DCS System Distributed Redundant System Solutions Training/Tutorial
-
Upload
icp-das-usa-inc -
Category
Technology
-
view
368 -
download
6
Transcript of DCS System Distributed Redundant System Solutions Training/Tutorial
Industrial Computer Product Data Acquisition System
DCS I/O SolutionsDCS I/O Solutions
Industrial Computer Product Data Acquisition System
ICP DAS DCS I/O SolutioniDCS-8830
Redundancy System
Industrial Computer Product Data Acquisition System
• Distributed Redundant System• ICP DAS DCS Solution• iDCS-8830 Introduction• iDCS-8830 Application Structure• iDCS-8830 Application Story
Agenda
Industrial Computer Product Data Acquisition System
Distributed Redundant System (1/3)• Integrated with computing, communication, control,
monitor etc. technique and widely applied by petrochemical factory.
• Dispersed or reduce the risk of automation, improve equipment reliability.
• Capture Various Signal (Digital I/O, Analog I/O, HART, Pulse, Temperature, …)
• Fast I/O Redundant Time• Fast I/O Data Exchange• Real-Time Control• Self-Error Detection• Suitable for Harsh Environments
Industrial Computer Product Data Acquisition System
Distributed Redundant System (2/3)
Industrial Computer Product Data Acquisition System
Distributed Redundant System (3/3)
Industrial Computer Product Data Acquisition System
ICP DAS DCS Solution (1/2)
• Host Software :EZ Data Logger,eLogger / InduSoft, NAPOPC Server …
• DCS Controller :WinPAC / ViewPAC / XPAC / LinPAC / iDCS-PAC / iPAC …
• I/O Module : I-7K / I-8K / I-87K / ET-7K / USB-87K / PROFI-8K /
CAN-2K / iDCS-8830 …
Click here to learn more…
Industrial Computer Product Data Acquisition System
• Single/Redundant Controller• Development Tools - SoftPLC...• Support Various OS
Windows CE
MiniOS 7 (DOS)
Embedded Linux Android 、 BSD etc..
ICP DAS DCS Solution (2/2)
Learn More…
Industrial Computer Product Data Acquisition System
• Remote I/O Redundant System• Equip Redundant Power Modules• Equip Redundant Communication Modules (with MB/TCP Server)• Equip eight I/O module slots - Max. 256 digital I/O channels - Max. 64 Analog Output channels - Max. 128 Analog Input channels - Max. 64 Pulse I/O channels• Four sets of I/O Redundant• Hardware Features : - Operation Temp. : -25 ~ +75 ℃ - ESD : 8KV - G3 Standard (ISA S71.04)
iDCS-8830 Introduction
Click here to learn more
Industrial Computer Product Data Acquisition System
iDCS-8830 Feature (1/2)• An Ethernet Remote I/O Unit with
Modbus TCP Server.• Expand to max. 255 stations.• Equip Redundant Communication
Modules to upgrade System Reliability.
• Equip Self-Error Detection Function.
• Fast I/O data exchange with host application.
Click here to learn more
Industrial Computer Product Data Acquisition System
• I/O Update Time :– 3 ms for data exchange between controller and I/O modules.
(256 Channels DO/DI)。• I/O Redundant Time :
– Seamless
• I/O Data Accuracy :– Analog I/O Accuracy : +/- 0.1% of FSR and Even better– Pulse Input Accuracy : Error less than one pulse in 10KHz
• I/O Exclusive Daughter Board• I/O Self-Error Detection :
– With terminal off detection function.– With Disconnection detection function.
iDCS-8830 Feature (2/2)
Click here to learn more
Industrial Computer Product Data Acquisition System
iDCS-8830 Maintenance
• Hot Swap– Auto Configuration When New Module is Installed.– Seamless with Power / Communication / IO modules.
• Easy Wiring– I/O Cable Plug & Play
• Intuitive Configuration– Provide Software Utility
Click here to learn more
Industrial Computer Product Data Acquisition System
Update Setting to new IOM.
iDCS-8830 HotSwap
iDCS-8830Traditional
I/O LAN I/O LAN
Control LANControl
LAN
Shutdown controller for IOM replace.
Without any action for IOM replace.
Industrial Computer Product Data Acquisition System
iDCS-8830 Wiring
Simple Wiring
MessyWiring
Industrial Computer Product Data Acquisition System
iDCS-8830 I/O Modules
Industrial Computer Product Data Acquisition System
iDCS-8830 I/O TableI/O Type Model Ch Features
Digital DI F-8040 32LED Display, 5 ~ 30V
DO F-8041 32
PO F-8041P 16 PWM / One-Shot / Continue Mode
Analog AII F-8017C1 8 4~20mA Input, S.E./Diff., 24VDC Output
F-8017C2 16 4~20mA Input, Diff.
F-8017CH 8 4~20mA Input with HART, S.E./Diff., 24VDC Output,
AOI F-8028CV 8 Voltage / Current Output
F-8028CH 8 4~20mA Output with HART
AIV F-8017V 8 Voltage Input, Diff.
RTD F-8015 8 Type: Pt100, Pt1000, Jpt100.. (3-wire)
TC F-8019 8 Type: J,K,T,E,R,S,N,B,C..
Pulse PI F-8084 8 FrequencyCounter (Up, Dir/Pulse, A/B-Phase, Up/Down)
Industrial Computer Product Data Acquisition System
Digital Module
DN-DO-16DR-A
DN-DO-16DR-B
DN-DO-16FRW-A
DN-DO-16FRW-B
DN-DI-32F
[ I/O Feature ]1. Single/Redundant2. 32ch LED Display3. DO with PWM
[ Daughter Board ]1. Relay(6A,250VAC) 、 Fuse2. DO supports Dry/Wet contact3. DI with fuse 、 EMS protection4. With Ch LED Display
Industrial Computer Product Data Acquisition System
Analog Module
[ I/O Feature ]1. Single/Redundant2. Fast I/O Data Rate
[ Daughter Board ]1. With fuse 、 EMS protection
DN-AIO-08F DN-AIO-16F
Click here to learn more
Industrial Computer Product Data Acquisition System
Temp. & Pulse Module
[ I/O Feature ]1. Single/Redundant2. RTD supports 3-wire3. Pulse Redundant error
less than one count4.TC supports multi-type
[ Daughter Board ]1. DN-TC-08 supports
CJC
DN-RTD-16DN-TC-08
Industrial Computer Product Data Acquisition System
RealTime I/O Redundant
• I/O Redundant Time– How to prove?– How many time does I/O take over?
• Test Method– Remove module by hand.– Switch Command from utility.
• Test Result– I/O Seamless Redundant!
Industrial Computer Product Data Acquisition System
Application Structure ( 一 )High-Reliability PLC System
Industrial Computer Product Data Acquisition System
Application Structure ( 二 )Controller Redundant System
Industrial Computer Product Data Acquisition System
Application StructureDistributed Redundant Application Ethernet
Redundant
Controller Redundant
I/O Redundant
Industrial Computer Product Data Acquisition System
iDCS-8830 On-site Installation
Industrial Computer Product Data Acquisition System
Questions?
Making Data Acquisition Easy
• Please ask any questions you may have.• Contact us:Tel: +1 (310) 517-9888 +1 888-971-9888Website: http://www.icpdas-usa.comEmail: [email protected] Follow ICP DAS USA On:
Stay up-to-date with the latest technology in automation and control!
Ladder Logic and Touch Screen PLC Programming Training | 8/28/2015