Transducer ETM 15 DATA SHEET - N00300 For alternating current or voltage Página 1/4 july 2005 Characterísties Measuring of sinusoidal electric magnitudes. Measuring RMS (Optional) of sinusoidal eletric magnitudes or not sinusoidal Linear measuring field. Output signal with or without suppressed zero. Galvanic isolation between in- and output and auxiliary power supply. Reduced size for mouting space saving. Case type housing for fastening with screws or on rail . Application Conversion of an alternating sinusoidal voltage or current into a signal of direct current or voltage, which is independent on the load. Functioning The transducer ETM 15 with alternating sinusoidal voltage or current input is a fully electronic instrument, whick work on the principle of rectification. The transformer (1) attenuates the input signal for the rectifierador (2) and effectuates a galvanic isolation between the in- and output signals. The amplifier (3) converts the input signal into an output of alternating voltage or current. The rectifier (2) and the output modelu (3) need an auxiliary power supply (4). Characteristic curves Technical data (NBR 8145) Input Voltage 0..100/110/220/380/500V (others on consult) Current 0..1/2/5A (others on consult) Consumption voltage input: 0,65VA for error limit of 0,5% 1,00VA for error limit 0,25% Current input: 0,15VA Rated frequency 50;60 Hz ±10% (others on consult) Overload permanently: 1,5 x UrtdI ; 2 x IrtdI briefly: 4 x UrtdI/1s; 50 x IrtdI/1s Máximum: 250A/1s Output Current 0...1/5/10/20mA, 4...20mA (others on consult) Signal limit 1,5 IrtdI, UrtdI. 25V RC = infinite Load limit Rc= 15.000(mV) Ω max. output signal (mA) f.ex.: Rc=750Ω for 20mA Output with load divider (Optional) To calculate RC use 7.500mV instead of 15.000mV, the results will be the same for both outputs Voltage 0...10V; Rc500Ω (others on consult) Residual ripple 0,5% (peak to peak) Power supply 85...265Vca and 90...300Vcc 20...60Vca/Vcc consumption 4VA approx

description

TR

Transcript of ETM15EN

Page 1: ETM15EN

Transducer ETM 15 DATA SHEET - N00300

For alternating current or voltage Página 1/4 july 2005

Characterísties • Measuring of sinusoidal electric magnitudes. • Measuring RMS (Optional) of sinusoidal eletric magnitudes or

not sinusoidal • Linear measuring field. • Output signal with or without suppressed zero. • Galvanic isolation between in- and output and auxiliary power

supply. • Reduced size for mouting space saving. • Case type housing for fastening with screws or on rail .

Application Conversion of an alternating sinusoidal voltage or current into a signal of direct current or voltage, which is independent on the load.

Functioning The transducer ETM 15 with alternating sinusoidal voltage or current input is a fully electronic instrument, whick work on the principle of rectification.

The transformer (1) attenuates the input signal for the rectifierador (2) and effectuates a galvanic isolation between the in- and output signals. The amplifier (3) converts the input signal into an output of alternating voltage or current. The rectifier (2) and the output modelu (3) need an auxiliary power supply (4).

Characteristic curves

Technical data (NBR 8145) Input Voltage 0..100/110/220/380/500V (others on consult) Current 0..1/2/5A (others on consult) Consumption voltage input: ≤ 0,65VA for error limit of 0,5% ≤ 1,00VA for error limit 0,25% Current input: ≤ 0,15VA Rated frequency 50;60 Hz ±10% (others on consult) Overload permanently: 1,5 x UrtdI ; 2 x IrtdI briefly: 4 x UrtdI/1s; 50 x IrtdI/1s Máximum: 250A/1s Output Current 0...1/5/10/20mA, 4...20mA (others on consult) Signal limit ≤ 1,5 IrtdI, UrtdI. 25V RC = infinite Load limit Rc= 15.000(mV) Ω max. output signal (mA) f.ex.: Rc=750Ω for 20mA Output with load divider (Optional)

To calculate RC use 7.500mV instead of 15.000mV, the results will be the same for both outputs

Voltage 0...10V; Rc≥500Ω (others on consult) Residual ripple ≤ 0,5% (peak to peak) Power supply 85...265Vca and 90...300Vcc

20...60Vca/Vcc consumption 4VA approx

Page 2: ETM15EN

Transducer ETM 15 DATA SHEET - N00300

For alternating current or voltage Página 2/4 july 2005

Influence magnitudes Error Limit 0,5% (normal)

0,25% (optional) Reference conditions Input:

U I = UrtdI

II = 0...IrtdI for sinusoidal electrical magnitudes without zero displacement

Frequency: frtd ±2% Form factor: 1,111 Auxiliary power supply : UAX ±2% Load: 0,5RC max. Ambient temperature 25°C ±2K Heat up time: 20 min. approx. Additional error above 1,2IErtdI ou UrtdI

≤ 0,2%

Linearity deviation ≤ 0,2% (included in error limit) Load ≤ 0,05% RC = 0....RC max. (included in error limit) Temperature ≤ 0,2% /10 K; rated

temperature 25°C Auxiliary power supply ≤ 0,05% within the permitted

tolerance range for the supply voltage

Response time ≤ 200 ms External magnetic fields ≤ 0,5% for field intensity of

0,4 kA/m Radio frequency interference

≤ 0,5% between 27...460MHz at a distance 1m; power 1 W

≤ 0,5% entre 27...460MHz distância 1m; potência 1 W

Electrical test Uax ≥ 85V 2,5KV/1mim; 60Hz (for all circuits mutually). Uax ≤ 60V 2,5KV/1mim; 60Hz (for all circuits mutually). Pulse voltage 5kV; 1,2/50us; 0,5Ws Peaks 2,5kV;1MHz; 400 pulses / 1s

Construction and mounting Type Case Housing Base and cover of plastic

Fastening Surface mouting with two screws M4, or using

DIN rail. Electrical connection

Frontal terminals for eye and fork type cable sgoes

Protection class (NBR 6146)

IP 50 in housing IP 20 at the connection terminals

Weight 0,7 kg approx Climatic conditions Operation temperature -20...+60°C Functioning temperature -25...+70°C Transport and storage temp. -40...+80°C Relative humidity ≤ 75% of anual average with light

condensation (others on consult)

Mechanical test Mecânicos

Impact acceleration 30g during 11ms Vibration acceleration 2g frequency

5..150Hz Notes: Related to the final outuput value. UrtdI = Reted voltage IrtdI = Rated Current Response times below 200ms result in bigger residual ripple.

Page 3: ETM15EN

Transducer ETM 15 DATA SHEET - N00300

For alternating current or voltage Página 3/4 july 2005

Electric Connections

II , UI = Input Current or Voltage UAx = Auxiliary power supply O1 = Current or voltage output - normal O2 = Output with load divider (double output)

optional Notes: When using only O2 jump terminals 61 and 62 When using “double output”, there is no galvanic isolation between the output signals. Dimensional Drawing Dimensions in mm

Additional information The following items contain tips and cautions to be observed by the user for a good functional performance, as well as the maintenance of the instrument and the safety of the installations. Cautions Be sure the voltages and currents to be connected to the instrument, are compatible. Loosen all connections from the instrument before removing it from the installation . Mounting Instructions Oserve the ambient temperature range. At the place of installation, values for vibration, dust, dirt and humidity, which must remain between the limits, established by the protection class of the housing and the climatic group, specified in this data sheet, have to be observed . For fastening on flat area use two M4 screws. For mounting on DIN rail, use the snap-in device on the rear of the instrument. The connections can be made with eye or fork type cable shoes. Instructions for use When connections have been made, switch on the power supply and check at the output the functioning of the transducer. For quoting and ordering please issue your order according to the specification text. Example: Transducer ETM 15 Rated frequency: 60Hz Measuring range: 0…5A Auxiliary power supply: 220Vac Output signal: 4…20mADC Optional: Error limit 0,25% Additional information: Standard Code number: N003002804511

1 3 2 5 13 14 61 62+ _

I U O1UI AXI

63 64+ _

O2

Page 4: ETM15EN

Transducer ETM 15 DATA SHEET - N00300

For alternating current or voltage Página 4/4 july 2005

Ordering information Catalog number TRANSDUCER ETM-15 for alternated current or alternated voltage N 0 0 3 0 - - - - - - Housing Normal 0 RMS 1

Rated Frequency 50 Hz 1 60 Hz 2 400 Hz 3 Others 0 Measuring range: Voltage: between 0...10 up to 0..20VAC 1 between 0...21 up to 0...50VAC 2 between 0...51 up to 0...97VAC 3 between 0...98 up to 0...180VAC 4 between 0...181 up to 0...340VAC 5 between 0...341 up to 0...600VAC 6 Current: 0...1A 7 0...5A 8 Others 0

Auxiliary Power Supply 20…60Vca/Vcc 12 85…265Vca and 90…300Vcc 13 Output Signal 0...1mADC 1 0...5mADC 2 0...10mADC 3 0...20mADC 4 4...20mADC 5 0...10VDC 6 Others( 0...1mAdc até 20mAdc e 0...1Vdc até 0...15Vdc) 0 Optional Error Limit 0,25% 1 Output with load divider (double output) 2 Others response times between 50ms and 2s 4 Standard (Class 0,5%) 5

Additional information Standard 1 Complement (Inform input signal voltage) C

ABB Ltda - ATLV/IE Instrumentation Electrical Avenue. Dos Autonomistas, 1496 - 06020-902 - Osasco - SP

Phone: +55 11 3688-8320 / 8323 / 8347 - Fax: +55 11 3688-8322 [email protected]