Energy Storage System (ESS) Update

27
www.NFPA.Org/Foundation | © Fire Protection Research Foundation. All rights reserved. Energy Storage System (ESS) Update Presented by: Victoria Hutchison & Casey Grant | Fire Protection Research Foundation at NFPA On behalf of: Brian O’Connor, NFPA 855 Staff Liaison

Transcript of Energy Storage System (ESS) Update

www.NFPA.Org/Foundation | © Fire Protection Research Foundation. All rights reserved.

Energy Storage System (ESS) Update

Presented by:

Victoria Hutchison & Casey Grant | Fire Protection Research Foundation at NFPA

On behalf of: Brian O’Connor, NFPA 855 Staff Liaison

www.NFPA.Org/Foundation | © Fire Protection Research Foundation. All rights reserved.

Understanding NFPA and FPRF

NFPA – National Fire Protection Association• Non Profit Membership Association• Established in 1896; Approximately 65K members• Headquartered in Quincy, MA, though no geographic boundaries• Mission: Make the world safer from fire and related hazards• 300 plus “model Codes & Standards; administered by 8K volunteers

FPRF– Fire Protection Research Foundation• NFPA’s Research Affiliate: Separate non-profit research

organization• Mission: Facilitate research on behalf of the NFPA mission• Analogy: Similar to “Special Ops”, to address real-world problems

2

www.NFPA.Org/Foundation | © Fire Protection Research Foundation. All rights reserved.

-- The Research Pathway --

3

NFPA 855, Standard for the Installation of Stationary Energy Storage Systems

Presented by:

Jim Biggins PE, TUV SUD GRC

Chad Duffy PE, NFPA

Brian O’Connor PE, NFPA

• NFPA 855: Standard for Installation of Stationary Energy Storage Systems (2020 edition)

• Standard development began in 2016.

• Final document released September 2019.

• Purpose: To establish fire protection criteria for ESS installations. — To consider and mitigate fire and life safety risks of

ESS installations

Scope

1.1

• Emergency Operations Plan—Safe shutdown

—Emergency procedures

—Response considerations (SDS)

—Removal of damaged ESS

—Annual staff training

• Hazard Mitigation Analysis (HMA)

• Fire Mitigation Personnel

4.1.3

4.1.4

4.16

• System listed to UL 9540

• Charge Controllers

• Inverters & Converters

• Energy Storage Management System

• Reused and Repurposed Equipment

84.2

• NFPA 70 or IEEE C2

• ESS Signage

• Separation (2hr Fire Rating)

• Impact Protection

• Security

• Elevation

• Open Rack

94.3

• Dedicated Use Buildings

• Non-dedicated Use Buildings

• Dwelling and Sleeping Units

104.4.2

• Remote

• Near Exposures

• Rooftop & Open Parking Garage

11

100 ft

100 ft

100 ft

100 ft

ESS

4.4.3

• Charging and Storage

• Deployed

124.5

• 50kWh groups

• Spaced 3ft from groups & walls

• Other arrangements based on large

scale fire test

• Exempt: Remote Locations

13

50 kWh

3 ft.3 ft.

4.6

Exempt: Dedicated use buildings and remote locations

144.8

• Exhaust Ventilation—1ft3/min/ft2

—Designed to keep flammable gasses under 25% of LFL

—Exhaust away from openings

• Smoke and Fire Detection —Gas detection activates

ventilation

—Smoke detection per NFPA 72

15

4.9

4.10

• Sprinkler System 0.3gpm/ft2

over 2,500 ft2

• Other Fire Protection Systems

—Large Scale Fire Test

—UL 9540A

• Explosion Control

—ESS exceeds 25% LFL

164.11 & 4.12

Telecommunication • Listings

• Retrofits

• Energy Storage Management System

• Elevation Restrictions

• Size and Separation

• Smoke and Fire Detection

• Fire Suppression

• Water Supply

• System Interconnections

• Commissioning

• Decommissioning

• Explosion Control

Electric Power Utility Exemptions • Temporary ESS out of scope

• Plans and specifications

• Emergency Operations Plan

• Listing

• Retrofits

• Energy Storage Management System

• Elevation Restrictions

• Mobile ESS

• Size and Separation

• Smoke and Fire Detection

• Fire Suppression

• Water Supply

• System Interconnections

• Commissioning

• Operations

• Decommissioning

• Explosion Control

Non-dedicated use building

2 Hr Rating

Office Space

Hal

lwayESS Room

2hr Fire rating

Near Exposures

Elevation

Laddering Capabilities

Non-dedicated use building

Height Restrictions

Fire rating

Grouping Spacing 50kWh

Maximum

Fire Area (600kWh)

50kWh Li-Ion ESS

Office Space

Hal

lway

50 kWh

3 ft

3 ft

3 ft

• Size and Separation

• Explosion Venting

• Storage

ESS Related Combustible Storage

Explosion Vent

Storage

3 ft

Storage

Suppression

Detection

Sprinkler

Detector

Office Space

Hal

lway

100 ft from Exposures

180ft140ft

• No Max Stored Energy

• No Group Spacing

NFPA 855

Adoption Process and Timeline