electrical machines -1 lab

download electrical machines -1 lab

of 53

description

practical lab manual for electrical machines 1

Transcript of electrical machines -1 lab

  • 5/28/2018 electrical machines -1 lab

    1/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 1

    S.No. Name of the Experiment Page.No

    1 MAGNETIZATION CHARACTERISTICS OF A DC

    SHUNT GENERATOR

    2

    2 LOAD TEST ON DC SHUNT GENERATOR 6

    3 LOAD TEST ON DC COMPOUND GENERATOR 10

    4 BRAKE TEST ON DC SHUNT MOTOR 14

    5 SWINBURNES TEST ON A DC SHUNT MACHINE 18

    6 LOAD TEST ON DC SERIES GENERATOR 22

    7 HOPKINSONS TEST ON DC SHUNT MACHINE 26

    8 FIELDS TEST ON DC SERIES MACHINES 31

    9 SPEED CONTROL OF DC SHUNT MOTOR 36

    10 SEPERATION OF LOSSES IN DC SHUNT MOTOR 41

    11 BRAKE TEST ON DC COMPOUND MOTOR 45

    12 RETARDATION TEST ON DC SHUNT MOTOR 50

  • 5/28/2018 electrical machines -1 lab

    2/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 2

    1.MAGNETISATION CHARACTERISTICS OF AD.C SHUNTGENERATOR.

    AIM:

    To find the magnetization characteristics of a D.C shunt generator.

    To find the critical field resistance and critical speed.

    NAMEPLATE DETAILS:

    MOTOR GENERATOR

    Power3.7kw 3.7kw

    Wound Shunt ShuntArmature voltage 220V. 220V.

    Armature current 20 A 17A

    Excitation 220V, 0.9A 220V, 0.9A

    Speed 1500. 1500.

    APPARATUS:

    Name Type Range QtyVoltmeter M.C 0-300V 2

    Ammeter M.C 0-1A 1

    Rheostat___

    0-300 , 1.7A 1

    0-1500 , 1A 1

    Tachometer --- 1

  • 5/28/2018 electrical machines -1 lab

    3/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 3

    CIRCUIT DIAGRAM:

    THEORY:The magnetization characteristics of D.C. shunt generator shows the relationship

    between the no-load generated emf in armature (E0) and field current (If) at any constantspeed. Due to residual magnetism in the poles, some emf is produced initially. The current

    while passing through the field coils will strengthen the magnetism of the poles. This willincrease the pole flux with further increase the generated emf. Increased emf means morecurrent which further increase the flux so on. If field resistance is increased the slope ofthe resistance line increased and hence maximum voltage will build up at the generator ata given speed. If the resistance line just lies along the slope then with that value of thefield resistance, the machine will just excite. the value of the resistance represented by thetangent to the curve is known as critical resistance for a given speed.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the motor field rheostat at minimum position and generator field

    rheostat at maximum position.3. Start the motor with the help of 3- point starter and adjust the motor field

    rheostat till the motor reaches to its rated speed.4. Gradually increases the field current of generator by minimize the generator

    field rheostat resistance.5. Note the terminal voltage (V) of generator at various field currents (If). Till

    the generator attains its rated voltage.

  • 5/28/2018 electrical machines -1 lab

    4/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 4

    6. The relationship between no load voltage (V) and field current (If) gives theopen circuit characteristics (OCC).

    7. Draw the graph (OCC) between terminal voltage (V) and field current (I f) tofind out the critical field resistance and critical sped.

    TABULATION:

    S.noField current

    If(A)Voltage

    (V)

    MODEL GRAPH:

    V

    Voltage

    Field current If

  • 5/28/2018 electrical machines -1 lab

    5/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 5

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Proper rating meters should be used.4.

    Run the motor rated speed.5. Check the connections before giving supply.

    RESULT:Magnetization characteristics of D.C shunt generator is observed and plotted

    VIVA QUESTIONS:

    1. What is the purpose of plotting the magnetization curve?2. What is meant by the term critical field resistance related to DC shunt generator?3. What are the conditions to be fulfilled for the shunt generator to build up voltage?4. Why does saturation curve starts from some value higher than zero?5. What is the type of voltage induced in the armature of a DC generator?

  • 5/28/2018 electrical machines -1 lab

    6/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 6

    2. LOAD TEST ON D.C SHUNT GENERATOR

    AIM:To determine the internal and external load characteristics of a D.C shunt

    Generator.

    NAMEPLATE DETAILS:MOTOR GENERATOR

    Power5hp 5hp

    Wound Shunt Shunt

    Armature voltage 220V. 220V.

    Armature current 20A 13.6A

    Excitation 220V, 0.75A 220V,Speed 1500. 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-300V1

    Ammeter M.C 0-10A,0-1A 2

    Rheostat___

    0-300 , 1.7A 1

    0-570, 1.2A 1

    Tachometer ---1

    Load Resistive 5kw1

  • 5/28/2018 electrical machines -1 lab

    7/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 7

    CIRCUITDIAGRAM:

    THEORY:For a generator the induced emf is equal to the terminal voltage when the generator

    is not loaded. When the generator is loaded there is a fall in terminal voltage. The fall in

    terminal voltage of dc shunt generator is due to IaRa drop in the armature, the effect ofarmature reaction and brush contact resistance these causes reduce the voltage across thefield terminals of the dc generator. Thus the field current and hence the induced emf isreduced which results in further reduction of the terminal voltage. The externalcharacteristics of a dc shunt generator are more drooping.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the motor field rheostat at minimum position and generator field rheostat

    at maximum position.3. Start the motor with the help of 3- point starter and adjust the motor field rheostat

    till the motor reaches to its rated speed. Now close the generator switch and adjustthe field rheostat of the generator till it reaches to its rated voltage.

    4. Connect the load in step-by-step and each step note the load current andterminal voltage of the generator.

    5. Maintain load current will note exceed rated current.6. After note the readings first switch off the generator load and than switch off themotor supply.

  • 5/28/2018 electrical machines -1 lab

    8/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 8

    TABULAR FORM:

    S.NO Voltage(V)

    Loadcurrent

    IL(A)

    Fieldcurrent

    If(A)

    ArmatureCurrent

    Ia(A)

    ArmatureVoltage

    Eg(v)

    GeneratorTerminal

    Voltage V

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Loads should not be exceeding beyond their ratio

    MODEL GRAPHInternal characteristics:

    Eg

    IaARMATURE CURRENT

    ARMATU

    REVOLVOLTAGE

  • 5/28/2018 electrical machines -1 lab

    9/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 9

    External characteristics:

    Vt

    ILLOAD CURRENTRESULT:

    Hence the internal and external load characteristics of a D.C shunt Generator areobtained and plotted.

    VIVA QUESTIONS:

    1. What are the reasons for the drop in terminal voltage of a shunt generator when it isloaded?

    2. What is internal or total characteristic of a DC generator?3. What should be done if the DC shunt generator fails to build up? 4. What is armature reaction?

    TERMINALVOLTAGE

  • 5/28/2018 electrical machines -1 lab

    10/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 10

    3.LOAD TEST ON D.C COMPOUND GENERATOR

    AIM:To determine the internal and external load characteristics of a D.C compound

    Generator.

    NAMEPLATE DETAILS:MOTOR GENERATOR

    Power5hp 5hp

    Wound Shunt Compound

    Armature voltage 220V. 220V.

    Armature current 20A 13.6A

    Excitation 220V, 0.75A 220V,

    Speed 1500. 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-300V1

    Ammeter M.C0-15A 1

    Rheostat___

    0-300 , 1.7A 1

    0-570, 1.2A 1

    Tachometer ---1

    Load Resistive 5kw1

  • 5/28/2018 electrical machines -1 lab

    11/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 11

    CIRCUITDIAGRAM:

    THEORY:In a dc compound machine both the series, and the shunt field coils are present.

    While shunt field is the main field, series field either it or opposes. The first type is knownas cumulative compounding whiles the other as differential compounding .Cumulatively compounded D.C. generator:

    The voltage drop in armature resistance and the drop due to armature reactiontake place in this case also, but they are compensated by the increase in the flux due tothe mmf established by series winding carrying the load current, depending on the degreeof compensation.Differentially compounded D.C. generator:

    The terminal voltage drops due to the following reasons in this case: (1)armature resistance drop; (2) armature reaction effect (3) reduction in flux per pole due tothe series winding m.m.f opposing the shunt winding mmf.(4) reduction in shunt fieldcurrent due to reduction inarmature voltage.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the motor field rheostat at minimum position and generator field rheostat at

    maximum position.3. Start the rheostat till the motor reaches to its rated speed. Motor with the help of 3-

    point starter and adjust the motor field4. Now adjust the field rheostat of the generator till it reaches to its rated voltage.5. Connect the load in step-by-step and each step note the load current (IL), field current

    (If) and terminal voltage (V) of the shunt generator.6. Maintain load current will note exceed rated current.

  • 5/28/2018 electrical machines -1 lab

    12/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 12

    7.After note the readings first switch off the generator load and then switch off themotor supply.

    TABULATION:

    S.NO Voltage (V) Load

    current,

    IL(A)

    Field

    current

    If(A)

    Armature

    current

    Ia=IL+If(A)

    Armature

    Voltage

    Eg=V+IaRa

    MODEL GRAPH:

    Internal characteristics:

    Eg

    IaARMATURE CURRENT

    ARMATURE

    VOLVOLTAGE

  • 5/28/2018 electrical machines -1 lab

    13/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 13

    External characteristics:

    Vt

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Loads should not be exceeding beyond their rating.

    RESULT:

    Hence the internal and external load characteristics of a D.C compoundGenerator are obtained and plotted.

    VIVA QUESTIONS:1. What is external characteristic of dc generator?2. What is the function of commutator in a DC generator?3. Mention the difference between cumulative and differential compound DC

    generators?4. Can you measure the induced voltage under load condition for a DC generator?

    Why?5. Do you require a starter for a DC motor under the running condition, why?

    TERMINALVOLTAGE

  • 5/28/2018 electrical machines -1 lab

    14/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 14

    4.BRAKE TEST ON D.C SHUNT MOTOR

    AIM:To find the efficiency of D.C shunt motor by a direct load test.

    NAMEPLATE DETAILS:D.C SHUNT MOTOR

    Power5hp

    Wound Shunt

    Armature voltage 220V.

    Armature current 20A

    Excitation 220V, 0.75A

    Speed 1500.APPARATUS:

    NameType Range Qty

    Voltmeter M.C 0-300V1

    Ammeter M.C0-20A 1

    Rheostat___

    0-300 , 1.7A1

    Tachometer ---1

    CIRCUIT DIAGRAM:

  • 5/28/2018 electrical machines -1 lab

    15/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 15

    THEORY:It is a direct method and consists of applying a brake to a water cooled pulley

    mounted on the shaft of motor. The brake band is fixed with the help of wooden blocksgripping the pulley one end of the band is fixed to earth a spring balance and other is

    connected to a suspended weight. The motor is running and the load on the motor isadjusted till it carries its full load current. The simple brake test described above can beused for small motors only. Because, in the case of large motors, it is difficult to dissipatethe large amount of heat generated at the brake.

    PROCEDURE:1.Connect the circuit as per the circuit diagram.2.Keep the motor field rheostat at minimum position.3.Start the motor with the help of 3- point starter and Adjust the motor field

    rheostat till the motor reaches To its rated speed.

    4.Now gradually apply the mechanical load by tightening the Belt over the shaft.5.Note the corresponding spring balance readings, line current, Voltage and speed at

    particular load.6.Repent the above process at different load condition.7.Before the motor going to be switched off the motor must be in no load condition.8.Using the above data determine the efficiency of the compound motor.

    CALCULATIONS:

    Shaft torque = (S1-S2) x rx 9.81 (r = 0.1 m)= (2N) /60.

    Shaft O/P = Shaft Torque X

    Efficiency= = X100

    TABULAR FORM:

    S.NOVoltage

    (V)Line

    current(A)S1(kg) S2(kg) Speed(rpm) INPUT

    VI(W)ShaftTorque

    (N-M)

    rad/sec

    Shaft

    Output

    (W)

    Efficie

    %

    Shaft O/PPower I/P

  • 5/28/2018 electrical machines -1 lab

    16/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 16

    GRAPHS:Graphs are plotted between1. Speed and output2. Speed and torque3. Current and torque

    4. Efficiency and out put

    MODEL GRAPH:

    N N IL % O/PVs %

    TVSIL

    TVSN

    ILVSN

    Output(W)

    Torque(N-m)

    Torque(N-m)IL(A)

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Cool the shaft pulley with water.4. Proper rating meters should be used.5. Check the connections before giving supply.

  • 5/28/2018 electrical machines -1 lab

    17/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 17

    RESULT:Hence the efficiency of the D.C shunt motor at various load conditions

    are calculated and plotted.

    VIVA QUESTIONS:1. What is back EMF?2. How can the direction of rotation be reversed in a DC motor?3. Do you require a starter for a DC motor under the running condition, why?4. Why does the speed fall slightly when the DC shunt motor is loaded?5. What happens if the field circuit of a DC motor is opened under running condition?

  • 5/28/2018 electrical machines -1 lab

    18/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 18

    5.SWINBURNES TEST ON D.C SHUNT MACHINE

    AIM:To predetermine the efficiency of D.C shunt machine by conducting No load test.

    NAMEPLATE DETAILS:D.C SHUNT MOTOR

    Power5hp

    Wound Shunt

    Armature voltage 220V.

    Armature current 20A

    Excitation 220V, 0.75A

    Speed 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-300V1

    Ammeter M.C0-5A

    1

    0-1A 1

    Rheostat___

    0-300 , 1.7A1

    Tachometer ---1

    CIRCUITDIAGRAM:

  • 5/28/2018 electrical machines -1 lab

    19/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 19

    THEORY:The most obvious method of determining the efficiency of any machine at any

    load would be to measure the output and input when the machine is running at that load.For machines of higher rating, loads of the required size may not be available. Moreover,

    even if it was possible to provide such loads, large power would be consumed, making it anexpensive method. All big electrical machines are tested indirectly by measuring the losses.The machine is run as a motor on no-load at its rated voltage and the input powermeasured. In this, the motor is running at no load at the rated speed, with the help ofshunt regulator. No load power input to armature supplies iron losses, friction losses,windage losses and armature copper losses.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the motor field rheostat at minimum position.3. Start the motor with the help of 3- point starter.

    4. Adjust the motor field rheostat till the motor reaches to its rated speed.5. Note the armature current, field current and voltage.6. using the above data determine the efficiency of the D.C shunt machine.

    TABULAR FORM:

    Voltage(V)

    Armature current(Ia)

    Field current(If)

    Load current(IL0= Ia+ If)

    CALCULATIONS:MOTOR:

    Ia=IL-IshIL0=Ia0+IshConstant losses Wc=VIL0-Ia0

    2RaArmature cupper losses Wcu=Ia

    2 Ra

    Total losses in the motor Wt=(Wc+ Ia2 Ra)

    Efficiency =output/input=input-losses/input

    GENERATOR:Ia=IL+IshIL0=Ia0+IshConstant losses Wc=VIL0-Ia0

    2RaArmature cupper losses Wcu=Ia

    2 Ra

    Total losses in the motor Wt=(Wc+ Ia2 Ra)

    Efficiency =output/input

  • 5/28/2018 electrical machines -1 lab

    20/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 20

    =output/output+losses

    MODEL GRAPH:

    Motor:

    A graph is plot output of Motor Vs efficiency.

    M

    EFFICIENCY

    OUTPUT OF MOTOR

    Generator:A graph is plot output of Generator Vs efficiency.

    G

    EFFICIENCY

    OUTPUT OF GENERATOR

  • 5/28/2018 electrical machines -1 lab

    21/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 21

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3.

    Dont run the motor above safe speed.4. Check the connections before givingsupply.

    RESULT:Hence the efficiency of the D.C shunt machine at various load conditions aredetermined and plotted.

    VIVA QUESTIONS:

    1.

    What are the losses in a DC machine?

    2. What is the purpose of the commutator in a DC machine?3. What is the power O/P during Swinburnes test?4. What is the efficiency of a DC machine during Swinburnes test?5. Why Swinburnes test cannot be performed on DC series machine?

  • 5/28/2018 electrical machines -1 lab

    22/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 22

    6.LOAD TEST ON D.C SERIES GENERATOR

    AIM:To determine the internal and external load characteristics of a D.C series

    Generator.

    NAMEPLATE DETAILS:MOTOR GENERATOR

    Power5hp 5hp

    Wound Shunt Series

    Armature voltage 220V. 220V.

    Armature current 20A 13.6A

    Excitation 220V, 0.75A --------

    Speed 1500. 1500.

    APPARATUS

    Name Type Range Qty

    Voltmeter M.C 0-300V1

    Ammeter M.C0-10A 1

    Rheostat___

    0-300 , 1.7A 1

    Tachometer ---1

    Load Resistive 5kw1

  • 5/28/2018 electrical machines -1 lab

    23/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 23

    CIRCUIT DIAGRAM:

    THEORY:In a series generator, there is only one field winding so that connected in

    series with armature winding so that whole current flows through winding as well as load,series field winding carries full load current. Therefore series field winding is designed witha fewer turns of thick wire. The resistance of series winding is very low. These generatorscan be used for few applications and employed as constant current source. By making useof drooping portion of voltage-current characteristics. The best application is for supplyingfield current for regenerative braking in DC locomotives.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the motor field rheostat at minimum position and make sure all the load

    switches are in off position3. Start the motor with the help of 3- point starter and adjust the motor field rheostat

    till the motor reaches to its rated speed.4. Connect the load in step-by-step and each step note the load current and terminal

    voltage of the generator.

    5. Maintain load current will note exceed rated current.6. After note the readings first switch off the generator load and than switch off themotor supply.

  • 5/28/2018 electrical machines -1 lab

    24/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 24

    TABULAR FORM:

    S NoVoltage

    V(V)

    Current

    Ia(A) Eg=V+Ia (Ra+Rse)

    MODEL GRAPH:

    Internal characteristics:

    Vt

    CURRENT I

    TERMINA

    LVOLTAGE

  • 5/28/2018 electrical machines -1 lab

    25/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 25

    External characteristics:

    Eg

    ICURRENT

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Loads should not be exceeding beyond their rating

    RESULT:

    Hence the internal and external load characteristics of a D.C series Generator areobtained and plotted.

    VIVA QUESTIONS:

    1. Can a DC series generator excite on no-load, why?2. What is meant by critical resistance of a DC series generator?3. What are the reasons for the failure of a DC series generator to build up voltage? 4. What are the advantages of a DC series motor?5. Why is the starting torque of the series motor high?

    EFFICIENCY

    ARMATUREVOLVOLTAG

    E

  • 5/28/2018 electrical machines -1 lab

    26/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 26

    7.HOPKINSONS TEST ON DC SHUNT MACHINES

    AIM:

    To perform Hopkinsons test on two DC shunt machines and hence obtain Theirefficiencies at various loads.

    NAMEPLATE DETAILS:MOTOR GENERATOR

    Power3.7kw 3.7kw

    Wound Shunt Shunt

    Armature voltage 220V. 220V.

    Armature current 20.5A 17A

    Excitation 220V, 0.9A 220V, 0.9ASpeed 1500. 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-300V 2

    Ammeter M.C

    0-10A 2

    0-2A 2

    Rheostat___

    0-300 , 1.7A 1

    0-570 , 1.2A 1

    Tachometer --- 1

  • 5/28/2018 electrical machines -1 lab

    27/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 27

    CIRCUITDIAGRAM:

    THEORY:This method load test can be carried out on two shunt machines, preferably

    identical ones without wasting their outputs. The two machines are mechanically coupledand are so adjusted electrically that one of them runs as a motor and other as a generator.The mechanical output of the motor drives the generator and output of the generator is

    used as greater part of input to motor. If there are no losses, they would run without anyexternal power supply but due to losses generator output is not sufficient to drive motorand vice versa. The two shunt machines are connected in parallel they are to begin withstarter as unloaded motors. Then field of one is weakened and that of other isstrengthened. So former it acts as motor and later acts asgenerator.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the switch S in open position3. Keep the motor field rheostat at minimum position and generator field rheostat at

    maximum position.

    4. Start the motor with the help of 3- point starter and adjust the motor field rheostattill the motor reaches to its rated speed

    5.Adjust the field rheostat of the generator till the voltmeter Now close the switch Scarefully.

    6. Decrees the excitation of the motor.Or Increase the excitation of the generator7. That means the M.G set is loaded.8. Take the all meters readings at various conditions.9.After taking the readings open the switch s and then Switch of the motor supply.

  • 5/28/2018 electrical machines -1 lab

    28/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 28

    TABULAR FORM 1:

    s.no Linevoltage

    V2(V)

    LineCurrent

    I1(A)

    Generatorcurrent

    I2(A)

    Motorfield

    currentI3(A)

    Generatorfield

    currentI4(A)

    Motorarmature

    currentIaM(A)I1+I2-I3

    Generatorarmature

    currentIaG(A)I2+I4

    TABULAR FORM 2:

    Totalstraylosses

    (W)

    Straylossesper each

    machine(W/2)

    Totalmotorlosses

    (WM)

    Totalgeneratorlosses

    (WG)

    Inputof motor

    V(I1+I2)

    Output ofMotor

    V(I1+I2)-

    WM

    Output ofgenerator(VI2+WG)

    Input ofgenerator(VI2+WG)

    m

    CALCULATIONS:

    Total stray losses for the Motor Generator set is W

    W=VI1- [(I2+I4)2 Ra+ (I1+I2-I3)

    2 Ra+VI4+ VI3] Watts

    Stray losses per each machine = W/2 Watts

  • 5/28/2018 electrical machines -1 lab

    29/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 29

    MOTOR:Motor total losses WM= ((I1+I2-I3)

    2 Ra+VI3+ W/2 ) Watts

    Motor Input = (V (I1+ I2) ) watts

    Motor Output = (V (I1+ I2) - WM ) watts

    Motor efficiency M = [V (I1+ I2) - WM] / [V (I1+ I2)]

    GENERATOR:Generator total losses WG= ((I2+I4)

    2 Ra +VI4+ W/2)

    Generator output = (VI2 ) watts

    Generator Input = ( VI2+ WG ) watts

    Generator efficiency G= VI2/ (VI2+ WG)

    MODEL GRAPH:

    Motor:

    A graph is plot output of Motor Vs efficiency.

    M

    EFFICIENCY

    OUTPUT OF MOTOR

  • 5/28/2018 electrical machines -1 lab

    30/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 30

    Generator:A graph is plot output of Generator Vs efficiency.

    G

    EFFICIENCY

    OUTPUT OF GENERATOR

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Loads should not be exceeding beyond their rating.4. Proper rating meters should be used.5. Check the connections before giving supply.

    RESULT:Hence the efficiency of the two machines at various load conditions are calculated

    and plotted.

    VIVA QUESTIONS:1. Which loss is obtained from the Hopkinsons test?2. Why Hopkinsons test is also called the regenerative or back-to-back test?3. Is the stray loss obtained from the Hopkinsons test really same for both the

    machines? Why?4. What is the difference between the Swinburnes test and Hopkinsons test?5. Stray loss in a DC machine depends on what quantities?

  • 5/28/2018 electrical machines -1 lab

    31/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 31

    8.FIELDS TEST ON D.C SERIES MACHINES

    AIM:To conduct fields test on two D.C series machines and find out the efficiency of

    Motor and Generator at different loads.

    NAMEPLATE DETAILS:MOTOR GENERATOR

    Power3.7kw 3.7kw

    Wound Series Series

    Armature voltage 220V. 220V.

    Armature current 21A 17A

    Speed 1500. 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C0-300V 2

    0-250V 1

    Ammeter M.C 0-20A 2

    Tachometer --- 1

    Load Resistive 5kw 1

    CIRCUIT DIAGRAM:

  • 5/28/2018 electrical machines -1 lab

    32/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 32

    THEORY:This test is applicable to two similar series machines which are mainly used for

    traction work easily available in pairs. The two machines are coupled mechanically. Onemachine runs normally as a motor and drives generator whose output is wasted in a

    variable load. Iron and friction losses of two machines are made equal by joining the seriesfield winding of generator in the motor armature circuit so that both machines are equallyexcited. By running them at equal speed load resistance is varied till the motor currentreaches its full load value.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Initially put some sufficient load on the series generator.3. Start the motor with the help of 2- point starter.4.Add the loads till the armature current reaches rated value and note down the

    voltages and currents.

    5. Reduce the loads step by step and each step note down the voltages and currentstill the motor speed doesnt exceed safe value.

    6. Keep again sufficient load on the series generator and switch off the motor supply.

    TABULARFORM1:

    S.No TerminalvoltageV1(V)

    MotorVoltageV2(V)

    LineCurrent

    I1(A)

    GeneratorVoltageV2(V)

    LoadCurrentI2(A)

    SpeedN(rpm)

  • 5/28/2018 electrical machines -1 lab

    33/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 33

    TABULARFORM2:

    Totalstraylosses(W)

    Straylossespereachmachine(W/2)

    Totalmotorlosses(WM)

    Totalgeneratorlosses(WG)

    Inputofmotor

    V2I1

    OutputofMotor

    V2I1-WM

    Output ofgeneratorV3I2

    Input ofgenerator(V3I2+WG)

    m

    CALCULATIONS:

    Input of the Motor Generator set is = V1I1 Watts

    Output of the Motor Generator set is = V3I2 Watts

    Total losses of Motor Generator set is W t= (VI1- V3I2) Watts

    Armature and field losses of the M.G. set

    Wcu= ((Ra+2Rse) I12+ I2

    2 Ra) Watts

    Total stray losses for the Motor Generator set is W = W t-Wcu

    Stray losses per each machine Ws= W/2 Watts

    MOTOR:Motor total losses WM= ((Ra+Rse) I1

    2+ Ws) Watts

    Motor Input = V2I1watts

    Motor Output = ( V2I1- WM) watts

    Motor efficiency M = [V2I1- WM] / [V2I1]

  • 5/28/2018 electrical machines -1 lab

    34/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 34

    GENERATOR:

    Generator total losses WG= ( I22 Ra +I1

    2Rse+ Ws) Watts

    Generator output = V3I2watts

    Generator Input = ( V3I2+ WG) watts

    Generator efficiency G = V3I2/ (V3I2+ WG)

    MODEL GRAPH:

    MOTOR:A graph is plot output of Motor Vs efficiency.

    M

    EFFICIENCY

    OUTPUT OF MOTOR

  • 5/28/2018 electrical machines -1 lab

    35/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 35

    GENERATOR:A graph is plot output of Generator Vs efficiency.

    G

    EFFICIENCY

    OUTPUT OF GENERATOR

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 2- point starter carefully.3. Loads should not be exceeding beyond their rating.4. Dont run the motor above safe speed.5. Check the connections before giving supply.

    RESULT:

    Hence the efficiency of the two series machines at various loadConditions are calculated and plotted.

    VIVA QUESTIONS:

    1. What is the usual range of field winding resistance in case of a DC series machine?2. What is field test and on what type of DC machines it is performed?3. How are large series machines tested?4. How to minimize the eddy current & hysteresis losses in case of a DC machine?5. How a DC series motor can be used as DC shunt motor?

  • 5/28/2018 electrical machines -1 lab

    36/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 36

    9.SPEED CONTROL OF D.C SHUNT MOTOR

    AIM:To determine the speed control characteristics of D.C shunt motor by

    1.Armature control.2. Field control.

    NAMEPLATE DETAILS:D.C SHUNT MOTOR

    Power5hp

    Wound Shunt

    Armature voltage 220V.Armature current 20A

    Excitation 220V, 0.75A

    Speed 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter

    M.C

    0-300V1

    Ammeter M.C0-2A 1

    Rheostat___

    0-300 , 1.7A1

    0-36 , 12A1

    Tachometer ---1

  • 5/28/2018 electrical machines -1 lab

    37/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 37

    CIRCUITDIAGRAM:

    THEORY:

    The speed of the DC shunt motor can be controlled by two methods they are:Flux control:

    The speed equation of DC motor is N1/. By decreasing the flux, speed isincreases. The flux of DC motor can be changed by shunt field current with the help ofshunt field rheostat. Shunt field current is small which means I2R loss is small. In thismethod speed control above rated speed is possible.Armature control:

    In this method the supply voltage is normally constant. The voltage across thearmature is varied by inserting a variable rheostat in series with the armature circuit. Ascontroller resistance is increases potential difference across the armature decreases. Sospeed control below rated speed is possible.

    PROCEDURE:

    1. Connect the circuit as per the circuit diagram.2. Keep the all rheostat at minimum resistance position.3. Start the motor with the help of 3- point starter and

    initially maintain the field current at some constant value.4. Now slowly increases the armature resistance by adjust the rheostat and note the

    corresponding voltage V and speed N.5.Again set the fields current If at some other constant value and done the above

    process.

  • 5/28/2018 electrical machines -1 lab

    38/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 38

    6. Now set the armature voltage at some constant value and increase the fieldresistance by adjusting the rheostat and note the corresponding field current I fandspeed N.

    7. Again set the armatures voltage at some other constant value and done the aboveprocess.8. Draw the relating graphs.

    Observation Table:Field Control current control method:

    Eb= Eb=

    Armature voltage control method:

    If= If=

    S.noField current

    (If)Speed

    (N)

    S.noField current

    (If)Speed

    (N)S.noField current

    (If)Speed

    (N)

    S.no Field current(If)

    Speed(N)

  • 5/28/2018 electrical machines -1 lab

    39/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 39

    MODEL GRAPH:Armature voltage control method:

    A graph is drawn between Armature voltage V and speed N.

    N

    VArmature voltage

    Field Control current control method:

    A graph is drawn between field current Ifand speed N.

    N

    If

    S

    PEED

    SPE

    ED

  • 5/28/2018 electrical machines -1 lab

    40/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 40

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Dont run the motor above safe speed.

    RESULT:

    Hence the speed control of D.C shunt motor by armature control and field controlare obtained.

    VIVA QUESTIONS:

    1. On what factors does the speed of a DC motor depend?2. How can the speed of a DC shunt motor be controlled by field control method?3. What will be the effect on the speed of a DC shunt motor if an additional resistance

    is introduced in the field circuit?4. Do the motors run faster in series combination or parallel combination? 5. Why is it not possible to obtain speed of a DC shunt motor above normal by

    armature resistance control?

  • 5/28/2018 electrical machines -1 lab

    41/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 41

    10.SEPARATION OF LOSSES IN DC SHUNT MOTOR

    AIM:

    To separate the losses in a D.C shunt Motor.

    NAMEPLATE DETAILS:D.C SHUNT MOTOR

    Power5hp

    Wound Shunt

    Armature voltage 220V.

    Armature current 20A

    Excitation 220V, 0.9A

    Speed 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-250V 1

    Ammeter M.C0-2A 1

    0-5A 1

    Rheostat___

    0-300 , 1.7A1

    0-150 , 5A1

    Tachometer---

    1

  • 5/28/2018 electrical machines -1 lab

    42/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 42

    CIRCUITDIAGRAM:

    THEORY:It is the simplest indirect method of testing dc machines in which the losses are

    measured separately and efficiency at any desired load is predetermined. In this testvarious losses in a dc machine can be found into their components. The dc machine is runat no-load by varying the speed and keeping the excitation constant. If N is the speed ofthe shunt motor at any given time, then the frictional losses are found to be proportional to

    N.similarly the windage losses are found to be proportional to N2.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Keep the all rheostat at minimum resistance position.3. Start the motor with the help of 3- point starter.4.Adjust the speed of the motor to rated speed by adjusting the field rheostat.5. Note down the speed, voltage across armature and armature current.6. Keeping the field excitation constant. The speed of the motor can be varied by

    controlling the armature voltage by varying the armature resistance.

    7. The experiment is repeated at of the field current

  • 5/28/2018 electrical machines -1 lab

    43/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 43

    TABULAR FORM 1:

    S.No Speed

    N(rpm)

    Armature

    Voltage V

    (volts)

    Armature

    Current I

    (Amp)

    Cu losses

    Ia2Ra

    (Watts)

    Input

    VIa(Watts)

    Constant

    losses W

    (Watts)

    W/N

    Field current If=

    S.No.Speed(rpm)

    ArmatureVoltage

    (V)

    ArmatureCurrent

    (A)

    ArmatureCupperlosses

    IaRa (W)

    InputVIa(W)

    ConstantLosses

    = VIa-IaRa (W)WN

  • 5/28/2018 electrical machines -1 lab

    44/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 44

    MODEL GRAPH:

    W

    N

    P - - - - - -- - - -- - - - - - - - - - - - - - - - - - - - - -

    R - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    Speed (N) (rpm)

    PRECAUTIONS:1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Dontrun the motor above safe speed.

    RESULT:Hence the separation of losses in a DC shunt motor was obtained.

    VIVA QUESTIONS:

    1. On what factors do hysteresis and eddy current losses depend?2. Why mechanical losses occur in a DC machine?3. What are the magnetic losses in a DC machine?4. Why do iron losses occur in a DC machine?5. Does core loss occur in armature or in the poles of a DC machine?

  • 5/28/2018 electrical machines -1 lab

    45/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 45

    11.BRAKE TEST ON DC COMPOUND MOTOR

    AIM:To find the efficiency of D.C compound motor by a direct load test.

    NAMEPLATE DETAILS:D.C COMPOUND MOTOR

    Power3.7kw

    Wound Compound

    Armature voltage 220V.

    Armature current 20.5A

    Excitation 220V, 0.9A

    Speed 1500rpm.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-250V1

    Ammeter M.C0-20A 1

    Rheostat___

    0-300 , 1.7A1

    Tachometer ---1

  • 5/28/2018 electrical machines -1 lab

    46/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 46

    CIRCUIT DIAGRAM:

    THEORY:

    It is a direct method and consists of applying a brake to a water cooled pulleymounted on the shaft of motor. The brake band is fixed with the help of wooden blocksgripping the pulley one end of the band is fixed to earth a spring balance and other isconnected to a suspended weight. The motor is running and the load on the motor isadjusted till it carries its full load current. The simple brake test described above can beused for small motors only. Because, in the case of large motors, it is difficult to dissipatethe large amount of heat generated at the brake.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2.

    Keep the motor field rheostat at minimum position.3. Start the motor with the help of 3- point starter and adjust the motorfield rheostat till the motor reaches to its rated speed.

    4. Now gradually apply the mechanical load by tightening the belt over theshaft.

    5. Note the corresponding spring balance readings, line current, Voltageand speed at particular load.

    6. Repent the above process at different load condition.

  • 5/28/2018 electrical machines -1 lab

    47/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 47

    7. Before the motor going to be switched off the motor must be in no loadcondition.

    8. Using the above data deter mine the efficiency of the Compound motor.

    CALCULATIONS:

    Shaft torque = (S1-S2) x rx 9.81 (r = 0.146 m)= (2N) /60.Shaft O/P = Shaft Torque X

    Efficiency= X100

    TABULAR FORM:

    S.No Voltage

    (V)

    Current

    (A) S1(kg) S2(kg) Speed(rpm) InputPower(W) ShaftTorque(N-M)

    rad/sec Efficien%

    GRAPHS:Graphs are plotted between1. Speed and output2. Speed and torque3. Current and torque

    4. Efficiency and out put

    Shaft O/PPower I/P

  • 5/28/2018 electrical machines -1 lab

    48/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 48

    MODEL GRAPH:

    N N IL % O/PVs %

    TVSIL

    TVSN

    ILVSN

    Output(W)

    Torque(N-m)

    Torque(N-m)

    IL(A)

    PRECAUTIONS:

    1. Loose connection should be avoided.2. Operate the 4- point starter carefully.3. Cool the shaft pulley with water.4. Proper rating meters should be used.5. Check the connections before giving supply.

    RESULT:Hence the efficiency of the D.C compound motor at various load

    Conditions are calculated and plotted.

  • 5/28/2018 electrical machines -1 lab

    49/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 49

    VIVA QUESTIONS:

    1. What is brake test?2. What is the main drawback of brake test?3. Why brake test is performed with the small machines only?4. What is the condition for maximum output in a DC motor?5. What are the possible causes of sparking at brushes?

  • 5/28/2018 electrical machines -1 lab

    50/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 50

    12.RETARDATION TEST ON DC SHUNT MOTOR

    AIM:To conduct retardation test on a given DC machine

    NAMEPLATE DETAILS:D.C SHUNT MOTOR

    Power5hp

    Wound Shunt

    Armature voltage 220V.

    Armature current 20AExcitation 220V, 0.9A

    Speed 1500.

    APPARATUS:

    Name Type Range Qty

    Voltmeter M.C 0-300V 1

    Ammeter M.C0-5A 1

    Rheostat___

    0-300 , 1.7A1

    0-1500 , 15A0-500,5A 2

    Tachometer ---1

  • 5/28/2018 electrical machines -1 lab

    51/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 51

    CIRCUITDIAGRAM:

    THEORY:This test is also known as running down test. It is used for finding out the stray

    power losses of shunt wound DC machines. In this method of testing dc machines,machine under test is speeded up slightly above its normal speed and supply to the

    armature is cut off. Consequently the armature slows down and its kinetic energy is utilizedto meet the rotational losses. The voltmeter connected across the armature shows theinstantaneous back emf of the motor. Since back emf of the motor is directly proportionalto speed, therefore, the voltmeter can be suitably calibrated to indicate speed. When thesupply to armature is cut off, the speed of the motor decreases.

    PROCEDURE:1. Connect the circuit as per the circuit diagram.2. Run the motor at a speed slightly higher than rated speed by

    adjusting field external rheostat..

    3. Disconnect the armature circuit from supply by opening switch S.4. Note down the time taken for the machine to come down to zero

    speed.5. Now, once again start the motor and run at a speed slightly higher

    than rated speed.6. Disconnect the armature circuit from supply and connect it across

    the rheostat by throwing switch S into the position 1& 2.7. Note down the readings of voltmeter and ammeter for two speeds

    and time taken for the machine to come down to zero speed.

  • 5/28/2018 electrical machines -1 lab

    52/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 52

    OBSERVATIONS

    Without load: With load:

    Time taken = seconds (with load)

    CALCULATIONS:

    Rotational losses W=W

    (dt2)(dt1-dt2)Where W

    =average load power=VavgIavgwatts

    dt2is the time taken for the speed to come down from N1to N2with load.

    dt1is the time taken for the speed to come down from N1to N2under no-load.

    S .no Speed

    (rpm)

    Time

    (sec) S .no Speed

    (rpm)

    Time

    (sec)

    Speed (rpm) V IL Vav IavN1=

    N2=

  • 5/28/2018 electrical machines -1 lab

    53/53

    Electrical Machines-I Lab

    EEE Department,GIST-Jaggayyapet Page 53

    MODEL GRAPH:speed (rpm)

    N1 No-load

    N2

    With load

    Time (sec)

    PRECAUTIONS:

    1. Loose connection should be avoided.2. Operate the 3- point starter carefully.3. Dont run the motor above safe speed.

    RESULT:Hence the separation of losses in a DC shunt motor was obtained.

    VIVA QUESTIONS:

    1. What is retardation test and on what type of dc machines it is performed?2. What are the stray losses in a DC machine? 3. The lost torque in a DC motor is proportional to which loss?