ERVXXSHA1130, ERVXXSVA1130: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.1
Product Data
A200611• 35 to 131 CFM @ 0.2 in. w.g.• 35 to 119 CFM @ 0.4 in. w.g.Introducing the industry’s most advanced residential fresh air system,created to offer a universal platform specifically designed and improvedto make the contractor’s life easier and more profitable while deliveringconstant superior air quality.• Thanks to new technology, the airflow calibration and auto-balancing
are achieved quickly and maintained throughout the life of the product• Select the desired CFM (from 35 to 130 CFM) using the very first
integrated LCD screen. The airflow is then set up automatically• Integrated electronic airflow measurement device with real time LCD• Integrated diagnostic tool• PMSM ECM motors for very low power consumption• Suspended installation (chains included)
OR• Wall-mount installation (universal brackets included)
– installation with 2 brackets– installation with 4 brackets
CORE• Coroplast and plastic membrane with polymer base, non washable• Dimensions: 12" x 12" x 9" (30.5 cm x 30.5 cm x 23 cm)
FILTERS• MERV 8 grade washable standard filter (included)• Optional MERV13 grade filter part no. SV24285
OPTIONS• Complete line of registers and diffusers• Compatible with the Tandem transition (part no. KVAAC0101HCO)
(for units producing up to 130 CFM only)
UNIT DESCRIPTION• SRE of 67% at 0°C and 56% at -25°C (64 CFM)• Ports size: 5 in.• Recirculation Mode and Recirculation Defrost• Painted door, corrosion resistant galvanized body• One-piece molded insulation shell, no air leakage (expanded
polystyrene; UL 94 HF-1 certified)• Constant airflow and auto-balancing device• Motorized dampers (no additional backdraft dampers required)• No drain required• 120V, 60 Hz, 2.5 A, 110 W with 6 foot power cord• Sound: 70.0 dBA at 115 CFM @ 0.4 in. w.g.
60.1 dBA at 64 CFM @ 0.2 in. w.g.
A200636
CONTROLSNOTE: Do not connect the Infinity® System Control directly to theventilator, as that may cause damage. If you have an Infinity® SystemControl use one of the optional Main Wall Controls. Please do not connect the Network Interface Module (NIM) or theInfinity® Damper Control Module to the two terminal blocks on the newventilator. The new ventilator terminals do not match up to the NIM orInfinity® Damper Control terminals. Connecting the two controls maycause damage.
A200612CAThere are 4 optional main controls and 1 optional auxiliary controlavailable. Refer to the applicable Wall Control specification sheet formore information.NOTE: These controls are compatible only with the latest versions ofERV and HRV ventilators. Older controls will not work with the newestventilators.
ERVXXSHA1130, ERVXXSVA1130Performance™ Fresh Air Systems – 130 CFM
Control Name Description of Modes Model #
Premium Touch Screen, Auto 2.0 Fully Configurable, Multiple Modes KVACN0101CPC
Automatic Auto 1.0, Filter Alert KVACN0101CACDehumidistat Humidity Sensor / Selection KVACN0101CDHSpeed Selector 5 Operating Time Periods KVACN0101CSSAuxiliaryBathroom Override 20 - 40 - 60 min. Settings KVACN0101CBO
Fabriqué au
Made in
CANADACANADA
AUTOMATICBATHROOMOVERRIDEPREMIUM DEHUMIDISTAT SPEED SELECTOR
ERVXXSHA1130, ERVXXSVA1130: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.2
DIMENSIONS
A200613
• Total assembled weight (core included) - approx 37 lb. (16.8 kg) • Shipping weight - approx 44 lb. (20 kg)
Ø
Ø
EXHAUST AIR FROM BUILDING FRESH AIR TO BUILDING
EXHAUST AIR TO OUTSIDEFRESH AIR FROM OUTSIDE
21”
21-1/2”
19-1/8”
18-3/4” 8” 16-1/8”
8”1”
5” TYP
CLEARANCEFOR DUCTING
POWERCORD
TERMINALS
DRAINS
LATCHES
CLEARANCEREQUIRED FORMAINTENANCE
POWERCORD
TERMINALSDRAINS
LATCHES
CLEARANCEREQUIRED FORMAINTENANCE
CLEARANCEFOR DUCTING
1”
16-1/8”
19-1/8”
5” TYP
23-1/2”
8”
18-3/4”
21”
EXHAUST AIR FROM BUILDING
FRESH AIR TO BUILDING
5” TOP PORTS
5” SIDE PORTS
8”
EXHAUST AIR TO OUTSIDEFRESH AIR FROM OUTSIDE
ERVXXSHA1130, ERVXXSVA1130: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.3
DEFROST SYSTEMNo negative pressure is created by air exhausted to the outdoors since theair is recirculated into the house, helping to prevent any backdraft.
A200615
FAN CURVESThanks to new technology, no need to balance the unit manually. Both PMSM motors are controlled by an artificial intelligence performing 120readings per minute then processing this information to maintain the requested airflow.For typical installation, the software will ensure a balanced ventilation at every selected speed regardless of the weather conditions, the type ofconnection, the variable speed furnace/AHU, the stack effect, the filter clogging and so on. This results in peace of mind for installers and usersknowing that the unit will always remain balanced and that it will maintain its maximum heat/energy recovery efficiency.
A200635
FACTORY SETTING OUTDOOR TEMPERATURE*
-5°C TO -15°C / 23°F TO 5°F -15°C TO -27°C / 5°F TO -17°F -27°C AND LESS / -17°F AND LESS
CFM AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
0 to 59 30 5 18 5 17 860 to 90 40 5 21 5 21 8
91 and more 20 5 15 5 15 8
PLUS OUTDOOR TEMPERATURE*
-5°C TO -15°C / 3°F TO 5°F -15°C TO -27°C / 5°F TO -17°F -27°C AND LESS / -17°F AND LESS
CFM AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
AIR EXCHANGE IN MINUTES
DEFROST IN MINUTES
0 to 59 24 7 14 7 14 1060 to 90 30 7 16 7 15 10
91 and more 18 7 12 7 12 10
*Outdoor temperature is read by a thermistor located inside the unit, next to fresh air from outdoor port.
y = -2E-07x3 - 2E-05x2 - 0.0029x + 1.3072R² = 0.9987
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
Net Airflow (CFM)
AIRFLOW IS FULLY ADJUSTABLE WITH 1 CFM INCREMENT
STATIC
P RESSURE
(PA )
STATIC
P RESSURE
(IN . W .G.)
N ET SUPPLY
AIRFLOW
(L/ S)
N ET SUPPLY
AIRFLOW
(CFM )
GROSS
AIRFLOW
SUPPLY
(L/ S)
GROSS
AIRFLOW
SUPPLY
(CFM )
GROSS
AIRFLOW
E XHAUST
(L/ S)
GROSS
AIRFLOW
E XHAUST
(CFM )
25 0.1 64 136 65 138 65 138
50 0.2 62 131 63 133 63 133
75 0.3 58 123 59 125 59 125
100 0.4 56 119 57 121 57 121
125 0.5 53 112 54 114 54 114
150 0.6 49 104 50 106 50 106
175 0.7 45 95 46 97 46 97
200 0.8 41 87 42 89 42 89
225 0.9 36 76 37 78 37 78
250 1.0 30 64 31 66 31 66
© 2021 Carrier. All rights reserved. Edition Date: 1/21 Catalog No: ERV-130-01PDReplaces: New
ERVXXSHA1130, ERVXXSVA1130: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.4
ENERGY PERFORMANCE
REQUIREMENTS AND STANDARDS• UL 1812 compliant (safety)• Could be installed in compliance with CSA F326• Performance tested as per CSA C439 Standard• Complies with ROHS 2015/863 directive• Compliant with Prop 65
SUPPLY TEMPERATURE
NET AIR-FLOW POWER
CONSUMED WATTS
SENSIBLE RECOVERY EFFICIENCY
ADJUSTED SENSIBLE
RECOVERY EFFICIENCY
LATENT RECOVERY / MOISTURE TRANSFER
APPARENT SENSIBLE
EFFECTIVENESS
TOTAL RECOVERY EFFICIENCY
ADJUSTED TOTAL
RECOVERY EFFICIENCY°C °F L/S CFM
HEATING
0 32 30 64 32 67 70 0.65 72 – –
0 32 62 131 112 63 69 0.53 71 – –
-25 -13 30 64 57 56 58 0.62 72 – –
35 95 33 70 36 – – 0.54 60 56 58