CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 1 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Bus SupplyAn EcoSystem lighting network containing more than one ballast, module, or driver requires an EcoSystem Bus Supply. This supply powers one or two independent EcoSystem buses with up to 64 ballasts or ballast modules per bus.
Features•ProvidespowerforeitheroneortwoEcoSystem
buses, depending on model.•Reprogramssettingsofreplacementballasts
automatically.•Maintainsredundantmemoryofballastandmoduleprogrammingforbuildingsustainability.
•Acceptsuptotwonormallyopenornormallycloseddry contact closures per bus to allow integration with occupancy sensors, demand response inputs, or AV equipment.
•Acceptsonenormallyclosedemergencyinputpersupply to allow integration with building management and/or security systems.
•EcoSystemBusmaybewiredNEC®Class 1,IEC PELVorNEC®Class 2.
•Buswiresarepolarityinsensitiveandtopologyfree•Voltageinput:100–277 V~50/60 Hz.•Non-volatile(EEPROM)memorystoresspecificsysteminformationfor10 yearsfrompower-downtopowerrestoration.
•100%performancetestedatfactory.•AllowsprogrammingviatheEcoSystemProgrammer.ProgrammingcanbelockedoutviaDIPswitch.
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
Front View (CS-1Lshown)
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
Bottom View (CS-1Lshown)
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
Top View (CS-1Lshown)
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
Side View
Model Number Links EnclosureCS-1L-CM 1 NoCS-1L-WM 1 YesCS-2L-CM 2 NoCS-2L-WM 2 Yes
Building a Model Number
CS – XL – XM
Power ProvidedCode Number of Buses Powered
1 1 EcoSystem Bus2 2IndependentEcoSystemBuses
EnclosureCode EnclosureC Notshippedwithanenclosure
W UnitpremountedinUL-listed8×8×4in (203×203×102mm)enclosure
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c204.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals•UL,CUL,andNOMlisted•MeetsANSIC62.41CategoryAsurgeprotection
standards up to and including 4 kV.•LutronQualitySystemsregisteredtoISO 9001.2000•Forcommercialuse,ClassAonly
Power•InputVoltage:100–277 V~50/60 Hz•OutputVoltage:18 V-250 mAmaximum NEC®Class 1,IEC PELVorNEC®Class 2perbus•Devicedrawslessthan0.18 A.
Wiring•PowerWiring:12–18 AWG(1.0–4.0 mm2)•EcoSystemBus,Class2contactclosures:12–22 AWG(0.5–2.5 mm2)
Mounting Considerations•RequiresUL508listedenclosureperNEC(customer-suppliedifCMmodel).
•EnclosureprovidedifWMmodelisordered.•MountstostandardDINrail(included).
Environment•AmbientTemperatureOperatingRange:32–104 °F(0–40 °C)
•Relativehumidity:lessthan90%non-condensing
EcoSystem Lighting Network Example•EcoSystemBusmaybewiredinaccordancewithNEC®Class 1,IEC PELVorNEC®Class 2practices.
•SensorsandEcoSystemBusSupplycontactclosuresmustbewiredIEC PELVorNEC®Class 2.
12
34
56
78
EcoSystem Bus
EcoSystem Ballast
EcoSystem Module
EcoSystem Ballast
EcoSystem Ballast
Eco-10orHi-lumeBallast*
IRReceiver
Occupancysensor
To additional ballasts and modules (upto64 total)
Keypad
DaylightSensor
LightingRemote
EcoSystem Bus Supply
(CS-1Lshown)
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 3 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
DimensionsMeasurementsareshownas:in(mm)
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
12
34
56
78
H/L H/L N N
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
12345678
H/LH/LNN
H/LH/LNN
ON
E1E1E2E2BACC//EmC
E1E1E2E2BACC//EmC
ERREMG
BUS
STAT
V~ PWR
Front View
Top View
Bottom View
Left-Side View Right-Side View
1.77(45)
3.62(92)3.62(92)
3.56 (85)
3.62(92)
3.62(92)
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 4 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
CM Models•SelectaUL508listedelectricalenclosurewithminimumdimensions(w × h × d):8 × 8 × 4 in(203 × 203 × 102 mm).
•Mountenclosureasperapplicableinstructions.•MountDINrailhorizontallyinthecenterofthe
enclosure.•CliptheEcoSystemBusSupplyontoDINrail(seediagrambelow).
CS-1/2L-(CS-1Lshown)Measurementsareshownas:in(mm)
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C / / Em C
ERREMG
BUS
STAT
V~ PWR
Knockoutsforwiring:f0.75(19)MountingHoles
6(152)
8(203)1(25),typically
8(203)
6(152)
4(102)
4(102)
WM Models•Mountenclosureusingthefourmountingholeswithintheenclosure(shownbelow).
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 5 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring: Overview
Mains Wiring and Low-Voltage Separation•TheEcoSystem® Bus Supply is designed to separate mainswiring(NEC®Class 1)andlow-voltageIEC PELVorNEC®Class 2circuits
•Followappropriatelocalandnationalcodestoavoidviolating required separation guidelines
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
CS-2L- shown
Tofirstbusballasts and modules
To second bus ballasts and modules(2Lversiononly)
LineVoltageWiringArea
LowVoltageWiringArea
Ground
Hot/Live
Neutral
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 6 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring: Overview(continued)
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
Top View(CS-2L-shown)
Mains Wiring Terminal(black)Neutral
Hot/Live
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
Front View(CS-2L-shown)
Option (OPT) Switches
LED Indicator Lights:Bus2(green)Error/Emergency(CS-2Lonly)
Bus2(green)Status CS-2Lonly)
Bus1(blue)Error/Emergency
Bus1(blue)Status
MainsStatus
MainsPower
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
Bottom View(CS-2L-shown)EcoSystem Bus 1 (blue)Terminal:E2
E1
EcoSystem Bus 2(green) Terminal(CS-2Lonly):E1
E2
Contact Closure Bus 1 (red)Terminal:EcoSystemBus1CCICom
EcoSystemBus1CCI1
EcoSystemBus1CCI2
EmergencyContactClosure
Contact Closure Bus 2(red) Terminal(CS-2Lonly):EcoSystemBus2CCI2
EcoSystemBus2CCI1
EcoSystemBus2CCICom
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 7 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring: Line Voltage (Mains)
Wiring from Distribution to Bus Supply•SelectsourceoffeedfortheEcoSystemBusSupply(100–277 V~).
•Turnoffbreakeratdistributionpanel.•Runhot,neutral,andgroundwiresfromdistribution
panel to the EcoSystem Bus Supply.•TheEcoSystemBusSupplyisgroundedviagroundclipsonbottomofmodulethroughtheDINrail.EnsurethattheenclosureandDINrailareproperlygroundedper national and local electrical codes.Note:Ballasts,modules,anddriversareinemergency(bypass)mode(lightsatfulloutput)untilpowerisapplied to the EcoSystem Bus Supply.Emergency Feeds and the Bus Supply
•Usenormal(non-essential)poweronly.•Whennormalpowerdropsout,theEcoSystemBusSupplycannotpowertheEcoSystemBus.Whenthis occurs, ballasts, modules, and drivers go to emergency(bypass)mode(fulllightoutputbydefault).
SeeApplicationNote#140foradditionalinformationrelatedtoemergencyfeedwiring.
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
CS-1L- shown
Ground
Hot/Live
Neutral
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c804.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring: EcoSystem BusThe EcoSystem Bus connects all ballasts together and requiresaBusSupply.1LmodelspoweroneEcoSystemBus;2LmodelspowertwoindependentEcoSystem buses. Each EcoSystem Bus can support amaximumof64ballasts,modules,ordrivers.
Class 1 and Class 2 Wiring•TheEcoSystemBusmaybeNEC®Class 1,IEC PELVorNEC®Class 2–NEC®Class 1:Low-voltagebuswiringmayberunwithmainsvoltagetoanyfixturethebusiscontrolling
–IEC PELVorNEC®Class 2:Low-voltagebuswiringmustbeseparatedfromallmainsandClass 1wiring
•UsingtwodifferentcolorsforE1andE2wirehelpsprevent miswires when multiple buses are present in the same conduit
•Consultallnationalandlocalelectricalcodesforseparation requirements
Wiring Details•E1andE2wiresarenotpolaritysensitive•BuslengthislimitedbythewiregaugeusedforE1andE2asfollows:
Wire Gauge Bus Length(max)12 AWG(4.0 mm2) 2200 ft(671 m)14 AWG(2.5 mm2) 1400 ft(427 m)16 AWG(1.5 mm2) 900 ft(275 m)18 AWG(1.0 mm2) 570 ft(175 m)
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
ERREMG
BUS
STAT
V~ PWR
/ / Em C
CS-1L- shown
E1 E2
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 9 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring: Contact ClosuresContactclosureinputsareIEC PELVorNEC®Class 2circuits and cannot be run with mains wiring. Unless otherwisespecified,thevoltagesshouldnotexceed12–35 V-. These circuits comply with the requirementsofNFPA 70,NationalElectricCode(NEC®).Followallapplicablenationaland/orlocalwiring regulations.
Contact Closure Bus Terminals
Terminal Unit Label FunctionC COM CommonEm CCI-EMERG EmergencyA CCI-1 ContactClosure 1B CCI-2 ContactClosure 2
EmergencyForintegrationwithasecurityorfirealarmsystem,the emergency input may be used. The alarm system musthaveanormallyclosedrelayforproperoperation.Wiringisshowntotheright.CommonisTerminal CandEmergencyisTerminal EmontheEcoSystemBusSupply.Ona2-linksupply,thereisonlyoneEmergencyInput,whichaffectsbothlinks.EmergencymodemustbeactivatedusingOPTswitch 5.Bydefaultemergencyinputsareignored(DIPswitch 5setto“ON”).Whenswitch 5is“OFF”anopenconditionbetweenterminals 5and6resultsinemergency mode activation.
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
Bottom View(CS-2L-shown)
Contact Closure Bus 1 (red)Terminal:EcoSystemBus1CCICom
EcoSystemBus1CCI1
EcoSystemBus1CCI2
EmergencyContactClosure
Contact Closure Bus 2(red) Terminal(CS-2Lonly):EcoSystemBus2CCI2
EcoSystemBus2CCI1
EcoSystemBus2CCICom
C Em A B
C Em
NCSecurityContactor
Emergency Input
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 10 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Operation: Contact Closures
Contact Closure InputsContactClosureInputs(CCI)ontheBusSupplymaybeusedtointegrateaBMSsystemoroccupancysensorswithanEcoSystemLightingNetwork.Ona2-linksupply,thereisonepairofCCIsforeachEcoSystem Bus.TherearethreemodesofCCIoperation:
•Occupancymode•DemandResponsemode•SceneSelectionmodeThesemodescanbeselectedandconfiguredusingtheEcoSystemProgrammer.Occupancy ModeCCIscommandassignedgroupsonthecorrespondingbustoan“Occupied”lightleveloran“Unoccupied”lightlevelwhenthecontactclosuresareopened or closed.
•WhentheCCIisinthe“occupied”state,thesystemwillcommandballastsassignedtothatCCItogototheir“occupied”level.
•WhentheCCIisinthe“unoccupied”mode,thesystemwillcommandballastsassignedtothatCCItogototheir“unoccupied”level.NotethatifballastsaregroupedtobothaCCIinOccupancymodeandanoccupancysensor,theoccupancy sensor will not sweep the group to its unoccupiedlevelunlesstheCCIisalsounoccupied.Demand Response ModeIndemandresponsemode,eachCCI,whenclosed,appliesaconfigurable“demandresponse”leveltothegroup.WhentheCCIisopened,thedemandresponse level is cleared.Ballasts will scale their current light level by the demandresponselevel(e.g.,ifthedemandresponselevelissetto25%,allballastswilldimtoalightlevelthatis75%oftheirpreviouslevelandwillnotdimabove75%untiltheCCIisopened).CCI-2takespriorityoverCCI-1,soifthesamegroupofballastsareassignedtobothCCIs,whenbothCCIsareclosed,theballastswillscaletothelevelsetforCCI-2.
Scene Select ModeWhentheCCIsareclosedandmaintainedaccordingto the table below, the corresponding scene is selectedonallballastsonthelink.MomentarycontactinputsmaybeusedifScene 1issetto“Unaffected”.
CCI 1 CCI 2 SceneOpen Open 1Closed Open 2Open Closed 3Closed Closed 4
SeeApplicationNote#236forfurtherinformationonEcoSystem Bus Supply contact closure input modes.
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 11 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Operation: Status LEDsLEDsontheEcoSystemBusSupplyindicatenetworkstatus.ThespecificLEDs,colorandflashingmethodis detailed below.
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
LED Normal Operation
Problem Indicator
Probable Cause
ERR/EMG OffOn Emergency contact
closure is activeSteady flash
Miswiredetectedoncorresponding bus
BUS Intermittent flashorOff On Unitfault
STAT Steady flash
Off NoMainspowerorunitfault
On Unitfault
V~PWR On Off NoMainspower
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c1204.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Operation: OPT SwitchesOPTswitchesareusedtoconfiguretheBusSupply.The table below describes the options.ToplaceanOPTswitchintheOFFposition,slidetheswitchtotheleft.DefaultswitchpositionisON.
12
34
56
78
H/L H/L N N
ON
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
ERREMG
BUS
ERREMG
BUS
STAT
V~ PWR
E1 E1 E2 E2B A C C
E1 E1 E2 E2B A Em C
H/L H/L N N
OPT Description Switch Position Function
1 Firstbus(green)CCI-1inputtype
ON Normallyopen1 (default)
OFF Normallyclosed2
2 Firstbus(green)CCI-2inputtype
ON Normallyopen1 (default)
OFF Normallyclosed2
33 Secondbus(blue)CCI-1inputtype
ON Normallyopen1 (default)
OFF Normallyclosed2
43 Secondbus(blue)CCI-2inputtype
ON Normallyopen1 (default)
OFF Normallyclosed2
5 Emergency disable
ON
Emergency contact closure input disabled (default)
OFFEmergency contact closure input enabled
6 Programming
ON
Programmingenabled via EcoSystem programmer (default)
OFF
Programmingdisabled via EcoSystem programmer
7,8 Normal/Override
7 ON,8 ON Normaloperation(default)
7 ON,8 OFF Override: Highend
7 OFF,8 ON Override: Lowend
7 OFF,8 OFF Override: Off
12
34
56
78
ON
12
34
56
78
ON
OPTSwitchOFF
OPTSwitchON
CS-1L-CM; CS-1L-WM; CS-2L-CM; CS-2L-WMEcoSystem Bus Supply
369973c 13 04.07.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Operation: Combining Occupancy Sensors with CCIsOccupancysensorswithrelayoutputscanbewiredtothecontactclosureinputsonthebussupply.Followthe diagram below.Occupancysensorrelayoutputscanbenormallyopenornormallyclosed.SettheOPTswitchfortheCCItomatchthetypeofsensoroutputbeingused.
Occupancysensor(rearview)
Relayoutput
Common
+24 V-
120~ or 277 V~
Bus supply
Toterminals:C:CommonA:CCI 1orB:CCI 2
PowerPackPP-120H(for120 V~)
orPP-277H(for277 V~)
Lutron,Lutron,Eco-10,Hi-lume,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.