S

D

0

F19D

F41D

nul

0

G38D

5 Reschedule Time-20 Gain10 Integral Time

Deadband

92Heat demand

F52

RSCL TOD=100(G-E)/(F-E)

E

G

F

D

0

F51D

50

94Cool demand

F53

RSCL TOD=100(G-E)/(F-E)

E

G

F

D

0

F51D

-50

86Loop override required

G36

COMB

E

F

G

H

D

W12D

G20D

0

0

J orK orL orM

E F J Comb.K Comb.L Comb.M Comb.

87Heating loop enable

G37

COMB

E

F

G

H

D

G16D

0

F78D

0

J orK orL orM

e g J Comb.K Comb.L Comb.M Comb.

93Heating requested

F54

HYST BANDE=Level F=Band

E

G

F

D

3

F52D

4

95Cooling required

F55

HYST BANDE=Level F=Band

E

G

F

D

3

F53D

4

89Cooling loop enable

G38

COMB

E

F

G

H

D

G16D

0

F78D

0

J orK orL orM

e g J Comb.K Comb.L Comb.M Comb.

96Heating Demand

S11

INTERNALS

VF52D

% Units101 High Alarm Limit-1 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

97Cooling Demand

S12

INTERNALS

VF53D

% Units101 High Alarm Limit-1 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

Cooling Demand

P3SYNC

SS12V

15 Min Period

101Fan cool demand

F58

RSCL TOD=100(G-E)/(F-E)

E

G

F

D

-50

F51D

-100

F19DActual space temperature

From Page 8

F40DHeat setpointFrom Page 9

F41DCool setpointFrom Page 9

F52D

Heat demandTo Page(s) 11,

F53D

Cool demandTo Page(s) 11,

G16DUnit interruptFrom Page 7

G39D

Heating requiredTo Page(s) 13,

F55D

Cooling requiredTo Page(s) 13,

G20DUnit - unoccupied

From Page 7

W12D = 0Frost Condition 1=Frost

From Page 3

F40DHeat setpointFrom Page 9

Page 22: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-11 Heating Cooling Valves

0 - 01

May2011_v2

015

19/05/2011

11 of 17Trend Control Systems Ltd

107Heat override balance select

F62

GATED = F when B = 1

E

F

B

D

K21D

100

G65D

108Heat valve override required

G41

COMB

E

F

G

H

D

G65D

0

W21D

W32D

J orK orL orM

E J Comb.G H K Comb.

L Comb.M Comb.

110Heating Valve

D5

RAISE LOWER END

S

l

aF63D

5

6

180 fs DriveDisabled Invert

PositionDisabled Position Sync.

114Cooling Valve

D7

RAISE LOWER END

S

l

aF65D

7

8

180 fs DriveDisabled Invert

PositionDisabled Position Sync.

111Cool override balance select

F64

GATED = F when B = 1

E

F

B

D

K22D

100

G65D

112Cool valve override required

G42

COMB

E

F

G

H

D

G65D

0

W22D

W32D

J orK orL orM

E J Comb.G H K Comb.

L Comb.M Comb.

109Heating valve demand

F63

GATED = F when B = 1

E

F

B

D

F52D

F62D

G41D

113Cooling valve demand

F65

GATED = F when B = 1

E

F

B

D

F53D

F64D

G42D

G65DWater balance required

From Page 14

G65DWater balance required

From Page 14

F52DHeat demand

From Page 10

F53DCool demand

From Page 10

W21D = 0Heating Override 1=Enabled

From Page 4

W22D = 0Cooling Override 1=Enabled

From Page 4

K21D = 0Heating Override Value

From Page 4

K22D = 0Cooling Override Value

From Page 4

W32D = 1Overrides 0=Disabled 1=Enabled

From Page 4

W32D = 1Overrides 0=Disabled 1=Enabled

From Page 4

G41D

Heat valve override requiredTo Page(s) 17,

G42D

Cool valve override requiredTo Page(s) 17,

F63D

Heating valve demandTo Page(s) 16,

F65D

Cooling valve demandTo Page(s) 16,

Page 23: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-12 Fan Control - Variable Speed

0 - 01

May2011_v2

015

19/05/2011

12 of 17Trend Control Systems Ltd

0 = Off1 = Low2 = Medium3 = High4 = Auto(1001-7)

Room Display Fan Speed0 = Off1 = Low2 = Medium3 = High4 = Auto255 = On(1001-23)

131Selected Fan Speed

S7

INTERNALS

VF77D

enum Units4.5 High Alarm Limit-0.5 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

124Select fan speed 1=Remote

G46

COMB

E

F

G

H

D

0

0

F71D

i2F

J orK orL orM

H J Comb.G K Comb.

L Comb.M Comb.

125Remote fan speed selected

F74

GATED = F when B = 1

E

F

B

D

F73D

K15D

W39D

128Room Display Fan Speed

K45KNOB

DF77D

enum Units79 Pin Level255 Top of Range0 Bottom of Range

127Fan speed selected

F77

GATED = F when B = 1

E

F

B

D

4

F74D

F75D

130Fan control off selected

F78

COMPARATORD = 1 when F > E

E

FD

F77D

0.9

126Fan speed in range

F75

PROXIMITYE +/- F

E

G

F

D

2

F74D

2

129Fan control auto selected

F76

PROXIMITYE +/- F

E

G

F

D

4

F77D

0.01

122Remote fans speed adjustment

F73

GATED = F when B = 1

E

F

B

D

F72D

K15D

G46D

121Selected fan speed adjustment

F72

GATED = F when B = 1

E

F

B

D

K45D

4

i2F

123Local fan speed select

F71

COMPARATORD = 1 when F > E

E

FD

K15D

3.9

K15D = 4Remote Fan Speed

From Page 3W39D = 0

Fan Speed Select 1=RemoteFrom Page 4

F77D

Fan speed selectedTo Page(s) 13,

F76D

Fan control auto selectedTo Page(s) 13,

i2FI/O2 Failed Status

i2FI/O2 Failed Status

F78D

Fan control off selectedTo Page(s) 10,13,

K15D = 4Remote Fan Speed

From Page 3

Page 24: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-13 Fan Control - Variable page 2

0 - 01

May2011_v2

015

19/05/2011

13 of 17Trend Control Systems Ltd

137Fan control required

G51

COMB

E

F

G

H

D

F78D

0

G20D

F76D

J orK orL orM

J Comb.H K Comb.G L Comb.

M Comb.

Fan Running

F89DI5INTERNAL

S

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

153Actual EC Fan Speed

S17

INTERNALS

VD9l

V Units10.1 High Alarm Limit-0.5 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

Actual EC Fan Speed

P5SYNC

SS17V

15 Min Period100 Records

138Fan manual value select

F80

GATED = F when B = 1

E

F

B

D

F77D

F79D

G51D

149Fan on required

F87

COMPARATORD = 1 when F > E

E

FD

0.5

F86D

147Effective fan speed

F86

GATED = F when B = 1

E

F

B

D

F91D

K28D

G53D

146Fan speed override required

G53

COMB

E

F

G

H

D

W27D

W32D

0

F85D

J orK orL orM

E F J Comb.K Comb.L Comb.M Comb.

145Override speed off

F85

COMPARATORD = 1 when F > E

E

FD

K28D

20

136Fan on value select

F79

GATED = F when B = 1

E

F

B

D

0

1

G49D

151Fan anti cycle seleted

F88

GATED = F when B = 1

E

F

B

D

F86D

0

G55D

154Fan enabled

F89

COMPARATORD = 1 when F > E

E

FD

0.5

D9l

148Anti cycling active

G54

TIMER

S DF89D

0 On Delay0 Minimum On300 Off Delay

150Fan anti cycle active

G55

COMB

E

F

G

H

D

G55D

F87D

G54D

F89D

J orK orL orM

f G J Comb.E G h K Comb.G h L Comb.

M Comb.

132Fan demanded

G47

COMB

E

F

G

H

D

G20D

G39D

F55D

W45D

J orK orL orM

e F H J Comb.e G H K Comb.e h L Comb.

M Comb.

133Fan required

G48

COMB

E

F

G

H

D

G39D

G20D

G16D

G47D

J orK orL orM

E F g J Comb.g H K Comb.

L Comb.M Comb.

134Fan enabled to run

G49

COMB

E

F

G

H

D

G48D

0

0

0

J orK orL orM

E J Comb.K Comb.L Comb.M Comb.

135Manual fan speed enabled

G50

COMB

E

F

G

H

D

G47D

0

G20D

F76D

J orK orL orM

h J Comb.G K Comb.e g H L Comb.

M Comb.

152EC Fan

D9

ANALOGUE

S

l

F88D

9

0 Override Enable0 Override Value

139Fan manual demand

F81

RSCL TOD=100(G-E)/(F-E)

E

G

F

D

1

F80D

3

140Fan speed = off

F82

COMPARATORD = 1 when F > E

E

FD

F80D

0.5

141Fan required speed

F83

GATED = F when B = 1

E

F

B

D

F59D

F81D

G50D

142Off fan speed select

F84

GATED = F when B = 1

E

F

B

D

K39D

0

F82D

143Minimum fan speed select

F90

GATED = F when B = 1

E

F

B

D

K39D

F84D

G50D

144Calculated fan speed

F91

RSCL FRD=(G/100)(F-E)+E

E

G

F

D

F90D

F83D

K40D

156Delayed fan start

G56

TIMER

S DG52D

R1L On Delay0 Minimum On0 Off Delay

157Occupation Relay

D1

DIGITAL

S

l

G56D

1

0 Override Enable0 Override Value

155Fan power required

G52

COMB

E

F

G

H

D

G16D

W27D

G20D

G49D

J orK orL orM

e g J Comb.e G H K Comb.F L Comb.

M Comb.F89D

Fan enabledTo Page(s)

G49DFan enabled to run

From Page 13

F59DFan demand

From Page 10

W27D = 0Fan Override 1=Enabled

From Page 4

K28D = 50Fan Speed Override Value EC

From Page 4

F76DFan control auto selected

From Page 12

F77DFan speed selected

From Page 12

F78DFan control off selected

From Page 12K28D = 50

Fan Speed Override Value ECFrom Page 4

G20DUnit - unoccupied

From Page 7G16D

Unit interruptFrom Page 7

G39DHeating required

From Page 10

F55DCooling required

From Page 10

W45D = 0Fan Off at Setpoint 1=Enabled

From Page 5

G39DHeating required

From Page 10

G49D

Fan enabled to runTo Page(s) 13,

G20DUnit - unoccupied

From Page 7F76D

Fan control auto selectedFrom Page 12

G20DUnit - unoccupied

From Page 7

W32D = 1Overrides 0=Disabled 1=Enabled

From Page 4

K39D = 37Minimum Fan Speed Setpoint

From Page 4

K40D = 70Maximum Fan Speed Setpoint

From Page 4

G20DUnit - unoccupied

From Page 7

G16DUnit interruptFrom Page 7

W27D = 0Fan Override 1=Enabled

From Page 4

G49DFan enabled to run

From Page 13

R1LLocal Address

K39D = 37Minimum Fan Speed Setpoint

From Page 4

Page 25: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-14 Service Pin - Water balance

0 - 01

May2011_v2

015

19/05/2011

14 of 17Trend Control Systems Ltd

Required Action Water Balance On for the Lan Water Balance Off for the Lan Water Balance On for the Unit Water Balance Off for the Unit

Phase 1 No Press Press No Press Press

Phase 2 No Press No Press Press Press

Phase 3No PressNo PressNo PressNo Press

159Water balance iccoms required

G62

TIMER

S DG61D

0 On Delay0 Minimum On300 Off Delay

158Service button WB enable

G61

COMB

E

F

G

H

D

W31D

I101S

I102S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

SB - Water Balance ON Lan

I101

EXTERNAL

Sc101

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

SB - Water Balance OFF Lan

I102

EXTERNAL

Sc102

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

SB - Water Balance ON Unit

I103

EXTERNAL

Sc103

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

160Water balance enable

G63

COMB

E

F

G

H

D

W31D

I101S

I103S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

164Water balance iccoms disable

G66

COMB

E

F

G

H

D

G62D

0

0

0

J orK orL orM

e J Comb.K Comb.L Comb.M Comb.

Water balance iccoms

N6

GLOBAL TOTrend

L RW28DW28S

3 Remote Attributes0 Remote Lan1 Message Interval

Failed Bit

G65D

Water balance requiredTo Page(s) 11,

SB - Water Balance OFF Unit

I104

EXTERNAL

Sc104

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

161Water balance disable

G64

COMB

E

F

G

H

D

W31D

I102S

I104S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

162Water balance required

G65

COMB

E

F

G

H

D

G63D

G64D

0

W28D

J orK orL orM

E J Comb.f H K Comb.

L Comb.M Comb.

163Water Balance 1=Enabled

W28SWITCH

DG65D

60 Pin Level

W31D = 1Service Button Mode 1=Enabled

From Page 4

Page 26: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-15 Service Button - Occupancy

0 - 01

May2011_v2

015

19/05/2011

15 of 17Trend Control Systems Ltd

Required ActionOccupied for the Lan Unoccupied for the LanOccupied for the Unit Unoccupied for the Unit

Phase 1No PressPressNo PressPress

Phase 2No PressNo PressPressPress

Phase 3PressPressPressPress

166Occupancy iccoms required

G72

TIMER

S DG71D

0 On Delay0 Minimum On300 Off Delay

165Service button Occ enable

G71

COMB

E

F

G

H

D

W31D

I105S

I106S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

SB - Occupancy ON Lan

I105

EXTERNAL

Sc105

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

SB - Occupancy OFF Lan

I106

EXTERNAL

Sc106

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

SB - Occupancy ON Unit

I107

EXTERNAL

Sc107

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

SB - Occupancy OFF Unit

I108

EXTERNAL

Sc108

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

167Occupancy enable

G73

COMB

E

F

G

H

D

W31D

I105S

I107S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

168Occupancy disable

G74

COMB

E

F

G

H

D

W31D

I106S

I108S

0

J orK orL orM

E F J Comb.E G K Comb.

L Comb.M Comb.

169Service button occ active

G75

COMB

E

F

G

H

D

G73D

G74D

0

F9D

J orK orL orM

E H J Comb.F h K Comb.

L Comb.M Comb.

170Occupancy iccoms disable

G76

COMB

E

F

G

H

D

G72D

0

0

0

J orK orL orM

e J Comb.K Comb.L Comb.M Comb.

Occupancy Iccoms

N7

GLOBAL TOTrend

L RK11DK11V

3 Remote Attributes0 Remote Lan1 Message Interval0 Significant Change

Failed Bit

W31D = 1Service Button Mode 1=Enabled

From Page 4

G75D

Service button occ activeTo Page(s) 7,

F9DUnit not in occ mode

From Page 7

K11D = 1Remote Occupancy

From Page 7

Page 27: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-16 Virtual Energy Meter

0 - 01

May2011_v2

015

19/05/2011

16 of 17Trend Control Systems Ltd

Fan Duty Maximum Speed kW >>>

Heat exchanger power estimation.

Heating Power = (Heating medium temperature – Space temperature) * Coil duty * Valve position / 100Power kW (D) = (Water Supply Temp DegC (E) – Space Temp DegC (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Water Supply Temp DegF (F) – Space Temp DegF (E)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)

Cooling Power = (Space temperature – Cooling medium temperature) * Coil duty * Valve position / 100Power kW (D) = (Space Temp (E) – Water Supply Temp (F)) * Coil Duty kW/degK (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I) Power Btu/s (D) = (Space Temp DegF (E) – Water Supply Temp DegF (F)) * Coil Duty Btu/sDegF (G) * Valve Position %(0-100)(H) * 0.01 (constant)(I)(1001-25)

1 kW = 0.948608 Btu/s1 hp = 0.7074163 Btu/s1 Btu/h/3600 = 1 Btu/s(1001-26)

Heating Coil Duty Fan Off >>>Heating Coil Duty Max Speed >>>

Cooling Coil Duty Fan Off >>>

Cooling Coil Duty Max Speed >>>

Occupation Relay Duty kW>>

178Fan duty max speed

F113

GATED = F when B = 1

E

F

B

D

0

0.16

I5S

183Heating coil energy level

F118

HEAT METERD=0 if F>E Else D=(E-F)*G*H*I

E

F

G

H

I

D

K17D

S2V

F108D

F63D

0.01

184Coiling coil energy level

F119

HEAT METERD=0 if F>E Else D=(E-F)*G*H*I

E

F

G

H

I

D

S2V

K18D

F111D

F65D

0.01

185Heat and cool energy level

F120

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F118D

1

1

F119D

191Unit energy consumption

F124

INTEGRATORD=D+(G*seconds/F)

G

F

H

D

F123D

3600

G81D∫dt

190Meter reset

G81

COMB

E

F

G

H

D

W52D

T1o

T1q

T1r

J orK orL orM

E J Comb.G K Comb.

L Comb.M Comb.

192Unit Energy Meter

S51

INTERNALS

VF124D

kWh Units500 High Alarm Limit-1 Low Alarm Limit0 High Alarm Delay0 Low Alarm DelayDisabled Low AlarmDisabled High Alarm

Unit Energy Meter

P6SYNC

SS51V

30 Min Period200 Records

188Unit total energy level

F123

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F122D

1

K52D

F121D

187Heating coolng load

F122

GATED = F when B = 1

E

F

B

D

0

F120D

I5S

189Energy Meter 1=Reset

W52SWITCH

DF1D

60 Pin Level

172Heating coil duty max speed

F107

GATED = F when B = 1

E

F

B

D

0

0.327778

I5S

175Cooling coil duty max speed

F110

GATED = F when B = 1

E

F

B

D

0

0.333333

I5S

181Occupation relay duty

F116

GATED = F when B = 1

E

F

B

D

0.01

0.5

D1l

186Fan and electric heater energy

F121

ADD/SCLRD = (E * G) + (F * H)

E

F

G

H

D

F114D

1

1

F116D

173Calculated heating duty

F108

MULTIPLYD=G*E*F

E

G

F

D

F107D

0.1

S17V

176Calculated cooling duty

F111

MULTIPLYD=G*E*F

E

G

F

D

F110D

0.1

S17V

179Calculated fan duty

F114

MULTIPLYD=G*E*F

E

G

F

D

F113D

0.1

S17V

S2VSpace Temperature

From Page 8

S2VSpace Temperature

From Page 8

K17D = 80Heating Flow Temperature

From Page 3

T1o15 minute pulse

T1q30 minute pulse

K52D = 1Power Conversion Factor

From Page 5

I5SFan Running

From Page 13

T1r60 minute pulse

I5SFan Running

From Page 13

F1DOne shot switch reset

From Page 2

I5SFan Running

From Page 13

I5SFan Running

From Page 13

D1lOccupation Relay

From Page 13

S17VActual EC Fan Speed

From Page 13

S17VActual EC Fan Speed

From Page 13

S17VActual EC Fan Speed

From Page 13

F63DHeating valve demand

From Page 11

F65DCooling valve demand

From Page 11

K18D = 6Cooling Flow Temperature

From Page 3

Page 28: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

Drawing Reference Page Details Issue Revision Checked By Project Number:

Outstation:

Date:

Page:

SET StrategyDesigned By:SET-019-015-17 IC Comms and Alarm Group

0 - 01

May2011_v2

015

19/05/2011

17 of 17Trend Control Systems Ltd

Alarm Group 1

g1

ALARM GROUPN

RO

LH

0 Priority

Alarm Route 1

o1

ALARM ROUTE

G

E

Dg1O

0

Alarm Destination

e1

ALARM DEST

S

H

Fo1D

0

1 Message Format0 Retry Pause Int.Disabled Inhibit Cleared1 Alarm Address0 Remote Lan

Slave Remote Space Temp

N1

GLOBAL TOTrend

L RS2VK12V

3 Remote Attributes0 Remote Lan0 Message Interval0.1 Significant Change

Slave Remote Setpoint

N2

GLOBAL TOTrend

L RS3VK14V

3 Remote Attributes0 Remote Lan0 Message Interval0.01 Significant Change

Slave Remote Occupancy

N3

GLOBAL TOTrend

L RS10VK11V

3 Remote Attributes0 Remote Lan0 Message Interval1 Significant Change

Slave Remote Fan Speed

N4

GLOBAL TOTrend

L RS7VK15V

3 Remote Attributes0 Remote Lan0 Message Interval1 Significant Change State Holder

A99Analogue

V D0

Read AlarmOut. Limits AlarmLow AlarmHigh Alarm

9Override active

G111

COMB

E

F

G

H

D

G41D

G53D

G42D

0

J orK orL orM

E J Comb.F K Comb.G L Comb.

M Comb.

Stratgey Override 1=Active

G111DI11INTERNAL

S

0 Alarm Delay0 Required StateDisabled State Alarm

Hours RunStarts

S2VSpace Temperature

From Page 8

S3VSetpoint

From Page 9

S10VOccupancy

From Page 7

S7VSelected Fan Speed

From Page 12

G53DFan speed override required

From Page 13

G42DCool valve override required

From Page 11

G41DHeat valve override required

From Page 11

Page 29: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

SensorNumber Type Label Units

S.E.T.Part Number Offset Source

I/OChannel

1 2 Discharge Air Temperature DegC F16D

2 2 Space Temperature DegC F19D

3 2 Setpoint DegC F42D

7 2 Selected Fan Speed enum F77D

10 2 Occupancy enum F7D

11 2 Heating Demand % F52D

12 2 Cooling Demand % F53D

17 2 Actual EC Fan Speed V D9l

21 1 Local Discharge Air Temp DegC 101 - 10k Therm DegC T0 1

22 1 Local Space Temperature DegC 101 - 10k Therm DegC T0 2

23 1 Local Setpoint Adjust DegC 102 - Knob TB 0.5deg tri 0 3

31 1 Room Display Space Temp DegC 112 - WMB Prescaled 0 1

51 2 Unit Energy Meter kWh F124D

Project: Project Number:Outstation:

Date:Page:

Sensor ListIQeco Standard Strategies May2011_v2

015

19/05/2011

T01 of T05

Page 30: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

Dig InNumber Label

I/OChannel Source

1 Unit Occupied 0 G18D

2 Unit Unoccupied 0 G20D

3 Unit In Bypass 0 G19D

4 Unit In Standby 0 G21D

5 Fan Running 0 F89D

11 Stratgey Override 1=Active 0 G111D

24 Window Pushbutton PIR 4

101 SB - Water Balance ON Lan 101

102 SB - Water Balance OFF Lan 102

103 SB - Water Balance ON Unit 103

104 SB - Water Balance OFF Unit 104

105 SB - Occupancy ON Lan 105

106 SB - Occupancy OFF Lan 106

107 SB - Occupancy ON Unit 107

108 SB - Occupancy OFF Unit 108

Project: Project Number:Outstation:

Date:Page:

Digital Inputs ListIQeco Standard Strategies May2011_v2

015

19/05/2011

T02 of T05

Page 31: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

KnobNumber Label Units Value Max. Level Min. Level Pin Level

1 Pushbutton PIR Timeout min 30 1440 0 79

2 Setpoint Adjust Timeout min 60 1440 0 79

3 Offset Range DegC 2 10 1 79

4 OCC Deadband DegC 1 2 0.5 60

5 NOCC Deadband DegC 12 20 8 60

6 Standby Deadband DegC 2 3 1 60

7 Heating Setpoint DegC 19.5 24 8 79

8 Cooling Setpoint DegC 20.5 34 18 79

11 Remote Occupancy enum F11D 3 0 79

12 Remote Space Temperature DegC 20 30 0 79

13 Remote Setpoint Offset DegC 0 10 -10 79

14 Remote Setpoint DegC 20 24 18 79

15 Remote Fan Speed enum 4 4 0 79

17 Heating Flow Temperature DegC 80 0 0 79

18 Cooling Flow Temperature DegC 6 0 0 79

21 Heating Override Value % 0 100 0 60

22 Cooling Override Value % 0 100 0 60

28 Fan Speed Override Value EC % 50 100 0 60

31 Fan Anti Cycle Time min 5 60 0 79

39 Minimum Fan Speed Setpoint % 37 50 0 79

40 Maximum Fan Speed Setpoint % 70 100 50 79

44 Room Display Setpoint DegC F42D 24 18 79

45 Room Display Fan Speed enum F77D 255 0 79

51 ECO Mode Deadband Increase DegC 4 6 2 79

52 Power Conversion Factor 1 0 0 0

Project: Project Number:Outstation:

Date:Page:

Knobs ListIQeco Standard Strategies May2011_v2

015

19/05/2011

T03 of T05

Page 32: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

SwitchNumber Label Status

Pin LevelState

1 Unit Bypass Request 1=Active G9D 60

11 Remote Shutdown 1=Shutdown 0 79

12 Frost Condition 1=Frost 0 79

21 Heating Override 1=Enabled 0 60

22 Cooling Override 1=Enabled 0 60

27 Fan Override 1=Enabled 0 60

28 Water Balance 1=Enabled G65D 60

31 Service Button Mode 1=Enabled 1 79

32 Overrides 0=Disabled 1=Enabled 1 79

34 Temperature Select 1=Remote 0 79

35 SP Offset Select 1=Remote 0 79

36 HeatCool Setpoint 1=Separate 0 79

37 Pushbutton TETS KO 1=Fitted 0 79

39 Fan Speed Select 1=Remote 0 79

41 Window Mode 1=Enabled 0 79

42 0=Pushbutton 1=PIR 0 79

45 Fan Off at Setpoint 1=Enabled 0 79

51 Operating Mode 0=Comfort 1=ECO 0 60

52 Energy Meter 1=Reset F1D 60

Project: Project Number:Outstation:

Date:Page:

Switch ListIQeco Standard Strategies May2011_v2

015

19/05/2011

T04 of T05

Page 33: FCU EC Fan WR4 Strategy Data Sheet - Energy Controls Online · 2015. 6. 15. · FCU EC Fan WR4 FCU EC Fan WR4 Strategy Data Sheet TA201212 Issue 1, 20-May-2011 3 Remote Control K11

DriverNumber Label Type Source Inv?

AnalogueOffset Range

TP+OverridePeriod Override

Raise/LowerDrive Feedbk

HysteresisOn Off

ChannelPhase

ChannelAntiPhase

1 Occupation Relay 1 G56D 0 1 0

5 Heating Valve 4 F63D 0 180 nul 5 6

7 Cooling Valve 4 F65D 0 180 nul 7 8

9 EC Fan 2 F88D 0 0 100 9 0

Project: Project Number:Outstation:

Date:Page:

Drivers ListIQeco Standard Strategies May2011_v2

015

19/05/2011

T05 of T05