EM Lab Manual - Cycle - I2

download EM Lab Manual - Cycle - I2

of 43

Transcript of EM Lab Manual - Cycle - I2

  • 8/3/2019 EM Lab Manual - Cycle - I2

    1/43

    Ex. No:1 OPEN CIRCUIT AND LOAD CHARACTERISTICS OF

    Date : SEPARATELY EXCITIED DC GENERATOR

    Aim:

    1. To draw open circuit characteristics of the given separately excited DC

    generator at rated speed and determine the critical resistance.

    2. To determine load characteristics (Internal & External) of the given DC

    separately excited generator.

    Apparatus required:

    Sl.No. Name Range Type Quantity

    1 Voltmeter (0-300V) MC 1

    2 Ammeter (0-10A)

    (0-2A)

    MC

    MC

    1

    1

    3 Rheostat 300/1.4 A Wire wound 2

    4 Tachometer (0-1500) rpm Analog/Digital 1

    5 Connecting wires Required

    Formula:

    Where, Rc Critical resistance

    Eg Incremental generated EMF (measured from the linear portion

    on the OCC)

    If Incremental field current (measured from the linear portion on

    the OCC).

    1

  • 8/3/2019 EM Lab Manual - Cycle - I2

    2/43

    Circuit Diagram:

    +

    -

    DPSTSwitch

    Fuse

    220VoltsD.C

    Supply

    +

    -

    220

    VoltsD.CSupply

    LF

    A

    DPSTSwitch

    Fuse

    F1

    F2

    A1

    A2

    3-Point Starter

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    Fuse

    Fuse

    VariableResistive

    Load

    (0-10 A) MC

    (0-300 V)

    MCDPST

    Switch

    10 A

    10 A

    A

    A

    V

    (0-2 A)

    MC

    F1

    F2

    Fuse

    Fuse

    300 /

    1.4 A

    15 A

    15 A

    M G

    15 A

    15 A

    300 /

    1.4 A

    Fuse Rating Calculation

    125% of Rated Current

    Motor =

    Generator =O.C & Load Characteristics of DC Separately Excited Generator

    Generator Name Plate Details

    KVA________

    RPM________

    Volts________

    Amps________

    2

  • 8/3/2019 EM Lab Manual - Cycle - I2

    3/43

    Precaution:

    1. The field rheostat on the motor side must be kept at minimum resistance position at the

    time of starting.

    2. The field potentiometer on the generator side must be kept at minimum potential

    position at the time of starting.

    3. DPST switches must be kept open at the time of power on.

    Procedure:

    1. Connections are given as per the circuit diagram.

    2. Observing the precautions the motor side DPST switch is closed.

    3. The motor is started with the help of three- point DC starter slowly.

    4. The speed is measured with the help of a hand tachometer.

    5. If the speed is below the rated value, then it is brought to the rated value by adjustingthe field rheostat.

    6. With DPST switch on the generator field side open, the voltmeter reading is noted

    down. (This is the residual voltage at the rated speed at which the motor-generator set is

    running now.)

    7. The DPST switch on the generator field side is closed.

    8. By adjusting the potentiometer on the generator field side suitably for various

    increasing field currents, note down the terminal voltages till around 125% of the rated

    voltage. The speed is maintained constant throughout this process.

    9. The generator terminal voltage is minimized to zero.

    10.The speed is brought down to minimum value and the motor is switched off with the

    help of DPST switch. (Note the starter holding coil releasing the handle else bring it

    back to start position)

    Tabulation:

    Speed = _________rpm

    Residual voltage = ________ Volts

    S. No. If(amps) Eg (volts)

    3

  • 8/3/2019 EM Lab Manual - Cycle - I2

    4/43

    Model graph:

    Load Characteristics:

    Precaution:

    1. The field rheostat on the motor side must be kept at minimum resistance position at the

    time of starting.2. The field potentiometer on the generator side must be kept at minimum potential

    position at the time of starting.

    3. DPST switches must be kept open at the time of power on.

    4. There should be no load at the time of starting.

    Procedure:

    1. Connections are given as per the circuit diagram.

    2. Observing the precautions the motor side DPST switch is closed.

    3. The motor is started with the help of three- point DC starter slowly.

    4. The speed is measured with the help of a hand tachometer.

    5. If the speed is below the rated value, then it is brought to the rated value by adjusting

    the field rheostat.

    6. By adjusting the potentiometer on the generator side the generator terminal voltage is

    brought to the rated value.

    Eg E

    g

    If

    If

    4

  • 8/3/2019 EM Lab Manual - Cycle - I2

    5/43

    7. Load side DPST switch is closed.

    8. The load is applied gradually. For various load currents voltmeter and ammeter

    readings are noted down till full current of the generator. (Avoid sustained overload.)

    9. The load is brought back to initial no load position.

    10.DPST switch on the load side is opened.

    11.Generator field circuit potentiometer is brought to minimum potential position.

    12. DPST switch on the generator field side is opened.

    13. The speed is brought down to minimum value and the motor is switched off with the

    help of DPST switch. (Note the starter holding coil releasing the handle else bring it

    back to start position)

    14. Disconnect and return the apparatus.

    Tabular column:

    Ra = _________ Ohms

    Load

    current

    IL(amps)

    Shunt

    Field

    current

    I sh(amps)

    Load

    voltage

    VL(volts)

    Armature current

    Ia = IL

    Generated voltage

    Eg = V + Ia Ra

    Model graph:

    5

  • 8/3/2019 EM Lab Manual - Cycle - I2

    6/43

    Ia = IL + I sh Amps

    Eg = V + Ia Ra Volts

    Ra Armaure resistance ohms

    Eg generated voltage volts

    V Terminal voltage volts

    I sh Shunt field current Amps

    Result:

    1. The Open Circuit Characteristics of the given separately excited DC generator was

    obtained and the Critical resistance at rated speed is found to be ______ohms.

    2. The Load Characteristics (Internal & External) of the given separately excited DC

    generator was obtained.

    Ia

    & IL

    Eg Vs Ia

    V Vs IL

    V

    &Eg

    6

  • 8/3/2019 EM Lab Manual - Cycle - I2

    7/43

    Ex. No: LOAD CHARACTERISTICS OF SELF EXCITIED

    Date : DC SHUNTGENERATOR

    Aim:

    1. To determine load characteristics (Internal & External) of the given DC self excited

    generator.

    Apparatus required:

    Sl. No Name Range Type Quantity

    1 Voltmeter (0-300) V MC 1

    2 Ammeter (0-10) A MC 1

    3 Ammeter (0-2) A MC 1

    4 Rheostat300 / 1.4 A

    100 / 4 AWire wound Each 1

    5 Tachometer Analog / Digital

    6 Connecting wires Required

    Formulae:

    Eg = V + Ia Ra

    Ia = IL + I sh

    Where,

    Ra Armature resistance

    Eg Generated voltage

    V Terminal Voltage

    I sh Shunt field current

    IL Load Current

    7

  • 8/3/2019 EM Lab Manual - Cycle - I2

    8/43

    Circuit Diagram:

    +

    -220 Volts

    D.C

    Supply

    LF

    A

    DPSTSwitch

    F1

    F2

    A1

    A2

    3-Point Starter

    M

    FuseFuse

    A

    v

    Fuse

    VariableResistive

    Load

    (0-10 A)

    MC

    (0-300 V)MC

    (0-2 A)

    MC

    f1

    f2

    100 /4A

    DPST

    SwitchFuse

    300 /

    1.4 A

    15 A

    15 A 10 A

    10 A

    G

    A1

    A2

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    Generator Name Plate Details

    KVA________

    RPM________

    Volts________

    Amps________

    Fuse Rating Calculation

    125% of Rated Current

    Motor =

    Generator =

    O.C & Load Characteristics of DC Shunt Generator

    A

    8

  • 8/3/2019 EM Lab Manual - Cycle - I2

    9/43

    Precaution:

    The field rheostat on the motor side must be kept at minimum resistance position at

    the time of starting.

    The field rheostat on the generator side must be kept at maximum resistanceposition at the time of starting.

    DPST switches must be kept open at the time of power on.

    There should be no load at the time of starting.

    Procedure:

    Connections are given as per the circuit diagram.

    Observing the precautions the motor side DPST switch is closed. The motor is started with the help of three- point DC starter slowly.

    The speed is measured with the help of a hand tachometer.

    If the speed is below the rated value, then it is brought to the rated value by

    adjusting the motor field rheostat.

    By adjusting the field rheostat on the generator side the generator terminal voltage is

    brought to the rated value.

    Load side DPST switch is closed.

    The load is applied gradually. For various load currents voltmeter and ammeter

    readings are noted down till full current of the generator. (Avoid sustainedoverload.)

    The load is brought back to initial no load position.

    DPST switch on the load side is opened.

    Generator field circuit rheostat is brought to maximum resistance position.

    DPST switch on the generator field side is opened.

    The speed is brought down to minimum value and the motor is switched off (Note

    the starter holding coil releasing the handle else bring it back to start position)

    9

  • 8/3/2019 EM Lab Manual - Cycle - I2

    10/43

    Tabular column:

    Ra = ________ Ohms

    S.

    No.IL(amps)

    I sh(amps)

    V(volts)Ia = IL + I sh

    (amps) Eg = V + Ia Ra

    Model graph:

    Result:

    Ia

    & IL

    Eg

    Vs Ia

    VL

    Vs IL

    VL&

    Eg

    10

  • 8/3/2019 EM Lab Manual - Cycle - I2

    11/43

    Thus the Load Characteristics (Internal & External) of the given self-excited DC

    shunt generator was obtained.

    11

  • 8/3/2019 EM Lab Manual - Cycle - I2

    12/43

    Ex. No: LOAD TEST ON DC SHUNT MOTOR

    Date :

    Aim:

    To perform load test on the given D.C shunt motor and to obtain the performance

    characteristics.

    Apparatus Required:

    Sl.No Name of the apparatus Range Type Quantity

    1. Ammeter (0-2) A

    (0-20) A

    MC Each 1

    2. Voltmeter (0-300) V MC 1

    3. Tachometer (0-1500) rpmAnalog/Digita

    l1

    4. Rheostat 300/1.4 A Wire wound 1

    5. Connecting wires Required

    Formulae:

    IL = Ia + I sh

    Input power = V x IL (Watts)

    Torque (T) = (S 1 ~ S 2) x 9.81 x R (Nm) S 1, S 2 spring balance readings (Kg)

    Output power = 2 N T (Watts) N speed of the motor in rpm

    60

    Efficiency = Output power x 100

    Input power Ia - Armature current (Amps) I sh Shunt field current (Amps)

    IL - Load Current (Amps) V Supply voltage (Volts)

    R Radius of the brake drum = Circumference / 2 (m).

    12

  • 8/3/2019 EM Lab Manual - Cycle - I2

    13/43

    Circuit Diagram:

    +-

    220 VoltsD.C

    Supply

    DPSTSwitch

    A1

    A2

    Fuse

    Fuse

    15 A

    15 A

    M

    LF

    A

    F1

    F2

    3-Point Starter

    300 /

    1.4 A

    A

    A

    V

    (0-20 A) MC

    (0-300 V)

    MC

    (0-2 A)MC

    SpringBalance

    BrakeDrum

    S1 S2

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    Fuse Rating Calculation

    125% of Rated Current

    Motor =

    Load Test on DC Shunt Motor

    13

  • 8/3/2019 EM Lab Manual - Cycle - I2

    14/43

    Tabular column:

    Sl.No

    Input

    voltage(Volts)

    (V)

    Load

    Current(Amps)

    (IL)

    Field

    Current(Amps)

    (Ish)

    Armature

    Current(Amps)

    (Ia = IL - Ish )

    Speed(N)

    (rpm)

    Spring Balance

    Readings Torque(T)

    (Nm)

    InputPower

    (Watts)

    OutputPower

    (Watts)

    Efficienc(%)S1

    kg

    S2kg

    (S1~ S2)

    kg

    14

  • 8/3/2019 EM Lab Manual - Cycle - I2

    15/43

    Model Graph:

    ELECTRICAL CHARACTERISTICS MECHANICAL CHARACTERISTICS PERFORMANCE CHARS

    Torque (T)(Nm)

    23

    4

    1 Output Vs Speed

    2 Output Vs % Efficiency

    3 - Output Vs Torque

    4 Output Vs Armature Current

    Speed (N)

    % Efficiency ()

    Torque (T)Arm. Current (Ia)

    Output power in wattsTorque (Nm)Arm. Current (Ia) in Amps

    Speed (N)(rpm)

    15

  • 8/3/2019 EM Lab Manual - Cycle - I2

    16/43

    Precautions:

    1. The motor field rheostat must be kept at minimum resistance position at

    the time of starting.

    2. There should be no load at the time of starting.

    Procedure:

    Make the connections as per the circuit diagram

    Switch on the supply and move the starter handle slowly and gradually to start the motor

    Now observe the speed. If the speed is less than the rated speed adjust the field

    rheostat and bring the speed to rated value. Readings are taken for no load.

    Load on the motor is varied with the help of pony brake arrangement.

    Spring balance, ammeter, voltmeter and speed-readings are noted down for various

    line currents as the load is increased (till the rated current is reached).

    Pour water in the brake drum to avoid over heating.

    Unload the machine and bring back the rheostat to minimum position.

    Switch off the supply

    Result:

    Thus the load test on the given DC Shunt motor was conducted and its performance

    characteristics were drawn.

    16

  • 8/3/2019 EM Lab Manual - Cycle - I2

    17/43

    Ex. No: LOAD TEST ON DC SERIES MOTOR

    Date :

    Aim:

    To perform load test on the given D.C shunt motor and to obtain the performance

    characteristics.

    Apparatus Required:

    Sl.No Name of the apparatus Range Type Quantity

    1. Ammeter (0-20) A MC 12. Volt meter (0-300) V MC 1

    3. Tachometer (0-1500) rpmAnalog/Digita

    l1

    4. Connecting wires Required

    Formulae:

    IL = Ia = ISe

    Input power = V x IL (Watts)

    Torque (T) = ( S 1 ~ S 2 ) x 9.81 x R (Nm) S 1 , S 2 spring balance readings(Kg)

    Output power = 2 N T (Watts) N speed of the motor in rpm

    60

    Efficiency = Output power x 100

    Input power

    Ia - Armature current (Amps) I se Series field current (Amps)

    IL - Load Current (Amps) V Supply voltage (Volts)

    R Radius of the brake drum = Circumference / 2 (m)

    17

  • 8/3/2019 EM Lab Manual - Cycle - I2

    18/43

    Circuit Diagram:

    +

    -220 Volts

    D.CSupply

    DPSTSwitch

    A1

    A2

    Fuse

    Fuse

    15 A

    15 A

    M

    2-Point Starter

    A

    V

    (0-20 A) MC

    (0-300 V)

    MC

    SpringBalance

    Brake

    Drum

    S1 S2

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    Fuse Rating Calculation

    125% of Rated Current

    Motor =

    L A

    S1 S2

    Load Test On DC Series Motor

    18

  • 8/3/2019 EM Lab Manual - Cycle - I2

    19/43

    Tabular column:

    Sl.

    No

    Inputvoltage

    (Volts)

    (V)

    Load

    Current

    (Amps)

    (IL = Ia)

    speed

    (N)

    (rpm)

    Spring Balance

    Readings Torque

    (T)

    (Nm)

    Input

    Power

    (Watts)

    Output

    Power

    (Watts)

    Efficiency

    (%)S1kg

    S2kg

    (S1~ S2)kg

    19

  • 8/3/2019 EM Lab Manual - Cycle - I2

    20/43

    Model Graph:

    ELECTRICAL CHARACTERISTICS MECHANICAL CHARACTERISTICS PERFORMANCE CHARS

    % EfficiencySpeed Speed

    (N) Torque

    Torque (T) rpm Arm. Current(Nm)

    Arm. Current (Ia) in Amps Torque (Nm)

    Output power in watts

    4

    1 Output Vs Armature Current

    2 Output Vs Torque

    3 Output Vs % Efficiency

    4 Output Vs Speed

    20

  • 8/3/2019 EM Lab Manual - Cycle - I2

    21/43

    Precautions:

    1. The motor should be started with some load.

    2. Brake drum should be cooled throughout the experiment.

    Procedure:

    1. Connections are given as per the circuit diagram

    2. Observing the precautions the DPST switch is closed.

    3. The motor is started with the help of two-point dc starter slowly.

    4. Load on the motor is varied with the help of pony brake arrangement.

    5. Spring balance, ammeter, voltmeter and speed readings are noted down for

    various line currents as the load is applied. Care must be taken to avoid the speed

    reaching dangerously high values while reducing the load.

    6. Pour water in the brake drum to avoid overheating.

    7. At a minimum safe load the DPST switch is opened.

    8. Disconnect and return the apparatus.

    Result:

    Thus the load test on the given DC Series motor was conducted and its performance

    characteristics were drawn.

    21

  • 8/3/2019 EM Lab Manual - Cycle - I2

    22/43

    Ex. No: SPEED CONTROL OF DC SHUNT MOTOR

    Date :

    Aim:

    To vary the speed of the given dc shunt motor by the following methods.

    (i). Armature control method (below rated speed)

    (ii). Field control method (above rated speed)

    Apparatus Required:

    Sl. No Name of the apparatus Range Type Quantity

    1. Ammeter (0-2) A M.C 1

    2. Volt meter (0-300) V M.C 1

    3. Tachometer (0-1500) rpm Analog/Digital 1

    4. Rheostat300 / 1.4 A

    100 / 4 AWire wound Each 1

    5. Connecting wires Required

    Precautions:

    1. The field rheostat must be kept at minimum resistance position at the time of starting.

    2. The armature rheostat must be kept at maximum resistance position at the time of

    starting.

    22

  • 8/3/2019 EM Lab Manual - Cycle - I2

    23/43

    Circuit Diagram:

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    +

    -220

    Volts

    D.C

    Supply

    DPST

    Switch

    A1

    A2

    Fuse

    Fuse

    2 A

    2 A

    V

    (0-300 V)

    MC

    Fuse Rating Calculation

    10% of Rated Current

    Motor =

    F1

    F2

    300 /

    1.4 A

    (0-2.5 A)

    MC

    M V

    100 / 4 A

    Speed Control of DC

    Shunt Motor

    A

    Model Graph:

    (i) Armature Control method (ii) Field control method

    Speed

    (Rpm) Speed

    (Rpm)

    Armature voltage (volts) Field current (amps)

    23

  • 8/3/2019 EM Lab Manual - Cycle - I2

    24/43

    Tabulations:

    (i). Armature control method:

    Field current (If) = ______ Amps kept constant

    SL.

    No

    Armature voltage

    (Volts)

    Speed

    (rpm)

    (ii) Field control method

    Armature voltage (Va) = ______ Volts kept constant

    SL.

    No

    Field current

    (Amps)

    Speed

    (rpm)

    24

  • 8/3/2019 EM Lab Manual - Cycle - I2

    25/43

    Procedure:

    (i). Armature control method:

    Make the connections as per the circuit diagram

    Switch on the supply

    Keep the field current constant and for different armature voltage (by varying

    armature rheostat) note down the corresponding speed.

    Bring back the rheostat to initial position and switch off the supply

    (ii). Field control method

    Switch on the supply

    Start the motor by closing the DPST switch

    Keep the armature voltage constant and for various field current (by varying field

    rheostat) note down the corresponding speed.

    Bring back the rheostat to initial position and switch off the supply

    Result:

    Thus the speed of the given DC shunt motor is varied by both armature control

    and field control method and the graphs are plotted. The speed is directly proportional to

    the armature voltage by graph (i) and inversely proportional to the field current by graph

    (ii).

    25

  • 8/3/2019 EM Lab Manual - Cycle - I2

    26/43

    Ex. No: OC AND SC TEST OF SINGLE PHASE TRANSFORMER

    Date :

    Aim:

    To perform open circuit and short circuit test on a single phase transformer and

    predetermine the efficiency at various loads and also draw the equivalent circuit.

    Apparatus Required:

    Sl.No Name of the apparatus Range Type Quantity

    1. Ammeter (0-2) A

    (0-5) AMI Each 1

    2. Volt meter (0-150) V

    (0-30) VMI Each 1

    3. Watt meter 150V, 2A, LPF

    30V, 5A, UPFDynamo meter Each 1

    4. 1- Autotransformer (0-270) V 1

    5 Connecting wires Required

    Formulae:

    Transformer Ratings: 1 KVA, 220 V/ 110V, 50HZ

    V1 = 220 V & V2 = 110 V

    I 1 = 1000/220 = 4.55 A & I2 = 1000/110 = 9.09 A

    K = V2 / V1 = 110/220 = 0.5

    From open circuit test:

    26

  • 8/3/2019 EM Lab Manual - Cycle - I2

    27/43

    In the open circuit test the primary is open circuited and the meters are connected on

    L.V side, which is secondary of the transformer. Thus O.C test will give us no load

    current, I01. (i.e referred to secondary)

    Since K = V2/V1, the corresponding no load primary current, I0 = I01 * K

    W0 = V1 I0 Cos 0 ( watts)

    Where,

    W0 = No load input power = core (or Iron) loss = Wi

    I0 - No load input current

    V1 - No load rated input voltageCos - Power factor

    Cos 0 = W0 / V1 I0I w = I0 Cos 0 A ( Iron loss component)

    I = I0 Sin 0 A ( Magnetizing component)

    R0 = V1 / I w (Resistance to represent core loss)

    X0 = V1 / I (Reactance to represent magnetizing component)

    From short circuit test:

    In the Short circuit test the secondary is short circuited and the meters are on H.V

    side, which is primary of the transformer. Hence it gives parameters referred to primary.

    R01 = Wsc / Isc2

    Z01 = Vsc / Isc

    X01 = Z012 - R012

    I21 = I2 * K & I1 = I0 + I2

    1

    Where,

    R01 - Equivalent resistance of transformer referred to primary side

    27

  • 8/3/2019 EM Lab Manual - Cycle - I2

    28/43

    X01 - Equivalent reactance of transformer referred to primary side

    Z01 - Equivalent impedance of transformer referred to primary side

    Wsc Full load copper loss

    Isc Short Circuit Current

    Vsc Short circuit voltage corresponding to Isc

    Equivalent Circuit Parameters referred to secondary side:

    R01 = R0 * K

    2 I01 = No load current from O.C Test

    X01

    = X0 * K2

    I w1

    = V11

    / R01

    R02 = R01 x K2 I

    1 = V11 / X0

    1

    X02 = X01 x K2 Where, V1

    1 = V1 * K

    Z02 = Z01 x K2 I1

    1 = I01 + I2

    Regulation = [ I2 R02 Cos + I2 X02 Sin / V2 ] X 100

    + Ve for lagging Power factor

    - Ve for leading power factor

    (X * KVA * P.f)

    % Efficiency at various loads = x 100

    [(X * KVA * P.f ) + (Wi + X 2 Wsc)]

    X Load ratio

    28

  • 8/3/2019 EM Lab Manual - Cycle - I2

    29/43

    Circuit Diagram:

    DPSTSwitch

    Fuse

    230 V

    1- 50 HZ

    AC Supply V

    A

    C

    M L

    V

    Fuse

    5 A

    5 A

    (0-270 V) 1

    AutoTrnsformer (0-150 V)MI

    (0-2 A) MI

    150 V, 2A, LPF

    Wattmeter

    110 V 220 V

    Open Circuit

    Name Plate Details

    Single Phase Transformer

    Auto TransformerFuse Rating Calculation

    KVA________

    Voltage Ratio________

    20 % of Rated Current(Max. Load of A.T )

    Maximum Load =

    Maximum KVA =

    Input =

    0 V 0 V

    Open Circuit Test on Single Phase Transformer

    P

    N

    29

  • 8/3/2019 EM Lab Manual - Cycle - I2

    30/43

    Circuit Diagram:

    DPST

    Switch

    Fuse

    230 V1- 50 HZ

    AC Supply V

    A

    C

    M L

    V

    Fuse

    5 A

    5 A

    (0-270 V) 1

    Auto

    Trnsformer

    (0-30 V)

    MI

    (0-5 A) MI

    30 V, 5A, UPF

    Wattmeter

    220 V 110 V

    Fuse Rating Calculation

    Short Circuit

    0 V 0 V

    Isc = KVA / V

    = Short Circuit Test on Single Phase Tranformer

    P

    N

    30

  • 8/3/2019 EM Lab Manual - Cycle - I2

    31/43

    Equivalent circuit referred to primary side:

    V1

    I21

    I0

    I1

    IW I

    X0R0

    R01 X01

    ZL1

    V21

    Equivalent circuit referred to secondary side:

    V11

    I11

    I01

    I2

    IW1 I

    1

    X01R0

    1

    R02 X02

    ZL

    V2

    Model Graph:

    UPF

    %Reg.

    % 0.8

    Leading P.F Lagging P.F

    31

  • 8/3/2019 EM Lab Manual - Cycle - I2

    32/43

    O/P Power (Watts) %Reg.

    Tabulations:

    Open circuit test:

    Short circuit test:

    Sl.

    No

    Vo

    (Volts)

    Io

    (Amps)

    Wo

    (Div)

    Wo x M.F

    (Watts)

    Sl.

    No

    Vsc(Volts)

    Isc(Amps)

    Wsc(Div)

    Wsc x M.F

    (Watts)

    32

  • 8/3/2019 EM Lab Manual - Cycle - I2

    33/43

    Tabulation for determine the Efficiency:

    Sl.

    No

    Load

    ratio

    (X)

    Output power

    (Watts)

    Wi(Watts)

    Wcu(Watts)

    Input Power

    (Watts)

    %

    Efficiency

    UPF 0.8 UPF 0.8 UPF 0.8

    1

    2

    3

    41

    Tabulation for determine the Regulation:

    Sl.No Power Factor (Cos )

    % Regulation

    Leading Lagging

    1 0

    2 0.2

    3 0.4

    4 0.6

    5 0.8

    6 1.0

    33

  • 8/3/2019 EM Lab Manual - Cycle - I2

    34/43

    Precautions:

    Autotransformer must be kept at minimum potential point during starting condition.

    Procedure:

    Open circuit test:

    Make the connections as per the circuit diagram

    Switch on the supply and vary the autotransformer to get rated voltage

    Note down ammeter, voltmeter and wattmeter readings.

    Bring back the autotransformer to original position.

    Switch off the supply

    Short circuit test:

    Make the connections as per the circuit diagram

    Switch on the supply and vary the autotransformer to get rated short circuit current.

    Note down ammeter, voltmeter and wattmeter readings.

    Bring back the autotransformer to original position.

    Switch off the supply

    Result:

    Thus the open circuit and short circuit tests were performed on a single-phase

    transformer and the efficiency was predetermined at various loads.

    34

  • 8/3/2019 EM Lab Manual - Cycle - I2

    35/43

    Ex. No: LOAD TEST ON SINGLE PHASE TRANSFORMER

    Date :

    Aim:

    To perform load test on a single phase transformer and determine its performance

    characteristics

    Apparatus Required:

    Sl.no Name of the apparatus Range Type Quantity

    1. Ammeter (0-5) A

    (0-10) AMI Each 1

    2. Volt meter (0-150) V

    (0-300) VMI Each 1

    3. Watt meter 150V, 5A, UPF

    300V, 10 A, UPFDynamo meter Each 1

    4. 1- Autotransformer (0-270) V 1

    5 Connecting wires Required

    Formulae:

    Input power = W1 x M.F1 watts

    Output power = W2 x M.F2 watts

    % Efficiency = Output power / Input power X100

    % Regulation = (E02 V2) / E02 x 100

    E 02 - No load secondary voltage

    V 2 - Secondary voltage at various loads

    35

  • 8/3/2019 EM Lab Manual - Cycle - I2

    36/43

    M.F Multiplication factor

    W1, W2 - Wattmeter readings

    V I cos Multiplication factor (M.F) =

    No of divisions in the watt meter

    Precautions:

    Autotransformer must be kept at minimum potential point during starting condition.

    There should be no load at the time of starting the experiment

    Procedure:

    Make the connections as per the circuit diagram.

    Switch on the supply and vary the autotransformer to get rated primary voltage.

    Note down the no load readings.

    Add the load in steps and note down all the meter readings till the rated secondarycurrent is reached.

    Remove the load and bring back the autotransformer to original position.

    Switch off the supply.

    36

  • 8/3/2019 EM Lab Manual - Cycle - I2

    37/43

    Circuit Diagram:

    DPST

    Switch

    Fuse

    230 V1- 50

    HZ AC

    Supply

    A

    C

    M L

    V

    Fuse

    15 A

    15 A

    (0-270 V)

    1 Auto

    Trnsform

    er

    (0-150 V)

    MI

    (0-5 A) MI

    150 V, 5A, UPF

    Wattmeter

    110 V 220 V

    Fuse Rating Calculation

    0 V 0 V

    Load Test on Single Phase Tranformer

    C

    M L

    V

    A

    DPST

    Switch

    Fuse

    Fuse

    10 A

    10 A

    (0-10 A) MI

    300 V, 10A, UPF

    V V(0-300 V)

    MI

    Wattmeter

    Load

    Name Plate Details

    Primary Side Secondary Side

    Power =

    Voltage =

    Current =

    Power =

    Voltage =

    Current =

    Primary Side: 125 % of Rated Current

    =

    Secondary Side: 125 % of Rated Current

    =

    P

    N

    37

  • 8/3/2019 EM Lab Manual - Cycle - I2

    38/43

    Tabulation:

    Sl. Primary

    Voltage

    Primary Input Power Secondary

    Voltage

    Secondar Output PowerEfficiency Reg

    W1 W1 X M.F W2 W2 X M.F

    (Volts) (Amps) (Div) (Watts) (Volts) (Amps)(Div

    (Watts) %

    38

  • 8/3/2019 EM Lab Manual - Cycle - I2

    39/43

  • 8/3/2019 EM Lab Manual - Cycle - I2

    40/43

    Ex. No: SWINBURNES TEST(No load Test)

    Date :

    Aim:

    To predetermine the efficiency of DC shunt machine at various load current while

    operating as a motor and generator and plot a graph output Vs % efficiency.

    Apparatus required:

    Sl. No. Name Range Type Quantity

    1 Voltmeter (0-300) V MC 1

    2 Ammeter (0-2.5) A MC 2

    3 Rheostat 300 / 1.4 A Wire wound 1

    4 Tachometer Analog / Digital 15 Connecting wires Required

    Formula:

    Constant Losses WC = Input Power - No load Armature copper loss

    = VIo Iao2X Ra

    Where, Iao= Io - IfRa = Armature resistance

    For motor:1. Ia = IL If Amps

    2. Armature copper loss = Ia2 Ra watts

    3. Total loss WT = WC +Ia2 Ra watts

    4. Input power = V IL watts

    5. Output Power = Input Power Total Loss watts

    6. Efficiency % m = [Output Power / Input Power ] X 100 No unit

    For Generator:

    1. Ia = IL +If Amps

    2. Armature copper loss = Ia2 Ra watts

    3. Total loss WT = WC +Ia2 Ra watts

    4. Output power = V IL watts

    5. Input Power = Output Power + Total Loss watts

    6. Efficiency % G = [Output Power / Input Power ] X 100 No unit

    40

  • 8/3/2019 EM Lab Manual - Cycle - I2

    41/43

    Circuit Diagram:

    Motor Name Plate Details

    KW________

    RPM________

    Volts________

    Amps________

    +

    -220

    VoltsD.C

    Supply

    DPST

    Switch

    A1

    A2

    Fuse

    Fuse

    2 A

    2 A

    M

    LF

    A

    F1

    F2

    3-Point Starter

    300 /

    1.4 A

    A

    A

    V(0-300 V)

    MC

    (0-2.5 A)

    MC

    (0-2.5 A)MC

    Fuse Rating Calculation

    10% of Rated Current

    Motor =

    Swinburnes Test

    Model graph:

    %

    Output (watts)Tabulation:

    Sl. No V (volts) I0 (amp) If(amp)

    Generator

    Motor

    41

  • 8/3/2019 EM Lab Manual - Cycle - I2

    42/43

    Motor:

    Ra = _______ Ohms

    Sl.

    No

    V

    (volts)

    IL(amp)

    Ia=IL-If(amp)

    Ia2Ra

    _(watts)

    WC

    _(watts)

    WT =WC+Ia2Ra

    _(watts)

    Input

    VIL

    _(watts)

    Output

    _(watts)%

    Generator:

    Ra = _______ Ohms

    Sl. NoV

    (volts)

    IL(amp)

    Ia=IL+I

    f

    (amp)

    Ia2Ra

    _(watts

    )

    WC

    _(watts)

    WT=WC+Ia

    2Ra

    _(watts)

    Outpu

    t

    VIL

    _(watt

    s)

    Input

    _(watts)

    %

    Precautions:

    1. The motor field rheostat should be kept at minimum resistance position.

    Procedure:

    42

  • 8/3/2019 EM Lab Manual - Cycle - I2

    43/43

    1. Connections are made as per the circuit diagram.

    2. Observing the precaution the DPST switch is closed and the motor is started with

    the help of 3-point DC starter slowly.

    3. The motor field rheostat is adjusted and the motor is brought to rated speed.

    4. The voltmeter and ammeter readings are noted down

    5. Field rheostat is brought back to minimum position

    6. Disconnect and return the meters.

    Result:

    The efficiency of the dc shunt machine was determined when it was running as a

    generator as well as a motor.

    43