Energy Criteria Presentation-GRIHA
description
Transcript of Energy Criteria Presentation-GRIHA
-
G R I H A
Energy Criteria in GRIHA
Pradeep Kumar Senior Fellow & Associate Director
Centre for Research on Sustainable Building Sciences
TERI, New Delhi
-
G R I H A
Room Temperature :
Up to 38 0 C
Annual Energy Consumption:
45 kWh/m2-yr
Non-Air conditioned Buildings
-
G R I H A
Room Temperature :
24 0 C
Annual Energy Consumption:
200 kWh/m2-yr
Air conditioned Buildings
-
G R I H A
Room conditions
26~28 0 C
Room conditions
24 0 C
Annual Energy Consumption
200 kWh/m2-yr
Annual Energy Consumption
< 90 kWh/m2-yr
Challenges in Building Design
-
G R I H A
Room conditions
26~28 0 C
Annual Energy Consumption
90 kWh/m2-yr
Energy Efficient Building
45 45
-
G R I H A
Efficiency in Buildings: how?
Efficient building
Regulation
Analysis
Inefficient buildings
-
G R I H A
Design Standards
Energy Efficient Building Design: How?
Energy Standards
Regulatory Framework
Design Standards
Energy Standards
Design Standards
Regulatory Framework
Energy Standards
Design Standards Design Standards
Energy Standards
Design Standards
Regulatory Framework
Energy Standards
Design Standards
-
G R I H A
Energy Criteria in GRIHA
Criterion 06: Outdoor Lighting System
Criterion 13: Indoor Lighting System
Criterion 14: Overall Energy Performance
Criterion 18: Renewable energy Utilization
Criterion 19: Solar hot water system
-
G R I H A
GRIHA-Criterion 6
Objective Enhance outdoor lighting system efficiency and use renewable energy system for meeting outdoor lighting requirements
-
G R I H A
Street Lighting/Security Lighting
High Pressure
Sodium Vapour
Metal Halide
High Pressure
Ceramic Discharge
Metal Halide
-
G R I H A
Road way lighting
High Pressure
Sodium Vapour
High Pressure Metal
Halide
High Pressure
Ceramic Discharge
Metal Halide
Compact
Fluorescent Lamps
-
G R I H A
Garden Lighting
High Pressure Sodium
Vapour (HPI)
High Pressure Metal Halide
(MH)
High Pressure Ceramic
Discharge Metal Halide
(CDM)
Compact Fluorescent Lamps
(CFL)
-
G R I H A
Parking Lighting
High Pressure
Sodium Vapour
High Pressure Metal
Halide
Fluorescent Lamps
Compact
Fluorescent Lamps
-
G R I H A
Luminous Efficacy
Light output
(Lumens)
Electrical input (W)
Luminous Efficacy = Light output/Electrical input (lm/W)
-
G R I H A
Luminous Efficacy - CFL
Luminous Efficacy : 900/(13+5) = 50 lm/W
5 W
13 W
18 W
900 lm
-
G R I H A
Luminous Efficacy of TLD with HPF
Luminous Efficacy : 2450/(36+15) = 48 lm/W 15 W
36 W
51 W
2450
lm
-
G R I H A
Luminous Efficacy of TLD with HF
Luminous Efficacy : 2450/(36+2) = 65 lm/W
2 W
36 W
38 W
2450 lm
-
G R I H A
Luminous Efficacy of T5
Luminous Efficacy : 2900/(28+2) = 97 lm/W
2 W
28 W
38 W
2900 lm
-
G R I H A
Efficacy of Metal halide with HPF
Luminous Efficacy : 20000/(250+24) = 73 lm/W
24 W
250 W
274 W
20000 lm
-
G R I H A
Efficacy of Metal halide with HF
Luminous Efficacy : 20000/(250+10) = 77 lm/W
10 W
250 W
260W
20000 lm
-
G R I H A
Efficacy of Sodium Vapor with HPF
Luminous Efficacy : 25000/(250+26) = 91 lm/W
26 W
250 W
276 W
25000 lm
-
G R I H A
Commitment-1
Luminous efficacy of external light sources used
for outdoor lighting shall equal or exceed as
specified minimum allowable luminous efficacy
-
G R I H A
Lighting Source Minimum allowable luminous
efficacy (lm/W)
CFL (Compact fluorescent
lamps)
50
FL( fluorescent lamp) 75
MH (metal halide) 75
HPSV (high pressure
sodium vapour) lamp
90
Minimum allowable values of luminous efficacy of lamps for outdoor lighting
-
G R I H A
Commitment-2
All outdoor lighting to be fitted with an automatic on/off switch
-
G R I H A
Commitment-3
A minimum of 25% of the total number or 15% of the total connected load of outdoor lighting fixtures (whichever is higher) to be powered by solar energy
-
G R I H A
Compliance
The documents of Luminous efficacy (lm/W) of each type
of lamp used in outdoor lighting.
Outdoor lighting layout with manufacturers details of lamps, ballasts, luminaires, and automatic controls with
wiring diagram and placement of automatic switches for
outdoor lighting.
Demarcate solar lighting systems for outdoor lighting in
outdoor lighting layout and give details of the same.
-
27 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Appraisal
Luminous efficacy of 100% of lamps used in outdoor lighting meets
the GRIHA recommended corresponding values
1 point
Automatic controls for 100% of outdoor lights
1 point
Load of 25% of total number of light fixtures or 15% of the total
connected outdoor lighting load whichever is higher on RE system
1 point
-
28 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Example Outdoor lighting layout
-
29 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Example: Outdoor lighting layout
-
30 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Example: Outdoor fixtures details
-
31 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Product Catalogues to Calculate Efficacy
-
32 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Exercise Efficacy Calculation
Sl.
No.
Lighting Type Type of
Lamp
Lamp
Wattage
(W)
Lumen
Output
(lm)
Ballast
Power
Loss (W)
Total
Wattage
(W)
Luminous
Efficacy
(lm/W)
GRIHA
Luminous
Efficacy
(lm/W)
Remark
1. Street Light HPSV 70 6600 15
2. Street Light HPSV 150 17000 21
Luminous Efficacy = Lamp Lumen Output
Lamp Input Power + Ballast Power Loss
-
33 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Commitment-1: Luminous Efficacy Calculation
S No. Lighting
Type
Type of Lamp Wattage of
lamp (W)
Lumen
Output (lm)
Ballast
Power loss
(W)
Total
Wattage
(W)
Luminous
Efficacy
(lm/W)
GRIHA-
Luminous
Efficacy
(lm/W)
Remark
1
Gate light Metal Halide (MH)
70 5500 17 87 63 75
Efficacy is less than
recommended-need to
be changed
2
Street Light Metal Halide (MH)
150 12100 25 175 69 75
Efficacy is less than
recommended-need to
be changed
3
Landscape
light
Ceramic discharge
metal halide
(CDM) 70 6600 17 87 76 75
GRIHA compliant
4
Inground
tree
uplighter
Ceramic discharge
metal halide
(CDM) 70 6600 17 87 76 75
GRIHA compliant
5
Parking post
top
Ceramic discharge
metal halide
(CDM) 70 6600 17 87 76 75
GRIHA compliant
6
Tubelights in
parking
T-5 lamps
28 2900 4 32 91 75
GRIHA compliant
-
34 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Case study
100 m
80 m
Ga
rde
n /P
ark
4
0 m
N
` Road way
Garden /Park
Building Block
Path ways
-
35 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Outdoor Lighting Controls
Timer Form:Analog Timer 1/16 DIN IP54, 48x48 mm Contact Current, Ratings:5 A @ 250 VAC DPDT Mounting Type:Panel, Surface, DIN 8 pin base Power Rating:1.3 W Led Status indicator:Time status and power supply Temperature, Operating,:Maximum 55 C Minimum -10 C Timer Type:Solid State Timing Function:Selectable Multi-Function Timing Mode:ON-Delay Timing Range:0.1 Sec. to 300 hr Voltage, Input:12 to 48 VDC or 24 VAC Manual Timer Control
Non-Volatile Memory 3 Year Battery Backup Switch Single-pole or 3-way (Multi-way) Compatible Switch Rating
Resistive (heater): 20 Amp, 120-277 VAC Tungsten (incandescent): 15 Amp, 120 VAC; 6 Amp, 208-277 VAC
Ballast (fluorescent): 16 Amp, 120-277 VAC Motor: 1 H.P., 120 VAC; 2 H.P., 240 VAC; 4 Amp, DC Loads:12 VDC; 2 Amp, 28 VDC
Programmable Timer
Control
-
36 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Outdoor Lighting Controls
PIR (Passive Infrared) Sensor
Auto switch ON of light at dusk Auto switch OFF at dawn or after selected duration
No clock setting or clock tuning Direct switching load up to 3kw single phase Wide operating AC supply voltage (185 to 275 V)
ED10MRA- 365-Day NEMA 1 Indoor or panel mount
4 Circuit - SPST - 8 Amps - 120/208/240/Volt
365-Day Electronic programmable
120/208/240/Voltand DC operation 12, 24 VDC Number of Circuits: 4 With control inputs NEMA 1 Indoor
Astronomical Switch
-
37 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Case study
100 m
80
m
Ga
rden
/Pa
rk
40
m
N
` Road way
Garden /Park
Building Block
Path ways
-
38 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Example - Commitment-3
Street lights 150 W HPSV 10 Nos. 1.75 kW
Driveway lighting 70W CDM 10 Nos. 0.87 kW
Garden lighting 18 W CFL 20 Nos. 0.50 kW
Total lighting load 3.12 kW
15% of total lighting load 0.468 kW
Total No. of fixtures 40
25% of total fixtures 10
Load of 10 fixtures 0.25 kW
Lighting load on RE system 0.468 kW
-
39 II G r e e n R a t i n g f o r I n t e g r a t e d H a b i t a t A s s e s s m e n t II
Exercise - Commitment-3
Street lights 150 W HPSV 12 Nos. 2.1 kW
Total lighting load 2.1 kW
15% of total lighting load 0.315 kW
Total No. of fixtures 12
25% of total fixtures 3
Load of 3 fixtures 0.53 kW
Lighting load on RE 0.53 kW
-
G R I H A
Criterion 13: Indoor lighting design
Objective
Indoor lighting shall provide required visual
comfort in all the spaces in a building
-
G R I H A
TCS306/236M6HPF
General practice
-
G R I H A
Green Practice
-
G R I H A
Commitment: Visual Comfort
Lighting levels in each space of proposed indoor
lighting design meet the required visual comfort as
recommended in table 4, Part 8, Building Services,
section 1: Lighting & Ventilation of NBC-2005
-
G R I H A
NBC-2005 recommended lighting levels
-
G R I H A
Analysis tool
Lumen designer
Calculux
Dialux
AGI 32
-
G R I H A
Non AC spaces: 0.7-
0.75
AC spaces: 0.8-0.95
Maintenance Factor
-
G R I H A
NBC-2005: Recommended Working Plane Height
In case precise height and
location of the task is not
specified, the recommended
working plane is horizontal and at
a height of 850 mm
-
G R I H A
Roof:0.7
Wall:0.5
Floor:0.2
Surface Reflectance
-
G R I H A
Luminaire
TCS 306 Model no.
Lamp 36W Fluorescent Tube Lamp
HF Electronic ballast
Lumen output 2450 lm output
Lamp per Fixture 2x36W TLD
TCS306/236 HF NORMAL 2xTLD 36W
-
G R I H A
Luminaire
TBS 669 Model no.
Lamp 28W T5 lamp
D6 Type of louver
HF Electronic ballast
Lumen output 2900 lm output
Lamp per Fixture 2x28W T5
TBS669/228 D6 HF 2x 28W T5
-
G R I H A
Lamp Efficiency
1. Lamp Type Lumen Wattage Efficacy
2. TLD 36W/ HFP 2450 lm 46.5W (36+10.5) 53 lm/W
3. TLD 36W/ HF 2450 lm 38W (36+2) 64 lm/W
4. Trulite 36W/ HFP 3250 lm 46.5W (36+10.5) 70 lm/W
5. Trulite 36W/ HF 3250 lm 38W (36+2) 86 lm/W
6. CFL 36W/ HF 2900 lm 38W (36+2) 76 lm/W
7. T5 28W/ HF 2900 lm 30W (28+2) 97 lm/W
-
G R I H A
Lighting simulation results
-
G R I H A
Compliance
Floor
Level
Room
/ Area
Room
Dimen
sion
(L*W)
Luminaire
used
No. of
luminaires
Calculated
Average
Lighting
Levels (lux)
NBC-2005
illuminance
(lux)
Remarks
First
Floor
Office 12.5m
X8m
TBS
669/228
8 337 300 GRIHA
Compliant
Produce lighting level analysis results in
prescribed format
-
G R I H A
If lighting level compliance is shown for all the
indoor spaces
Appraisal
2 Points
-
G R I H A
ECBC Mandatory Requirements (Automatic lighting shutoff)
Buildings Area> 500 m2
Interior lighting system shall be equipped with automatic control device
Applicable to only daytime occupied buildings
-
G R I H A
Automatic lighting shutoff contd.
All offices spaces < 30 m2, shall be equipped with occupancy sensors
All meeting rooms, conference rooms, class rooms, storage shall be equipped with occupancy sensors
-
G R I H A
Automatic lighting shutoff contd.
Programmable timer with independent program schedule for areas < 2500 m2 and not more than one floor or
Occupancy sensor with manual override
-
G R I H A
Space control
Each space shall have one control device controlled manually or automatically. Each control device shall control a maximum of 250 m2 for a space less than or equal to 1000 m2 and a maximum of 1000 m2 for spaces having greater area
-
G R I H A
Daylight control
Control device shall control only the luminaires entirely within day lighted area. Shall reduce the light output by 50%.
Luminaries in day lit area> 25m2 shall be equipped with either a manual or automatic control device.
-
G R I H A
Criterion 14 Optimize energy performance of the building
within specified comfort limits
-
G R I H A
Thermal comfort in AC spaces
DB 23-26 C
RH 50-60 %
DB 23-26 C
RH 55-60 %
DB 23-26 C
RH 50-60 %
DB 23-26 C
RH 50-60 %
-
G R I H A
GRIHA Energy Performance Benchmark for
AC buildings Office
School
Hospital
Hotel
10 hr occupied For Mumbai Climate, EPI
-
G R I H A
DBT (o
C) Relative humidity (%)
30 40 50 60 70 80 90
(1) (2) (3) (4) (5) (6) (7) (8)
28 * * * * * * *
29 * * * * *
0.0
6
0.1
9
30 * * *
0.0
6
0.2
4
0.5
3
0.8
5
31 *
0.0
6 0.24
0.5
3
1.0
4
1.4
7
2.1
0
32 0.2
0.4
6 0.94
1.5
9
2.2
6
3.0
4 **
33 0.77
1.3
6 2.12
3.0
0 ** ** **
34 1.85
2.7
2 ** ** ** ** **
35 3.2 ** ** ** ** ** **
Thermal comfort limits
Indoor temperature within 33 o C and RH 70% is considered
comfortable
Dry bulb temperature (o C) Relative humidity (%) Air velocity (m/s)
Thermal Comfort in Non-AC spaces
-
G R I H A
Whole building performance analysis-
Non AC buildings
-
G R I H A Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
-
G R I H A
Comfort Hours
Monthly distribution of discomfort hours
0
100
200
300
400
500
600
700
800
Month
hour
s
comfortable uncomfortable
uncomfortable 53 135 365 512 609 370 176 93 194 281 84 65
comfortable 691 536 379 208 135 350 568 651 526 463 636 679
jan feb mar apr may jun jul aug sep oct nov dec
-
G R I H A
Appraisal
Compliance with mandatory requirements of Energy Conservation building code (ECBC-2007)
Points
6
Energy consumption index and the thermal criteria are fully met.
Every 10% reduction fetch additional 2 points with maximum up to 10 points.
2 10
Total GRIHA Points 16
1
2
-
G R I H A
GRIHA Performance Benchmark for
Non AC buildings
Comfort conditions shall be met 60% in
Mumbai Climate
Climate Classification
EPI
(kWh/m2/year)
EPI
(kWh/m2/year)
Day time
occupancy
24 hours
Occupancy
5 Days a week 7 days a week
For Mumbai Climate 25 100
-
G R I H A
EPI calculation for partly AC building
Type of space Area (m2)
GRIHA Energy Consumption benchmark (kWh/m2/year)
Predicted Energy Consumption (kWh/m2/year)
Air Conditioned A1 140 E1
Non Air Conditioned A2 25 E2
Benchmark Building Energy consumption (kWh/m2/year) =
(140*A1+25*A2)/(A1+A2)
Actual Building Energy Consumption (kWh/m2/year) =
(E1*A1 + E2*A2)/(A1+A2)
% saving = (Benchmark Actual) * 100 / Benchmark
-
G R I H A
EPI calculation : Example
Building type : Office
Occupancy : 24*7
Air conditioned area : 4000 m2
Non air-conditioned area : 4250 m2
Predicted energy performance of building: 197 kWh/m2
Building energy performance benchmark calculation
GRIHA bench mark for AC spaces : 450 kWh/m2-yr
GRIHA bench mark for Non AC spaces: 100 kWh/m2-yr
GRIHA benchmark : (450*4000 + 100*4250)/(4000+4250) = 270 kWh/m2-yr
-
G R I H A
EPI calculation : Example
% Reduction from the benchmark EPI = (270-197)*100/270
= 27%
Total Points Scored = 6+2+4
= 12
-
G R I H A
EPI calculation : Case Study
Case Study - A 5 storey BPO office building is located in Delhi.
Typical floor plate area of the building is 10000 sqft. 40% of the
total built-up area of the building is non air-conditioned and
remaining 60% is air-conditioned. Energy consultant with the
help of simulation predicted that annual electrical energy
consumption will sum up to 2000000kWh for the facility.
Predicted energy consumption for various energy systems are
Lighting 35% (The LPD ratio of Non AC and AC space is 2:3)
Equipment 25%
HVAC 40%
It has been predicted that in non air-conditioned spaces comfort
can be achieved for 7900 hours out of 8760 hours in a year.
-
G R I H A
EPI calculation : Case Study
Determine the following
1. Building GRIHA benchmark EPI
2. Predicted EPI for the building
3. Is the project eligible for GRIHA?? If yes how many
points will be scored?
-
G R I H A
Follow Compliance - Mandatory
Requirements of ECBC-2007
Building
Envelope
Lighting
Electrical
Chiller
-
G R I H A
Envelope-Glazing Solar Heat Gain Coefficient
SHGC as indicated by
daylight analysis
-
G R I H A
Distribution Transformer
Transfo
rmer
type
Rating
(kVA)
Max. Losses
at 50%
loading (kW)
Max. Losses at
100% loading
(kW)
Dry
type 1000 5.3 12.8
Oil filled 1000 3.45 11.35
Max. allowable losses for dry
type/Oil filled at highest voltage
and at 50% & 100% load shall not
be more than whatever is
specified in ECBC (IS 2026: Part
11, 2007)
-
G R I H A
Electrical Motors
Motors of 0.375 kW to 50 kW
rating expected to operate
more than 1500 hrs/year
and
Motors of 50 kW rating and
above expected to operate
more than 500 hrs/year
shall have minimal acceptable
nominal full load efficiency as
mentioned in IS-12615
-
G R I H A
Electrical Motors IS 12615
-
G R I H A
ECBC-Electrical-Mandatory Requirements
Power factor shall be maintained between 0.95
Lag and unity at the point of connection
Services>1000 kVA, shall have permanently
Installed energy meter to record, kVA, kWh
V,I,PF and THD
Distribution losses in electrical cables
shall not exceed 1% of the total power
usage
-
G R I H A
Chiller efficiency COP
Chiller cooling capacity : 120 TR
Input kW of Compressor : 96
Specific energy ratio : 96/120 = 0.8 kW/TR
Coefficient of performance (COP): 3.51/0.8 = 4.4
-
G R I H A
ECBC-HVAC
Size of chiller COP
Less than 150 TR 2.9
Greater than equal
to 150 TR 3.05
HVAC
Chiller Efficiencies
Air Cooled Chiller Water Cooled Chiller
Size of chiller COP
Less than 150 TR 5.8
>=150 TR < 300
TR 5.8
>= 300 TR 6.3
Centrifugal Screw
Size of chiller COP
Less than 150 TR 4.7
>=150 TR < 300
TR 5.4
>= 300 TR 5.75
-
Energy performance optimisation using Visual DOE
-
How Simulation is done
-
Analysis Tool for AC spaces
Show that utilization of energy systems in a
building, under a specified category, is less than the
benchmarked energy consumption figure, through a simulation
exercise.
-
Whole Building Simulation
Simulation software used for whole building performance
analysis
Performs hourly analysis for the whole year (8760 hours)
Simulate AC buildings and predict annual energy
consumption
1
2
3
-
Result
Pictorial View of the final simulation results
-
General Case Study
-
Building Type
Location Delhi
Office Building
Fully Air conditioned
Office Occupancy (10hrs)
-
Building Details
125 ft 80 ft
11 ft No of floors -8 Total Area 80000 sqft
W-1
W-2
-
Building details
W-1 W-2
W-1 100 ft * 6 ft
50 ft * 6 ft W-2
WWR 69%
-
Coordinates
0,0 125,0
125,80 0,80
N
W-1
W-2
-
Building Input File
-
Wall construction
9 inch Brick Wall
1 inch cement plaster on both sides
U value- 0.32 btu/h/ft2/deg F
-
Roof Construction
8 inch Heavy wt undried
concrete
4 inch brick coba
1 inch brick tile
1 inch cement plaster
U value- 0.4 btu/h/ft2/deg F
-
Glass
6 mm Single Clear
U value- 1.087 btu/h/ft2/deg F
SHGC -0.815
-
Building Internal loads
Occupancy
Lighting
Equipment
Infiltration
Fresh Air
40 Persons
2 W/ft2
1 W/ft2
0
15 CFM/Person
-
Minimum Supply Air
Temperature 55 deg F
EER (Energy Efficiency Ratio) 7
HVAC system
-
Result
EPI - =(1820592-233056)/7434
213 kWh/m2/yr
-
Impact of Low Energy
Strategies
-
Impact of Orientation
Favorable orientation, Roof shading, window shading 10
-
Energy Simulation screen shot
-
Base Case 225
5 % Best orientation 214
Impact on Cooling load (TR)
Impact of Orientation
Base Case 213
3 % Best orientation 207
Impact on EPI (kWh/m2/yr)
-
Impact of lower WWR
Base Case 225
20 % Optimized WWR 180
Impact on Cooling load (TR)
Base Case 213
14 % Optimized WWR 184
Impact on EPI (kWh/m2/yr)
-
Building Envelope impact
on Energy Performance
-
Energy Efficient Envelope-Wall
9 inch Brick Wall
+ 1 inch
cement plaster on both sides
U Value- 0.32 btu/f2/hr/degF
9 inch Brick Wall
+ 1 inch plaster on both sides
+ 3 inch
Insulation
U Value- 0.07 btu/f2/hr/degF
Conventional case Energy Efficient Case
WALL
-
Energy Efficient Envelope-Roof
U Value- 0.40 btu/ft2/hr/degF
U Value- 0.07 btu/ft2/hr/degF
Conventional case
Energy Efficient Case
Roof
4 inch brick coba
1 inch plaster
+
1 inch brick tile +
8 inch RCC
4 inch brick coba
1 inch plaster
+
1 inch brick tile +
8 inch RCC
3 inch insulation
+
-
Energy Efficient Envelope-Glass
U Value- 1.087 btu/ft2/hr/degF
SHGC 0.815 U Value- 0.58 btu/ft2/hr/degF
SHGC 0.25 for WWR
-
Impact of Efficient Envelope
Base Case 225
32 % Efficient Envelope 153
Impact on Cooling load (TR)
Base Case 213
24 % Efficient Envelope 163
Impact on EPI (kWh/m2/yr)
-
Lighting System impact on
Energy Performance
-
Energy Efficient Lighting
LPD 21 W/m2
T-12 FTL with copper
choke
Wattage - 40+15=55 W
Conventional case Energy Efficient case
T-5 FTL with electronic
choke
Wattage - 28+2=30 W
LPD 10.8 W/m2
-
Integrating Artificial Lighting with Day lighting
T-5 FTL with electronic
choke
Wattage - 28+2=30 W
Continuous Dimming
sensor
LPD 10.8 W/m2 LPD 7 W/m2
-
Impact of Efficient Lighting system
Base Case 225
9% Efficient lighting system 204
Impact on Cooling load (TR)
Base Case 213
27% Efficient lighting system 156
Impact on EPI (kWh/m2/yr)
-
HVAC
System impact on Energy
Performance
-
Heat gain Optimization
Heat gain from roof
Heat gain from walls
Heat gain from glass/daylight from
glass
Heat gain from infiltration
Heat gain from equipment/lighting/pe
ople
23-26 deg C
65%RH
Building Envelope optimization
Building Lighting system optimization
Inside temperature Optimization
Ventilation Rate optimization
-
Inside Temperature Conditions
DB 23-26 C
RH 50-60 %
DB 23-26 C
RH 55-60 %
DB 23-26 C
RH 50-60 %
DB 23-26 C
RH 50-60 %
Follow
NBC 2005
-
Inside Temperature optimization
460
480
500
520
540
560
580
23
C/5
0%
23
C/6
0%
24
C/5
0%
24
C/6
0%
25
C/5
0%
25
C/6
0%
26
C/5
0%
26
C/6
0%
1deg C decrease in temperature increases cooling load by 3.5%
-
Pre cooling of Fresh Air
Energy Recovery
Wheel
Supply air
Outside air damper
Outside air
Return air
Filters
Cooling demand
Reduction 16%
-
Building Cooling Demand (TR)
Building Type Cooling Demand
Small Buildings 150 TR and 300 TR
-
Coefficient of Performance of chillers
Rated cooling capacity: 400 TR
Rated motor kW: 252 kW
IKW/TR: 0.63
COP
(3.517/IKW/TR):5.6
-
Equipment Selection
Small
Buildings
Cooling
demand
-
Equipment Selection
Medium
Buildings Cooling demand >150 TR & 150TR &
-
Equipment Selection
Large
Buildings Cooling demand >300 TR
COP = 3.05
Water cooled chiller Air cooled chiller
COP= 6.3
Centrifugal Chillers Screw Chillers
COP= 5.75
Centrifugal Chillers
COP= 6.3
Centrifugal Chillers
-
Controls
Variable Frequency Drives on motors
of Fans and Pumps
-
Impact of Efficient HVAC system
Base Case 225
0% Efficient HVAC system 225
Impact on Cooling load (TR)
Base Case 213
27% Efficient HVAC system 155
Impact on EPI (kWh/m2/yr)
-
Impact of all combined measures
Base Case 225
51% All combined measures 109
Impact on Cooling load (TR)
Base Case 213
63% All combined measures 80
Impact on EPI (kWh/m2/yr)
-
Summary-Optimized Heat Load
Heat load (TR) Optimization
Base Case 225 TR
9 % Optimized Envelope as per ECBC
Optimized lighting
All
180 TR
109 TR
204 TR 17 %
42 %
20 % Optimized WWR
153 TR
5 % Orientation 214 TR
-
Summary Optimized Energy Performance
Base Case 214
24 % Optimized Envelope as per ECBC
Optimized lighting
All
184
80
156 27 %
63 %
14 % Optimized WWR
163
3 % Orientation 207
Optimized HVAC 155 27 %
EPI (kWh/m2/yr)
-
THANK YOU
-
G R I H A
Renewable Energy Integration in Buildings
II T h e E n e r g y a n d R e s e a r c h I n s t i t u t e II N e w D e l h i II
-
G R I H A
Criterion- 18: Renewable energy
utilization
OBJECTIVE
To use renewable sources in buildings to reduces
the use of conventional/ fossil-fuel-based energy
resources
-
G R I H A
Fuel cell
Renewable Energy sources
RE Wind Energy Solar Energy
Bio Energy Geothermal Energy Water energy
-
G R I H A
Photo Voltaic System
-
G R I H A
Solar cell Types
-
G R I H A
PV Module Efficiency
-
G R I H A
System configurations
Stand alone systems
Grid connected power plants
Home lighting
Street lights
Water pumps
Garden lights
Illuminated hoardings
Hybrid Power system
Building Integrated Photovoltaic (BIPV)
-
G R I H A
Off-grid PV system (Stand alone system)
-
G R I H A
On grid PV system
-
G R I H A
Centralized PV system
Source : www.retscreen.net
-
G R I H A
Solar energy based external lighting
-
G R I H A
Hybrid System
-
G R I H A
BIPV
Skylight
Window
Roof
-
G R I H A
Commitment-Mandatory
Rated capacity of proposed renewable energy system is equal to or more than 1% of connected internal lighting load & HVAC load of the building
1 % of connected load
-
G R I H A
HVAC load details
AC
Machine
4*161 =644 kW
Primary
Pump
4*15 = 60 kW
Secondary
Pump
4*22.5 = 90 kW
Condenser
Pump
4*37.5=150 kW
Cooling
Towers
4*15 = 60 kW
Air handling
units
500 kW
Total HVAC load 1504 kW
-
G R I H A
Internal lighting load details
Ground
floor lighting
71.47 kW
1 to 5
Floors
lighting
386.1 kW
Cafeteria
lighting
56.61 kW
Total internal lighting
load
514.18 kW
-
G R I H A
Renewable Energy System Sizing
Total internal lighting load 514.18 kW
Total HVAC load 1504 kW
Total load 2018.18 kW
1% of Total load 20.18 kW
Min size of PV system 21 kWp
-
G R I H A
Roof Area Needed in Square meter
PV
Module
Efficiency
(%)
PV Capacity Rating (Watts)
100 250 500 1,000 2,000 4,000 10,000
4 2.8 7 13.9 28 56 112 279
8 1.4 3.5 7 14 28 56 139.5
12 0.9 2.3 4.6 9.5 18.6 37 93
16 0.7 1.9 3.7 7.5 15 30 74.5
PV systems are classified by their rated power output (the peak power they produce
when exposed to solar radiation of 1000 watts per square meter at a module
temperature of 25C
For example, 1,000 watts capacity PV system with 12% efficiency, you need ~10
square meter of roof area. Also 1kWp generates 1400 kWh annually
Source: www.eere.energy.gov
-
G R I H A
18.3 Appraisal
PV capacity of 21kWp with 12%
efficiency Generates annually
(21 x 1400) = 29400 kWh
Annual lighting Energy Consumption
= 1388329 kWh
-
G R I H A
18.3 Appraisal
Case PV sizing
(kWp)
Energy generated
through PV system
(kWh/yr)
% offset of
annual
lighting
energy
consumption
Points
Mandatory
case
21 =21 x 1400
= 29400
1
Case1 50 =50 x 1400
=70000
5 % 1+1
Case2 100 =100 x 1400
=140000
10 % 1+2
Case3 200 =200 x 1400
=280000
20 % 1+3
Case4 300 =300 x 1400
=420000
30% 1+4
Annual lighting Energy Consumption = 1388329 kWh
-
G R I H A
18.1 Commitment
Atleast 1% of internal lighting and space conditioning connected loads
of building met from renewable energy sources (solar, wind, biomass,
fuel cells, and so on)
Feasibility of the proposed renewable energy system to be verified by
the competent authority.
-
G R I H A
18.2 Compliances
Detailed listing of connected load for lighting /HVAC
Calculation of connected load for lighting and energy requirement for
the same.
List of all loads that are being powered by renewable energy system
sources (other than lighting load) and their energy requirements.
Design calculations for renewable energy system sizing and
performance including annual energy generation.
Cut sheets of renewable energy systems with necessary details.
Drawings in CAD format to show location of renewable energy
systems.
-
G R I H A
18.2.2 Calculation of connected load for lighting and energy
requirement for the same.
-
G R I H A
18.2.4 Design calculations for RE system
and
performance including annual energy
generation.
-
G R I H A
18.2.5 Cut sheets of renewable energy
systems with necessary details
-
G R I H A
18.2.6 Drawings in CAD format to show
location of renewable energy systems.
-
G R I H A
18.3 Appraisal
1% of internal lighting and space conditioning connected
loads or its equivalent in the building shall met through
renewable energy system (1 point) (mandatory)
Rated capacity of proposed renewable energy system
meets annual energy requirements of equal to or more
than
5% of internal lighting in the building (1 point)
10% of internal lighting in the building (2 point)
20% of internal lighting in the building (3 points)
30% of internal lighting in the building (4 points)
-
G R I H A
PV Energy Calculation
-
G R I H A
Criterion- 19: Renewable-energy- based hot
water system
OBJECTIVE
To use renewable energy sources to meet the hot water requirement
-
G R I H A
Collectors for Solar Hot Water System
Relatively insensitive to placement angle
No convection and conduction losses
Uses a heat pipe for super efficient heat conduction. No water enters to the collector
Easy installation and no maintenance
Fragile & Installation - complicated
Snow is less of problem in cold climate
Require accurate southern exposure and elevation placement
The air gap allows heat losses to occur
Prone to leakage, corrosion and restriction of flow due to possible air lock
Heavier and more fragile
Installation is difficult.
Flate Plate
-
G R I H A
Components of SWH Systems
Source : www.retscreen.net
-
G R I H A
Where do SWH systems use?
Domestic Hot Water
Process Heat
Swimming Pool Heating
-
G R I H A
Methodology for RE System Sizing
Activities
Water Consumption
per person LPD
Shower/Tub Bathing 35LPD per person 5390
For cooking 5LPD per person 770
For washing clothes 10 LPD per person 1540
Washing utensils per person per
meal 5 LPD per person 2310
Making tea/coffee 150ml per person per cup 69.3
Total LPD ( rounded) 10100
No of Persons = 158 Station : Chandigarh
-
G R I H A
19.1 Commitment
Atleast 20% of Energy required for
hot water generation through
renewable energy system. Here it
is SHW system.
-
G R I H A
Hot water requirement
10100 LPD requirement per day during winter
168.1 MWh Energy is required to heat water
upto 60 oC
-
G R I H A
Renewable Energy System Sizing
To offset 20% of Total Energy consumption,
Min size of SHW system = 1900 LPD
The floor area required is ~ 2.5 to 3 Sq.m for 100 LPD SHW system
-
G R I H A
19.3 Appraisal
Case SHW sizing
At 60 oC
(LPD)
Annual Energy saved
by SHW system
(MWh)
% offset of
annual
energy
consumption
Points
Case1 1900 35.6 21% 1
Case2 5400 86.1
51% 1+1
Case3 8800 119.3 71% 1+2
Total hot water requirement = 10100 LPD
-
G R I H A
SWH Energy Calculation
Source : www.retscreen.net
-
G R I H A
19.2 Compliance
Detailed calculations of hot water requirements.
Detailed calculations on energy required for heating water for all needs except for space heating
Detailed design calculations for renewable energy system sizing and performance including annual energy generation.
Layout of the proposed renewable energy system.
Test reports from approved test centre for system performance and efficiency .
-
G R I H A
19.2.1 Detailed calculations of hot water
requirements.
Client
-
G R I H A
19.2.2 Detailed calculations on energy required for heating
water
-
G R I H A
19.2.3 Detailed design calculations for renewable energy system sizing
and performance
-
G R I H A
19.2.4 Layout of the proposed renewable
energy system.
-
G R I H A
19.3 Appraisal (maximum points 3)
Annual Energy saved by proposed renewable energy system is 20% to 50% of annual energy required for water heating to meet the hot water
requirements of the occupants in the building (1 point)
50% to 70% of annual energy required for water heating to meet the hot water requirement of the occupants in the building is saved (2 points)
70% of annual energy required for water heating to meet the hot water requirements of the occupants in the building is saved (3 points)
-
G R I H A
MNRE Scheme on SPV systems
-
G R I H A
Thank You
All the presentations are copyright of GRIHA. It can not be printed or presented without permission of
GRIHA Secretariat.