CP 55-1991 Portible Fire Extingusher

37
SINGAPORE STANDARD CP 55 : 1991 (UDC 61 4.845) CODE OF PRACTICE FOR Use And Maintenance Of Portable Fire Extinguishers Copyright Reserved Singapore Institute of Standards and Industrial Research 1 Science Park Drive, Singapore 0511 Cable: SlSlR SINGAPORE Telex: RS 28499 SlSlR ISBN 9971-67-401-7

description

Code of Practice for Use and Maintenance of Portable Fire Extinguishers

Transcript of CP 55-1991 Portible Fire Extingusher

Page 1: CP 55-1991 Portible Fire Extingusher

SINGAPORE STANDARD

CP 55 : 1991 (UDC 61 4.845)

CODE OF PRACTICE FOR

Use And Maintenance Of Portable Fire Extinguishers

Copyright Reserved

Singapore Institute of Standards and Industrial Research 1 Science Park Drive, Singapore 051 1 Cable: SlSlR SINGAPORE Telex: RS 28499 SlSlR

ISBN 9971-67-401-7

Page 2: CP 55-1991 Portible Fire Extingusher

This Singapore Standard having been approved by the Building and Construction lndustry Practice Committee was endorsed by the Standards Council on 3 January 1991.

First published, 1991

The Building and Construction lndustry Practice Committee appointed by the Standards Council consists of the following members:

Name Organisation

Chairman : Mr Chow Kok Fong Construction Industry Development Board

Deputy Chairman : Mr Lam Siew Wah Construction lndustry Development Board

Secretary : Mr Stephen Chua Singapore Institute of Standards and Industrial Research

Members : Mr Chee Keng Yam Association of Consulting Engineers. Singapore

Mr Chia Kok Leong Singapore Institute of Architects

Mr Lai Chong Meng Singapore Contractors Association Limited

Mr Gary Ong Khim Chye National University of Singapore

Assoc Prof Phang Kok Wai Nanyang Technological lnstitute

Mr Phang Pock Tong, Tony Housing and Development Board

Mr Song Wee Ngee Institution of Engineers, Singapore

Mr Benedict Tan Public Works Department

Mr Harry K C Wong Department of Industrial Safety

The Technical Committee appointed by the Building and Construction lndustry Practice Committee and responsible for the preparation of this standard consists of representatives from the following organisations:

Name Organisation

Chairman : Mr Boo Geok Kwang Singapore Joint Civil Defence Forces

Secretary : Miss Tan Meow Leng Singapore Institute of Standards and Industrial Research

Members : Mr Choy Marn Koon Singapore Joint ~ i v i i Defence Forces

Mr Ho Siong Hin Department of Industrial Safety

Mr Loke Chong Ngean Singapore Manufacturers' Association

Mr Mohammed Bin Awi Singapore Institute of Standards and Industrial Research

Mr Charles Rudd Institution of Engineers, Singapore

Mr Augustus Tan Singapore Contractors' Association Limited

Page 3: CP 55-1991 Portible Fire Extingusher

CONTENTS

Foreword

Section One. General

1.1 Scope -

1.2 Purpose

1.3 Definitions

1.4 Classification and ratings of fire extinguishers -

1.5 Classification of hazards-

1.6 General requirements -

Section Two. Selection of extinguishers

2.1 General requirements -

2.2 Selection by hazard -

Section Three. Distribution of extinguishers

3.1 General requirements -

3.2 Fire extinguisher size and placement for Class A hazards

3.3 Fire extinguisher size and placement for Class B fires (excluding fires in flammable liquids of appreciable depth)

3.4 Fire extinguisher size and placement for Class B fires in flammable liquids of appreciable depth -

3.5 Class B fire extinguishers for pressurized flammable liquids and gas fires -

3.6 Cooking grease fires -

3.7 Three-dimensional Class B fires -

3.8 Fire extinguisher size and placement for Class C hazards

3.9 Fire extinguisher size and placement for Class D hazards

Section Four. Inspection, maintenance and recharging

4.1 General

4.2 Inspection -

Page

5

Page 4: CP 55-1991 Portible Fire Extingusher

4.3 Maintenance - 4.4 Recharging -

Section Five. Hydrostatic Testing

5.1 General 18

5.2 Frequency - 19

5.3 Testing pressures 19

5.4 Test equipment and procedures 20

APPENDICES

A. Ratings of commonly used fire extinguishers -

B. Maintenance procedures

C. General safety guidelines for recharging

D. Features of common types of extinguishers -

E. Hydrostatic test - Proof pressure test method -

TABLES

1. Minimum sizes of fire extinguishers for Class A hazards - 11

2. Travel distance to extinguishers for different hazards - 12

3. Requirements for recharging gases - 18

4. Hydrostatic test interval for extinguishers 19

FIGURES

1. Stored pressure powder extinguisher - 30

2. Stored pressure mechanical foam extinguisher - 30

3. Stored pressure halon extinguisher - 31

4. Stored pressure halon extinguisher with fixed nozzle - 31

5. Cartridge-operated water extinguisher - 32

6. Carbon dioxide extinguisher - 32

7. Hydrostatic testing of extinguisher bodies - Proof pressure test method - 34

Page 5: CP 55-1991 Portible Fire Extingusher

SINGAPORE STANDARD

CODE OF PRACTICE FOR USE AND MAINTENANCE OF PORTABLE FIRE EXTINGUISHERS

FOREWORD

This Code of Practice was prepared by the Technical Committee for Code of Practice on the Use and Maintenance of Portable Fire Extinguishers under the direction of the Building and Construction Industry Practice Committee. This Code covers the requirements and procedures on the selection, installation, inspection, servicing, maintenance and recharging of portable fire extinguishers used in buildings. It is intended to complement the Singapore Standard 232 : 1980 Specification for Portable Fire Extinguishers and provide guidance to persons who need to use and/or maintain portable fire extinguishers.

In addition to conforming to this Code, individuals or organizations servicing fire extinguishers should familiarise themselves with other applicable legislations.

In preparing this code, reference was made to the following standards:

1. BS 5045 Transportable containers Part 3 : 1984 Specification for seamless aluminium alloy gas containers above 0.5 litre water capacity and up to 300 bar charged pressure at 15°C

2. BS 5306 Fire extinguishing installations and equipment on premises Part 3 : 1985 Code of practice for selection, installation and maintenance of portable fire extinguishers

3. BS 5423 : 1987 Specification for portable fire extinguishers

4. NFPA 10 - 1984 Portable fire extinguishers

5. SS 232 : 1980 Specification for portable fire extinguishers

6. Fire Precautions for Buildings 1982

Acknowledgement is made for the use of information from the overseas publications and the fire regulation.

NOTE

1. Singapore Standards are subject to periodical review to keep abreast of technological changes and new technical develo~ments. The revisions of Sinaa~ore Standards are announced throuah - the issue either of amendment slips or of revised ediiions.

2. Compliance with a Singapore Standard does not exempt users from legal obligations.

Page 6: CP 55-1991 Portible Fire Extingusher

SECTION ONE

GENERAL

1.1 SCOPE

This Code covers the selection, installation, inspection, testing and maintenance of portable fire extinguishers and the requirements given herein are minimum. Portable fire extinguishers are appliances to be used as a first line of defence to cater for small fires. They are essential even if other forms of fire protection equipment like hose reels, sprinklers and rising mains are installed in the premises.

1.2 PURPOSE

This Code is specially prepared to assist in selecting the proper extinguishers and to install and maintain them correctly. The requirements are general in nature and are not intended to supersede the specific requirements of relevant authority for specific occupancies.

The requirements of this Code are by no means the ultimate and may be replaced by new technologies and better alternatives provided the degree of protection meets the requirement of the relevant authority.

1.3 DEFINITIONS

1.3.1 The different types of fires are classified into Classes A, B, C and D and are defined as follows:

(a) Class A

Class A fires are fires involving the burning of ordinary combustible materials like wood, paper, cloth, furnishing, plastics and rubber.

(b) Class B

Class B fires are fires involving flammable liquids, solvents, oils, paints, thinner and flammable gases.

(c) Class C

Class C fires are fires involving live electrical equipment like electrical mains, transformers and electrical appliances, etc and where extinguishing medium used must be electrically n ~ n - ~ ~ n d ~ ~ t i v e . (If the electrical equipment is de-energized, extinguishers for Classes A and B can be used.)

(d) Class D

Class D fires are fires involving combustible metals eg. potassium, magnesium, titanium, sodium, lithium and zirconium.

1.3.2 Body (Or Extinguisher Body). The metal shell of an extinguisher, excluding all closures, safety devices and pressure indicators, designed to contain the extinguishing medium, and including any skirt.

Page 7: CP 55-1991 Portible Fire Extingusher

1.3.3 Inspection. lnspection is a "quick checK' that an extinguisher Is available and will operate. It is intended to give reasonable assurance that the extinguisher is fully charged and operative. This is done by seeing that it is in its designated place, that it has not been actuated or tampered with, and that there is no obvious or physical damage or condition to prevent operation.

1.3.4 Maintenance. Maintenance is a 'thorough check" of the extinguisher. It is intended to give maximum assurance that an extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair or replacement. It will normally reveal the need for hydrostatic testing.

1.3.5 Manufacturer's Test Pressure. The manufacturer's test pressure is the pressure at which the body was tested at time of manufacture. This pressure is shown on the body in the case of carbon dioxide extinguishers and on the permanent nameplate or label in the case of other types of extinguishers.

1.3.6 Portable Extinguisher. An extinguisher which is designed to be carried and operated by hand and which in working order has a mass of not more than 20 kg.

1.3.7 Occupancy. Occupancy refers to contents and activities in the buildings.

1.3.8 Operating Pressure. The pressure as indicated on the gauge and label.

1.3.9 Recharging. Recharging is the replacement of the extinguishing agent and also includes the expellant for certain types of extinguishers.

1.3.10 Relevant Authority. Relevant authority is the organisation, office or individual responsible for consenting to the use of the equipment, installation or a procedure.

1.3.11 Shall. lndicates a mandatory requirement.

1.3.12 Should. lndicates recommendations made.

1.4 CLASSIFICATION AND RATINGS OF FIRE EXTINGUISHERS

Portable fire extinguishers are classified for use on certain classes of fires and rated for relative extinguishing effectiveness at ambient temperature. This is based upon the preceding classification of fires and the fire-extinguishment potentials as determined by fire tests (refer to SS 232).

The classification and rating system described in this Code is based on extinguishing pre- planned fires of determined size and description as follows:

Class A Rating - Wood crib

Class B Rating - Flammable liquid tray

Class C Rating - No fire test. Agent must be a non-conductor of electricity

Class D Rating - Special tests on specific combustible metal fires (The carrying out of such tests and the rating of extinguisher shall be the responsibility of the manufacturers.)

Page 8: CP 55-1991 Portible Fire Extingusher

1.5 CLASSIFICATION OF HAZARDS

1.5.1 Low Hazard. Where the amount of combustibles or flammable liquids present is such that fires of small size may be expected and these may include offices, classrooms, places of worship, assembly halls, telephone exchanges and domestic kitchens.

1.5.2 Medium Hazard. Where the amount of combustibles or flammable liquids present is such that fires of moderate size may be expected and these may include storage and display area, motor showrooms, covered car parks, light-industry premises, warehouses not classified as high hazard, shopping areas, laboratories, small painting areas and commercial kitchens.

1.5.3 High Hazard. Where the amount of combustibles or flammable liquids present is such that fires of severe magnitude may be expected and these may include exhibition areas, furniture showrooms, wood working premises, vehicle repair workshops, aircraft hangars, warehouses with high-bay (4 m or higher) storage and processes such as flammable liquid handling, paint and dipping.

1.6 GENERAL REQUIREMENTS

1.6.1 The classification of extinguishers shall be in accordance with the definition of test fires and shall consist of a LETTER which indicates the class of fire on which an extinguisher has been found to be effective, preceded by a rating NUMERAL (Class A and B only) which indicates the relative extinguishing effectiveness (refer to SS 232 for definitions of test fires).

1.6.2 ~xtin~uishers shall be conspicuously located in positions where they will be readily accessible and immediately available in the event of fire. Preferably they shall be located near to room exits, corridors, stairways, lobbies and landings. In large rooms, and in certain locations where visual obstruction cannot be completely avoided, signs shall be provided to indicate the location.

1.6.3 Extinguishers provided to deal with special risks shall be sited near to the risk concerned, but not too near as to be inaccessible in case of fire. If the special risk is contained in a confined space, it is generally advisable to position the extinguisher outside that space.

1.6.4 Extinguishers shall not be located in places where they may be exposed to unduly corrosive atmospheres or splashing by corrosive fluids.

1.6.5 Extinguishers shall be mounted on walls by the hangers or brackets supplied.

1.6.6 Cabinets, if permitted to house extinguishers, shall not be locked. Where extinguishers are subject to malicious use, locked cabinets may be used provided they Include means of emergency access eg. a glass-fronted box to house key to unlock fire extinguisher cabinet. Such key shall be located next to the cabinet or as part of the cabinet.

1.6.7 If permitted by the relevant authority, free-standing extinguishers may be placed on shelves or on the floor if these extinguishers are designed for such form of placement.

1.6.8 Extinguishers installed under conditions where they could be subject to dislodgement shall be installed in brackets specifically designed to cope with this problem.

1.6.9 Extinguishers installed under conditions where they could be subject to physical damage shall be protected from possible impact.

Page 9: CP 55-1991 Portible Fire Extingusher

1.6.10 Extinguishers shall be installed so that the carrying handle of the extinguisher is not more than 1.50 m above the floor.

1.6.11 Operating instructions as in accordance with SS 232 shall be located on the front of the extinguisher.

SECTION TWO

SELECTION OF EXTINGUISHERS

2.1 GENERAL REQUIREMENTS

2.1.1 All extinguishers used shall comply with the requirements of SS 232 and approved by the relevant authority.

2.1.2 The selection of extinguishers for a given situation shall be determined by the hazards anticipated, the construction and occupancy (see 1.3.7) of individual property. (See Appendix A.) The number, size and placement of extinguishers required shall be determined using Section Three.

2.2 SELECTION BY HAZARD

Extinguishers shall be seiected for the specific class or classes of hazards to be protected in accordance with the following sub-divisions :

2.2.1 Extinguishers for protecting Class A hazards shall be selected from the following:

Water types, multi-purpose powder types, bromochlorodifluoromethane (BCF/Halon 1211), bromotrifluoromethane (BTM/Halon 1301) or foam types.

2.2.2 Extinguishers for protecting Class B hazards shall be selected from the following:

Powder, bromochlorodifluoromethane (Halon 1211), bromotrifluoromethane (Halon 1301), carbon dioxide and mechanical foam such as aqueous film forming foam (AFFF).

NOTE 1. When used in open areas, the powder type is recommended since in the open both carbon dioxide gas and brom~chlor~difluoromethane (Halon 1211) gas are less efficient.

NOTE 2. Foam is generally unstable in the presence of powder and it is imperative that the two agents should Only be used together when special compatible powders and/or foams are provided.

2.2.3 Extinguishers for protection of Class C hazards shall be seiected from the following:

Bromotrifluoromethane (Halon 1301), bromochlorodifluoromethane (Halon 121 I ) , carbondioxide and powder types.

NOTE. Carbon dioxide extinguishers equipped with metal horns are not considered safe for use on fires in energized electrical equipment and, therefore, are not classified for use on Class C hazards.

2.2.4 Extinguishers and extinguishing agents for the protection of Class D hazards shall be of types approved for use on the specific combustible metal hazard.

Page 10: CP 55-1991 Portible Fire Extingusher

2.2.5 Class B Fire Extinguishers For Pressurized Flammable Liquids And Gas Fires. Fires of this nature are considered to be a special hazard. Powder type fire extinguishers are the only type of extinguishers which may be effectively used on this type of hazard like outdoor LPG (Liquefied Petroleum Gas) tanks. However bromochlorodifluoromethane (Halon 121 1) may also be used for small fires involving LPG cylinders.

Selection of extinguishers for this type of hazard shall be made on the basis of recommendations by manufacturers of this specialized equipment subject to the approval of the relevant authority. Special nozzle design and rates of agent application are required to cope with such hazards.

2.2.6 Cooking Grease Fires. Fires involving liquified fat or oil in depth, such as fat fryers, are considered to be a special hazard. Only powder type extinguishers containing sodium bicarbonate or potassium bicarbonate have been proven effective on this hazard due to agent characteristics. Bromochlorodifluoromethane (Halon 121 1) extinguishers may also be used for smallerfires involving this hazard.

2.2.7 Three-dimensional Class B Fires. A three-dimensional Class B fire involves Class B materials in motion such as pouring, running, or dripping flammable liquids and generally includes vertical as well as one or more horizontal surfaces.

Fire of this nature are considered to be a special hazard. The installation of fixed system should be considered. Portable fire extinguishers shall be deemed insufficient to curb with a three-dimensional Class B fire. However, adequate number of powder extinguishers should be provided in the vicinity of the area containing such hazard to tackle any incipient fire.

2.2.8 Water Soluble Flammable Liquid Fires. Foam and AFFF type fire extinguishers shall not be used for the protection of water soluble flammable liquids, such as alcohols, acetone, esters, ketones etc. Only special types of foams recommended by manufacturers shall be used.

2.2.9 Electronic Equipment Fires. Extinguishers for the protection of delicate equipment shall be selected from the following types:

(a) Bromochlorodifluoromethane (Halon 121 1);

(b) Bromotrifluoromethane (Halon 1301);

(c) Carbon dioxide.

Caution: While use of other extinguishers and extinguishing agents may successfully extinguish a fire in this equipment, their use may render the equipment damaged beyond repair. Dry powder residue will probably not be able to be completely and immediately removed and in addition, multi-purpose powder agent, when exposed to temperatures in excess of 250°F (121°C) or relative humidity in excess of 50 percent, may cause corrosion.

SECTION THREE

DISTRIBUTION OF EXTINGUISHERS

3.1 GENERAL REQUIREMENTS

3.1.1 The minimum number of fire extinguishers required for the protection of a given area shall be in accordance with Section Three. Additional numbers may be added to upgrade the protection.

Page 11: CP 55-1991 Portible Fire Extingusher

3.1.2 Fire extinguishers shall be provided for the protection of building structures as well as for hazards pertaining to occupancies therein. The building structure, i f combustible, shall be protected by extinguishers suitable for Class A fires. Protection for the occupancy in that building shall be provided by fire extinguishers suitable for Class A, 6, C or D fire potentials as may be present.

3.1.3 Areas to be protected shall be classified as low, medium or high hazard. Isolated small areas within these hazards which occupancies differ shall be appropriately protected.

3.2 FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS A HAZARDS

3.2.1 Extinguishers shall be located so that no person needs to travel more than 15 m to reach an extinguisher.

3.2.2 Minimum sizes of fire extinguishersfor the listed grades of Class Afire hazards shall be provided in accordance with Table 1, subject to the following:

(a) For the high hazard occupancy the minimum rating shall be 21A.

(b) There shall be at least one extinguisher of the minimum size on each storey/level of buildings.

/

Table 1. Minimum sizes of fire extinguishers for Class A hazards

NOTE. For each unit of "A", the maximum floor area to be covered is 40 mz for the low hazard occupancy, 20 m2 for the medium hazard occupancy and 15 mZ for the high hazard occupancy.

Minimum extinguisher

rating

3A 5A 8A

13A 21A 27A 34A 43A 55A

3.2.3 Combination Of Sizes. In selecting the sizes of extinguishers to meet the requirements of Table 1, consideration shall be given to the circumstances and the arrangement of the building or floor space to be protected.

It is undesirable to choose to provide a small number of extinguishers of the highest rating or a large number of extinguishers of the very low rating to make up the minimum aggregate required. For example, it would be undesirable to meet a lOOA rating by providing 2 x 55A or 21 x 5A extinguishers. One of the following combinations would be a better choice:

Maximum floor area to be covered (mZ)

Low hazard occupancy

120 200 320 520 840

1080 1360 1720 2200

Medium hazard occupancy

60 100 160 260 420 540 680 860

1100

High hazard occupancy

- 315 405 510 645 825

Page 12: CP 55-1991 Portible Fire Extingusher

8 x 13A extinguishers; 5 x 21A extinguishers; 4 x 27A extinguishers; 2 x 27A t 7 x 8A extinguishers; or 1 x 43A t 5 x 13A extinguishers.

NOTE. The travel distance from any point of the floor to the nearest extinguisher must not exceed 15 m. This means that more extinguishers in addition to this minimum recommendation may have to be provided.

3.2.4 The protection requirements may be fulfilled by the provision of extinguishers of higher rating provided that the maximum travel distance as in 3.2.1 is not exceeded.

3.3 FIRE EXTINGUISHER SlZE AND PLACEMENT FOR CLASS B FIRES (EXCLUDING FIRES IN FLAMMABLE LIQUIDS OF APPRECIABLE DEPTH) (Appreciable depth refers to flammable liquid hazards having a depth greater than 8 mm.)

3.3.1 Extinguishers shall be located so that the maximum travel distances shall not exceed those specified in Table 2. For various grades of hazards listed, the lowest rating of fire extinguishers provided shall be as indicated in the table.

Table 2. Travel distance to extinguishers for different hazards

NOTE. The specified ratings do not imply that fires of the magnitudes indicated by these ratings will occur, but rather to give the.operators more time and agent to handle difficult spill fires that may occur.

Type of hazard

Low

Medium

High

3.3.2 Combination of extinguishers of lower ratings may be used to fulfill the protection requirements of Table 2 for high hazard type only. Such combination shall be limited to a maximum of three extinguishers of individual rating 218 or higher.

3.4 FIRE EXTINGUISHER SlZE AND PLACEtJlENT FOR CLASS B FIRES IN FLAMMABLE LIQUIDS OF APPRECIABLE DEPTH (Appreciable depth refers to flammable liquid hazards having a depth greater than 8 mm.)

Basic minimum extinguisher rating

88 138 348

708

1448

3.4.1 Portable fire extinguishers shall not be installed as the sole protection for flammable liquid hazards of appreciable depth where the surface area exceeds 1 m2.

Maximum travel distance to extinguishers (m)

3 5

10

15

15

NOTE. Fuel depth has little effect on ease of extinction until the fuel depth is less than about 8 mm, when fires become easier to ext'ng~ish the less the depth. Ease of extinction then becomes more a fdncton of voldme of fuel than area of fire "rider normal circ~mstances spillage may be expected to spreaa to any depth dp to a m:n'mum o f , say, 1 mm. Spi lage to a depth of 1 mm of, for example, petrol could be expected to burn itself out in less than 0.5 minute afler ignition. Under these circumstances, extinguishers would be required only for any secondary fires, as the time available to attack the original spill fire would be so short.

Page 13: CP 55-1991 Portible Fire Extingusher

3.4.2 For flammable liquid hazards of appreciable depth such as in dip or quench tanks, a Class B fire extinguisher shall be provided as follows:

(0 34Bfor sutface area not exceeding 0.5 m2

(ii) 708 for surface area not exceeding 1 m2

3.4.3 Travel distances for portable extinguishers shall not exceed 7 m.

Scattered or widely separated hazards shall be individually protected. An extinguisher in the proximity of a hazard shall be carefully located so as to be accessible in the presence of a fire without undue danger to the operator.

3.5 CLASS B FIRE EXTINGUISHERS FOR PRESSURIZED FLAMMABLE LIQUIDS AND GAS FIRES

Travel distances for hand portable extinguishers used to protect pressurized flammable liquids or gas hazards shall not exceed 7 m.

Caution: It is undesirable to attempt to extinguish this type of fire unless there is reasonable assurance that the source of fuel can be promptly shut off.

3.6 COOKING GREASE FIRES

An extinguisher which uses one of the agents specified in 2.2.6 and has at least a rating of 70B shall be selected for this type of hazard.

As for bromochlorodifluoromethane (Halon 1211) extinguishers which are normally recommended for domestic kitchens, they should have a minimum rating of 8B.

Such extinguishers shall be located at a safe distance away from the potential hazard area and shall have a travel distance of not more than 7 m.

3.7 THREE-DIMENSIONAL CLASS B FIRES

The travel distance for portable fire extinguishers provided for three-dimensional Class B hazards shall not exceed 7 m.

3.8 FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS C HAZARDS

Extinguishers with Class C ratings shall be required where energized electrical equipment may be encountered. This will include fire either directly involving or surrounding electrical equipment. Since the fire itself is a Class A and/or Class B hazard, this Class Cfire extinguishers shall be sized and located on the basis of the anticipated Class A and/or Class B hazards.

NOTE. Electrical equipment should be de-energized as soon as possible to prevent reignition

Page 14: CP 55-1991 Portible Fire Extingusher

3.9 FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS D HAZARDS

Extinguishers or extinguishing agents with Class D ratings shall be provided for fires involving combustible metals.

Extinguishing equipment shall be located in the vicinity of the Class D hazard.

Size and determination shall be on the basis of the specific combustible metal, its physical particle size, area to be covered and recommendations on data from control tests conducted by the extinguisher manufacturer, subject to the approval of the relevant authority.

SECTION FOUR

INSPECTION, MAINTENANCE AND RECHARGING

4.1 GENERAL

4.1.1 This section is concerned with the rules governing inspection, maintenance and recharging of extinguishers. These factors are of prime importance in ensuring operation at the time of a fire.

4.1.2 The owner or occupant of a property in which ektinguishers are located shall be responsible for such inspection, maintenance and recharging.

4.1.3 Inspection is normally performed by the owner or occupant, or any designated responsible personnel.

4.1.4 Maintenance and recharging shall be performed by trained persons of an approved organisation authorised by the relevant authority and having available the proper types of tools, recharge materials, lubricants, and manufacturer's recommended replacement parts.

4.2 INSPECTION (see 1.3.3)

4.2.1 Frequency Of Inspection. It is recommended that extinguisher should be inspected monthly, or at more frequent intelvals when the following circumstances exist:

(a) High frequency of fires in the past;

(b) Severe hazards;

(c) Susceptibility to tampering, vandalism, or malicious mischief;

(d) Possibility of, or experience with, theft of extinguishers;

(e) Locations that make extinguishers susceptible to mechanical injury;

(9 Possibility of visible or physical obstructions;

(g) Exposure to abnormal temperatures or corrosive atmospheres;

(h) Characteristics of extinguishers, such as susceptibility to leakage.

Page 15: CP 55-1991 Portible Fire Extingusher

4.2.2 Inspection Procedures. Periodic inspection of extinguishers shall include a check of at least the following items:

(a) Located in its designated place;

(b) No obstruction to access or visibility;

(c) Operating instructions on the extinguisher label legible and facing outward;

(d) Seals and tamper indicators not broken or missing;

(e) Determine fullness by weighing or "hefting';

(9 Examine for obvious physical damage, corrosion, leakage or clogged nozzle;

(g) Pressure gauge reading or indicator in the operative range or position.

4.2.3 Corrective Action. When an inspection of any extinguisher reveals a deficiency in any of the conditions listed in (a) and (b) of 4.2.2, immediate corrective action shall be taken.

4.2.3.1 Rechargeable extinguisher. When an inspection of any rechargeable extinguisher reveals a deficiency in any of the conditions listed in (c), (d), (e), (9 and (g) of 4.2.2, it shall be subjected to applicable maintenance procedures.

4.2.3.2 Non-rechargeable extinguisher. When an inspection of any non-refillable disposable extinguisher reveals a deficiency in any of the conditions listed in (c), (e), (9 and (g) of 4.2.2, it shall be discharged and removed from setvice.

4.2.4 Record Keeping

4.2.4.1 Personnel making an inspection should keep records for those extinguishers that were found to require corrective actions.

4.2.4.2 The date of inspection and the initials of the person performing the inspection should be recorded.

4.3 MAINTENANCE (see 1.3.4)

4.3.1 Frequency Of Maintenance. Extinguishers shall be subjected to maintenance not more than one year apart or when specifically indicated by an inspection. Maintenance procedures shall be performed in accordance with 4.3.2.

Extinguishers taken away for maintenance or recharge shall have in replacement, extinguishers of the same type and at least equal rating.

4.3.2 Maintenance Procedures. Maintenance procedures shall include a thorough examination of the three basic elements of an extinguisher:

(a) Mechanical parts;

Page 16: CP 55-1991 Portible Fire Extingusher

(b) Extinguishing agent; and

(c) Means of expulsion.

Exception: It is not necessary during the annual maintenance to internally examine stored pressure extinguishers equipped with pressure indicators or gauges or carbon dioxide extinguishers. However, such extinguishers shall be thoroughly examined externally in accordance with the applicable items of 4.3.2(a).

Detail maintenance procedures are described in Appendix B.

4.3.3 Record Keeping. Each extinguisher shall have a tag or label securely attached that indicates the month and year the maintenance was performed and shall identify the person and organisation performing the service. The same record tag or label shall indicate if recharging was also performed.

4.3.3.1 In addition to the required tag or label (see 4.3.3), a permanent file record should be kept for each extinguisher. This file record should include the following information as applicable:

(a) The maintenance date and the name of person or agency performing the maintenance;

(b) The date when last recharged and the name of person or agency performing the recharge;

(c) The hydrostatic retest date and the name of person or agency performing the hydrostatic test;

(d) The date of the next recharge

4.3.3.2 Labels indicating inspection, maintenance, hydrostatic retests, and recharge dates shall not be placed over the operating instructions of the extinguisher.

4.4 RECHARGING (see 1.3.9)

4.4.1 General. All extinguishers shall be recharged after use or as indicated by an inspection or when performing maintenance. When performing the recharging, the recommendations of the manufacturers shall be followed. For recharge chemicals, see 4.4.3.1. (Refer to Appendix C for general safety guidelines for recharging.)

4.4.2 Frequency Of Recharging. All extinguishers shall be completely emptied and recharged at intervals as follows:

(a) Every 25 years water (stored pressure) chemical foam mechanical foam (gas cartridge) mechanical foam (stored pressure)

(b) Every 5 years

(c) Every 10 years

water (gas cartridge) powder (gas cartridge) powder (stored pressure)

carbon dioxide halon 1301 halon 121 1

Page 17: CP 55-1991 Portible Fire Extingusher

4.4.3 Recharging Procedures. The procedure specified in BS 6643 : Part 1 and as detailed by the manufacturer should be followed.

Before recharging, the extinguisher should be emptied and the extinguishing medium discarded. Water and foam extinguishers should be thoroughly washed out with clean water but on no account should this procedure be applied to powder, halon or carbon dioxide extinguishers, which have to be kept completely free of water. Cartridges more than 10 years from date of manufacture shall be replaced.

4.4.3.1 Recharge chemicals. Only those materials specified by the manufacturer or the equivalent shall be used. Tests should be conducted to assure equal performance.

NOTE 1. Powder refills should only be opened immediately before use, and bulk refills should be resealed immediately after use, to reduce the possibility of contamination or absorption of moisture from the atmosphere.

NOTE 2. The recommended filling densities for halon 1211, halon 1301 and carbon dioxide are 1.668, 1.51 and 0.667 respectively.

4.4.3.2 Mixing of agents. Mixing or cross-contamination of different types of powder shall be avoided.

NOTE. Some types of powder are capable of reacting with other types to produce water and carbon dioxide. This reaction often does not become apparent until after a delay of weeks during which no apparent reaction occurs. The water causes caking and, in a closed container the carbon dioxide causes a pressure rise that might be dangerous.

4.4.3.3 Replacement pressure gauges shall be compatible with the extinguisher in terms of its operating pressure range, empty-full markings, material of the valve body and the type of extinguishing agent.

4.4.3.4 Precautionary pressurization measures. A rechargeable stored pressure type extinguisher shall be pressurized only to the charging pressure specified on the extinguisher nameplate. A regulated source of pressure, set no higher than 200 kPa above the operating pressure, shall be used to pressurize fire extinguishers.

NOTE. An unregulated source of pressure such as a nitrogen cylinder without a pressure regulator, should never be used because the extinguisher could be overpressurized and possibly rupture.

4.4.3.5 Pressurizing gas. For stored pressure powder and halon type fire extinguishers, the pressurizing gas used can be compressed air, nitrogen, argon or helium and shall have a moisture content of not more than 80 ppm by volume.

4.4.3.6 Conversion of extinguisher types. No extinguisher shall be converted from one type to another, nor shall any extinguisher be converted to use a different type of extinguishing agent.

4.4.3.7 Removal of moisture. For all non-water types of extinguishers any moisture shall be removed before recharging. This can be done by purging with dry gas or evacuating with a vacuum pump.

Caution: Moisture within non-water type extinguisher creates both a serious corrosion hazard to the extinguisher body and a probably inoperative extinguisher.

4.4.3.8 Recharging water types. When recharging stored pressure extinguishers, overfilling will result in improper discharge. The proper amount of liquid agent shall be determined by using one of the following:

(a) Exact measurement in litres, or by weight;

(b) Use of an anti-overfill tube when provided; or

(c) Use oi a fill mark on extinguisher body, if provided

Page 18: CP 55-1991 Portible Fire Extingusher

4.4.3.9 Carbon dioxide and halon gas recharging. The recharging gases used shall comply with the minimum requirements specified in Table 3.

Table 3. Requirements for recharging gases

4.4.3.10 Leak test. After recharging, a leak test shall be performed on stored pressure and self- expelling types.

SECTION FIVE

HYDROSTATIC TESTING

Gases

Purity in vapour phase (v/v)

Moisture (ppmv)

Acidity [ppm (m)]

oi l [ P P ~ (m)l

5.1 GENERAL

Halon 121 1

99.0%

180

3.0

Carbon Dioxide

99.5%

240

5

5.1.1 Hydrostatic testing shall be performed by persons having practical knowledge of pressure testing procedures and safeguards and having available suitable testing equipment and facilities. Such persons

Halon 1301

99.6%

80

3.0

- ~~

shall be employed b; an organisatioithat is approved by the relevant authority.

5.1.2 If, at any time, an extinguisher shows evidence of corrosion or mechanical damage, it shall be hydrostatically tested, subject to the provisions of 5.1.3.

5.1.3 Examination Of Extinguisher Body Condition. When an extinguisher body has one or more conditions listed in this subdivision, it shall not be hydrostatically tested but shall be destroyed by the owner or at his direction:

(a) When there exists repair by soldering, welding, brazing or use of patching compounds;

(b) When the extinguisher body threads are damaged;

(c) When there exists corrosion that has caused pitting such as hidden areas under removable nameplate band assemblies shall be examined;

(d) When there is evidence that the extinguisher has been burnt;

(e) When a calcium chloride type of extinguishing agent was used in a stainless steel extinguisher.

Page 19: CP 55-1991 Portible Fire Extingusher

5.2 FREQUENCY

Extinguishers shall be hydrostatically tested at intervals not exceeding those specified in Table 4.

Table 4. Hydrostatic test interval for extinguishers

5.2.1 Hose Assemblies. A hydrostatic test shall be performed on extinguisher hose assemblies which are equipped with a shut-off nozzle at the end of the hose. The test interval shall be the same as specified for the extinguisher on which the hose is installed.

Extinguisher type

Cartridge operated water

Stored pressure water

Foam

AFFF (Aqueous Film Forming Foam)

Powder type with stainless steel body

Carbon dioxide

Powder type, stored pressure, with mild steel shells or aluminium body

Powder type, cartridge or cylinder operated, with mild steel body

Bromochlorodifluoromethane (Halon 121 1)

Bromotrfluoromethane (Halon 1301)

5.3 TESTING PRESSURES

Test interval (Years)

5

5

5

5

5

10

5

5

10

10

5.3.1 Carbon Dioxide Extinguishers. Carbon dioxide extinguishers shall be tested to the test pressure as stamped on the body.

5.3.2 Stored Pressure Types. All stored pressure and bromochlorodifluoromethane (Halon 1211) types of extinguishers shall be hydrostatically tested at the manufacturer's test pressure (see 1.3.5). The &sting pressure shall not exceed the manufacturer's test pressure.

5.3.3 Self-generating And Cartridge Operated Types

5.3.3.1 Self-generating foam extinguishers of stainless steel construction and cartridge operated water type extinguishers of stainless steel construction shall be hydrostatically tested at 2.4 MPa.

Page 20: CP 55-1991 Portible Fire Extingusher

5.3.3.2 Cartridge operated powder extinguishers shall be hydrostatically tested at their original manufacturer's test pressure as shown on the extinguisher body.

5.3.4 Test Pressure For Hose Assemblies. The hose assemblies for all extinguishers requiring a hydrostatic test shall be tested at the same pressure as that of the body.

NOTE. The test should be carried out within a protective device.

5.4 TEST EQUIPMENT AND PROCEDURES

5.4.1 General

5.4.1.1 Air or gas pressure shall not be used for pressure testing. The failure of an extinguisher body may be violent and dangerous.

5.4.1.2 When extinguisher bodies or cartridges fail a hydrostatic test, they shall be destroyed by the owner or at his direction.

5.4.2 Testing Standards. The equipment and procedures for hydrostatic testing of cylinders with water capacity of 1 litre and above shall be in accordance with either:

(a) Singapore Standard CP 12 : Part 1 - for seamless steel cylinders

(b) British Standard 5430 : Part 2 - for welded steel cyiinders

or (c) British Standard 5430 : Part 3 - for seamless aluminium alloy cylinders

whichever is applicable.

For cylinders or cartridges smaller than 1 litre water capacity, these are covered only as far as it is practicable to apply the requirements of the standards to them.

5.4.3 Testing Methods. A few testing methods are described in the standards stated in 5.4.2. The preferred method, which is also the only method common to all 3 standards, is the proof pressure test method.

5.4.4 Test Equipment And Procedures. The test equipment and procedure for the proof pressure test method shall be as described in Appendix E.

Page 21: CP 55-1991 Portible Fire Extingusher

APPENDIX A

RATINGS OF COMMONLY USED FIRE EXTINGUISHERS

NOTE. The above table shows the common types of extinguishers with their corresponding capacities and ratings. The ratings are the minimum ratings to which the extinguishers are to be tested. However high ratings may be given if the particular

Type

Bromochlorodifluoremethane (Halon 121 1)

ABC Powder (Mono Ammonia Base)

BC Powder (Potassium Bicarbonate)

BC Powder (Sodium Bicarbonate)

Carbon Dioxide

Water

Foam (AFFF)

Foam (Fluoro Protein)

extinguisher can pass the test of that higherrating.

Capacity

1.5 kg 2.5 kg 4.5 kg 5.5 kg

1 kg 2.5 kg 4.5 kg 6 kg 9 kg

1 kg

9 kg

2.2 kg 4.5 kg

9 litre

9 litre

9 litre

Rating

3A/8B 5A/13B 8A/21 B 13A/34B

3A/13B 8A/21 B 13A/34B 21A/55B 21A/70B

-/21 B

-/70B

-/8B -/21 B

13A/-

13A/34B

8A/34B

Page 22: CP 55-1991 Portible Fire Extingusher

APPENDIX Ei

MAINTENANCE PROCEDURES

For convenience, the following check lists are organized into two parts. The first is arranged by mechanical parts (components and containers) common to most extinguishers. The second is arranged by extinguishing material and expelling means and involves a description of the problems peculiar to each agent.

6.1 CHECKLIST AND CORRECTIVE ACTION - MECHANICAL PARTS

Mechanical Parts. Any parts needed for replacement should be obtained from the manufacturer

Corrective action

1. Clean or replace

2. Inspect body under label for corrosion and refix label

1. Retest if expired

2. Hydrostatic test and repaint; or discard

3. Hydrostatic test and repaint; or discard

4. Clean and repaint

5. Discard or consult manufacturer

6. Discard or consult manufacturer

7. Clean, repair, and leak test; or discard

8. Discard or consult manufacturer

Part

Label

Body

.

Items to check

1. Illegible wording

2. Corrosion or loose label

1. Hydrostatic test date or date of manufacture

2. Corrosion

3. Mechanical damage (denting or abrasion)

4. Paint condition

5. Evidence of previous repairs (welding, soldering, brazing, etc)

6. Damaged threads (corroded, cross- threaded, or worn)

7. Damaged sealing surface (nicks or corrosion)

8. Broken hanger attachment, carrying handle lug

Page 23: CP 55-1991 Portible Fire Extingusher

Part

Nozzle or Horn

Hose Assembly

Valve Safety Device

Gauge or Other Pressure Indicating Device

Items to check

1. Brittle, deformed, damaged or cracked

2. Blocked openings

3. Damaged threads (corroded, cross-threaded or worn)

1. Punctured, cracked or worn hose

2. Cracked or corroded couplings

3. Cracked or corroded swivel joint

4. Damaged threads (corroded, cross-threaded or worn)

5. Hose cut at couplings

6. Clogged or deformed hose

1. Damaged (corroded, bent or seized)

2. Missing

1. Damaged, jammed or missing pointer

2. Illegible or faded dial

3. Corrosion

4. Dented casing or defaced, broken or cracked cover

5. Jammed or corroded pressure-indicating stem (non-gauge type)

Corrective action

1. Replace

2. Clear blockage

3. Replace

1. Replace

2. Replace

3. Replace

4. Replace

5. Repair or replace

6. Clear blockage or replace

1. Repair and lubricate; or replace

2. Replace

1. Depressurize and replace gauge

2. Depressurize and replace gauge

3. Depressurize and check calibration, clean and repaint; or replace gauge

4. Depressurize and check calibration; or replace gauge

5. Depressurize and replace head assembly, or body whichever appropriate.

Page 24: CP 55-1991 Portible Fire Extingusher

Corrective action

1. Depressurize, check freedom of movement, and repair; or replace

2. Depressurize and replace

1. Repair and lubricate; or replace

2. Clean or replace

1. Replace

2. Replace

3. Replace

1. Replace

2. Replace cartridge

3. Replace cartridge

4. Replace cartridge

1. Replace

2. Replace

3. Clean, repair and leak test; or replace

4. Clear blockage

Part

Body Valve

Nozzle Shut-off Valve

Puncture Mechanism

Gas Cartridge

Head Cap

Items to check

1. Corroded, damaged or jammed lever, handle, spring, stem, or fastener joint

2. Damaged outlet threads (corroded, cross-threaded, or worn)

1. Corroded, damaged, jammed or binding lever, spring, stem, or fastener joint

2. Clogged, deformed or corroded nozzle

1. Darnaged jammed or binding puncture lever, stem or fastener joint

2. Blunt or damaged cutting or puncture pin

3. Damaged threads (corroded, cross-threaded, or worn)

1. Corrosion

2. Damaged seal disc

3. Damaged threads (corroded. cross-threaded, or worn)

4. Illegible weight markings

1. Corroded, cracked or broken

2. Damaged threads (corroded, cross-threaded or worn)

3. Damaged sealing surface (nicked, deformed or corroded)

4. Blocked vent hole or slot

Page 25: CP 55-1991 Portible Fire Extingusher

Part

Carrying Handle

Pressurizing Valve

Gasket "0 Ring and Seals

Brackets

Gas Tube and Siphon Tube

Safety Relief Device

Items to check

1. Broken handle lug (integral part of shell or valve)

2. Broken handle

3. Corroded, jammed or worn fastener joint

1. Leaking seals

1. Damaged (cut, cracked or worn)

2. Missing

3. Aged or weathered (compression set, brittle, cracked)

1. Corroded, worn or bent

2. Loose or binding fit

3. Worn, loose, corroded or missing screw or bolt

1. Corroded, dented, cracked or broken

2. Blocked tube or clogged openings in tube

1. Corroded or damaged

2. Broken, operated or clogged

Corrective action

1. Replace shell or valve

2. Replace

3. Clean or replace

1. Depressurize and replace valve or core

1. Replace and lubricate

2. Replace and lubricate

3. Replace and lubricate

1. Repair and repaint; or replace

2. Adjust or replace

3. Tighten or replace

1. Replace

2. Clear blockage or replace

1. Depressurize and replace

2. Depressurize and replace; or repair

Page 26: CP 55-1991 Portible Fire Extingusher

8.2 CHECKLIST AND CORRECTIVE ACTIONS - EXPELLING MEANS AND EXTINGUISHING AGENT

Self-expelling Type

Gas Cartridge Type

Agent

Carbon Dioxide

Bromotrifluoromethane (Halon 1301)

Part/Checkpoints

1. Incorrect weight

2. Broken or missing tamper indicator

1. Punctured cylinder seal disc

2. Incorrect weight

3. Broken or missing tamper indicator

Agent

Powder

Corrective action

1. Recharge to correct weight .

2. Conduct leak test and weigh, recharge or replace indicator

1. Replace extinguisher body

2. Replace body or return to manufacturer for filling

3. Examine cylinder seal disc, replace indicator

Part/Checkpoints

1. Incorrect weight or charge level

2. Contaminated, caked or wrong agent

3. Cartridge condition

(a) Punctured seal disc

(b) Incorrect weight

(c) Broken or missing tamper indicator

Corrective action

1. Refill to correct weight

2. Empty and refill

(a) Replace seal disc and refill cartridge to correct weight or replace

(b) Replace seal disc and refill cartridge to correct weight or replace

(c) Examine seal disc and replace indicator

Page 27: CP 55-1991 Portible Fire Extingusher

Stored Pressure Type

Agent

WaterIMechanical Foam

Part/Checkpoints

1. Recharging date due

2. Incorrect fill level

3. Agent condition (presence of precipitate or foreign material, dirty or cloudy)

4. Broken cartridge seal disc

5. lncorrect cartridge weight

6. Broken or missing tamper indicator

Agent

Powder

Bromochlorodifluoromethane (Halon 121 1)

-

Corrective action

1. Empty, clean and recharge

2. Refill to correct level

3. Empty and refill

4. Replace seal disc and refill cartridge to correct weight or replace

5. Replace seal disc and refill cartridge to correct weight or replace

6. Examine seal disc and replace indicator

PartICheckpoints

1. Refillable type

(a) lncorrect extinguisher weight

(b) Incorrect gauge pressure

(c) Broken or missing tamper indicator

1. Broken or missing tamper indicator

2. lncorrect gauge pressure

3. Incorrect weight

Corrective action

(a) Refill to correct weight

(b) Repressurize and conduct leak test

(c) Leak test and replace indicator

1. Weigh, conduct leak test, and replace indicator

2. Weigh, repressurize and conduct leak test

3. Conduct leak test and refill to correct weight

Page 28: CP 55-1991 Portible Fire Extingusher

Agent

Water

Mechanical Foam

Part/Checkpoints

1. Incorrect fill level (by weight or observation)

2. lncorrect gauge pressure

3. Broken or missing tamper indicator

1. Recharging date due

2. Incorrect fill level (by weight or observation)

3. Agent condition (presence of precipitate or foreign material)

4. lncorrect gauge pressure

5. Broken or missing tamper indicator

Corrective action

1. Refill to correct level

2. Repressurize and leak test

3. Conduct leak test and replace indicator

1. Empty, clean and recharge

2. Empty and recharge with new solution

3. Empty and refill

4. Repressurize and leak test

5. Conduct leak test and replace indicator

Page 29: CP 55-1991 Portible Fire Extingusher

APPENDIX C

GENERAL SAFETY GUIDELINES FOR RECHARGING

The general safety guidelines for recharging extinguishers are as follows :

(a) Make sure all pressure is vented from extinguisher before attempting to remove valve.

Warning. Do not depend on pressure indicating devices to tell 1 extinguisher is under pressure as they could malfunction.

(b) Use proper recharge materials in the refilling of an extinguisher. Mixing of some extinguishing agents could cause a chemical reaction resulting in a dangerous pressure build-up in the extinguisher.

(c) All sealing components should be cleaned and properly lubricated to prevent leakage after recharge.

(d) Check pressure indicating device to ascertain that it is reading properly,

(e) Most manufacturers recommend the use of dry nitrogen as an expellant gas for stored pressure extinguishers. Do not set charging pressure regulator setting to more than 200 kPa above operating pressure as per 4.4.3.4 so as to prevent gauge damage.

Warning. Never connect the extinguisher to be charged directly to the high pressure source. Connecting directly to the high pressure source could cause the extinguisher to rupture, resulting in injury to persons. Never leave an extinguisher connected to the regulator of a high pressure source for an extended period of time. A defective regulator could cause the extinguisher to rupture due to excess pressure.

(9 Pressure regulators should be regularly checked and se~ iced in accordance with manufacturer's test procedures.

(g) Use the manufacturer's recommended charging adaptor to prevent damage to valve and its components.

(h) When recharging cartridge type extinguishers, make sure the cap is in place and tightened down. Replace all safety devices prior to installing replacement cartridges.

(i) To ensure proper operation, only those gas cartridges recommended by the manufacturer should be used. Cartridge features such as pressure relief, puncturing capabilities, fill density and thread compatability are designed to specific functional requirements.

0') Use proper safety seals; as other types such as meter seals may not break at the prescribed requirements.

Page 30: CP 55-1991 Portible Fire Extingusher

APPENDIX D

FEATURES OF COMMON TYPES OF EXTINGUISHERS

Pressure gauge

Hose

Horn

Discharge lever

Carrying handle

Powder

Syphon tube

Body

Figure 1. Stored pressure powder extinguisher

- Discharge lever

'essure gauge Carrying handle

Anti-overfill tube

Body

Air aspirating foam nozzle Premixed solution

Figure 2. Stored pressure mechanical foam extinguisher

30

Page 31: CP 55-1991 Portible Fire Extingusher

Discharge lever

Pressure gauge Carrying handle

Hose

Halon

Syphon tube

Horn

Body

Figure 3. Stored pressure halon extinguisher

Nozzle

Discharge lever

Pressure gauge

Carrying handle

Halon

Syphon tube

Body

Figure 4. Stored pressure halon extinguisher with fixed nozzle

31

Page 32: CP 55-1991 Portible Fire Extingusher

Discharge lever

Safety pin

Carrying handle

Neck ring

Hose water

Carbon dioxide gas cartridge

Nozzle Syphon tube

Skirting Filter

Figure 5. Cartridge-operated water extinguisher

Release hand

Figure 6. Carbon dioxide extinguisher

32

Page 33: CP 55-1991 Portible Fire Extingusher

APPENDIX E

HYDROSTATIC TEST - PROOF PRESSURE TEST METHOD

E.l TEST EQUIPMENT

The schematic diagram of the test equipment set up is shown in Figure 7

The following requirements shall apply:

(a) All rigid pipework, flexible tubing, valves, fittings and components forming the pressure system of the test equipment shall be capable of withstanding a minimum pressure of not less than two times the hydrostatic test pressure of the extinguisher body undergoing testing.

The equipment shall have no leakage. There shall be no air trapped in the equipment or extinguisher body under testing. The maximum applied test pressure shall be the manufacturer's test pressure (see 1.3.5) marked on the extinguisher body.

(b) Pressure gauges used shall be manufactured and maintained in accordance with BS 1780 or any accepted equivalent. They shall be tested at regular intervals in any case not less frequently than once per month.

(c) The test medium shall be water delivered by a high pressure water pump.

E.2 TEST PROCEDURE

(a) All test equipment shall be checked to ensure good condition before commencement of each test.

(b) Extinguisher body undergoing test shall be checked to ensure no residual gas and the external surfaces of the extinguisher shall be completely clean and dry.

(c) Only extinguisher bodies having the same hydrostatic test pressure shall be tested together.

(d) To commence testing, the applied hydrostatic pressure shall be gradually increased until the normal filling pressure is reached. This pressure is then maintained for 30 seconds, to conduct a check on the extinguisher body. If no leakage, defect or deformation is observed, the hydrostatic pressure shall then be increased to the manufacturer's test pressure (as marked on the extinguisher body or label) and shall be maintained at this pressure for a minimum of 2 minutes.

(e) Under these test conditions, the extinguisher body shall not show any sign of leakage, defect or visible deformation.

(f) If there is any leakage in the pressure system, it shall be corrected and the extinguisher body shall be retested.

(g) An extinguisher body is deemed unsuitable for further service if it leaks, ruptures, or shows evidence of bad dents, corroded areas or other conditions that indicate possible weakness which would render the extinguisher body unfit for service.

Page 34: CP 55-1991 Portible Fire Extingusher
Page 35: CP 55-1991 Portible Fire Extingusher

Standards referred to in this Code :

BS 1780 : 1985 Specification for bourdon tube pressure and vacuum gauges

BS 5430 : - Specification for periodic inspection, testing and maintenance of transportable gas containers (excluding dissolved acetylene containers) Part 2 : 1977 We!ding steel containers of water capacity 1 litre up to

130 litres Part 3 : 1980 Seamless aluminium alloy containers

BS 6643 : - Recharging fire extinguishers (manufactured to BS 5423 "Specification for portable fire extinguishers") Part 1 : 1985 Specification for procedure and materials

SS 232 : 1980 Specification for portable fire extinguishers

SSCP12 : - Code of practice for filling, inspection, testing and maintenance Part 1 : 1980 Seamless metal containers for gases, excluding dissolved

acetylene

Page 36: CP 55-1991 Portible Fire Extingusher

SINGAPORE INSTITUTE OF STANDARDS AND INDUSTRIAL RESEARCH

The Singapore lnstitute of Standards and Industrial Research (SISIR) was incorporated as an independent statutory body in October 1973 in accordance with an Act of Parliament, the Singapore lnstitute of Standards and Industrial Research Act (Chapter 301). Its role is to promote and upgrade the quality and technology levels of Singapore industries.

One of the functions of SlSlR is the establishment of a national standardisation programme to support industrialisation in Singapore. The lnstitute is vested with the authority to appoint, with the approval of the Minister, a Standards Council to advise on the preparation, publication and promulgation of Singapore Standards, and promotion of their adoption. Standards are in the form of specifications for materials and products, codes of practice, methods of testing, nomenclature, etc. The standards are drawn up by the various Technical Committees appointed by the Product Standards Committees (for product standards) or the Practice Committees (for codes of practice), the final approval body being the Standards Council.

To ensure adeauate re~resentation of all view~oints in the reo oar at ion of standards. all . . Committees appointed consist of ;epresentatives from varidus interest groups which include ~overnment agencies, professional bodies, tertiary institutions and consumer, trade and manufacturing organisations.

SlSlR also operates a national product certification scheme. The lnstitute is the owner of the Certification Mark shown below. This Mark can be used only by manufacturers licensed under the Scheme in accordance with the SlSlR (Certification Mark) Regulations, 1987. The presence of this Mark on a product with the inscription "Certified to Singapore Standard" is an assurance that the product has been produced to comply with requirements of the relevant Singapore Standard under a system of supervision, control and testing operated during manufacture and including regular inspection at the manufacturer's premises.

Besides being engaged in standardisation and certification work, SlSlR is involved in several other programmes and activities in support of its mission. These include quality promotion; laboratory accreditation; inspection and testing services; training and consultancy; calibration; patent and other technical information services; and research and development work.

For further information on SlSlR setvices and activities, please write to:

SlSlR P O Box 1128

Kent Ridge Singapore 91 1 1

Page 37: CP 55-1991 Portible Fire Extingusher

IMPORTANT NOTICE

If you wish to be notified of any changes in the Singapore Standard, please complete and return this form to:

SlSlR Library Singapore Institute of Standards

and Industrial Research P O Box1128 Kent Ridge Singapore 91 11

Please print clearly full name and address