Chapter 3 – Loads and Load effects
description
Transcript of Chapter 3 – Loads and Load effects
1
Chapter 3 – Loads and Load effects
Dr. -Ing. Adil Z.Eng. Asmerom
2
Loads on Structures
• Classification of loads Area of application: Concentrated, Distributed (UDL) Direction: Vertical (Gravity), Horizontal (Lateral) Response: Static, Dynamic Variation with time: Permanent (Dead), Variable
(Live)
3
Loads on Structures
• Classification of loads in Building Codes Permanent (Dead) Variable (Live) Environmental Loads
• Wind• Earthquake (Seismic)• Snow• Rain• Earth pressure
4
Wind LoadEBCS -1, 1995
5
Wind load
• Wind is air in motion• Structure deflects or stops the wind, converting the
wind’s kinetic energy into potential energy of pressure
• The wind loads that act on a structure result from movement of the air against the obstructing surfaces.
• Wind effects induce forces, vibrations, and in some cases instabilities in the overall structure as well as its non-structural components.
6
• Wind velocity increases with the power of the structural height
Wind load
7
Wind load
8
Wind load• These wind effects depend on:
the wind speed, density of the air, shape of the structure location and geometry of the structure, and vibrational characteristics of the system.
• Wind Forces According to EBSC-1, 1995 wind pressure in this section is valid for rigid
surface only and neglects their resonant vibration
9
Wind Load
Two method of analysis is provided the static procedure Only used for structures whose structural properties
do not make them susceptible to dynamic excitation (Cd ≤ 1.2)
A detailed Dynamic Procedure must be used for those structures which are likely to
be susceptible to dynamic excitation (Cd > 1.2) In order to determine Dynamic coefficient Cd , Charts and
figures can be used (EBCS 1-1995 fig 3.7 to 3.13)
10
Wind Load
11
Wind load (the simple procedure)Wind Pressure: The external and internal wind pressures are
given as: We = qref Ce (ze )cpe
Wi = qref Ce (zi )cpi
• Where: We and Wi are the external and internal pressures; Ce(ze ) and Ce(zi ) are the external and internal exposure
coefficients; Cpe and Cpi are the external and internal pressure coefficients. • The design wind pressure that is used to establish the wind load on
a structure is directly related to reference velocity pressure (qref) and is given by:
refref Vq2
12
Wind load• Where: ρ is the density of air andVref is the reference wind velocity to be taken as 22m/s. • The air density is a function of altitude and depends
on the temperature and pressure to be expected in the region during storms. A temperature of 200C has been selected as appropriate for Ethiopia and the variation of mean atmospheric pressure with altitude is given in Table 2.3.(NS)
13
• Table 2.1 Values of air density ρ
Site Altitude (m)Above sea level
(kg/m3)
0 1.20
500 1.12
1000 1.06
1500 1.00
2000 0.94
14
Wind load• Exposure Coefficient : takes into the account the effects
of terrain, topography and elevation.
Where: KT - the terrain factor Cr(z ) - the roughness coefficient Ct(z ) - the topography coefficient *** Or use table 3.5 from EBCS-1 1995 for Ce(ze ) & Ce(zi )
(See next slide)
)()(71)()()()(
22
zCzCkzCzCzCzCtr
Ttrieee
15
Exposure coefficient Ce
Table 3.5 from EBCS-1 1995
16
Wind load• Terrain Category: The terrain category attempts to take
into account the effect of the land coverage, and is given below.
The terrain type is classified into 4 groups as follows: • Category I: Lakes with at least 5 km fetch upwind and
smooth flat country without obstacles. • Category II: Farmland with boundary hedges, occasional
small farm structure, houses or trees • Category III: Suburban or industrial areas and
permanent forests. • Category IV: Urban areas in which at least 15% of the
surface is covered with buildings and their average height.
17
Wind load• Cr(z ) - the roughness coefficient
Attempts to take into account the effect of the land coverage
Where kT terrain factorzo roughness lengthzmin minimum height
For ground height above 200 m specialist advice is recommended.
min
min
)min()(
200ln)(
ZZforzrCzrC
mZZforzzkzCo
Tr
18
Wind load
Terrain Category KT Zo(m) Zmin(m)
I 0.17 0.01 2II 0.19 0.05 4III 0.22 0.3 8IV 0.24 1 16
Terrain factor (KT) can be taken from table or calculated as follows:
Z0= minimum height defined Z0,II= minimum height of category II (0.05)
07.0
,
19.0
IIo
oT z
zk
19
Wind load• Ct(z ) - the topography coefficient
It accounts for the increase of mean wind speed over isolated hills and escarpments
Ct(z ) =1 for φ<0.05 Ct(z ) =1+2S φ for 0.05≤ φ <0.3 Ct(z ) =1+0.6 S for φ >0.3
Where: S the orographic location factor, φ the upwind slope H/Lu in the wind direction Le the effective length of the upwind slope, Lu the actual length of the upwind slope in the wind direction Ld the actual length of the downwind slope in the wind direction H the effective height of the feature X the horizontal distance of the site from the top of the crest z the vertical distance from the ground level of the site
20
Wind load
21
Wind load
22
Wind Load• Pressure Coefficient: The shape factor takes
into account the effect of shape of structure on the pressure distribution.
• The external pressure coefficients Cpe for buildings and individual parts of building depend on the size of the loaded area A. They are given for loaded area A of 1m2 and 10m2 in the relevant tables for the appropriate building configuration as cpe,1 and cpe,10, respectively. For areas between 1m2 and 10m2, values are obtained by linear interpolation. That is:
23
• Cpe = Cpe,1 for A≤1m2
• Cpe = Cpe,1 +( Cpe,10 – Cpe,1)log10A for 1m2<A<10m2
• Cpe = Cpe,10 for A≥10m2
Wind Load (Ext. Pressure Coeff.)
24
Wind Load (on building face)
• Values of external pressure coefficients for different cases are given in Table A.1 to Table A.5 of EBCS-1, 1995.
25
Wind Load (on building face)
• It accounts for the variation in dynamic pressure in different zones of the structure due to
• Its geometry• Area and • proximity to other structures
26
Wind Load (on building face)
27
• Reference height and wind pressure profile
Wind Load (on building face)
28
• Reference height and wind pressure profile
Wind Load (on building face)
29
Wind Load (on building face)
EXTERNAL PRESSURE COEFFICIENTS FOR VERTICAL WALL.
30
Wind Load (on flat roofs)• Flat roofs are defined as having a slope (α) of –5°< α < 5° • The roof should be divided into zones as shown in Figure
below.
31
Wind Load (on flat roofs)
32
Wind Load (on flat roofs)• External pressure coefficients for flat roof
33
Wind Load (on Monopitch roofs)• The roof, including protruding parts, should be
divided into zones as shown in Figure below and NS• The reference height Ze should be taken equal to h.
34
Wind Load (on Monopitch roofs)
35
Wind Load (on Monopitch roofs)• External pressure coefficients for Monopitch roof ϴ =0º
and ϴ =180º
36
Wind Load (on Monopitch roofs)• External pressure coefficients for Monopitch roof ϴ =90º
37
Wind Load (on Duo pitch roofs)• The roof, including protruding parts, should be
divided into zones as shown in Figure below and NS• The reference height Ze should be taken equal to h.
38
Wind Load (on Duo pitch roofs)
39
Wind Load (on Duo pitch roofs)• External pressure coefficients for Duopitch roof ϴ =0º
40
Wind Load (on Duo pitch roofs)• External pressure coefficients for Monopitch roof ϴ =90º
41
Wind Load (on Hipped roofs)• The roof, including protruding parts, should be
divided into zones as shown in Figure below and NS• The reference height Ze should be taken equal to h.
42
Wind Load (on Hipped pitch roofs)
43
Wind Load (on Hipped pitch roofs)• External pressure coefficients for Monopitch roof ϴ =0º
and ϴ =0º
44
Wind LoadInternal pressure Coefficient Cpi• Internal and external pressures shall be considered to
act at the same time. The worst combination of external and internal pressures shall be considered for every combination of possible openings and other leakage paths.
• The internal pressure coefficient Cpi for building w/o internal partition is a function of opening ratio m defined as
45
• For closed buildings with internal partitions and opening windows the extreme values :
Cpi = 0.8 and Cpi = -0.5
46
Wind loadNet pressure: the difference of the pressures (external and internal) on each surface due account of their signs.
47
Local effects of wind pressure
• Wind around a corner
Images from FEMA Multi Hazard Seminar
48
Local effects of wind pressure
Images from FEMA Multi Hazard Seminar
49
• Uplift on roof
Local effects of wind pressure
Images from FEMA Multi Hazard Seminar
50
Local effects of wind pressure
Images from FEMA Multi Hazard Seminar
51
Earthquake LoadEBCS -8, 1995
52
Earthquake Load An earthquake is the vibration of Earth
produced by the rapid release of accumulated energy in elastically strained rocks. It is the earth’s natural means of releasing stress. Energy released radiates in all directions
from its source, the focus; Energy propagates in the form of seismic
waves;
•Tectonic Earthquakes: occur when rocks in the earth's crust break due to geological forces created by movement of tectonic plates. • Volcanic Earthquakes: occur in conjunction with volcanic activity. • Collapse Earthquakes: are small earthquakes in underground mines, • Explosion Earthquakes: result from the explosion of nuclear and chemical devices. * About 90% of all earthquakes result from tectonic events, primarily movements on the faults
Types of Earthquakes
Basic principles of conceptual design
• The guiding principle in conceptual design against seismic hazard are: structural simplicity uniformity and symmetry bidirectional resistance and stiffness torsional resistance and stiffness diaphragmatic action at storey level adequate foundation
54
Consequence of structural regularity on seismic design EBCS 8, 1995
* Fundamental period < 2 seconds
REGULARITY SIMPLIFICATIONBEHAVIOR FACTORPLAN ELEVATIO
NMODE
LANALYSI
S
Yes Yes Planar Static* Basic
Yes No Planar Static* Increased
No Yes Spatial Static* Basic
No No Spatial
Dynamic
Increased 55
Regularity in Plan
• symmetric in plan w.r.t. 2 orthogonal directions• compact plan configuration (no H, I, X shapes) Re-
entrants in one direction <25%• In-plane stiffness of floors sufficiently large compared
to stiffness of vertical elements• Under the equivalent static seismic force, max.
displacement in the direction of seismic force does not exceed avg. displacement by 20%
56
Regularity in elevation
• All lateral load resisting systems run without interruption from foundation to top
• Both lateral stiffness & mass of story's remain constant or reduce gradually without abrupt changes
• ratio of actual storey resistance to required resistance should not vary disproportionately between adjacent storeys.
57
Regularity in elevation (contd.)
when setbacks are present:
58
Earthquake Analysis of Linear Systems
• Equivalent static analysis (ESA)• Dynamic analysis
Response history analysis (RHA) or (THA) Response spectrum analysis (RSA)
59
EBCS 8 Elastic Design Spectra
0
0.5
1
1.5
2
2.5
3
0 0.5 1 1.5 2 2.5 3Spec
tral a
ccel
erat
ion
/ Gro
und
acce
lera
tion:
b
o
Period T (sec)
Normalized Elastic Response Spectra
soil class A
soil class B
soil class C
60
Equivalent Static Analysis, EBCS 8, 1995
• Base shear force, Fb = Sd(T1) W• Fundamental period, T1 = C1 H3/4 ; T1 = 2
• Sd (T1) = abg• Distribution of lateral force
• Accidental torsion, eli = ±0.05 Li
• Torsional effects in individual elements, d=1+0.6 x/Le
d
btjj
iitbi FTFand
hWhWFFF 107.0)(
Rayleigh coefficient
Not explicitly shown
61
jj
jj
uFum
T
2
1 2
Design spectrum coefficients
a= aoI bedrock acceleration ao=0.1, 0.07, 0.05, 0.03 acceleration ratio
I = 1.4, 1.2, 1.0, 0.8 importance factor
S = 1.0, 1.2, 1.5 site coefficient
g= gokD kR kW 0.70 behavior factor
5.22.13/2
1
TS response factor
62
Seismic Hazard map of Ethiopia
0.1g0.05gao =
bedrock acceleration coefficient ao
63
Importance factors for buildingsImporta
nce category
BuildingsImporta
nce factor
IBldgs whose during EQ is
vital importance, e.g. hospitals, fire stations, ...
1.4
IIBldgs whose collapse
results in serious consequence, e.g. schools,
assembly halls, 1.2
IIIordinary buildings not
belonging to other categories
1.0
IVBldgs of minor importance
for public safety, e.g. agricaltural bldgs., etc.
0.864
Comparing acceleration coefficients
0
0.5
1
1.5
2
2.5
3
0 0.5 1 1.5 2 2.5 3
Res
pons
e fac
tor
Peroid T (sec)
Comparison of response factor ordinates for class C soil
Design Spectra
Response factor
65
in ESA and A/g in design spectrum are not identical
Subsoil classification
Subsoil
classDescription
Site coeff.
S
A
Rock vs 800 m/s in the top 5m
and stiff clay deposits vs 400 m/s at 10m depth
1.0
Bmedium dense sand, gravel or medium stiff clays vs 200 m/s
at 10m depth1.2
C
Loose cohesionless soil deposits with or without some
soft cohesive layers vs < 200 m/s in the uppermost
20m
1.5where vs is shear wave velocity
66
Torsional effects
• Spatial (3D) model, accidental torsional effectsMli = eli Fi
where Mli torsional moment at storey ieli accidental eccentricity of storey mass i
(eli = ± 0.05 Li)Fi horizontal force acting at storey i
• Planar (2D) models: amplify the action effects in individual load resisting elements with a factor d
• If torsional irregularity exists, increase eli by
(d=1+0.6 x/Le)
670.3
2.1
2
max
avg
A
Scaling of results
• when base shear determined from procedures of RSA < ESA: base shear shall be increased to the following
%age of the values determined from ESA• 100% for irregular buildings• 90% for regular buildings
deflections, member forces and moments increased proportionally
68
Combination of components of seismic action
• Horizontal components shall be considered to act non- concurrently
• Vertical components amounting to 70% of the horizontal components shall be taken into account for: horizontal (or nearly) members spanning 20 m horizontal (or nearly) cantilever components horizontal (or nearly) prestressed components beam supporting columns
analysis is made on a partial model consisting of the element under consideration and adjacent elements
69
Determination of displacements
• Displacements induced by the design seismic action:
ds = de / gd
where ds = displacement due to design seismic actionde = displacement from linear analysis based
on design spectrum (shall also include torsional effects)
gd = displacement behavior factor
70
Safety Verifications
1. Ultimate limit statessafety against collapse (ULS) is ensured if resistance, ductility, equilibrium, foundation stability and seismic joint conditions are met
a. Resistance condition Design action effects design resistance; Ed Rd
Second order effects:
if 0.10 no need to consider0.1 < 0.2 consider 2nd order effects by amplifying results by a factor 1/(1- )
shall not exceed 0.25
hVdP
tot
rtotInterstorey drift sensitivity coeff.,
71
Safety Verifications (contd.)b. Ductility condition
check that the structural elements and the structure as a whole posses adequate ductility
specific material related requirements shall be satisfied
c. Equilibrium condition bldg. should be stable against overturning and sliding additional SLS verification for bldgs with sensitive equipments
d. Resistance of horizontal diaphragms Horizontal diaphragms & bracings shall have sufficient over-
strength in transmitting lateral loads The above requirements are satisfied if the diaphragms can
resist 1.3 times forces obtained from analysis
72
Safety Verifications (contd.)e. Resistance of foundation
Verification of foundations according to EBCS 7. Action effects based on capacity design consideration, but shall
not exceed that of linear behavior with g =1. If the action effects are determined using g ≥ 0.7, no capacity
design consideration is needed
f. Seismic joint condition To check that there is no collision with adjacent structures
• Distance between potential points of impact < max. ds
• When floor elevations of adjacent bldgs are the same the max. separation distance referred above can be reduced by a factor of 0.7
• If shear (bumper) wall provided on the perimeter of the bldgs no separation distance needed, a 40 mm separation can be used for the rest of the bldg.
73
Safety Verifications
2. Serviceability limit stateslimitation of damage requirement (SLS) is satisfied if, under the design seismic action, the interstorey drifts dr are limited to:
a. For bldgs having non-structural elements of brittle materials attached to the structuredr ≤ 0.01 h
b. For bldgs having non-structural elements fixed in a way not to interfere with structural deformations dr ≤ 0.015 hwhere h is the storey height
c. Additional SLS verification may be req’d for important bldgs containing sensitive equipments
74
Design provisions for concrete buildings
• Design Concepts: EQ resistant concrete bldgs shall provide adequate energy
dissipation capacity Overall ductile behavior is ensured if the ductility demand is
spread over a large number of elements. Ductile mode of failure (flexure) should precede brittle failure modes (shear)
With regard to required dissipation capacity, three ductility classes are set to provide appropriate amount of ductility
Different behavior factors g are used for each ductility class In seismic zones 1 & 2 design load combinations according to
EBCS 2 provisions with an appropriate g.
75
Ductility Classes• Depending on the required hysteretic dissipation
capacity DC”L” (low ductility)
• structures designed and dimensioned according to EBCS 2• concrete class C 20
DC”M” (medium ductility)• specific provisions for design and detailing to ensure inelastic
behavior of the structure without brittle failure• concrete class C 25
DC”H” (high ductility)• special provisions for design and detailing to ensure stable
mechanisms with large dissipation of hysteretic energy • concrete class C 25
76
Behavior factors g• g = gokD kR kW 0.70
go = basic value of structural response, depends on structure type
Structural type go
Frame system 0.20
Dual system
Frame equivalent 0.20Wall eqv with coupled walls
0.20
Wall eqv with uncoupled walls
0.20
Wall system
with coupled walls 0.20with uncoupled walls 0.25
Core system 0.30Inverted pendulum system 0.50
77
Behavior factors g (contd.)
• kD = factor reflecting ductility class kD = 1.0 for DC”H”, kD = 1.5 for DC”M”, kD = 2.0 for DC”L”.
• kR = factor reflecting structural regularity in elevation kR = 1.00 for regular structures kR = 1.25 for irregular structures
• kW = factor reflecting the prevailing failure mode in structural systems with walls 1.00 for frame and frame equivalent systems (2.5 – 0.5 ao) 1.0 for wall, wall equivalent systems and
core systems78
Design criteria for concrete bldgs
• local resistance criterion all critical regions shall have adequate resistance second order effects shall be taken into account
• capacity design criterion brittle or undesirable failure mechanisms shall be
prevented, (e.g. shear failure of elements, BCJ failure, or yielding of foundation)
plastic hinges shall be distributed throughout the structure, only in beams and not in columns except at the base of the bldg. (refer to the next slide)
79
Choice of ductile mode failure
80