Ducts and Diffusers Design

download Ducts and Diffusers Design

of 106

description

Ducts and Diffusers Design

Transcript of Ducts and Diffusers Design

  • AIR DISTRIBUTION

    Abdullah Nuhait, PhDKing Saud University

  • Air Distribution cont.

    Questions:

    What is Air Distribution in HVAC? Why Does One Need to Study it?

  • Air Distribution cont.

    Air Distribution in HVAC:

    Distribution of Conditioned Air in Buildings and Rooms in Order to Hold Temperatures, Humidities and Air Velocities within Occupied Space at Acceptable Conditions

  • Air Distribution cont.: Air conditioning components

  • Air Distribution cont.

    With Some Knowledge of Air Distribution in HVAC, One:

    Can select optimum air outlets Can design optimum duct work

  • ROOM AIR DISTRIBUTION

    Distribution and Movement of Air within Conditioned Space

    Selection and Location of Optimum Air Outlets Delivering Proper Amount of Air:

    To Provide Comfort within Occupied Zone To Provide Suitable Indoor Quality within Occupied Zone To Meet Required Total Pressure To Produce acceptable Noise Level within Occupied Zone

  • Room Air Distribution Cont.

    Requirements Necessary for Good Air Distribution:

    Temperature: to be Hold within Tolerable Limits

    Air Velocity: Table Illustrates Occupant Reaction to Various Air Velocities in Occupied Space

  • Room Air Distribution Cont.: Occupied Zone Air Velocities

    Recommended Application Reaction Air Velocity (FPM)

    None Complaints About Stagnant Air 0-16

    All Commercial ApplicationComplaints About Stagnant Air 25

    All Commercial ApplicationProbably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People

    25-50

    Probably Favorable but 50 FPM is Approaching Maximum Tolerable Velocity for Seated People

    65

    Retail and Department Store Upper Limit For People Moving About Slowly-Favorable

    75

    Factory Air Conditioning Higher Velocities for Spot Cooling

    Some Factory Air Conditioning Installations-Favorable 75-300

  • Room Air Distribution Cont.: Air Direction

    Air Direction: Sketches Give Guide to Most Desirable Air Direction for Seated People

  • Room Air Distribution Cont.

    Air outlets can be classified into five groups:

    Group A: air outlets are mounted in or near ceiling that discharge air horizontally

    Group B: air outlets are mounted in or near floor that discharge air vertically in non-spreading jet

    Group C: air outlets are mounted in or near floor that discharge air vertically in spreading jet

    Group D: air outlets are mounted in or near floor that discharge air horizontally

    Group E: air outlets are mounted in or near ceiling that project air vertically downward

  • Room Air Distribution Cont.

    Group A:

    High sidewall type register Used in mild climates Used on second and succeeding floors of multistory floors Not recommended for cold climate

    Diffuser Ceiling diffuser very popular in commercial applications Linear or T-bar diffusers favored in VAV applications due to

    their better flow characteristics at reduced flow

  • Room Air Distribution Cont. Group A

  • Room Air Distribution Cont.

    Group B: Perimeter-type outlets with

    Non-Spreading: Satisfactory for Cooling Less Desirable for Heating

  • Room Air Distribution Cont.

    Group C:

    Perimeter-type outlets with Spreading:

    Considered as superior for heating applications Diffusers with wide spread are best for heating because

    buoyancy tends to increase flow Diffusers with wide spread are not good for cooling because

    buoyancy tends to decrease flow

  • Room Air Distribution Cont. Group C

  • Room Air Distribution Cont.

    Group D:

    Diffuser for Special Applications

  • Room Air Distribution Cont.

    Group E:

    Covers Downward Projected Air Jets for Special Application

  • Room Air Distribution Cont.

    Air outlets can be located on:

    Walls Floors Ceilings

  • Room Air Distribution Cont.

    Terminologies:

    Primary Air Induced Air Entrained Air Terminal Velocity Throw Radius of Diffusion Drop Temperature Differential Diffuser

    Linear Square Round T-Bar Perforated

    Grille Register Damper Spreading Jet Non-Spreading Jet

  • Room Air Distribution Cont

    Throw and Drop for Air

  • Jet and Room Air Velocities and Temperature for Vo = 1000 ft/min and t = - 20 F

  • Sound in HVAC

    Sound becomes noise when:

    Too load Unexpected Uncontrolled Happens at wrong time Contains pure tones Contains unwanted information Unpleasant

  • Sound in HVAC

    Audible frequency range for humans extends from 20 Hz to 20000 Hz

    Sound power and sound pressure

    Sound measured in decibel (dB): 10 Log10 ( W/10-12 ) dB relative to 1 pW 10 Log10 ( P/2X10-5 ) dB relative to 1 Pa

    Frequency range called octave used in sound frequency bandwidth having upper band limit twice frequency of its lower band limit

    All air outlets generate noise Noise can be annoying to occupants Noise level can be related to velocity of air through outlet:

    Lower air velocity produces low level of noise Higher air velocity makes air outlet noisy

    Noise criterion (NC) curves widely used to describe noise level of air outlets Level below NC of 30 considered quiet Level above NC of 50 considered noisy

  • Octave and 1/3 Octave Bands Series

  • NC Curves

  • Acceptable HVAC Noise Levels in Unoccupied Rooms

  • Linear Diffuser

  • Installation of Linear Diffuser

  • Installation of Linear Diffuser Cont.

  • Zero-Bar Diffuser

  • Round Diffuser

  • Round Diffuser Cont.

  • Perforated Diffuser

  • Grille

  • Square Diffuser

  • Slot-Bar Diffuser

  • Variable-Volume System (VAV)

    VAV air distribution systems use of: Linear or T-bar diffusers Thermostat-controlled metering device

    (called VAV terminal box)

  • Steps for Selecting Air Outlet

    Determine air flow requirement and room size

    Select type of diffuser to be used

    Determine room characteristic length

    Find throw

    Using performance data catalog, select appropriate diffuser

    Make sure any other specifications are met (noise, pressure drop etc.)

  • Table: Characteristic Room Lengths for Several Diffusers

    Characteristic Length LDiffuser Type

    Distance to wall perpendicular to jetHigh sidewall grille (wall)

    Distance to closest wall or intersecting air jetCircular ceiling diffuser (ceiling)

    Length of room in direction of jet flowSill grille (floor)

    Distance to wall or mid-plane between outlets

    Perforated diffuser (ceiling)

  • Performance Data for Round Diffuser

  • Performance Data for Square Diffuser

  • Example

    Room part of single-story office Building

    Building located in Riyadh

    Dimensions of room shown in sketch

    Ceiling height =10 ft

    Air quantity = 250 cfm

    Select Ceiling Diffuser

  • Example

  • Solution

    Noise level from above table, for office, NC < 35 Flow rate, Q = 250 cfm Room almost square

    From above table, Characteristic length, L = 14/2 = 7 ft Throw = L = 7 ft

    Using Q = 250 cfm, throw = 7 ft and NC < 35 From above performance table for round diffuser, size 10 will be

    right size Q ok between 220 cfm and 275 cfm Throw = 7.5 ft ok NC < 20 ok Pressure drop around 0.035 IWG ok

  • Fans and Building Air Distribution

    Second part of air distribution is distributing air in buildings through duct work

    Will cover followings: Fans and fan performance Methods of design of duct Examples showing how to design duct work

    Shown, in next slide, components of air conditioning system

  • Air Conditioning Components

  • Fans Used In HVAC

    One essential component of HVAC - FANS

    Fan used to move air through ducts and air outlets Two type of fans used in HVAC:

    Centrifugal fan (Blower) Forward-tip fan Backward-tip fan

    Axial fan Vane-axial fan Tube-axial fan

  • Exploded View of Centrifugal Fan

  • Axial Fans

  • Method of Obtaining Fan Performance Curves

  • Typical performance Curves:

    Forward-tip, Backward-tip, and Vane-axial Fans

  • Fans laws

    Relationships between fan capacity, pressure, speed, and power:

    First three fan laws (most useful) Capacity proportional to fan speed (rpm) Pressure proportional to square of fan speed Power proportional to cube of fan speed

    Other three fan laws Pressure and power proportional to density of air at constant

    speed and capacity

    Speed, capacity, and power inversely proportional to square rootof density of air at constant pressure

    Capacity, Speed, and pressure inversely proportional to density and power inversely proportional to of square of air at constantmass flow of air

  • Performance of fans

    Manufacturers present their fan performance data in form of:

    Graphs of pressure, efficiency, and power as functions of flow rate

    Example: Centrifugal fan operating at point 1, estimate capacity, pressure, and power at speed 1050 rpm, initial bhp = 2 hp

    Q2/Q1= rpm2/rpm1 Q2=5000 (1050/900)=5830CFM

    P2/P1= (rpm2/rpm1)2 P2=1.5(1050/900)2 =2.04 IWG

    W2/W1= (rpm2/rpm1)3 W2=2 (1050/900)3 = 3.2 hp

    Tables showing pressure, flow rate, rpm, and bhp Cannot use fan laws

  • Performance Curves for Fan

  • Pressure-Capacity Table

  • Selection of Fans

    System and fan characteristics combined on one plot

    Intersecting of system and fan characteristics is point of operation

    Range of Optimum matching of system and fan shown

    Slope of system and fan characteristics must be of opposite sign for stable operation

  • Fan Installation

    Performance of fan can be reduced due to:

    System effect factors Fan outlet connection Inlet conditions Enclosure restrictions

  • Fan and System Characteristics Showing Deficient Operation

    Point B is specific operation point Test may show point A as actual

    operation point

  • System Effect

  • Fan outlet Conditions

  • Outlet-Duct Elbow Positions

  • Inlet-Duct Elbow Configuration

  • Fans and Variable-Air-Volume Systems (VAV)

    Inlet Vanes of Centrifugal Fan for VAV

  • Air Flow in Ducts

    Pressure changes in duct Three constant area horizontal sections Two fittings

    Smooth converging transition Abrupt diverging transition

  • Duct Design

    General considerations

    Low-velocity duct system Pressure loss per 100 ft of duct range between 0.08 to 0.15 Pressure loss of 0.1 per 100 ft of duct is ok Pressure loss of 0.05 per 100 ft of duct used in most projects in KSA

    High-velocity duct system Pressure loss per 100 ft of duct range between 0.4 to 0.7

    Chart prepared to help designers to design duct cross section For flowing air in galvanized steel ducts Forty (40) joints per 100 ft Based on standard air and fully developed flow (constant area horizontal duct) Chart gives round cross section Table gives equivalent rectangular cross section

    Air-Duct Calculators (Duct-lator) constructed by manufacturers

  • Pressure Loss Due to Friction

  • Circular Equivalents of Rectangular Ducts

  • Simple Duct Systems with Outdoor Air Intake and Relief

    Shown Pressure Gradient Diagrams

  • Simple Duct Systems with Outdoor Air Intake and Relief Cont.

  • Total Pressure Profile for Typical Unitary System

    Shown Pressure Gradient Diagram

  • Air Flow in Fittings

    Losses in fitting called dynamic (minor) losses

    Computed using P = Co ( v2 )

    Tables give coefficients Co for different fittings

    Equivalent-length method used for fitting losses in low-velocity duct (table gives equivalent length)

  • Total Pressure Loss Coefficient (Pleated Elbow r/D=1.5)

  • Total Pressure Loss Coefficient (mitered elbow with vanes)

  • Total Pressure Loss Coefficient (mitered elbow)

  • Total Pressure Loss Coefficient (transition, round)

  • Total Pressure Loss Coefficient (transition, rectangular)

  • Total Pressure Loss Coefficient (conical converging bell-mouth)

  • Total Pressure Loss Coefficient (smooth converging bell-mouth)

  • Total Pressure Loss Coefficient (converging tee)

  • Total Pressure Loss Coefficient (diverging wye)

  • Total Pressure Loss Coefficient (diverging tee)

  • Total Pressure Loss Coefficient (diverging tee)

  • Equivalent Lengths of Some Fittings in Feet with Meters in Parentheses

  • Design of Low-Velocity Duct Systems

    Several methods can be used for design of low-velocity duct work:

    Equal-friction method

    Balanced-capacity method

    Constant-velocity method

    Reduced-velocity method

    Static-regain method

    T-method (optimization procedure)

    Will cover only equal-friction method in detail and briefly cover balanced-capacity method

  • Equal-friction method

    Principle of equal-friction method to make pressure loss per foot of duct length same for entire system

    Produce good balanced design for symmetrical duct layout

    Most duct systems have variety of duct runs ranging from long toshort

    Dampers may be used for short runs (may cause considerable noise) in order to balance system

    Equal-friction method reduces air velocity in direction of flow

  • Equal-friction method Cont.

    300 CFM

    25 ft20 ft

    300 CFM80 ft

    60 ft

    60 ft 300 CFM

    15 ft

    300 CFM

    30 ft1

    a3

    4

    57

    62

  • Equal-friction method Cont.

    One way of starting design of duct work

    To select maximum air velocity in main after fan outlet (based on some criterion)

    Using this velocity with flow rate, one can establish duct size of that section and pressure loss per 100 ft

    Using this pressure loss per 100 ft for all sections, one continue to

    find their diameters

  • Balanced-capacity method

    Principle of Balanced-capacity method, one makes loss in total pressure equal for all duct runs from fan tooutlets

    Each run may have different equivalent length

    Pressure loss per 100 ft may be different for each run This may result in high air velocity (noisy duct) Limit air velocity and use damper for balancing

    300 CFM

    25 ft20 ft

    300 CFM80 ft

    60 ft

    60 ft 300 CFM

    15 ft

    300 CFM

    30 ft1

    a3

    4

    57

    62

  • Balanced-capacity method Cont.

    Longest run form fan to outlets must be determine

    Pressure drop (loss) per 100 ft will be same for sections of longest run (same as equal-friction method)

    Establish pressure loss for branch by equating its pressure loss to pressure loss of branch of longest run

    Find pressure loss per 100 ft by divide pressure loss over equivalent length of that section

  • Constant- and Reduced-Velocity method

    From name of constant-velocity method, velocity selected and kept fixed for all duct runs

    Used for exhaust (kitchen exhaust, grease, industrial ventilation)

    In velocity-reduction method, velocities of air set from fan to outlet reduces air velocity in direction of flow

  • Static-Regain method

    Static-regain method reduces air velocity in direction of flow in such a way that increase (regain) in static pressure in transition just balances pressure loss in following section

    Used in high-velocity systems

    Method require iterations

  • Examples

    Several example will be solved using mainly method of equal friction

    Each example will be solved using computer software

    Ductlator will be used for designing some sections

    Examples done using single line duct work

  • Example # 1

    600 CFM

    25 ft30 ft

    400 CFM400 CFM55 ft

    85 ft

    60 ft 500 CFM

    25 ft

    300 CFM

    45 ft

    1

    2

    3 5 6

    47

    a

  • Example # 2

    25 ft20 ft

    300 CFM80 ft

    60 ft

    60 ft300 CFM

    15 ft

    300 CFM

    30 ft1

    a3

    4

    5 7

    62

    300 CFM

  • Example # 3

    90 ELBOW

    90 ELBOW

    90 ELBOW

    10 ft

    20 ft20

    ft

    10 ft

    10 ft

    5 ft

    diffP = 0.04 IWG

    400 CFM

    200 CFM

    300 CFM

    PLENUM

    SHARP INLETP = 0.04 IWGdiff

    P = 0.04 IWGdiff

    200 CFM

    90 ELBOW

    P = 0.04 IWGdiff

    5 ft20 ft

    PLENUM

    90 ELBOW

    SHARP INLET

    P = 0.04 IWGdiff

    400 CFM

    10 ft

    10 ft

    90 ELBOW

    300 CFM

    P = 0.04 IWGdiff

  • Example # 4

    300 CFM

    25 ft20 ft

    300 CFM80 ft

    60 ft

    60 ft 300 CFM

    15 ft

    300 CFM

    30 ft1

    a3

    4

    57

    62

  • Example # 5

    300 CFM

    25 ft20 ft

    300 CFM80 ft

    60 ft

    60 ft300 CFM

    15 ft

    300 CFM

    30 ft1

    a3

    4

    5 7

    62

  • Example # 6 Fan produce 0.7 IWG and 0.35 IWG lost pressure in coil, filter and furnace, divide remaining pressure 65% for supply duct and 35% for return duct

  • Duct layout

    Actual duct work of some projects shown using double line duct with sizes shown

    Different diffuser types shown

    Air conditioning equipment shown

  • Duct Work with Square Diffusers

  • Duct Work with Linear Diffusers

  • Duct Work with Round Diffusers (shown concealed equipment)

  • Duct Work with Linear Diffusers (shown concealed equipment)

  • Roof-Top Packaged Unit With Duct Work (25 tons, plan)

  • Roof-Top Packaged Unit With Duct Work (25 tons, Side view)

    AIR DISTRIBUTIONAir Distribution cont.Air Distribution cont.Air Distribution cont.: Air conditioning componentsAir Distribution cont.ROOM AIR DISTRIBUTIONRoom Air Distribution Cont.Room Air Distribution Cont.: Occupied Zone Air VelocitiesRoom Air Distribution Cont.: Air DirectionRoom Air Distribution Cont.Room Air Distribution Cont.Room Air Distribution Cont. Group ARoom Air Distribution Cont.Room Air Distribution Cont.Room Air Distribution Cont. Group CRoom Air Distribution Cont.Room Air Distribution Cont.Room Air Distribution Cont.Room Air Distribution Cont.Room Air Distribution Cont Jet and Room Air Velocities and Temperature for Vo = 1000 ft/min and t = - 20 FSound in HVACSound in HVACOctave and 1/3 Octave Bands SeriesNC CurvesAcceptable HVAC Noise Levels in Unoccupied RoomsLinear DiffuserInstallation of Linear DiffuserInstallation of Linear Diffuser Cont.Zero-Bar DiffuserRound DiffuserRound Diffuser Cont.Perforated DiffuserGrilleSquare DiffuserSlot-Bar DiffuserVariable-Volume System (VAV)Steps for Selecting Air OutletTable: Characteristic Room Lengths for Several DiffusersPerformance Data for Round DiffuserPerformance Data for Square DiffuserExampleExampleSolutionFans and Building Air DistributionAir Conditioning ComponentsFans Used In HVACExploded View of Centrifugal FanAxial FansMethod of Obtaining Fan Performance CurvesTypical performance Curves:Forward-tip, Backward-tip, and Vane-axial FansFans lawsPerformance of fansPerformance Curves for FanPressure-Capacity TableSelection of FansFan InstallationFan and System Characteristics Showing Deficient OperationSystem EffectFan outlet ConditionsOutlet-Duct Elbow PositionsInlet-Duct Elbow ConfigurationFans and Variable-Air-Volume Systems (VAV)Air Flow in DuctsDuct DesignPressure Loss Due to FrictionCircular Equivalents of Rectangular DuctsSimple Duct Systems with Outdoor Air Intake and ReliefShown Pressure Gradient DiagramsSimple Duct Systems with Outdoor Air Intake and Relief Cont.Total Pressure Profile for Typical Unitary System Shown Pressure Gradient DiagramAir Flow in FittingsTotal Pressure Loss Coefficient (Pleated Elbow r/D=1.5)Total Pressure Loss Coefficient (mitered elbow with vanes)Total Pressure Loss Coefficient (mitered elbow)Total Pressure Loss Coefficient (transition, round)Total Pressure Loss Coefficient (transition, rectangular)Total Pressure Loss Coefficient (conical converging bell-mouth)Total Pressure Loss Coefficient (smooth converging bell-mouth)Total Pressure Loss Coefficient (converging tee)Total Pressure Loss Coefficient (diverging wye)Total Pressure Loss Coefficient (diverging tee)Total Pressure Loss Coefficient (diverging tee)Equivalent Lengths of Some Fittings in Feet with Meters in ParenthesesDesign of Low-Velocity Duct SystemsEqual-friction methodEqual-friction method Cont.Equal-friction method Cont.Balanced-capacity methodBalanced-capacity method Cont.Constant- and Reduced-Velocity methodStatic-Regain methodExamplesExample # 1Example # 2Example # 3Example # 4Example # 5Example # 6 Fan produce 0.7 IWG and 0.35 IWG lost pressure in coil, filter and furnace, divide remaining pressure 65% for supDuct layoutDuct Work with Square DiffusersDuct Work with Linear DiffusersDuct Work with Round Diffusers (shown concealed equipment)Duct Work with Linear Diffusers (shown concealed equipment)Roof-Top Packaged Unit With Duct Work (25 tons, plan)Roof-Top Packaged Unit With Duct Work (25 tons, Side view)