CHP Unit with Waukesha Gas Engine - MOTORGAS Specifications CHP Unit with Waukesha Gas Engine for...
Transcript of CHP Unit with Waukesha Gas Engine - MOTORGAS Specifications CHP Unit with Waukesha Gas Engine for...
Type SpecificationsCHP Unit with Waukesha Gas Engine
for installation in engine room
(C) MOTORGAS 2012-10
INdoor MGW 350Biogas - emissions NOx < 500 mg/m3 @ 5%O2
Scope Specifications Technical Data Engine & Generator Control System Balance Data Cooling Device Requirements for the Construction Technical Diagram
Producer MOTORGAS s.r.o. Oderská 333/5 19600 Praha 9 Czech Republic www.motorgas.cz [email protected]
Scope Specifications
Compact CHP unit - consisting of modules to be connected on site
Gas engined generator set on steel base frameGas engine coupled with synchronous generator through elastic couplingEngine control and management (automatic AFR regulation included)Air filterGas mixerThrottle valveElectronic ignitionHeat Module - Equipment for heat production / coolingMain plate heat exchanger - engine coolingExhaust gas heat exchangerElectrical circulating pump - engine circuitSafety valve - engine circuitExpansion vessel - engine circuitCooling the filling mixture LT (technological circuit 54 °C)Radiator cooler for filling mixture coolingCirculating pump of mixture cooling circuitSafety valve mixture cooling circuitExpansion vessel -mixture cooling circuitGas lineGas filter
Zero gas pressure regulatorManometer - signalizing high / low gas pressureExhaust system - fully stainless steelInsulated flexible duct with heat-resistant textile material
Silencer Exhaust
Electrical SwitchboardControl system (separate description follows)Power section with integrated generator circuit breakerStarting batteries 24VDC with electronic charging with disconnecter
OPTIONS - per extra price
Equipment for connection to the heating circuitHeating circuit pumpReturn temperature control with three-way control valveEmergency cooling system to waste heat from engineEmergency radiator coolerEmergency circuit control equipmentAnti-noise coverAnti–noise cover with electrical motor driven ventilatoroptionally speed control of ventilatorOil filling equipmentThe central oil tank with optional volumeElectrical engine heaterOxidizing catalyst when required
Electric shut-off valves (2 pcs single or 1 pc of double valve)
Exhaust gas heat exchanger from stainless steel incl.heat insulation
Compensators
Technical Data
Fuel / Gas qualityNominal fuel calorific value 23 MJ/Nm3
Type of Co-generation UnitProducerNominal electrical power output 346Nominal heating output VT 70 / 90 °C (kW) 471Nominal voltage - frequency - speedNominal power factor 1Operating gas pressure entering the CHP gas lineThermal gradient of heating systemFlow of water in the heating circuit (kg/s) 5,6
Exhaust Gas EmissionsCompliance with emission limits according to Czech Government Regulation No. 146/2007 Sb
500CO @ 5% O2 dry gas (mg/m3) 650NMHC @ 5% O2 (mg/m3) 150
NoiseNoise pressure level at distance 1m (without anti-noise cover) 97 +- 3 dB/A/Noise pressure level at distance 1m (with anti-noise cover) 75 +- 3 dB/A/
73 +- 3 dB/A/
biogas / sewage gas
INdoor MGW 350MOTORGAS s.r.o.
400 V - 50 Hz - 1500 rpm
2 - 3 kPa90 / 70 °C
NOx @ 5% O2 dry gas (mg/m3)
Exhaust noise pressure level at distance 5 m from outlet
Engine
Type of engine - turbocharged WAUKESHA H24 GLDNominal speedNumber of cylinders 8 in lineBore 152 mmStroke 165 mm
DisplacementAir - Fuel ratio / combustionLube oil filling quantitySpecific oil consumption at nominal power outputCompression ratio 11:1Engine weight (dry) 3272 kg
Generator
Type of generator - synchronousProducerNominal apparent powerNominal active power 372 kWNominal voltageClass F / 105 KPower factor operating range 0,8 – 1,0Nominal voltage - frequency - speedNumber of bearingsGenerator weight 1240 kg
96,2% - 96,2% - 95,8%
1500 min-1
24 dm3 (l)1,5 / lean burn212 litres0,3 g/kWh
Leroy Somer LSAC 47.2 M7EMERSON / Leroy Somer465 kVA
40 °C
400 V - 50 Hz - 1500 rpmsingle-bearing
Efficiency (p.f.=1) @ 100% - 75% - 50 %
Control System
CharacteristicOptimal configuration for single and multiple generating setsGenerators can operate in parallel or island mode (stand-by)The control system is equipped with a powerful graphic display.Intuitive control based on icons, symbols and bar graphs.The choice of three types of display panel:
Possibility of external modules for additional measurements or programming functions.
Display screens and pages structuresThe measured values
Alarm listHistoryHelp / othersStandard FeaturesAutomatic start / stop unit
Automatic generator synchronizing controlMains protection including vector shift, load and power factor control, earth faultprotection and the major functions providedMeasuring temperatures, pressures and levels of operating media (gas, water, oil)
Protection upon module or sensor failureGas leakage detectionWarning operator before exceeding limit value
Up to 8 users defined, each one with different access rights (levels of protection)Engine run hours and time to service counters
Communication InterfaceBI 16x, 16x BO, 4 AI, 1 AO, signals for external communication
Optional extensionRemote control via GSM GPRS networkFunction island mode of CHP - delivery of power during blackout
Basic: InteliSys panel - Full graphic display with black and white screenOptional: InteliVision 5 - full graphic display panel with 5.7 "color display, resolution 320 x 240 pxOptional: InteliVision 8 - full graphic display panel with 8 "color display with resolution of 800 x 600 px
Predefined configurations for typical applications are available as well as user-defined configurations for special applications
Create graphs of measured values (only in combination with InteliVision 8)Setpoints
Speed / power control
Measurement of electrical values (voltage, current, power factor, frequency)
Creating trends of measured values on the display (only in combination with InteliVision 8)Automatic shutdown in case of exceeding limit value
Export data to USB flash drive (only in combination with InteliVision 8)
Serial communication with the master control system via Modbus
Serial communication with the master control system other than Modbus protocol
InteliSys BaseBox – control unit
Panel InteliSys - basic display (with black and white graphics)
InteliVision 5 - full-color graphic display size 5.7 "
InteliVision 8 - full-color graphic display size 8 "
Balance Data Sheet
TIC 54 C BIO BIO BIOH24 GLD MGW 350 MGW 350 MGW 350%load 100,0% 75,0% 50,0%Fuel input [kW] 965 750 526 Mechanical power [kW] 360 270 180
10,03 10,40 10,98151,0 117,4 82,3
Generator efficiency 96,2% 96,2% 95,8%Electrical power output [kW] 346 260 172 Total heating power [kW] 471 375 258 Heat from jacket water [kW] 230 200 140
40 30 18 40 22 5
Heat from exhaust [kW] 201 145 100 Electrical efficiency 35,9% 34,6% 32,8%Heating efficiency 48,8% 50,0% 49,1%Total efficiency 84,7% 84,6% 81,9%
816 Exhaust temperature [°C] 468 427 422
Heat losses [kW] 39 30 21
23Outlet exhaust gas temperature [°C]Technical data based on ISO 3046Standard reference conditions
Tolerance for fuel consumption + 5%Tolerance for heating outputs data +-8%
346 kWe 260 kWe 172 kWeTotal efficiency 84,7% 84,6% 81,9%
35,9% 34,6% 32,8%
Fuel Input 100%
48,8% 50,0% 49,1%
Fuel - required gas quality / limits23 MJ/Nm3
Limits of fuel pollutantsSulphide H2S concentrationChlorine concentration compounds < 100 mg/Nm3Fluorine concentration compounds < 50 mg/Nm3Total fluorine + chlorine concentration compounds < 150 mg/Nm3Silicone – Si concentration < 25 mg/Nm3Ammonia – NH3 concentration < 25 mg/Nm3Oil vapour concentration < 250 mg/Nm3CH4Particle solid sizeFuel relative humidity < 60%Fuel temperature
Spec. fuel consumption [MJ/kWh]Fuel consumption [m3/hr]
Heat from oil cooler [kW]Heat from intercooler LT [kW]
Combustion air [kg/hr] 1 451 1 158
Exhaust gas flow [kg/hr] 1 905 1 562 1 100
Caloric fuel value [MJ/m3]
Pressure 100 kPa, temperature 25°C, relative humidity 30%
Generator Power Output (kWe)
Electrical Efficiency
Heating Efficiency at 70/90 C
Loss
biogas / sewageNominal caloric fuel value of the biogas
Limit value< 0,1% by volume
< 5.10-6 m,< 10 mg/Nm3
10 – 30 oC
Emergency Cooling
GFH 067B/3-N(D)-F6/3P
Capacity 485 kW MediumAir flow Pressure drop 0.40 bar
Volume flow
Fans 3 Kusy 3~400V 50Hz Noise pressure levelData per motor At a distance ofSpeed 1340 min-1Capacity 2.20 kWCurrent 4.30 A
Tube volume Connections per unitWeight (dry) 307 kg Inlet DN65/PN10
Outlet DN65/PN10
Filling Mixture Cooling (Technological Cooling Circuit)
GFH 052C/1-N(D)-F6/8P
Capacity 46 kW MediumAir flow Pressure drop 0.59 bar
Volume flow
Fans 1 Kus 3~400V 50Hz Noise pressure levelData per motor At a distance ofSpeed 1340 min-1Capacity 0.78 kWCurrent 1.35 A
Tube volume Connections per unitWeight (dry) 116 kg Inlet DN65/PN10
Outlet DN65/PN10
Drycooler
ethylene glycol 34 %(1)
41 800 m³/h28.44 m³/h
68 dB(A)(2)
5.0 m
54 l
Drycooler
ethylene glycol 34 %(1)
8020 m³/h9.30 m³/h
54 dB(A)(2)
5.0 m
16 l
Requirements for design of CHP engine rooms construction
Placing and spaceMinimal free space from unit base frame on side of the unit 1500 mm (for both side)Minimal free space in front of electrical switchboard 1200 mmMinimal free space from side where piping connection 1000 mm
Requirement for engine room floor: dust free concrete or pavement
Ventilation of engine room
Oil handling equipmentOil tank is an option. Usually is mounted on the console on the wall of the machine room.
Setting of electrical switchboardSwitchboard is separated single mounted part.
Setting of emergency dry coolerOutside a) placed on concrete foundationb) placed on bracket mounted on building
Venting (degassing)piping above the roof with min. distance 3 m from possible source of the fire.
Exhaust pipinga) independent exhaust piping DN100 leaded over engine room
b) leaded into chimney – overpressure system required
Heating customer system (secondary circuit)Co-generation unit can be optionally equipped with secondary (heating) circuit water pumpThree way valve – controls return heating water temperatureSafety valves on primary and secondary circuits
Electrical equipment and power supply system
Arrange power outlet 3f+N+PE/16A close to the unit.
Other requirements and space demand Inlet gully for drainage from the exhaustFresh water including the washbasin in the engine room
Engine and generator are coupled and mounted on steel base frame with inserted anti-vibration elements. Transmission of the vibration is minimal. Normally there is no need to prepare anti-vibration concrete blocks. It is sufficient to calculate the floor as for static weight loading capacity
Engine room should be ventilated naturally or by ventilators with minimum three times per hour air change rate. Minimal air change quantity technically required corresponds to the heat lost from co-generation unit and inlet air to be burned by engine – see technical parameters chapter. Other safety requirements for air change will be solved according to locally valid safety rules and standards. To avoid freezing problems and because of better starting conditions it is recommended to keep inside temperature in the engine room not lower than 5°C.
piping is made of stainless steel DIN 1.4301
It is absolutely necessary to keep water flow through customer heating circuit when engine is in operation. Danger of exhaust boiler damage.
Earthing of the object with earth resistance less then 5 Ω must be supplied to the switchboard. Generator will be fix grounded according to standard ČSN 33 2000-4-41 article 413.1.
Specific solution and local requirements is always recommended to consult with the manufacturer of the co-generation unit in advance.
Technical Diagram