CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WM EcoSystem Bus Supply 369973c 1 04.07.17 SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: EcoSystem Bus Supply An EcoSystem lighting network containing more than one ballast, module, or driver requires an EcoSystem Bus Supply. This supply powers one or two independent EcoSystem buses with up to 64 ballasts or ballast modules per bus. Features • Provides power for either one or two EcoSystem buses, depending on model. • Reprograms settings of replacement ballasts automatically. • Maintains redundant memory of ballast and module programming for building sustainability. • Accepts up to two normally open or normally closed dry contact closures per bus to allow integration with occupancy sensors, demand response inputs, or AV equipment. • Accepts one normally closed emergency input per supply to allow integration with building management and/or security systems. • EcoSystem Bus may be wired NEC® Class 1, IEC PELV or NEC® Class 2. • Bus wires are polarity insensitive and topology free • Voltage input: 100–277 V~ 50/60 Hz. • Non-volatile (EEPROM) memory stores specific system information for 10 years from power-down to power restoration. • 100% performance tested at factory. • Allows programming via the EcoSystem Programmer. Programming can be locked out via DIP switch. 12345678 H/L H/L N N ON E1 E1 E2 E2 B A C C / / Em C ERR EMG BUS STAT V~ PWR Front View (CS-1L shown) E1 E1 E2 E2 B A C C / / Em C Bottom View (CS-1L shown) H/L H/L N N Top View (CS-1L shown) Side View Model Number Links Enclosure CS-1L-CM 1 No CS-1L-WM 1 Yes CS-2L-CM 2 No CS-2L-WM 2 Yes Building a Model Number CS X L X M Power Provided Code Number of Buses Powered 1 1 EcoSystem Bus 2 2 Independent EcoSystem Buses Enclosure Code Enclosure C Not shipped with an enclosure W Unit premounted in UL-listed 8 × 8 × 4 in (203 × 203 × 102 mm) enclosure

Transcript of EcoSystem Bus Supply SPEC (369973) - Lutron Electronics · EcoSystem S1 S1 S S Bus Supply 369973c 1...

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 1 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem Bus SupplyAn EcoSystem lighting network containing more than one ballast, module, or driver requires an EcoSystem Bus Supply. This supply powers one or two independent EcoSystem buses with up to 64 ballasts or ballast modules per bus.

Features•ProvidespowerforeitheroneortwoEcoSystem

buses, depending on model.•Reprogramssettingsofreplacementballasts

automatically.•Maintainsredundantmemoryofballastandmoduleprogrammingforbuildingsustainability.

•Acceptsuptotwonormallyopenornormallycloseddry contact closures per bus to allow integration with occupancy sensors, demand response inputs, or AV equipment.

•Acceptsonenormallyclosedemergencyinputpersupply to allow integration with building management and/or security systems.

•EcoSystemBusmaybewiredNEC®Class 1,IEC PELVorNEC®Class 2.

•Buswiresarepolarityinsensitiveandtopologyfree•Voltageinput:100–277 V~50/60 Hz.•Non-volatile(EEPROM)memorystoresspecificsysteminformationfor10 yearsfrompower-downtopowerrestoration.

•100%performancetestedatfactory.•AllowsprogrammingviatheEcoSystemProgrammer.ProgrammingcanbelockedoutviaDIPswitch.

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

Front View (CS-1Lshown)

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

Bottom View (CS-1Lshown)

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

Top View (CS-1Lshown)

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

Side View

Model Number Links EnclosureCS-1L-CM 1 NoCS-1L-WM 1 YesCS-2L-CM 2 NoCS-2L-WM 2 Yes

Building a Model Number

CS – XL – XM

Power ProvidedCode Number of Buses Powered

1 1 EcoSystem Bus2 2IndependentEcoSystemBuses

EnclosureCode EnclosureC Notshippedwithanenclosure

W UnitpremountedinUL-listed8×8×4in (203×203×102mm)enclosure

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c204.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Specifications

Regulatory Approvals•UL,CUL,andNOMlisted•MeetsANSIC62.41CategoryAsurgeprotection

standards up to and including 4 kV.•LutronQualitySystemsregisteredtoISO 9001.2000•Forcommercialuse,ClassAonly

Power•InputVoltage:100–277 V~50/60 Hz•OutputVoltage:18 V-250 mAmaximum NEC®Class 1,IEC PELVorNEC®Class 2perbus•Devicedrawslessthan0.18 A.

Wiring•PowerWiring:12–18 AWG(1.0–4.0 mm2)•EcoSystemBus,Class2contactclosures:12–22 AWG(0.5–2.5 mm2)

Mounting Considerations•RequiresUL508listedenclosureperNEC(customer-suppliedifCMmodel).

•EnclosureprovidedifWMmodelisordered.•MountstostandardDINrail(included).

Environment•AmbientTemperatureOperatingRange:32–104 °F(0–40 °C)

•Relativehumidity:lessthan90%non-condensing

EcoSystem Lighting Network Example•EcoSystemBusmaybewiredinaccordancewithNEC®Class 1,IEC PELVorNEC®Class 2practices.

•SensorsandEcoSystemBusSupplycontactclosuresmustbewiredIEC PELVorNEC®Class 2.

12

34

56

78

EcoSystem Bus

EcoSystem Ballast

EcoSystem Module

EcoSystem Ballast

EcoSystem Ballast

Eco-10orHi-lumeBallast*

IRReceiver

Occupancysensor

To additional ballasts and modules (upto64 total)

Keypad

DaylightSensor

LightingRemote

EcoSystem Bus Supply

(CS-1Lshown)

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 3 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

DimensionsMeasurementsareshownas:in(mm)

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

12

34

56

78

H/L H/L N N

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

12345678

H/LH/LNN

H/LH/LNN

ON

E1E1E2E2BACC//EmC

E1E1E2E2BACC//EmC

ERREMG

BUS

STAT

V~ PWR

Front View

Top View

Bottom View

Left-Side View Right-Side View

1.77(45)

3.62(92)3.62(92)

3.56 (85)

3.62(92)

3.62(92)

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 4 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Mounting

CM Models•SelectaUL508listedelectricalenclosurewithminimumdimensions(w × h × d):8 × 8 × 4 in(203 × 203 × 102 mm).

•Mountenclosureasperapplicableinstructions.•MountDINrailhorizontallyinthecenterofthe

enclosure.•CliptheEcoSystemBusSupplyontoDINrail(seediagrambelow).

CS-1/2L-(CS-1Lshown)Measurementsareshownas:in(mm)

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C / / Em C

ERREMG

BUS

STAT

V~ PWR

Knockoutsforwiring:f0.75(19)MountingHoles

6(152)

8(203)1(25),typically

8(203)

6(152)

4(102)

4(102)

WM Models•Mountenclosureusingthefourmountingholeswithintheenclosure(shownbelow).

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 5 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring: Overview

Mains Wiring and Low-Voltage Separation•TheEcoSystem® Bus Supply is designed to separate mainswiring(NEC®Class 1)andlow-voltageIEC PELVorNEC®Class 2circuits

•Followappropriatelocalandnationalcodestoavoidviolating required separation guidelines

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

CS-2L- shown

Tofirstbusballasts and modules

To second bus ballasts and modules(2Lversiononly)

LineVoltageWiringArea

LowVoltageWiringArea

Ground

Hot/Live

Neutral

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 6 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring: Overview(continued)

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

Top View(CS-2L-shown)

Mains Wiring Terminal(black)Neutral

Hot/Live

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

Front View(CS-2L-shown)

Option (OPT) Switches

LED Indicator Lights:Bus2(green)Error/Emergency(CS-2Lonly)

Bus2(green)Status CS-2Lonly)

Bus1(blue)Error/Emergency

Bus1(blue)Status

MainsStatus

MainsPower

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

Bottom View(CS-2L-shown)EcoSystem Bus 1 (blue)Terminal:E2

E1

EcoSystem Bus 2(green) Terminal(CS-2Lonly):E1

E2

Contact Closure Bus 1 (red)Terminal:EcoSystemBus1CCICom

EcoSystemBus1CCI1

EcoSystemBus1CCI2

EmergencyContactClosure

Contact Closure Bus 2(red) Terminal(CS-2Lonly):EcoSystemBus2CCI2

EcoSystemBus2CCI1

EcoSystemBus2CCICom

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 7 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring: Line Voltage (Mains)

Wiring from Distribution to Bus Supply•SelectsourceoffeedfortheEcoSystemBusSupply(100–277 V~).

•Turnoffbreakeratdistributionpanel.•Runhot,neutral,andgroundwiresfromdistribution

panel to the EcoSystem Bus Supply.•TheEcoSystemBusSupplyisgroundedviagroundclipsonbottomofmodulethroughtheDINrail.EnsurethattheenclosureandDINrailareproperlygroundedper national and local electrical codes.Note:Ballasts,modules,anddriversareinemergency(bypass)mode(lightsatfulloutput)untilpowerisapplied to the EcoSystem Bus Supply.Emergency Feeds and the Bus Supply

•Usenormal(non-essential)poweronly.•Whennormalpowerdropsout,theEcoSystemBusSupplycannotpowertheEcoSystemBus.Whenthis occurs, ballasts, modules, and drivers go to emergency(bypass)mode(fulllightoutputbydefault).

SeeApplicationNote#140foradditionalinformationrelatedtoemergencyfeedwiring.

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

CS-1L- shown

Ground

Hot/Live

Neutral

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c804.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring: EcoSystem BusThe EcoSystem Bus connects all ballasts together and requiresaBusSupply.1LmodelspoweroneEcoSystemBus;2LmodelspowertwoindependentEcoSystem buses. Each EcoSystem Bus can support amaximumof64ballasts,modules,ordrivers.

Class 1 and Class 2 Wiring•TheEcoSystemBusmaybeNEC®Class 1,IEC PELVorNEC®Class 2–NEC®Class 1:Low-voltagebuswiringmayberunwithmainsvoltagetoanyfixturethebusiscontrolling

–IEC PELVorNEC®Class 2:Low-voltagebuswiringmustbeseparatedfromallmainsandClass 1wiring

•UsingtwodifferentcolorsforE1andE2wirehelpsprevent miswires when multiple buses are present in the same conduit

•Consultallnationalandlocalelectricalcodesforseparation requirements

Wiring Details•E1andE2wiresarenotpolaritysensitive•BuslengthislimitedbythewiregaugeusedforE1andE2asfollows:

Wire Gauge Bus Length(max)12 AWG(4.0 mm2) 2200 ft(671 m)14 AWG(2.5 mm2) 1400 ft(427 m)16 AWG(1.5 mm2) 900 ft(275 m)18 AWG(1.0 mm2) 570 ft(175 m)

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

ERREMG

BUS

STAT

V~ PWR

/ / Em C

CS-1L- shown

E1 E2

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 9 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Wiring: Contact ClosuresContactclosureinputsareIEC PELVorNEC®Class 2circuits and cannot be run with mains wiring. Unless otherwisespecified,thevoltagesshouldnotexceed12–35 V-. These circuits comply with the requirementsofNFPA 70,NationalElectricCode(NEC®).Followallapplicablenationaland/orlocalwiring regulations.

Contact Closure Bus Terminals

Terminal Unit Label FunctionC COM CommonEm CCI-EMERG EmergencyA CCI-1 ContactClosure 1B CCI-2 ContactClosure 2

EmergencyForintegrationwithasecurityorfirealarmsystem,the emergency input may be used. The alarm system musthaveanormallyclosedrelayforproperoperation.Wiringisshowntotheright.CommonisTerminal CandEmergencyisTerminal EmontheEcoSystemBusSupply.Ona2-linksupply,thereisonlyoneEmergencyInput,whichaffectsbothlinks.EmergencymodemustbeactivatedusingOPTswitch 5.Bydefaultemergencyinputsareignored(DIPswitch 5setto“ON”).Whenswitch 5is“OFF”anopenconditionbetweenterminals 5and6resultsinemergency mode activation.

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

Bottom View(CS-2L-shown)

Contact Closure Bus 1 (red)Terminal:EcoSystemBus1CCICom

EcoSystemBus1CCI1

EcoSystemBus1CCI2

EmergencyContactClosure

Contact Closure Bus 2(red) Terminal(CS-2Lonly):EcoSystemBus2CCI2

EcoSystemBus2CCI1

EcoSystemBus2CCICom

C Em A B

C Em

NCSecurityContactor

Emergency Input

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 10 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Operation: Contact Closures

Contact Closure InputsContactClosureInputs(CCI)ontheBusSupplymaybeusedtointegrateaBMSsystemoroccupancysensorswithanEcoSystemLightingNetwork.Ona2-linksupply,thereisonepairofCCIsforeachEcoSystem Bus.TherearethreemodesofCCIoperation:

•Occupancymode•DemandResponsemode•SceneSelectionmodeThesemodescanbeselectedandconfiguredusingtheEcoSystemProgrammer.Occupancy ModeCCIscommandassignedgroupsonthecorrespondingbustoan“Occupied”lightleveloran“Unoccupied”lightlevelwhenthecontactclosuresareopened or closed.

•WhentheCCIisinthe“occupied”state,thesystemwillcommandballastsassignedtothatCCItogototheir“occupied”level.

•WhentheCCIisinthe“unoccupied”mode,thesystemwillcommandballastsassignedtothatCCItogototheir“unoccupied”level.NotethatifballastsaregroupedtobothaCCIinOccupancymodeandanoccupancysensor,theoccupancy sensor will not sweep the group to its unoccupiedlevelunlesstheCCIisalsounoccupied.Demand Response ModeIndemandresponsemode,eachCCI,whenclosed,appliesaconfigurable“demandresponse”leveltothegroup.WhentheCCIisopened,thedemandresponse level is cleared.Ballasts will scale their current light level by the demandresponselevel(e.g.,ifthedemandresponselevelissetto25%,allballastswilldimtoalightlevelthatis75%oftheirpreviouslevelandwillnotdimabove75%untiltheCCIisopened).CCI-2takespriorityoverCCI-1,soifthesamegroupofballastsareassignedtobothCCIs,whenbothCCIsareclosed,theballastswillscaletothelevelsetforCCI-2.

Scene Select ModeWhentheCCIsareclosedandmaintainedaccordingto the table below, the corresponding scene is selectedonallballastsonthelink.MomentarycontactinputsmaybeusedifScene 1issetto“Unaffected”.

CCI 1 CCI 2 SceneOpen Open 1Closed Open 2Open Closed 3Closed Closed 4

SeeApplicationNote#236forfurtherinformationonEcoSystem Bus Supply contact closure input modes.

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 11 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Operation: Status LEDsLEDsontheEcoSystemBusSupplyindicatenetworkstatus.ThespecificLEDs,colorandflashingmethodis detailed below.

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

LED Normal Operation

Problem Indicator

Probable Cause

ERR/EMG OffOn Emergency contact

closure is activeSteady flash

Miswiredetectedoncorresponding bus

BUS Intermittent flashorOff On Unitfault

STAT Steady flash

Off NoMainspowerorunitfault

On Unitfault

V~PWR On Off NoMainspower

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c1204.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Operation: OPT SwitchesOPTswitchesareusedtoconfiguretheBusSupply.The table below describes the options.ToplaceanOPTswitchintheOFFposition,slidetheswitchtotheleft.DefaultswitchpositionisON.

12

34

56

78

H/L H/L N N

ON

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

ERREMG

BUS

ERREMG

BUS

STAT

V~ PWR

E1 E1 E2 E2B A C C

E1 E1 E2 E2B A Em C

H/L H/L N N

OPT Description Switch Position Function

1 Firstbus(green)CCI-1inputtype

ON Normallyopen1 (default)

OFF Normallyclosed2

2 Firstbus(green)CCI-2inputtype

ON Normallyopen1 (default)

OFF Normallyclosed2

33 Secondbus(blue)CCI-1inputtype

ON Normallyopen1 (default)

OFF Normallyclosed2

43 Secondbus(blue)CCI-2inputtype

ON Normallyopen1 (default)

OFF Normallyclosed2

5 Emergency disable

ON

Emergency contact closure input disabled (default)

OFFEmergency contact closure input enabled

6 Programming

ON

Programmingenabled via EcoSystem programmer (default)

OFF

Programmingdisabled via EcoSystem programmer

7,8 Normal/Override

7 ON,8 ON Normaloperation(default)

7 ON,8 OFF Override: Highend

7 OFF,8 ON Override: Lowend

7 OFF,8 OFF Override: Off

12

34

56

78

ON

12

34

56

78

ON

OPTSwitchOFF

OPTSwitchON

CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply

369973c 13 04.07.17

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Operation: Combining Occupancy Sensors with CCIsOccupancysensorswithrelayoutputscanbewiredtothecontactclosureinputsonthebussupply.Followthe diagram below.Occupancysensorrelayoutputscanbenormallyopenornormallyclosed.SettheOPTswitchfortheCCItomatchthetypeofsensoroutputbeingused.

Occupancysensor(rearview)

Relayoutput

Common

+24 V-

120~ or 277 V~

Bus supply

Toterminals:C:CommonA:CCI 1orB:CCI 2

PowerPackPP-120H(for120 V~)

orPP-277H(for277 V~)

Lutron,Lutron,Eco-10,Hi-lume,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.