ENERGY SAVING SOLUTIONS FOR CHILLER PLANTProject Reference: EQUATORIAL INTERNATIONAL FIVE STARS HOTEL, VIETNAM
Equatorial hotel info:Standard: international 05 stars hotelOperated from: 1995CE: Mr. Chan Kum YuenAdd: 242, Tran Binh Trong street, district 5, HCMC, Vietnam
Background Equatorial hotel has been in Vietnam since 1995, one of leading hotels who is veryinterested in energy saving. Following the purpose, there are a lot of outlined solutions from consultants for chiller plant sent to the Owner but still don’t get the acceptance
ProblemTrane Chiller has play the role with around 4.5 of COP, non-VFD for chilled waterpump system, condenser water pump system, and cooling tower system.2,112,000 kWh/year for chiller plant next to annual maintenance cost is very high.
Project ScopeThe optimum solution was determined to be installation of SMARDT oil free – high efficiency chiller and CPECS solution for chilled water pump system, condenser water pump system, cooling tower system as a Turnkey Solution for chiller plant. 30% of saving was expected.
OutcomesThe revolutionary of energy saving has came to Equatorial hotel, just only around 67,830 kWh/month of chiller plant consumption at 4 first months
Main items Amazing numbers
61%
1.7
1,307,520 kWhAnnual energy saving
Energy saving percent of chiller plant
Pay back time