ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance...

26
1 ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES; Part 2: Examples of application to residential walls Thomas Thorsell and Mark Bomberg 1 The paper is submitted to the Journal of Building Physics; here is an extended abstract: It is often forgotten that the building sector consumes more energy than the transportation sector. To meet expectations and needs of our society we must seek significant improvements in the efficient use of energy for this purpose. In many instances our normal approach that is based on conventional testing methods, is not comprehensive enough. For instance, the thermal performance of a wall is defined by tests performed on walls with dry materials, without consideration of air and moisture movements even though we know that the energy performance of materials and building assemblies is affected by both moisture and air flows. The authors believe that a more precise means of evaluation of the thermal performance of assemblies must be used to guide us in developing construction practices that lead to better performance. That should include consideration of air and moisture transfer under field conditions. The previous part of this paper described the limitations of conventional thermal resistance testing using calibrated hot boxes and explained that the effect of climate on thermal performance must also involve use of computer models that are capable of simultaneous calculations of heat, air and moisture (HAM) transfer. In this paper, the integrated testing and modeling methodology proposed is applied to a few selected residential walls to highlight the magnitude of air flow effects compared with steady-state thermal resistance without air flows. Effectively, to characterize energy performance of the building enclosure one must use an integrated methodology that uses both testing and modeling. The paper represents a first Step in this direction. 2. Construction of tested residential wood-frame walls The material selection and construction technique used was identical for 6 residential test walls in pilot study and for the two walls (1 and 4) reported in this paper. 2.1 The reference wall (wall 1) The following describes the construction of Wall 1 1 Syracuse University, 149 Link Hall, Building Energy and Environmental Systems Laboratory, PhD student and Research Professor respectively

Transcript of ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance...

Page 1: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

1

ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES OF INTEGRATED METHODOLOGY FOR EVALUATION OF ENERGY

EQUIVALENT R-VALUE FOR BUILDING ENCLOSURES;

Part 2: Examples of application to residential walls

Thomas Thorsell and Mark Bomberg 1

The paper is submitted to the Journal of Building Physics; here is an extended abstract:

It is often forgotten that the building sector consumes more energy than the transportation sector. To meet expectations and needs of our society we must seek significant improvements in the efficient use of energy for this purpose. In many instances our normal approach that is based on conventional testing methods, is not comprehensive enough. For instance, the thermal performance of a wall is defined by tests performed on walls with dry materials, without consideration of air and moisture movements even though we know that the energy performance of materials and building assemblies is affected by both moisture and air flows. The authors believe that a more precise means of evaluation of the thermal performance of assemblies must be used to guide us in developing construction practices that lead to better performance. That should include consideration of air and moisture transfer under field conditions.

The previous part of this paper described the limitations of conventional thermal resistance testing using calibrated hot boxes and explained that the effect of climate on thermal performance must also involve use of computer models that are capable of simultaneous calculations of heat, air and moisture (HAM) transfer.

In this paper, the integrated testing and modeling methodology proposed is applied to a few selected residential walls to highlight the magnitude of air flow effects compared with steady-state thermal resistance without air flows. Effectively, to characterize energy performance of the building enclosure one must use an integrated methodology that uses both testing and modeling. The paper represents a first Step in this direction.

2. Construction of tested residential wood-frame walls

The material selection and construction technique used was identical for 6 residential test walls in pilot study and for the two walls (1 and 4) reported in this paper.

2.1 The reference wall (wall 1)

The following describes the construction of Wall 1

1 Syracuse University, 149 Link Hall, Building Energy and Environmental Systems Laboratory, PhD student and Research Professor respectively

Page 2: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

2

• Glass fibre batt insulation (R13) with dimensions 3 ½ “x15”x93” (manufactured by a large US manufacturer) with asphalt backed Kraft paper purchased from a building materials supplier.

• The dimensions of the wall were about 6'x8' and the tolerance of the frame dimensions was ¼ inch.

• A double sill plate was used at the top, and a single plate was used at the bottom. To represent typical workmanship there was no sealing between the sub-flooring and the wall assembly.

• The facer on the insulation batts was stapled to the inside of the studs on both sides of the cavities at a 12-inch spacing.

• The recommended procedure for installation was acquired from the manufacturer • To ensure that the installation of batt insulation represented typical workmanship,

several sources, such as Energy Gauge programmers and Building Professional Institute etc. were contacted for advice. The final choice of workmanship level was to represent the middle of category 1 (good workmanship) as defined in Energy Gauge (5 – 6 percent of deficiency). Because the facer was stapled to the studs, the area of unfilled corners was reduced by approximately 3% (i.e.the area of insulation was 97%).

• Corners next to the stud, on the back side of each cavity were unfilled. To ensure uniformity special triangular templates were prepared, see Figure 4. A similar approach to insulation installation was used by Brown et al, (1993).

• The 7/16" thick oriented strand board (OSB) sheathing was installed to the framing with galvanized roofing nails 1¼”, at about 1 foot spacing (30 cm). The OSB sheathing was installed with 1/8 inch (3 mm) gaps in the joints to allow for hygrothermal movement.

• The same layout was used for construction of all wood-frame test walls • In all cavities using batt insulation, they were joined at a height of 6 feet. • The drywall was mounted carefully on the interior surface to not affect or damage the

sensors on its surface. Drywall screws were used for the installation and the joints where taped and finished. At the bottom edge of the walls, the bottom edge of the gypsum board was installed 1/4” up from the sub floor.

• The polymeric WRB product selected was stapled to the OSB according to the manufacturer’s instructions with a stapling distance of 1 ft (30 cm) throughout the whole surface. Overlap between two rolls was about 6”. The WRB was also taped with a compatible tape according the manufacturer’s instructions.

(a) For full sized cavity 2 x 2 inch triangle

Page 3: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

3

(b) For narrow cavities 1.5 x 1.5 inch triangle

Figure 2: Typical spacer used to maintain 3% of unfilled corners on the back side of batt insulation.

2.2 The hygroscopic fibrous insulation (wall 4)

The same layout was used for construction of all wood-frame test walls. The other wall tested (Wall 4) was identical except for the thermal insulation material that will not be described except that it was blown in material based on cellulose fiber. When the construction of each test wall was completed, a layer of 1 inch thick expanded polystyrene with a nominal density of 1 lb/ ft3 was mounted and adhered to the interior surface of each wall. It was used as a calibrated boundary layer (CBL) for measuring heat flux.

3. Thermal resistance measurements of walls 1 and 4

These tests were performed at exterior temperature of 3 oF (-16 oC). The heat flux transducer (HFT) placed on thermal insulation at mid-height of wall 1 malfunctioned and is not reported in this paper.

3.1 Step 1 – measurement of the reference R-value on the section through insulation

Figure 3 shows results of measurements performed during the Step 1 on wall 1 under standard conditions namely room 24 oC and 50 %RH; weather -16 oC, uncontrolled RH and no air pressure difference.

Page 4: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

4

Figure 3: Results of heat flux and temperatures measured on wall 1

Tables 1 and 2 presents temperatures measured on both wall surfaces and heat fluxes measured at the interior surface of each wall. Since a 25 mm layer of EPS was placed against the inner surface of each wall, its effect was included in the measured Rsi-value2, and when its thermal resistance is subtracted, one obtains a local, apparent Rsi-value of the wall itself as indicated by the HFT. To continue the analysis of the primary measured data (temperatures and heat fluxes) with a view to establishing thermal resistance of the wall we need to define a few terms that will be used in this paper:

1) R-value in this paper represents the air to air resistance to heat flow. It is an inverse of the U-value. Note that this definition is different from that used in ASHRAE. This definition permits us to avoid several measurements on the wall surface to establish an average surface temperature when multi-dimensional heat transfer causes large local differences.

2) Apparent R-value = a ratio between temperature difference between indoor and outdoor air to the local heat flux measured at the local point without subtracting the resistance of calibrated boundary layer (CBL).

3) Local R-value = a ratio between temperature difference between indoor and outdoor air to the local heat flux measured at the local point when the resistance of calibrated boundary layer (CBL) is subtracted.

2 Rsi-value is thermal resistance in SI units, R-value is thermal resistance in Imperial (IP) units

Page 5: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

5

4) Nominal R-value = thermal resistance under steady-state, unidirectional heat flow through the center section of the insulation i.e. in the symmetry point between thermal bridges. R-values measured under standard conditions (Step 1) are considered as the reference.

5) Clear-wall R-value = the ratio between average temperature difference between indoor and outdoor air to the mean value of the heat flux across the whole wall. This would be R-value calculated for the central area of the wall (without consideration to increased heat flow on the wall perimeter, corners etc). Clear-wall R-value is used for calculating effects of air and moisture either in the laboratory testing protocol or for the field performance evaluation.

6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows measured under specified conditions.

Using these terms we can proceed from the measured local R-values to the clear-wall R-values.

Table 2 Nominal R-value through the insulation section measured on Wall 1 during Step 1

Wall location

Cold side, air

oC

Warm side, air

oC

Temp. difference

oC

Heat flux W/m2

Apparent Rsi-value, (m2K)/W

Local Rsi-value, (m2K)/W

Local R-value (IP units)

Top -14.9 18.9 33.8 10.06 3.36 2.72 15.44

bottom 15.0 17.9 32.9 10.21 3.22 2.58 14.65

Average (Nominal)

33.5 10.14 3.29 2.65 15.05

Table 3 Nominal R-value through the insulation section measured on Wall 4 during Step 1

Wall location

Cold side, air

oC

Warm side, air

oC

Temp. difference

oC

Heat flux

W/m2

Apparent Rsi-value, (m2K)/W

Local Rsi-value, (m2K)/W

Local R-value

(IP units)

top -17.0 -19.0 36.0 8.9 4.04 3.4 19.31

middle -16.6 18.9 35.5 10.15 3.50 2.85 16.22

bottom -15.1 17.8 33.9 8.15 4.16 3.52 19.99

Average (Nominal)

35.5 9.07 3.9 3.26 18.51

Adding up the R-values for the individual component materials, namely R13 fiberglass batt, OSB, drywall and surface air film resistances, one obtains the nominal R-value of R14.9 for Wall 1 and

Page 6: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

6

R15.8 for Wall 4. This agrees with the value measured on Wall 1 but disagree for Wall 4. These tests were, therefore, performed once more and results are presented in Tables 4 and 5. Table 4 Nominal R-value through the insulation section of Wall 1 during repeated Step 1 test

Wall location

Cold side, air

oC

Warm side, air

oC

Temp. difference

oC

Heat flux W/m2

Apparent Rsi-value, (m2K)/W

Local Rsi-value, (m2K)/W

Local R-value

(IP units)

Top -14.8 19.1 33.9 10.02 3.39 2.75 15.6

bottom -15.0 18.1 33.1 10.38 3.19 2.55 14.5

Average (Nominal)

2.65 15.05

Table 5 Nominal R-value through the insulation section of Wall 4 during repeated Step 1 test

Wall location

Cold side, air

oC

Warm side, air

oC

Temp. difference

oC

Heat flux W/m2

Apparent Rsi-value, (m2K)/W

Local Rsi-value, (m2K)/W

Local R-value (IP units)

top -17.0 19.1 36.2 9.38 3.86 3.22 18.28

middle -16.7 19.0 35.7 10.41 3.43 2.79 15.84

bottom -15.1 18.0 33.1 8.50 3.89 3.25 18.48

Average (Nominal)

3.73 3.09 17.53

Tables 4 and 5 show repeated measurements of nominal R-value in the section through the thermal insulation. The agreement remains good for Wall 1 but the change in test results for Wall 4, namely from 18.5 (ft2.h.oF)/Btu to 17 5 (ft2.h.oF)/Btu warrants a review of R-value stability for that wall.

3.2 Analysis of the stability of R-value on Wall 4

Wall 4 showed significant changes in thermal resistance during the extended period of testing. One hypothesis that comes to mind for this change is that this could be an effect related to moisture gain as this wall includes a non-traditional insulation system containing a hygroscopic material. The following section will provide theoretical background and elucidate the effect of moisture on the apparent R-value.

The hygrothermal properties of the insulation material were established in another project. Figure 4 shows measurements of heat flux on the surfaces of a sealed specimen having a constant total moisture content of 0.94 percent by volume (9.4 kg/m3).

Page 7: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

7

Figure 4: Heat flow flux measurements performed in an apparatus built for testing in accordance to ASTM C518 but performed on a sealed specimen having a moisture content of 9.4 kg/m3. This method is used for verification of the HAM model3. Calculations (solid line with triangles) show better agreement with the heat flux recorded on both surfaces (continuous lines) than calculations with moisture content of 6.8 kg/m3 (dashed line with triangles).

Under the influence of a thermal gradient the moisture moves towards the cold side causing changes in the heat flux with time. The agreement shown in Figure 4 is believed to be sufficient, and we will use this set of hygrothermal input data in the current project. Figure 5 shows the results of HAM model calculations based on this data.

g

Time in [h]35030025020015010050

Hea

t flu

x (c

ondu

ctio

n) in

[W/m

2] -10-11-12-13-14-15-16-17-18-19

HFT_studHF_wholeHFT1

3 Other results from MBES project led by Syracuse U in 2004-2006 and sponsored by BASF, Fortifiber and Greenfiber Corporations were published in several papers.

Page 8: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

8

Figure 5: Calculated heat flux through Wall 4 using hygrothermal data as shown in the verification tests (Figure 4)

Figure 5 shows the results of 2-D calculations performed with CHAMPS-BES4 software developed under joint project between Technical University of Dresden, Germany and Syracuse University. Figure 5 presents three curves. The top curve represents values of local heat flux expected to be measured by a HFT placed in the center of the insulation section . The second curve (HF whole) represents the mean value of the heat flux for the whole wall The third curve represents the maximum heat flux that would be measured at the stud location. Measurements of his value were attempted with small commercial HFT sensors but they were found to be unreliable.

We must note that we do not know the degree of connectivity between the cavities of Wall 4 and the indoor environment. We have, therefore, made calculations for the worst case scenario i.e., a full connectivity with indoor environment. This is the case presented in Figure 5.

Heat flux calculated at the 2’nd day of simulation was 10.1 W/m2 while on the 3’rd day it was 10.7 W/m2 - 6 % higher. The measured change in the R-value of Wall 4 was about 5 % which is in the same order of magnitude difference.

Now, we pose the question as to what resistance to water vapor diffusion is required to eliminate the effect of moisture on R-value of this wall providing that the effect of air flow was also eliminated by use of an air barrier. To provide an answer to this question, the same HAM model was used but assuming that the CBL layer was air impermeable and that its water vapor permeability was as recommended by ASHRAE for thermal zone 5 of the US. The results of that simulation are provided in Figure 6.

Time in [h]35030025020015010050

Hea

t flu

x (c

ondu

ctio

n) in

[W/m

2] -11-12-13-14-15-16-17-18-19-20-21

HF_wholeHFT1HFT_stud

Figure 6: Calculated performance of Wall 4 with the same hygrothermal input data as for Figure 5 but with a perfect air barrier and with a required water vapor retarder placed on the inner face of the wall.

4 This software was developed under a joint project between Technical University of Dresden, Germany and Syracuse University, NY.

Page 9: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

9

Two conclusions can be drawn from comparison between Figures 5 and 6. The first relates to the effect of moisture ingress. The wall provided with the water vapor retarder on the inner face showed practically constant heat flux (HFT1) with time. It only varied from 11 to 11.2 W/m2 over the 350 hours simulated. On the other hand, the wall with an air bypass carrying moisture into the wall cavity (Figure 5) showed that over that same period of time the heat flux at HFT1 increased from 9.6 W/m2 to 11.2 W/m2 (a 14.3% change).

The second conclusion is far more surprising – a short term thermal resistance measurement using a calibrated hot box of hygroscopic systems may give an overrated R-value result. While we are familiar with the situation when movement of moisture towards the cold side of a material increased the apparent conductance of heat and reduced the thermal resistance, we are not familiar with the opposite situation. We have not seen any report on the situation when an air bypass brings moisture to the hygroscopic material and therby reduces heat flux entering the wall.

Let us now compare the measurements and calculations. If the apparent R18.5 (h.oF.ft2)/Btu shown in Table 2 is reduced by 14 % one obtains R15.9 (h.oF.ft2)/Btu. The nominal R-value for this wall based on adding the R-values of the individual components was 15.8 (h.oF.ft2)/Btu and this value was also derived from the HAM calculations when the air bypass was eliminated. Therefore, the nominal R-value for Wall 4 in our integrated testing and modeling program is 15.8(h.oF.ft2)/Btu.

3.3 Clear-wall R-values as measured in this test program

Figures 4 and 5 show a difference of approximately 14% between heat fluxes on the inside face of the thermal insulation and the average value of the wall as calculated by 2-D software. This agrees with values measured for this type of the wall by Thorsell and Bomberg (2008). Attributing the 14% difference as the effect of thermal bridges to the nominal one obtains clear-wall R-values (Table 6). 

Table 6 Nominal and clear-wall R-values, measured and calculated for Walls 1 and 4

Wall number

Nominal measured R-value

Nominal R value (though

insulation)

Clear-wall R value from 2-D

calculations

Difference, percent

1 15.0 14.9 12.8 <1

4 15.9 15.8 13.6 <1

3.4 Effect of standard air infiltration on the apparent R-values

50 Pa air pressure was applied in the weather chamber and the bottom orifice plate on the weather side and the top orifice plate on the room side were opened to create a long-path for air infiltration inside the wall cavities. The results are presented in Tables 7 and 8 for Walls 1 and 4 respectively. Table 7 Apparent R-value measured on Wall 1 during a standard air infiltration test

Wall Temp. Heat Apparent Nominal Nominal Reference Reduction

Page 10: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

10

location differ. oC

flux W/ m2

Rsi-value, (m2K)/W

Rsi-value, (m2K)/W

R-value (IP units)

R-value (IP units)

of R-value %

Top 34.0 10.77 3.16 2.52 14.31 15.6 8.3

bottom 33.1 12.39 2.67 2.03 11.53 14.5 20.7

Avg 15.05 14.5%

The above measurements demonstrate that cold air infiltration has a very significant effect (up to 21% reduction) at the bottom level close to where the air entered and a much smaller decline at the top of the wall where the air exited. Table 8 Apparent R-value measured on Wall 4 during a standard air infiltration test.

Wall location

Temp. differ,

°C

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Wall R-value

(IP units)

R-value measured in Step 1

Reduction R-value, percent

top 36.3 9.36 3.88 3.24 18.38 18.28 0

middle 35.7 9.19 3.88 3.24 18.38 15.84 -13.8

bottom 32.3 10.21 3.16 2.53 14.35 18.48 22.3

Avg. 17.53 4.5

We observe that heat flux near the bottom of Wall 4 increased about 22% while the value in the middle was reduced. Note that measurements performed under all steps consistently showed that heat flux in the middle location of this wall were higher than at the other two locations. Under air infiltration all three values of heat flux are closer to each other but our information is insufficient to comment on these observations.

3.5 Effect of doubling the area of air infiltration orifices on the apparent R-value

Table 9 Nominal R-value measured on Wall 1 during the high air leakage test

Wall location

Temp. differ.,

oC

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value (IP units)

Reference R-value (Step 1)

Reduction of R-value,

percent

Top 33.2 18.1 1.83 1.23 7.0 15.6 55

bottom 32.8 26.1 1.25 0.61 3.48 14.5 76

average 15.05 66

Table 10: Nominal R-value measured on Wall 4 during the high air leakage test

Page 11: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

11

Wall

location Temp. differ.,

oC

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value (IP units)

Reference R-value (Step 1)

Reduction. of R-value,

percent

top 36 12.8 2.81 2.17 12.3 18.28 32.7

middle 35 17.7 1.98 1.34 8.8 15.84 45.0

bottom 33.2 24.0 1.38 0.74 4.2 18.48 77.3

average 17.53 52

Reduction of thermal performance caused by the increased level of air leakage appears excessive but one must bear in mind that this is a calibration test for estimating the air flow – pressure relationships for the tested wall and the measured influence of that flow on thermal performance. At least two levels of air flow (hence airtightness) are necessary for a linear approximation of R-values as a function of air flow. Knowing or assuming the overall airtightness of the wall (construction quality test) one can select the reduction in R-value caused by air flow through the wall.

3.6 Effect of wetting on the apparent R-values

Step 3 required a change in the weather chamber from cold to hot and humid conditions (40 oC and 85 % RH). The standard opening of the orifices was used again and moist air entry lasted 5 days.

Table 11: Nominal R-value for wall 1 during the Step 3 of the test sequence

Wall location

Temp. differ.,

oC

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value (IP units)

Reference R-value (IP), Step1

Reduction R-value, percent

Top 16.7 12.2 1.37 0.73 4.14 15.6 73.4

bottom 16.0 16.6 0.96 0.32 1.82 14.5 87.6

avg 15.05 80

Table 12: Nominal R-value for wall 4 during the Step 3 of the test sequence

Wall location

Temp. differ,

oC

Heat flux W/

m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value (IP units)

Reference R-value (IP), Step1

Reduction R-value, percent

Page 12: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

12

top 17.4 9.0 1.9 1.16 6.59 18.28 64.0

middle 17.3 14.5 1.19 0.55 3.1 15.84 80.4

bottom 16.9 12.9 1.31 0.67 3.8 18.48 79.5

avg 17.53 75

Evidently the combination of reverse thermal gradient and moisture entry will cause a much higher cooling load than it was in case for dry cold air entry.

3.7 R-value after a period of standard exposure Step 4

Tables 13 and 14 show the R-value measured after a transition period of 1 day plus 5 days of drying. This selection is arbitrary because different walls will dry to a different extent depending on many factors. But, for comparative purposes it is sufficient to examine the drying ability of the wall assembly. Note that this test is not included in the energy performance concept but serves as primary means of model verification.

Table 13: Nominal R-value for Wall 1 during the Step 4 of the test sequence

Wall location

Temp. difference,

oC

Heat flux W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value

(IP units)

Reference R-value (IP), Step1

Top 32.2 10.2 3.16 2.52 14.3 15.6

bottom 31.6 10.8 2.92 2.28 12.9 14.5

average 2.4 13.6 15.05

Table 14: Nominal R-value for Wall 4 during the Step 4 of the test sequence

Wall location

Temp. difference

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value, (m2K)/W

Nominal R-value (IP units)

Reference-R-value* (IP), Step1

top 34 8.9 3.82 3.18 18.06 18.28

middle 32 13.95 2.29 1.65 9.37 15.84

bottom 31 7.7 4.03 3.38 19.19 18.48

average 2.74 15.54 17.53

*/ Note that the actual reference value is 15.8 (h.oF.ft2)/Btu but the one measured during Step 1 was 17.5(h.oF.ft2)/Btu.

Page 13: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

13

4. Discussion on Energy Performance R-value (REP) of Walls

These two papers (Part 1 and Part 2) are aimed at two distinctly different, yet complementary issues:

1) There is a need for an index to appropriately rate the thermal performance of wall systems. We gave that index the name Energy Performance R-value (Rep). Such an index, as explained in the introduction to Part 1, should include the effect of air and moisture infiltration on thermal performance.

2) There is a need to develop a methodology for verification of HAM models so that they could be used for prediction of the actual field performance of materials and construction systems

The approaches taken in these two papers constitute a first step in providing information addressing both issues, yet before we propose any solution we need to step back and make a few observations.

Firstly, currently in the Building Physics domain there is a sufficient capability for characterizing air flow paths and for measuring / calculating the effect of dry air flow on thermal performance of construction systems.

Secondly, currently in the Building Physics domain there is insufficient capability to characterize the ingress of moisture carried by air or the capability of calculating moisture removal under simultaneous heat and air flows. To build confidence in the use models we need to verify them by comparing with the experimental that are related to the rate of those processes versus time More research in this area is urgently required.

In the meantime it is proposed that a Rep indicator be used that only includes two effects:

1) the effect of thermal bridges (framing correction) 2) the effect of standard air flow conditions on apparent R-value

Using this concept we obtain results shown in Table 15.

Table 15: Summary results of measurements on Walls 1 and 4

wall Nominal R-value, hoFft2/Btu

Measured nominal R-value )

Effect of airflow, percent

R energy performance;

hoFft2/Btu

1 15.0 12.9 14.5 11.0

4 15.9 13.7 4.5 13.1

We also propose to use a concept of thermal insulation efficiency. Using the nominal R-value as 100 percent we find the efficiency of Wall 1 is 73.3 percent and that for Wall 4 is 82.3%. Thorsell and Bomberg (2008) showed that using continuous exterior insulation modifies the thermal

Page 14: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

14

bridging reduction correction and improves the thermal efficiency of walls. For example, if Wall 4 had been covered with a 1.5 inch layer of continuous spray polyurethane foam the multiplier against the nominal R-value increases from 0.857 to 0.918 and the total R-value becomes R =(R15.9x0.918x0.955+R9.0) i.e., R22.94 increasing the efficiency factor to (22.94/24.9) = 92%.

5. Concluding Remarks

The methodology proposed here develops an interim indicator that includes two measured effects:

• effect of thermal bridges (framing correction) • effect of standard air flow conditions on apparent R-value

Furthermore, extended information obtained from this test protocol will be used for the verification of HAM models. It has been concluded that use of these models for calculating effects of moisture is necessary and only when heat, air and moisture transfer models are adequately verified can they be used for this purpose. The verification must performed at both the material level and at the assembly level. The latter is one of the objectives of the proposed integrated methodology.

While it may be premature to include moisture effects in the test energy efficiency R-value indicator, it was shown that addressing effects of moisture on thermal performance is necessary when testing hygroscopic insulation materials. Finally, the extended information derived from Steps 3 and 4 will be used for verification of HAM models.

Only two walls are discussed in this paper. However, this study dealt with 8 different walls to examine differences between several foamed and fibrous insulations. The foremost important conclusion was that air ingress into wall cavity has significant effects on thermal performance of walls. Changes caused by air intrusion to typical frame-wall constructions varied from 1 or 2 % when airtight foam filled the whole cavity to 20% reductions when insulation was permeable for air and moisture, or a large unfilled air space existed in the cavity. Obviously these numbers were lower (e.g. 4.5 % and 14.5 % shown in this paper) when the wall construction were more airtight.

Page 15: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Integrated methodology for evaluation of energy equivalent R-value for BE, 2: Application to residential walls

Integrated methodology for evaluation of energy equivalent R-value for BE, 2: Application to residential walls

Thomas Thorsell Mark BombergPhD student Research Professor

11

Syracuse University - Building Energy Building Energy & Environmental Systems Laboratory & Environmental Systems Laboratory

Wall 1 (reference wall)with MFI, R13 batt )

Wall 1 (reference wall)with MFI, R13 batt )

22

Page 16: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Reference wall (left) and test wall in series 1 before drywall placement

Reference wall (left) and test wall in series 1 before drywall placement

33

3% unfilled corners – spacer for MFI batt, facer stapled on side of studs3% unfilled corners – spacer for MFI batt, facer stapled on side of studs

44

(b) For narrow cavity 1.5 x 1.5 inch triangle

a) For full sized cavity 2 x 2 inch triangle

Page 17: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Effect of air flow is different depending on the path

Effect of air flow is different depending on the path

55Series 1 – no gaskets /sealing to the subfloor or floor joist

Reference wall – initial testsReference wall – initial tests

First wall with window and siding First wall with window and siding ––results were unreliable because the results were unreliable because the test method was under developmenttest method was under developmentSecond wall Second wall –– window and siding window and siding removed, elremoved, el--outlet remains and no outlet remains and no gaskets on the perimeter of the wallgaskets on the perimeter of the wallCalibrated inlet / outlet introduced for Calibrated inlet / outlet introduced for measurement of air flow effects on measurement of air flow effects on the energy equivalent Rthe energy equivalent R--valuevalue

66

Page 18: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Details of test wall preparationDetails of test wall preparation

77

RH, T and air pressure sensors at different locations

WRB has an overlap made in accordance with mfg instructions

Air pressure taps on the inner side of the batt

Air pressure taps on the inner side of the batt

88

Page 19: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Airtight connection between tested wall and the chamberAirtight connection between tested wall and the chamber

99

Climatic chambers at SU are used for H, A, M, and Pollutant tests

Climatic chambers at SU are used for H, A, M, and Pollutant tests

1010

Page 20: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

8 different residential walls were tested but only 2 are reported

8 different residential walls were tested but only 2 are reported

Results obtained during test method Results obtained during test method development are not reporteddevelopment are not reportedPublished results represent typical Published results represent typical and best achievable on market place and best achievable on market place energy equivalent Renergy equivalent R--values with a values with a small modificationssmall modificationsWall 4 has continuous, permeable air Wall 4 has continuous, permeable air barrier on inner side and dense pack barrier on inner side and dense pack CFI. There is a small air gap between CFI. There is a small air gap between drywall and AB material.drywall and AB material.

1111

Definitions – R-value in this paperDefinitions – R-value in this paper

RR--value value in this paper in this paper represents the air represents the air to air resistance to heat flow. to air resistance to heat flow. It is an It is an inverse of the Uinverse of the U--value. value. This definition This definition is different from one used in ASHRAE is different from one used in ASHRAE to avoid several measurements on the to avoid several measurements on the wall surface to establish the mean wall surface to establish the mean surface temperature when multisurface temperature when multi--dimensional heat transfer causes large dimensional heat transfer causes large temperature differences. temperature differences.

1212

Page 21: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Definitions = Nominal and Local R-values

Definitions = Nominal and Local R-values

Nominal RNominal R--value = thermal resistance value = thermal resistance under steadyunder steady--state, unidirectional state, unidirectional heat flow through the center section heat flow through the center section of the insulation. of the insulation. Local RLocal R--value = a ratio between value = a ratio between temperature difference between temperature difference between indoor and outdoor air and heat flux indoor and outdoor air and heat flux measured at this point (The Rmeasured at this point (The R--value value of calibrated boundary layer is of calibrated boundary layer is already subtracted). already subtracted).

1313

Energy equivalent R-valueEnergy equivalent R-value

RR--value that includes effect of value that includes effect of multidirectional heat flow and air multidirectional heat flow and air flow measured under specified flow measured under specified conditions. Effect of moisture is not conditions. Effect of moisture is not included as it requires performing a included as it requires performing a HAM model calculations.HAM model calculations.

1414

Page 22: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Reference wall, step 1, nominal R-value

Reference wall, step 1, nominal R-value

1515

Wall location

Cold side, air oC

Warm side, air oC

Temp. difference oC

Heat flux

W/m2

App. Rsi-value, (m2K)/W

Local Rsi-

value, (m2K)/W

Local R-value

(IP units)

Top -14.9 18.9 33.8 10.06 3.36 2.72 15.44bottom 15.0 17.9 32.9 10.21 3.22 2.58 14.65

Avg 33.5 10.14 3.29 2.65 15.0515.05

This agrees well with R15.0 hoFft2/Btu obtained as the sum of R13 batt, OSB, drywall and surface film resistance

values.

Calculation of multidimensional heat flow effect

Calculation of multidimensional heat flow effect

This calculation is performed with the This calculation is performed with the heat flow model (we used two 2heat flow model (we used two 2--D D models to eliminate calculation errors)models to eliminate calculation errors)With 14.3% effect for this geometry With 14.3% effect for this geometry (see introductory paper to session 4) (see introductory paper to session 4) one obtains R12.9 hone obtains R12.9 hooFftFft22/Btu/Btu

1616

Page 23: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

1717

Wall locat.

Tempdiffer.

oC

Heat flux

W/ m2

App. Rsi,

(m2K)/W

Nominal Rsi,

(m2K)/W

Nominal R-value (IP units)

Refer. R-value (IP units)

Reduced R-value

by %

Top 34.0 10.77 3.16 2.52 14.31 15.6 8.3

Bott. 33.1 12.39 2.67 2.03 11.53 14.5 20.7

Avg 15.05 14.5%

Measurements in stage 2 (50 Pa)Measurements in stage 2 (50 Pa)

From nominal R-value multi-dimensional flow 14.3% and air flow 14.5 % total 28.8%. Energy equivalent R-value is 15.0 (1-0.288) = 10.7 hoFft2/Btu

Wall 4, step 1, measured nominal R-value

Wall 4, step 1, measured nominal R-value

1818

Wall location

Cold side, air

oC

Warm side, air

oC

Temp. difference

oC

Heat flux W/m2

Apparent Rsi-value, (m2K)/W

Local Rsi-value, (m2K)/W

Local R-value (IP

units)

top -17.0 -19.0 36.0 8.9 4.04 3.4 19.31middle -16.6 18.9 35.5 10.15 3.50 2.85 16.22bottom -15.1 17.8 33.9 8.15 4.16 3.52 19.99

Average 35.5 9.07 3.9 3.26 18.51

top -17.0 19.1 36.2 9.38 3.86 3.22 18.28

middle -16.7 19.0 35.7 10.41 3.43 2.79 15.84

bottom -15.1 18.0 33.1 8.50 3.89 3.25 18.48

Average 3.73 3.09 17.53

Repeated test

Page 24: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

Heat flux measured in C518 apparatus on sealed , wet specimen vs calculated oneHeat flux measured in C518 apparatus on sealed , wet specimen vs calculated one

1919For moisture characteristics used as input consult other papers

Calculated heat flux during the test in climatic chamber caused by moistureCalculated heat flux during the test in climatic chamber caused by moisture

2020

g

Time in [h]35030025020015010050

Hea

t flu

x (c

ondu

ctio

n) in

[W/m

2] -10-11-12-13-14-15-16-17-18-19

HFT_studHF_wholeHFT1

Maximum, minimum and mean values of heat flux vs testing time

Page 25: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

The test as above but AB material on inner side is also a water vapor retarder

The test as above but AB material on inner side is also a water vapor retarder

2121

Time in [h]35030025020015010050

Hea

t flu

x (c

ondu

ctio

n) in

[W/m

2] -11-12-13-14-15-16-17-18-19-20-21

HF_wholeHFT1HFT_stud

With the mean heat flux calculated here, the nominal R-value is 15.9and the one expected from material testing is 15.8 hoFft2/Btu

Effect of air flow and energy equivalent R-value

Effect of air flow and energy equivalent R-value

2222

Wall location

Temp. differ,

°C

Heat flux

W/ m2

Apparent Rsi-value, (m2K)/W

Nominal Rsi-value,

(m2K)/W

Wall R-value

(IP units)

R-value measured in Step 1

Reduction R-value, percent

top 36.3 9.36 3.88 3.24 18.38 18.28 0mid 35.7 9.19 3.88 3.24 18.38 15.84 -13.8bott 32.3 10.21 3.16 2.53 14.35 18.48 22.3Avg 17.53 4.5

For wall 4 combined effects of thermal bridges and air flows is 18.8 i.e.10% less than for wall 1. Energy equivalent R-value is 15.9 (1-0.188) =

12.8 hoFft2/Btu

Page 26: ENERGY PERFORMANCE R-VALUE: PART 2, EXAMPLES ......performance evaluation. 6) Energy performance R-value = the clear-wall R-value that accounts for effects of air and moisture flows

ConclusionsConclusions

Demonstration of the proposed test Demonstration of the proposed test method show a reduction from the method show a reduction from the nominal R15 to nominal R15 to energy equivalent energy equivalent R10.7 hR10.7 hooFftFft22/Btu/BtuFurthermore, different air flow effect Furthermore, different air flow effect causes a difference about 10% in the causes a difference about 10% in the energy equivalent Renergy equivalent R--valuevalue..The proposed test method identified The proposed test method identified transient effect of moisture, an important transient effect of moisture, an important issue in verification of HAM models.issue in verification of HAM models.

2323