Ducts and Diffusers Design

106
AIR DISTRIBUTION Abdullah Nuhait, PhD King Saud University

Transcript of Ducts and Diffusers Design

Page 1: Ducts and Diffusers Design

AIR DISTRIBUTION

Abdullah Nuhait, PhDKing Saud University

Page 2: Ducts and Diffusers Design

Air Distribution –cont.

• Questions:

• What is Air Distribution in HVAC?• Why Does One Need to Study it?

Page 3: Ducts and Diffusers Design

Air Distribution –cont.

Air Distribution in HVAC:

• Distribution of Conditioned Air in Buildings and Rooms in Order to Hold Temperatures, Humidities and Air Velocities within Occupied Space at Acceptable Conditions

Page 4: Ducts and Diffusers Design

Air Distribution –cont.: Air conditioning components

Page 5: Ducts and Diffusers Design

Air Distribution –cont.

With Some Knowledge of Air Distribution in HVAC, One:

• Can select optimum air outlets• Can design optimum duct work

Page 6: Ducts and Diffusers Design

ROOM AIR DISTRIBUTION

• Distribution and Movement of Air within Conditioned Space

• Selection and Location of Optimum Air Outlets Delivering Proper Amount of Air:

• To Provide Comfort within Occupied Zone• To Provide Suitable Indoor Quality within Occupied Zone • To Meet Required Total Pressure• To Produce acceptable Noise Level within Occupied Zone

Page 7: Ducts and Diffusers Design

Room Air Distribution –Cont.

• Requirements Necessary for Good Air Distribution:

• Temperature: to be Hold within Tolerable Limits

• Air Velocity: Table Illustrates Occupant Reaction to Various Air Velocities in Occupied Space

Page 8: Ducts and Diffusers Design

Room Air Distribution –Cont.: Occupied Zone Air Velocities

Recommended Application Reaction Air Velocity (FPM)

None Complaints About Stagnant Air 0-16

All Commercial ApplicationComplaints About Stagnant Air 25

All Commercial ApplicationProbably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People

25-50

Probably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People

65

Retail and Department Store Upper Limit For People Moving About Slowly-Favorable

75

Factory Air Conditioning Higher Velocities for Spot Cooling

Some Factory Air Conditioning Installations-Favorable 75-300

Page 9: Ducts and Diffusers Design

Room Air Distribution –Cont.: Air Direction

• Air Direction: Sketches Give Guide to Most Desirable Air Direction for Seated People

Page 10: Ducts and Diffusers Design

Room Air Distribution –Cont.

• Air outlets can be classified into five groups:

• Group A: air outlets are mounted in or near ceiling that discharge air horizontally

• Group B: air outlets are mounted in or near floor that discharge air vertically in non-spreading jet

• Group C: air outlets are mounted in or near floor that discharge air vertically in spreading jet

• Group D: air outlets are mounted in or near floor that discharge air horizontally

• Group E: air outlets are mounted in or near ceiling that project air vertically downward

Page 11: Ducts and Diffusers Design

Room Air Distribution –Cont.

Group A:

• High sidewall type register• Used in mild climates• Used on second and succeeding floors of multistory floors• Not recommended for cold climate

• Diffuser• Ceiling diffuser very popular in commercial applications• Linear or T-bar diffusers favored in VAV applications due to

their better flow characteristics at reduced flow

Page 12: Ducts and Diffusers Design

Room Air Distribution –Cont. Group A

Page 13: Ducts and Diffusers Design

Room Air Distribution –Cont.

Group B:• Perimeter-type outlets with

Non-Spreading:• Satisfactory for Cooling• Less Desirable for Heating

Page 14: Ducts and Diffusers Design

Room Air Distribution –Cont.

Group C:

• Perimeter-type outlets with Spreading:

• Considered as superior for heating applications• Diffusers with wide spread are best for heating because

buoyancy tends to increase flow• Diffusers with wide spread are not good for cooling because

buoyancy tends to decrease flow

Page 15: Ducts and Diffusers Design

Room Air Distribution –Cont. Group C

Page 16: Ducts and Diffusers Design

Room Air Distribution –Cont.

Group D:

• Diffuser for Special Applications

Page 17: Ducts and Diffusers Design

Room Air Distribution –Cont.

Group E:

• Covers Downward Projected Air Jets for Special Application

Page 18: Ducts and Diffusers Design

Room Air Distribution –Cont.

Air outlets can be located on:

• Walls• Floors• Ceilings

Page 19: Ducts and Diffusers Design

Room Air Distribution –Cont.

Terminologies:

• Primary Air• Induced Air • Entrained Air• Terminal Velocity• Throw• Radius of Diffusion• Drop• Temperature Differential• Diffuser

• Linear• Square• Round• T-Bar• Perforated

• Grille • Register• Damper • Spreading Jet• Non-Spreading Jet

Page 20: Ducts and Diffusers Design

Room Air Distribution –Cont

Throw and Drop for Air

Page 21: Ducts and Diffusers Design

Jet and Room Air Velocities and Temperature for Vo = 1000 ft/min and ∆t = - 20 F

Page 22: Ducts and Diffusers Design

Sound in HVAC

Sound becomes noise when:

• Too load• Unexpected• Uncontrolled• Happens at wrong time• Contains pure tones• Contains unwanted information• Unpleasant

Page 23: Ducts and Diffusers Design

Sound in HVAC

• Audible frequency range for humans extends from 20 Hz to 20000 Hz

• Sound power and sound pressure

• Sound measured in decibel (dB):• 10 Log10 ( W/10-12 ) dB relative to 1 pW• 10 Log10 ( P/2X10-5 ) dB relative to 1 µPa

• Frequency range called octave used in sound• frequency bandwidth having upper band limit twice frequency of its lower band limit

• All air outlets generate noise• Noise can be annoying to occupants• Noise level can be related to velocity of air through outlet:

• Lower air velocity produces low level of noise• Higher air velocity makes air outlet noisy

• Noise criterion (NC) curves widely used to describe noise level of air outlets• Level below NC of 30 considered quiet• Level above NC of 50 considered noisy

Page 24: Ducts and Diffusers Design

Octave and 1/3 Octave Bands Series

Page 25: Ducts and Diffusers Design

NC Curves

Page 26: Ducts and Diffusers Design

Acceptable HVAC Noise Levels in Unoccupied Rooms

Page 27: Ducts and Diffusers Design

Linear Diffuser

Page 28: Ducts and Diffusers Design

Installation of Linear Diffuser

Page 29: Ducts and Diffusers Design

Installation of Linear Diffuser –Cont.

Page 30: Ducts and Diffusers Design

Zero-Bar Diffuser

Page 31: Ducts and Diffusers Design

Round Diffuser

Page 32: Ducts and Diffusers Design

Round Diffuser –Cont.

Page 33: Ducts and Diffusers Design

Perforated Diffuser

Page 34: Ducts and Diffusers Design

Grille

Page 35: Ducts and Diffusers Design

Square Diffuser

Page 36: Ducts and Diffusers Design

Slot-Bar Diffuser

Page 37: Ducts and Diffusers Design

Variable-Volume System (VAV)

• VAV air distribution systems use of:• Linear or T-bar diffusers• Thermostat-controlled metering device

(called VAV terminal box)

Page 38: Ducts and Diffusers Design

Steps for Selecting Air Outlet

• Determine air flow requirement and room size

• Select type of diffuser to be used

• Determine room characteristic length

• Find throw

• Using performance data catalog, select appropriate diffuser

• Make sure any other specifications are met (noise, pressure drop …etc.)

Page 39: Ducts and Diffusers Design

Table: Characteristic Room Lengths for Several Diffusers

Characteristic Length LDiffuser Type

Distance to wall perpendicular to jetHigh sidewall grille (wall)

Distance to closest wall or intersecting air jetCircular ceiling diffuser (ceiling)

Length of room in direction of jet flowSill grille (floor)

Distance to wall or mid-plane between outlets

Perforated diffuser (ceiling)

Page 40: Ducts and Diffusers Design

Performance Data for Round Diffuser

Page 41: Ducts and Diffusers Design

Performance Data for Square Diffuser

Page 42: Ducts and Diffusers Design

Example

• Room part of single-story office Building

• Building located in Riyadh

• Dimensions of room shown in sketch

• Ceiling height =10 ft

• Air quantity = 250 cfm

• Select Ceiling Diffuser

Page 43: Ducts and Diffusers Design

Example

Page 44: Ducts and Diffusers Design

Solution

• Noise level from above table, for office, NC < 35• Flow rate, Q = 250 cfm• Room almost square

• From above table, Characteristic length, L = 14/2 = 7 ft• Throw = L = 7 ft

• Using Q = 250 cfm, throw = 7 ft and NC < 35• From above performance table for round diffuser, size 10” will be

right size• Q ok between 220 cfm and 275 cfm• Throw = 7.5 ft ok• NC < 20 ok• Pressure drop around 0.035 IWG ok

Page 45: Ducts and Diffusers Design

Fans and Building Air Distribution

• Second part of air distribution is distributing air in buildings through duct work

• Will cover followings:• Fans and fan performance• Methods of design of duct• Examples showing how to design duct work

• Shown, in next slide, components of air conditioning system

Page 46: Ducts and Diffusers Design

Air Conditioning Components

Page 47: Ducts and Diffusers Design

Fans Used In HVAC

One essential component of HVAC - FANS

• Fan used to move air through ducts and air outlets• Two type of fans used in HVAC:

• Centrifugal fan (Blower)» Forward-tip fan» Backward-tip fan

• Axial fan» Vane-axial fan» Tube-axial fan

Page 48: Ducts and Diffusers Design

Exploded View of Centrifugal Fan

Page 49: Ducts and Diffusers Design

Axial Fans

Page 50: Ducts and Diffusers Design

Method of Obtaining Fan Performance Curves

Page 51: Ducts and Diffusers Design

Typical performance Curves:

Forward-tip, Backward-tip, and Vane-axial Fans

Page 52: Ducts and Diffusers Design

Fans laws

Relationships between fan capacity, pressure, speed, and power:

• First three fan laws (most useful)» Capacity proportional to fan speed (rpm)» Pressure proportional to square of fan speed» Power proportional to cube of fan speed

• Other three fan laws» Pressure and power proportional to density of air at constant

speed and capacity

» Speed, capacity, and power inversely proportional to square rootof density of air at constant pressure

» Capacity, Speed, and pressure inversely proportional to density and power inversely proportional to of square of air at constantmass flow of air

Page 53: Ducts and Diffusers Design

Performance of fans

Manufacturers present their fan performance data in form of:

• Graphs of pressure, efficiency, and power as functions of flow rate

• Example: Centrifugal fan operating at point 1, estimate capacity, pressure, and power at speed 1050 rpm, initial bhp = 2 hp

» Q2/Q1= rpm2/rpm1 Q2=5000 (1050/900)=5830CFM

» P2/P1= (rpm2/rpm1)2 P2=1.5(1050/900)2 =2.04 IWG

» W2/W1= (rpm2/rpm1)3 W2=2 (1050/900)3 = 3.2 hp

• Tables showing pressure, flow rate, rpm, and bhp» Cannot use fan laws

Page 54: Ducts and Diffusers Design

Performance Curves for Fan

Page 55: Ducts and Diffusers Design

Pressure-Capacity Table

Page 56: Ducts and Diffusers Design

Selection of Fans

• System and fan characteristics combined on one plot

• Intersecting of system and fan characteristics is point of operation

• Range of Optimum matching of system and fan shown

• Slope of system and fan characteristics must be of opposite sign for stable operation

Page 57: Ducts and Diffusers Design

Fan Installation

Performance of fan can be reduced due to:

• System effect factors• Fan outlet connection• Inlet conditions• Enclosure restrictions

Page 58: Ducts and Diffusers Design

Fan and System Characteristics Showing Deficient Operation

• Point B is specific operation point• Test may show point A as actual

operation point

Page 59: Ducts and Diffusers Design

System Effect

Page 60: Ducts and Diffusers Design

Fan outlet Conditions

Page 61: Ducts and Diffusers Design

Outlet-Duct Elbow Positions

Page 62: Ducts and Diffusers Design

Inlet-Duct Elbow Configuration

Page 63: Ducts and Diffusers Design

Fans and Variable-Air-Volume Systems (VAV)

Inlet Vanes of Centrifugal Fan for VAV

Page 64: Ducts and Diffusers Design

Air Flow in Ducts

• Pressure changes in duct• Three constant area horizontal sections • Two fittings

• Smooth converging transition • Abrupt diverging transition

Page 65: Ducts and Diffusers Design

Duct Design

General considerations

• Low-velocity duct system• Pressure loss per 100 ft of duct range between 0.08 to 0.15• Pressure loss of 0.1 per 100 ft of duct is ok• Pressure loss of 0.05 per 100 ft of duct used in most projects in KSA

• High-velocity duct system• Pressure loss per 100 ft of duct range between 0.4 to 0.7

• Chart prepared to help designers to design duct cross section• For flowing air in galvanized steel ducts • Forty (40) joints per 100 ft• Based on standard air and fully developed flow (constant area horizontal duct)• Chart gives round cross section• Table gives equivalent rectangular cross section

• Air-Duct Calculators (Duct-lator) constructed by manufacturers

Page 66: Ducts and Diffusers Design

Pressure Loss Due to Friction

Page 67: Ducts and Diffusers Design

Circular Equivalents of Rectangular Ducts

Page 68: Ducts and Diffusers Design

Simple Duct Systems with Outdoor Air Intake and Relief

Shown Pressure Gradient Diagrams

Page 69: Ducts and Diffusers Design

Simple Duct Systems with Outdoor Air Intake and Relief – Cont.

Page 70: Ducts and Diffusers Design

Total Pressure Profile for Typical Unitary System

Shown Pressure Gradient Diagram

Page 71: Ducts and Diffusers Design

Air Flow in Fittings

Losses in fitting called dynamic (minor) losses

• Computed using ∆P = Co ( v2 )

• Tables give coefficients Co for different fittings

• Equivalent-length method used for fitting losses in low-velocity duct (table gives equivalent length)

Page 72: Ducts and Diffusers Design

Total Pressure Loss Coefficient (Pleated Elbow r/D=1.5)

Page 73: Ducts and Diffusers Design

Total Pressure Loss Coefficient (mitered elbow with vanes)

Page 74: Ducts and Diffusers Design

Total Pressure Loss Coefficient (mitered elbow)

Page 75: Ducts and Diffusers Design

Total Pressure Loss Coefficient (transition, round)

Page 76: Ducts and Diffusers Design

Total Pressure Loss Coefficient (transition, rectangular)

Page 77: Ducts and Diffusers Design

Total Pressure Loss Coefficient (conical converging bell-mouth)

Page 78: Ducts and Diffusers Design

Total Pressure Loss Coefficient (smooth converging bell-mouth)

Page 79: Ducts and Diffusers Design

Total Pressure Loss Coefficient (converging tee)

Page 80: Ducts and Diffusers Design

Total Pressure Loss Coefficient (diverging wye)

Page 81: Ducts and Diffusers Design

Total Pressure Loss Coefficient (diverging tee)

Page 82: Ducts and Diffusers Design

Total Pressure Loss Coefficient (diverging tee)

Page 83: Ducts and Diffusers Design
Page 84: Ducts and Diffusers Design

Equivalent Lengths of Some Fittings in Feet with Meters in Parentheses

Page 85: Ducts and Diffusers Design

Design of Low-Velocity Duct Systems

Several methods can be used for design of low-velocity duct work:

• Equal-friction method

• Balanced-capacity method

• Constant-velocity method

• Reduced-velocity method

• Static-regain method

• T-method (optimization procedure)

Will cover only equal-friction method in detail and briefly cover balanced-capacity method

Page 86: Ducts and Diffusers Design

Equal-friction method

• Principle of equal-friction method to make pressure loss per foot of duct length same for entire system

• Produce good balanced design for symmetrical duct layout

• Most duct systems have variety of duct runs ranging from long toshort

• Dampers may be used for short runs (may cause considerable noise) in order to balance system

• Equal-friction method reduces air velocity in direction of flow

Page 87: Ducts and Diffusers Design

Equal-friction method –Cont.

300 CFM

25 ft20 ft

300 CFM80 ft

60 ft

60 ft 300 CFM

15 ft

300 CFM

30 ft1

a3

4

57

62

Page 88: Ducts and Diffusers Design

Equal-friction method –Cont.

• One way of starting design of duct work

• To select maximum air velocity in main after fan outlet (based on some criterion)

• Using this velocity with flow rate, one can establish duct size of that section and pressure loss per 100 ft

• Using this pressure loss per 100 ft for all sections, one continue to

find their diameters

Page 89: Ducts and Diffusers Design

Balanced-capacity method

• Principle of Balanced-capacity method, one makes loss in total pressure equal for all duct runs from fan tooutlets

• Each run may have different equivalent length

• Pressure loss per 100 ft may be different for each run• This may result in high air velocity (noisy duct)• Limit air velocity and use damper for balancing

300 CFM

25 ft20 ft

300 CFM80 ft

60 ft

60 ft 300 CFM

15 ft

300 CFM

30 ft1

a3

4

57

62

Page 90: Ducts and Diffusers Design

Balanced-capacity method –Cont.

• Longest run form fan to outlets must be determine

• Pressure drop (loss) per 100 ft will be same for sections of longest run (same as equal-friction method)

• Establish pressure loss for branch by equating its pressure loss to pressure loss of branch of longest run

• Find pressure loss per 100 ft by divide pressure loss over equivalent length of that section

Page 91: Ducts and Diffusers Design

Constant- and Reduced-Velocity method

• From name of constant-velocity method, velocity selected and kept fixed for all duct runs

• Used for exhaust (kitchen exhaust, grease, industrial ventilation)

• In velocity-reduction method, velocities of air set from fan to outlet • reduces air velocity in direction of flow

Page 92: Ducts and Diffusers Design

Static-Regain method

• Static-regain method reduces air velocity in direction of flow in such a way that increase (regain) in static pressure in transition just balances pressure loss in following section

• Used in high-velocity systems

• Method require iterations

Page 93: Ducts and Diffusers Design

Examples

• Several example will be solved using mainly method of equal friction

• Each example will be solved using computer software

• Ductlator will be used for designing some sections

• Examples done using single line duct work

Page 94: Ducts and Diffusers Design

Example # 1

600 CFM

25 ft30 ft

400 CFM400 CFM55 ft

85 ft

60 ft 500 CFM

25 ft

300 CFM

45 ft

1

2

3 5 6

47

a

Page 95: Ducts and Diffusers Design

Example # 2

25 ft20 ft

300 CFM80 ft

60 ft

60 ft300 CFM

15 ft

300 CFM

30 ft1

a3

4

5 7

62

300 CFM

Page 96: Ducts and Diffusers Design

Example # 3

90° ELBOW

90° ELBOW

90° ELBOW

10 ft

20 ft20

ft

10 ft

10 ft

5 ft

diffP = 0.04 IWG

400 CFM

200 CFM

300 CFM

PLENUM

SHARP INLETP = 0.04 IWGdiff

P = 0.04 IWGdiff

200 CFM

90° ELBOW

P = 0.04 IWGdiff

5 ft20 ft

PLENUM

90° ELBOW

SHARP INLET

P = 0.04 IWGdiff

400 CFM

10 ft

10 ft

90° ELBOW

300 CFM

P = 0.04 IWGdiff

Page 97: Ducts and Diffusers Design

Example # 4

300 CFM

25 ft20 ft

300 CFM80 ft

60 ft

60 ft 300 CFM

15 ft

300 CFM

30 ft1

a3

4

57

62

Page 98: Ducts and Diffusers Design

Example # 5

300 CFM

25 ft20 ft

300 CFM80 ft

60 ft

60 ft300 CFM

15 ft

300 CFM

30 ft1

a3

4

5 7

62

Page 99: Ducts and Diffusers Design

Example # 6 Fan produce 0.7 IWG and 0.35 IWG lost pressure in coil, filter and

furnace, divide remaining pressure 65% for supply duct and 35% for return duct

Page 100: Ducts and Diffusers Design

Duct layout

• Actual duct work of some projects shown using double line duct with sizes shown

• Different diffuser types shown

• Air conditioning equipment shown

Page 101: Ducts and Diffusers Design

Duct Work with Square Diffusers

Page 102: Ducts and Diffusers Design

Duct Work with Linear Diffusers

Page 103: Ducts and Diffusers Design

Duct Work with Round Diffusers (shown concealed equipment)

Page 104: Ducts and Diffusers Design

Duct Work with Linear Diffusers (shown concealed equipment)

Page 105: Ducts and Diffusers Design

Roof-Top Packaged Unit With Duct Work (25 tons, plan)

Page 106: Ducts and Diffusers Design

Roof-Top Packaged Unit With Duct Work (25 tons, Side view)