Cross-Reference - AWG to Metric Size (With Ampacity) of Insulated Conductors

1
(60°C ) (75°C ) (90°C ) (60°C ) (75°C ) (90°C ) TW, UF RHW, THHW, THW, THWN, XHHW, USE, ZW TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW- 2 TW, UF RHW, THHW, THW, THWN, XHHW, USE, ZW TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW- 2 20 | 20 20 | 20 25 | 25 25 | 25 25 | 25 30 | 30 20 | 20 20 | 20 25 | 25 30 | 30 35 | 35 40 | 40 25 | 25 30 | 30 35 | 35 40 | 40 50 | 50 55 | 55 30 | 30 40 | 40 45 | 45 55 | 55 65 | 65 70 | 75 40 | 40 50 | 50 60 | 60 70 | 70 85 | 85 90 | 95 55 | 55 65 | 65 75 | 80 85 |90 100 | — 110 |115 65 |65 75 | 80 85 | — 95 | — 115 | 110 130 | 75 |— 90 |— 90 | 90 110 | 100 130 | 125 150 | 130 85 | 75 100 | 90 115| 105 125 | 120 150 | 145 170 | 150 100 | 95 120 | 110 130 | 125 145 | 135 170 | 160 190 | 170 115 | 100 135 | 120 150 | 135 165 | 160 200 | 195 225 | 205 130 | 120 155 | 145 175 | 165 195 | 185 230 | 220 260 | 225 150 | 140 180 | 170 205 | 190 215 | 210 255 | 255 290 | 265 170 | 165 205 | 200 230 | 225 240 | 240 285 | 280 320 | 295 190 | 185 230 | 225 255 | 250 260 | 260 310 | 305 350 | 345 210 | 205 250 | 245 280 | 275 280 | 280 335 | 330 380 | 355 225 | 220 270 | 265 305 | 300 320 | 315 380 | 375 430 | 400 260 | 255 310 | 305 350 | 345 355 | 370 420 | 435 475 | 470 285 | 305 340 | 365 385 | 410 385 | 395 460 | 470 520 | 530 310| 315 375 | 380 420| 430 400 | 405 475 | 485 535 | 515 320 | 335 385| 405 435| 460 410 | — 490 | — 555 | — 330 | — 395 | — 450 | — 435 | 445 520 | 540 585 | — 355| 370 425 | 440 480 | 495 455 | — 545 | — 615 | — 375 | — 445 | — 500 | — 495 | — 590 | — 665 | — 405 | — 485 | — 545 | — 520 | — 625 | — 705 | — 435 | — 520 | — 585 | — 545 | — 650 | — 735 | — 455 | — 545 | — 615 | — 560 | — 665 | — 750 | — 470 | — 560 | — 630 | — 0.41 CORRECTION FACTORS 0.75 0.67 0.58 0.33 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.58 0.58 0.41 1.05 1.00 0.94 0.88 0.82 3 | 30.0 For ambient temperatures other than 30°C, multiply the allowable ampacities shown above by the appropriate factor shown below. 1.08 1.00 0.91 800 | — 900 | 500.0 1000 | — 1250 | — 400 | 200.0 500 | 250.0 600 | 325.0 700 | 375.0 750 | 400.0 2000 | — CROSS-REFERENCE - AWG TO METRIC SIZE (WITH AMPACITY) OF INSULATED CONDUCTORS Temperature Rating Based on Insulation Type Copper Aluminum or Copper-clad Aluminum Wire Size Note: Given values for wire sizes are not equivalents but give the nearest commercially available sizes between AWG and Metric standards Quantities before the " | " is for AWG/MCM and those after the vertical bar is for Metric System. The table is most useful when available wire sizes are in Metric System (mm 2 ) but design specifications are given in AWG or conversely. Ampacities may overlap between AWG-Metric wire sizes using certain insulation types. Due consideration must be practiced in selecting conductor size based on the nearest ampacity such that greater margin of safety is achieved (say, by choosing wire size which has one step higher ampacity). Ampacities applicable to not more than three conductors are in raceway, cable, or earth, rated up to 2000 V and at ambient temperature of 30°C. MCM is the same as kcmil . MCM to mm² conversion can use the relationship 1 kcmil = 0.5067 mm². AWG (/ MCM or kcmil) | mm 2 14 | 2.0 12 | 3.5 10 | 5.5 2/0 (or 00 ) | 60.0 46-50 21–26 26-30 31-35 36-40 41-45 1500 | — 1750 | — 350 | 175.0 Disclaimer: Effort has been made to ensure that data presented is free of any error, is provided "as is" and without warranty. Use the information contained in this compilation at your own risk. Compiled by JGP © 2010 0.82 0.71 Ambient Temp. (°C) 56-60 61-70 71-80 References: Table 310.16 of National Electrical Code 2008 Edition, Table 3.10.1.16 Philippine Electrical Code 2008 Edition, and http://en.wikipedia.org/wiki/American_wire_gauge 51-55 3/0 (or 000 ) | 80.0 4/0 (or 0000 ) | 100.0 250 | 125.0 300 | 150.0 8 | 8.0 6 | 14.0 4 | 22.0 2 | 30.0 1 | 38.0 1/0 (or 0 ) | 50.0

description

A compilation for AWG to Metric Size conversion/cross-reference of insulated conductors, ampacities provided.

Transcript of Cross-Reference - AWG to Metric Size (With Ampacity) of Insulated Conductors

Page 1: Cross-Reference - AWG to Metric Size (With Ampacity) of Insulated Conductors

(60°C ) (75°C ) (90°C ) (60°C ) (75°C ) (90°C )

TW, UF

RHW, THHW, THW,

THWN,

XHHW, USE, ZW

TBS, SA, SIS, FEP,

FEPB, MI,

RHH, RHW-2, THHN,

THHW,

THW-2, THWN-2,

USE-2, XHH,

XHHW, XHHW-2, ZW-

2

TW, UF

RHW, THHW, THW,

THWN,

XHHW, USE, ZW

TBS, SA, SIS, FEP,

FEPB, MI,

RHH, RHW-2, THHN,

THHW,

THW-2, THWN-2,

USE-2, XHH,

XHHW, XHHW-2, ZW-

2 20 | 20 20 | 20 25 | 25 — — — 25 | 25 25 | 25 30 | 30 20 | 20 20 | 20 25 | 2530 | 30 35 | 35 40 | 40 25 | 25 30 | 30 35 | 3540 | 40 50 | 50 55 | 55 30 | 30 40 | 40 45 | 4555 | 55 65 | 65 70 | 75 40 | 40 50 | 50 60 | 6070 | 70 85 | 85 90 | 95 55 | 55 65 | 65 75 | 8085 |90 100 | — 110 |115 65 |65 75 | 80 85 | —95 | — 115 | 110 130 | — 75 |— 90 |— 90 | 90

110 | 100 130 | 125 150 | 130 85 | 75 100 | 90 115| 105125 | 120 150 | 145 170 | 150 100 | 95 120 | 110 130 | 125145 | 135 170 | 160 190 | 170 115 | 100 135 | 120 150 | 135165 | 160 200 | 195 225 | 205 130 | 120 155 | 145 175 | 165195 | 185 230 | 220 260 | 225 150 | 140 180 | 170 205 | 190215 | 210 255 | 255 290 | 265 170 | 165 205 | 200 230 | 225240 | 240 285 | 280 320 | 295 190 | 185 230 | 225 255 | 250260 | 260 310 | 305 350 | 345 210 | 205 250 | 245 280 | 275280 | 280 335 | 330 380 | 355 225 | 220 270 | 265 305 | 300320 | 315 380 | 375 430 | 400 260 | 255 310 | 305 350 | 345355 | 370 420 | 435 475 | 470 285 | 305 340 | 365 385 | 410385 | 395 460 | 470 520 | 530 310| 315 375 | 380 420| 430400 | 405 475 | 485 535 | 515 320 | 335 385| 405 435| 460410 | — 490 | — 555 | — 330 | — 395 | — 450 | —435 | 445 520 | 540 585 | — 355| 370 425 | 440 480 | 495455 | — 545 | — 615 | — 375 | — 445 | — 500 | —495 | — 590 | — 665 | — 405 | — 485 | — 545 | —520 | — 625 | — 705 | — 435 | — 520 | — 585 | —545 | — 650 | — 735 | — 455 | — 545 | — 615 | —560 | — 665 | — 750 | — 470 | — 560 | — 630 | —

0.41

CORRECTION FACTORS

0.750.670.580.33 —

1.041.000.960.910.870.820.760.710.58

0.580.41 — — —

1.051.000.940.880.82

3 | 30.0

For ambient temperatures other than 30°C, multiply the allowable ampacities shown above by the appropriate

factor shown below. 1.081.000.91

800 | —900 | 500.01000 | —1250 | —

400 | 200.0500 | 250.0600 | 325.0700 | 375.0750 | 400.0

2000 | —

CROSS-REFERENCE - AWG TO METRIC SIZE (WITH AMPACITY) OF INSULATED CONDUCTORS

Temperature Rating Based on Insulation Type

Copper Aluminum or Copper-clad Aluminum

Wire Size

Note: Given values for wire sizes are not equivalents but give the nearest commercially available sizes between AWG and Metric standards Quantities

before the " | " is for AWG/MCM and those after the vertical bar is for Metric System. The table is most useful when available wire sizes are in Metric

System (mm2) but design specifications are given in AWG or conversely. Ampacities may overlap between AWG-Metric wire sizes using certain insulation

types. Due consideration must be practiced in selecting conductor size based on the nearest ampacity such that greater margin of safety is achieved (say,

by choosing wire size which has one step higher ampacity). Ampacities applicable to not more than three conductors are in raceway, cable, or earth,

rated up to 2000 V and at ambient temperature of 30°C. MCM is the same as kcmil . MCM to mm² conversion can use the relationship 1 kcmil =

0.5067 mm².

AWG (/ MCM or kcmil) | mm2

14 | 2.012 | 3.510 | 5.5

2/0 (or 00 ) | 60.0

46-50

21–2626-3031-3536-4041-45

1500 | —1750 | —

350 | 175.0

Disclaimer: Effort has been made to ensure that data presented is free of any error, is provided "as is" and without warranty. Use the information

contained in this compilation at your own risk.

Compiled by JGP © 2010

0.820.71

Ambient Temp. (°C)

56-6061-7071-80

References: Table 310.16 of National Electrical Code 2008 Edition, Table 3.10.1.16 Philippine Electrical Code 2008 Edition, and

http://en.wikipedia.org/wiki/American_wire_gauge

51-55

3/0 (or 000 ) | 80.04/0 (or 0000 ) | 100.0

250 | 125.0300 | 150.0

8 | 8.06 | 14.04 | 22.0

2 | 30.01 | 38.0

1/0 (or 0 ) | 50.0