TCVN 2737-1995-Loads and Effects
-
Upload
api-3825219 -
Category
Documents
-
view
3.194 -
download
71
Transcript of TCVN 2737-1995-Loads and Effects
VIETNAM STANDARD TCVN 2737:1995
285
Loads and Effects – Design standard
1. The scope of application
1.1. The standard stipulates loads and effects used for the design of construction,
foundation bed of house and projects.
1.2. The standard does not state loads and effects caused by railway traffic, road
traffic, wave, stream flow, goods loading and unloading, earthquake, storm,
temperature, a motive power of machinery and means of
transportation…However, those loads and effect are stipulated by the relevant
standards issued by the State.
1.3. A load is calculated and determined basing on the result of the real work-
observation during repairing.
1.4. Effects of the atmosphere is defined according to the standard climate-data for
the current construction design or according to the data from the head
department of hydrometeorology
1.5. Loads for the special and important projects is not included in the standard,
but defined by the authorized level.
1.6. To the industries with specific projects (such as traffic, irrigation, electricity,
post office…), basing on this standard; the specialty standard should be
determined accordingly.
2. Basic principle
2.1. General regulation
2.1.1 Loads generating during the process of usage, building and the process of
creating, maintaining and moving the structure as well must be determined
whenever designing house and projects
2.1.2 The standard quantities stated in this standard are basic characteristics of load.
The assumed load is determined by multiplying the standard load and the
reliable coefficient of load. This coefficient covers a disadvantageous error
which might be generated by load comparing with the standard value and
depends on the mentioned limitation status.
2.1.3 The assumed load is directly determined basing on the given-overload
probability in case of reasons and appropriate statistical data.
When there is concurrent effect from two or more temporary loads, the
calculation of structure and foundation bed under the first and second group of
limitation status must be done accordance with the most disadvantageous load
aggregate or their correlative inner force.
VIETNAM STANDARD TCVN 2737:1995
286
The load aggregate is built up by the methods which have simultaneous effect
from different loads, including a possibility of change of load’s effect chart.
When the load aggregate or correlative inner force is calculated, it must be
multiplied the aggregate coefficient.
2.2 The reliable coefficient γ (excess-load coefficient)
2.2.1 When determining the reliable coefficient for calculation of structure and
foundation bed, we must refer to as follow:
2.2.1.1 When doing calculation of the intensity and stabilization, it refers to the article
3.2, 4.2.2, 4.3.3, 4.4.2, 5.8, 6.3, and 6.17.
2.2.1.2 When doing calculation of durability, refer 1. To the crane girder, observe the
instruction at article 5.16
2.2.1.3 When doing calculation basing on the deformation and transposition, take 1 if
the standard structure and foundation bed design don’t state any other data.
2.2.1.4 When doing calculation of the different limitation status which does not
mention at the article 2.2.1.1, 2.2.1.2, 2.2.1.3, we use the standard structure and
foundation bed design.
Note:
1) When determining the structure and foundation bed under load which is
generated by the stage of construction, the assumed value of load of wind will
be reduced 20%
2) When we calculate the intensity and stabilization impacted by collision
between a bridge crane/chain-bridge and chair, the reliable coefficient is
referred to 1 for all kinds of load.
2.3 Classification of loads
2.3.1 Loads are divided into two categories: frequent load and temporary load (long
term, short term and special ones – depending on how long it effects to)
2.3.2 The frequent load (standard and assumed load) is loads whose effect does not
change during the stage of construction and usage of works. The temporary
load is loads whose effect may not exist for a certain period of time during the
process of project construction and usage.
2.3.2 The frequent load consists of:
2.3.3.1 The mass of house parts and works, including mass of force-resistant structure
and covering structure
2.3.3.2 Mass and pressure of earth (occluding and banking earth), pressure generated
from mining
VIETNAM STANDARD TCVN 2737:1995
287
Note: home-made or given strain in the structure and foundation bed design
must be considered during the calculation as the strain caused by the frequent
load.
2.3.4 The temporary load consists of:
2.3.4.1 Mass of temporary partition, mass of earth and prop-concrete beneath the
equipment.
2.3.4.2 Mass of fixed equipments: machines, motors, containers, conduit including
spare parts, pivot, partitions, conveyor belts, fixed lift including cable and
controlling set, mass of fluid and solid body in the equipments during usage.
2.3.4.3 Pressure of steam, fluid, in the containers and conduits during usage;
excessive pressure and loss of air pressure as ventilating the pits and others.
2.3.4.4 Load impacts on the floor, which is generated by material and equipment
platform in the room, cold storage, seed storage.
2.3.4.5 The effects of technological heat because the machine is placed fixedly.
2.3.4.6 Mass of layers of water on the water insulating roof.
2.3.4.7 Volume of layers of dust attaching to the structure.
2.3.4.8 Vertical loads from the bridge crane or suspension crane at the single span of
the house multiplied by the coefficient:
0.5 – for the bridge crane which operates lightly.
0.6 – for the bridge crane which operates hardly.
0.7 – for the bridge crane which operated very hardly.
2.3.4.9 Load on the floor of house, public house, production building and agricultural
building is mentioned at column 5 of the table 3.
2.3.4.10 Effect of foundation deformation is not included any earth structure change.
2.3.4.11 Effect due to humidity change, shrinkage and variation of material
2.3.5 The shortly temporary load consists of:
2.3.5.1 Mass of people, repairs, spare-parts, tools and assembly jig at the equipment-
maintain and fix area.
2.3.5.2 Load generated in process of manufacturing, transferring and doing
construction structure, in process of assembling and transferring the
equipments, including loads caused by mass of things and material kept in the
temporary store (excluding loads of selected area for the warehouse or for
material preservation), the temporary load of earth banking
2.3.5.3 Load generated from the machine during the staring, shutting down, transition
and testing stage, even change or replacement of equipment position.
VIETNAM STANDARD TCVN 2737:1995
288
2.3.5.4 Load caused by movement of lifting equipments such as bridge crane,
suspension crane, trolley hoist, loading machine…during the time of
construction, usage; loads from loading and unloading goods at warehouse
and cold storage.
2.3.5.5 Load on the floor of house, public-house, production building and agricultural
building is mentioned at column 4 of the table 3.
2.3.5.6 Loads of wind
2.3.6 The special load consists of:
2.3.6.1 Load of earthquake
2.3.6.2 Load of explosion
2.3.6.3 Load of serious violation of technological process, temporarily broken
equipment
2.3.6.4 Effect of foundation deformation due to earth structure change (example: earth
deformation because of land sliding or subsiding); effect due to ground
deformation at cracked areas, mining area, “caxto” phenomenon.
2.4 The load aggregate
2.4.1 The load aggregate comprises a basic and special complex, depending on the
elements of mentioned load.
2.4.1.1 The basic load aggregate includes frequent loads, the short- and long- term
temporary loads.
2.4.1.2 The special load aggregate includes frequent loads, long- term temporary
loads, short-term temporary loads (might happen) and one of the special loads.
The special load aggregate caused by the explosion or the collision of means of
transportation against project’s parts does not cover short-term temporary loads
as the article 2.3.5
The special load aggregate of earthquake does not include load of wind.
The special load aggregate is used to determine the capability of fire-resistance
of the structure.
2.4.2 If the basic load aggregate has one temporary load, the whole value of the
temporary load is counted.
2.4.3 If the basic load aggregate has two and more temporary loads, the value of the
temporary or their correlative inner force must be multiplied by the aggregate’s
coefficient as follow:
2.4.3.1 To long/short-term temporary load, do with 0.9
2.4.3.2 When specific effect of each short-term temporary load to the inner force,
transposition of structure, foundation can be analyzed, the load with the most
VIETNAM STANDARD TCVN 2737:1995
289
effect has no loss; the load with the second most effect will multiply by the
coefficient: 0.8 and the rest with 0.6
2.4.4 If the special load aggregate has one temporary load, the whole value of the
temporary load is counted.
2.4.5 To the special load aggregate with two and more temporary loads, value of the
special load is still kept as it is; the assumed value of the temporary load or
their correlative inner force is multiplied by the aggregate’s coefficient as
follow:
+ The long-term temporary load Ψ1 x 0.95
+ The short-term temporary load Ψ2 x 0.8
This will not be applied for the case which load is stated in the design standard
of projects at the earthquake areas or in the other standard of structure and
foundation design.
2.4.6 When we calculate structure and foundation bed under the intensity, stability
and the basic and special load aggregate which there are concurrent effect of at
least two temporary loads (long- or short-term), the assumed inner force is
suggested to use the instruction in the appendix A.
2.4.7 Determining the live load caused by equipments of the aggregate and other
loads is done according to standard of the machine’s foundation design or
standard of force-resistant structure of house and projects that the machine is
placed and generates the live load.
3. Mass of structure and earth
3.1 The standard load caused by mass of structure is determined the same as the
standard data and catalogue or dimension of projects and mass of material,
including the real humidity during construction, usage.
3.2 The reliable coefficient of load which is generated from mass of construction
structure and earth is stipulated in the table 1.
The table 1 – The reliable coefficient of load caused by mass of construction
structure and earth
Structures and Earth Reliable
coefficient
1. Steel
2. Concrete with mass of volume (over 1,600 kg/m3), ferro-
concrete, brick and stone, reinforced - steel/wood brick/stone.
3. Concrete with mass of volume (less 1,600kg/m3), partition
material, layers of plaster/complete coats(sheet, sheath, material
which can be rolled, covers, plaster…), depending on the
manufacturing condition:
- In the factory
1.05
1.1
1.2
VIETNAM STANDARD TCVN 2737:1995
290
- At the work site
4. Earth
5. Banked earth
1.3
1.1
1.15
Note:
1) For the mass of structure and earth; when we do checking the ability of
resistance to tilting, if the result is reduced, which probably causes the function
of structure some disadvantages, the reliable coefficient is 0.9
2) When we determine load of earth affecting on projects, the influence of real
humidity, load of material in storage, equipments and means of transportation
that effect on earth must also be considered.
3) For steel structure; if strain by specific volume is 50% more than the common
strain, the coefficient is 1.1
4. Load of equipments, people and material, commodity at storage
4.1 This section mentions the standard value of load caused by people, animal,
equipments, goods, material and temporary partition which effect to the floor of
house, common house, and agricultural manufacturers.
The methods of load arrangement on floor are carried out with the condition that
it must be based on the designated conditions prior to construction and usage. If
those conditions data are not adequate at the stage of design, when determining
structure and foundation bed, it is suggested to consider methods of load
arrangement for each floor as follow:
4.1.1 There is no temporary load influencing on floor
4.1.2 Arranging each disadvantageous part of load on floor as structure and
foundation bed is counted
4.1.3 Fully arranging loads on floor by the given loads
When arranging each disadvantageous part of load, the total load on the floor
of the multi-storied house does not surpass the determined load, including the
coefficient ψn which is counted as the article 4.3.5 when fully load
arrangement.
4.2 Determining load of equipment and material at the warehouse.
Load of equipment, material, goods at warehouse and means of transportation
is defined under the mission design and must be referred to the most
disadvantageous cases. It is clearly stated as follow:
Diagrams of equipment arrangement, place where stores or temporarily puts
material and goods; Quantity and position of means of transportation on each
floor. The diagram must show clearly how the equipments and means of
transportation occupy; the dimension of material storage; probable movement
VIETNAM STANDARD TCVN 2737:1995
291
of equipment during usage or space or re-arrangement of planes and other
load-set condition (equipment’s dimension, their distance).
4.2.2 Values of the standard load and the reliable coefficient follow up this standard’s
instruction. To the machine with a live load; the standard value, inertia force,
other necessary features is referred to the standard document which is used to
define a live load.
4.2.3 When the real load on floor is replaced by equivalent uniformly-distributed
loads, this equivalent load needs to be defined by specific calculation of each
components of floor (floor-sheet, the main girder, the extra girder). Doing
calculation based on the equivalent load must be guarantee that the force
resistance and hardness of structure must be the same as it is done with the real
load. The smallest equivalent uniformly-distributed load for industrial
manufacturer and warehouse is counted as follow: No less than 300daN/m3 for
the floor-sheet and the extra girder; No less than 200daN/m3 for the main
girder, column, and foundation.
4.2.4 Mass of equipment (even conduit) is defined accordance with the standard and
catalogue. To the equipment which is beyond the standard is defined
accordance with the machine’s history or the drawing.
4.2.4.1 The load of mass of equipment consists of mass of equipment or machine
(including wire, fixed–set devices and platform); mass of partition; mass of
devices which might be accompanied during as usage; mass of the heaviest
processed parts, transporting goods by the rated elevating capacity…
4.2.4.2 Load of equipment must be defined basing on their placement condition as
usage. It is suggested to prepare methods to avoid reinforcing the structure of
the force-resistance during equipment transportation, installation and usage.
4.2.4.3 When determining the different components, number of loading machine,
installing equipments with their concurrent present and the arrangement
diagram are counted as the function design.
4.2.4.4 The live effect of the vertical load caused by the loading machine or vehicles
is calculated by multiplying a static standard load and the live coefficient: 1.2.
4.2.3 The reliable coefficient of load caused by the mass of equipment is shown on
the table 2
Table 2 – The reliable coefficient of load by volume of equipment
Type of loads The reliable coefficient
1. Weight of the fixed equipment
2. Weight of the fixed equipment’s partition
3. Weight of the material remaining in the equipment,
container and pipe
1.05
1.2
VIETNAM STANDARD TCVN 2737:1995
292
a) Liquid
b) Suspended matter
4. Load of loading and unloading machine’s and
vehicle’s volume
5. Load of material with water absorptive (cotton, cloth,
fiber, foam, foods…)
1.0
1.1
1.2
1.3
4.3 The uniformly-distributed load
4.3.1 The table 3 shows the standard load which is uniformly distributed on the floor
and staircase
Table 3 – The standard load uniformly distributed on floor and staircase
Standard load
(daN/m2) Type of room Type of house/projects
Full Long-
term
1. Bedroom
2. Kitchen, living
room, toilet,
bathroom,
Billiard room
3. Kitchen,
washing room
4. Office,
laboratory
5. Room of
boiler, room of
engine and fan..
including volume
a) Casting shop
b) Flat-likely house, Kindergarten, Nursery
school, boarding-school, country-seat, rest-
home, convalescent home…
a) Flat-likely house
b) Kindergarten, nursery school, school,
country-seat, rest-home, convalescent home,
hotel, hospital, prison, head office, factory
a) Flat-likely house,
b) Kindergarten, nursery school, school,
country-seat, rest-home, convalescent home,
hotel, hospital, prison, factory
Head office, school, hospital, bank, science
institute
Skyscraper, office, school, country-seat, rest-
home, convalescent home, hotel, hospital,
prison, science institute
200
150
150
200
150
300
200
750
70
30
30
70
130
100
100
750
VIETNAM STANDARD TCVN 2737:1995
293
of machine
6. Reading-room
7. Restaurant
8. Conference
room, balling
room, waiting
room, audient
room, concert
room, gym, stand
9. Stage
10. Warehouse
11. Classroom
12. Workshop
13. Garret
14. Balcony and
a) With bookshelf
b) Without bookshelf
a) Food and drink
b) Exhibition, Display, Shop
a) With fixed seats
b) Without non-fixed seats
Load of 1 meter height of material at store:
a) store of book(book and document are put
closely
b) Store of book at library
c) Store of paper
d) Cold storage
School
a) Casting workshop
b) Vehicle repairing and maintenance workshop
with weight <=2500kg
c) Big room with machine and way
All kinds
a) Load evenly distributed to each band of 0.8
400
200
300
400
400
500
750
480/1m
240/1m
400/1m
500/1m
200
2000
500
400
70
400
140
70
100
140
140
180
270
480/1m
240/1m
400/1m
500/1m
70
70
-
-
-
140
VIETNAM STANDARD TCVN 2737:1995
294
balcony’s
protruding part
15. Lobby, foyer,
staircase, room-
to-room corridor
16. Mezzanine
17. Breeding
farm
18. Usable flat
roof
19. Non-use roof
20. Station’s
floor and subway
station
meter width along the banister, balcony,
balcony’s protruding part
b) Load evenly distributed to whole balcony,
balcony’s protruding part is defined if it has
disadvantageous effect when referring to the
article a.
a) Bedroom, office, laboratory, kitchen,
washing room, toilet, technology room
b) Reading-room, restaurant, meeting room,
ballroom, waiting room, audience room,
concert room, gym, warehouse, balcony, and
balcony’s protruding part.
c) Stage
a) Small livestock
b) Big livestock
a) Part of flat roof which people can gather in
(connecting to work floor, hall, big rooms)
b) Part of flat roof used for relaxing
c) Others
a) Tiling, concreted-fiber roof, metal roof and
other, straw and lime ceiling, concreted ceiling
which is made and no one travels on, but only
repair doers (excluding electricity, water and
ventilation equipment)
b) Ferro-concrete flat and sloping roof, eaves,
concreted ceiling which is put together without
people traveling, but repair doers (excluding
electricity, water and ventilation equipment)
200
300
400
500
75
>=200
>=500
400
150
50
30
75
400
70
100
140
180
-
>=70
>=180
140
50
-
-
140
VIETNAM STANDARD TCVN 2737:1995
295
21. Garage Road, up and down slope for car, coach and
light lorry with total weight: <= 2500kg
500 180
Note:
1) Load at the article 13, table 3 is defined for an area which is free of
machine and material.
2) Load at the article 14, table 3 is used for the force-resistant structure of
balcony, part of balcony. When we do calculating for structure of wall,
column, balcony’s and part of balcony’s foundation, load on balcony, part
of balcony is taken the same as load on the next-door main room and is
reduced accordance with the instruction of the article 4.2.5
3) Eaves or trough, whose function is the same as a bracket, is defined with
the vertical concentrated load which is placed at outside rim. The standard
value of the concentrated load is 75 daN/1 meter along the wall. To the
eaves or trough whose length along the wall is less than 1 meter, the
concentrated load is still 75 daN. The reliable coefficient of this
concentrated load is 1.3. After the concentrated load is defined, it must be
double-checked with the uniformly distributed load. The value of the
uniformly-distributed load follows up the article 19b of the table 9.
4) Value of long-term load for house and room stated in the article 12, 13, 16,
17, 18c and 19 in the table 3 is defined under technological design.
5) Value of load for breeding farm in the article 17, table 3 follows the
technological design.
4.3.2 Load caused by mass of temporary partition must be calculated basing on its
structure, position, features of leaning against floor and hanging to wall. When
we calculate load of other different parts, load can be referred to:
4.3.2.1 The real effect
4.3.2.2 As an other distributed-uniformly load. If so, this auxiliary load is define by a
calculation based on the anticipating partition arrangement diagram and it is
not less than 75 daN/m2.
4.3.3 The reliable coefficient for load evenly distributed on floor and staircase is 1.3 if
the standard load is less than 200 daN/m2; it is 1.2 if the standard load is more
than or equal to 200 daN/m2. The reliable coefficient for load of the temporary
partition follows the article 3.2
4.3.4 When we do calculation of load for the main girder, the auxiliary girder, floor-
plane, column and foundation bed, the full load in the table 3 is reduced as
follow:
4.3.4.1 to the room stated in the article 1, 2, 3, 4, 5 of table 3, it is multiplied by the
coefficient ψA1 (with A>A1 = 9m2)
VIETNAM STANDARD TCVN 2737:1995
296
1Aψ = 0,4 + 1/
6,0
AA (1)
With: A – Area which is affected by load and its unit is square meter.
4.3.4.2 To the room stated in the article 6, 7, 8, 10, 12, 14 of the table 3, it is
multiplied by the coefficient ψA2 (with A > A2 = 36 m2)
2Aψ = 0,5 + 2/
5,0
AA (2)
Note:
1) When we do calculation for the wall which gets effect from load of floor, the
value of load gets reduction, depending on the influenced-A load area which
leans against the wall.
2) In the warehouse, garage and workshop, it is admitted there is a loss of load
accordance with the instruction of the equivalent process.
4.3.5 When determination of the longitudinal force to calculate the column, wall and
foundation which bear loads from two floors and more, the value of load in the
table 3 is reduced by multiplying a coefficient ψn:
4.3.5.1 to the room stated in the article 1, 2, 3, 4, 5 of table 3:
1nψ = 0,4 + n
A 4,01 −ψ (4)
4.3.5.2 to the room stated in the article 6, 7, 8, 10, 12, 14 of table 3
2nψ = 0,5 + n
A 5,02 −ψ (5)
With
ψA1, ψA2 are defined as the article 4.3.4
n – Number of floors placed load on the defined area is included during
determination of load.
Note: When we determine the moment of flexure inside the column and wall,
we need to consider a reduction mentioned in the article 4.3.4 – the main
girder and auxiliary girder leaning against those column and wall.
4.4 The concentrated load and load on the banister
4.4.1 All parts of floor, roof, staircase, balcony, part of balcony need to be checked
their endurability of the concentrated load, which is requested to vertically
place the components at a disadvantageous position and to place on the square
area which is not more than 10 cm (when there is no other temporary load).
If the function design does not stipulate value of the standard concentrated
loads which is higher, we can use:
VIETNAM STANDARD TCVN 2737:1995
297
4.4.1.1 150 daN for the floor and staircase
4.4.1.2 100 daN for the floor of basement, roof, terrace and balcony
4.4.1.3 50 daN for the roof to which is reached through a staircase leaning against the
wall:
If the components includes a partial load which the equipment or vehicle
causes during construction and usage, we do not need to check it versus the
concentrated load as mentioned above.
4.4.2 The horizontal standard load effects to handrail, balcony, and part of balcony is:
4.4.2.1 30 daN/m for the house, nursery home, rest-home, convalescent home,
hospital and other heath centers.
4.4.2.2 150 dan/m for stand and gym
4.4.2.3 80 daN/m for house and room with special requirement
For the operation floor, the way at the top, out-rising roof which is for several
travelers, the concentrated horizontal standard load affecting on the handrail
and the wall is 30 daN (at any position as long as it is in the length of handrail)
if the function design does not ask for the higher load.
5. Load of Bridge crane and suspension crane
5.1 Load of bridge crane and suspension crane are defined accordance with their
operation as shown in the appendix B
5.2 The vertical standard load which effects through the wheel of the bridge crane to
the beam of “crane-way” and other necessary date for calculation follows up the
requirement of the state standard on bridge crane and suspension crane. To the
case which is beyond the standard, follow up the data in the machine’s history.
Note: The term “crane-way” means two crane girders, all beam of a suspension
crane (two for one span suspension crane and three for two span one…)
5.3 The horizontal standard load along the crane girder caused by a braking force of a
crane is 0.1 of the vertical standard load, which effects to the braked wheel of the
crane.
5.4 The horizontal standard load being perpendicular to the crane girder which is
caused by braking an electrical trolley, is 0.05 of the total rated elevating
capacity and mass of trolley for a crane with soft hook, is 0.1 of that total value
for a crane with hard hook.
This load is included when doing calculation for the house’s horizontal frames
and for the crane girder which is distributed evenly to all wheels of the crane at
one beam of the crane and can direct to in or out of the assumed span.
5.5 The horizontal standard load perpendicular to a crane girder which is caused by
the deviated electrical crane and “crane-way” which does not parallel (force of
VIETNAM STANDARD TCVN 2737:1995
298
pushing) to each wheel of the crane is 0.1 of the vertical standard load effecting
to the wheel. This load is only included when the strength and stability of a crane
and its relationship to the columns in the houses which there is cranes with its
hard or very hard working status are counted. So, the load all effects on the beam
of crane girders as all wheels at the same side of crane can direct to in or out of
the assumed span. The load stated in the article 5.4 does not need to be
mentioned at the same time with force of pushing.
5.6 The horizontal load which is a force of pushing caused by braking a crane and
trolley, is placed at the position which there is a contact between the wheel of a
crane and a rail
5.7 The horizontal standard load along the crane girder caused by a collision between
a crane and a chair-block at the end rail is defined as the appendix C. This load is
included when the chair-block and its link to a crane girder are calculated.
5.8 The reliable coefficient for the load of crane is 1.1.
Note:
1) When we do calculation of durability of a bridge crane’s beam, which is
effected locally and lively by the vertical concentrated load at each wheel of
the bridge crane, the standard value of this load is multiplied by the auxiliary
coefficient γ as follow:
1.6 – for the bridge crane which works very hardly and has a hard hook
1.4 – For the bridge crane which works very hardly and has a hard
hook
1.3 – for the bridge crane which works hardly
1.1 – for the rest of the bridge crane
2) When we check the local stability of the bridge crane’s abdominal beam, γ1=1.1
5.9 When we calculate durability and stability of bridge crane’s beam and their link
to the force-resistance structure:
5.9.1 The vertical assumed load caused by bridge cranes must be multiplied by the
live coefficient:
- When column’s span is not more than 12m:
1.2 – for the bridge crane which works very hard
1.1 – for the bridge crane which works averagely, hard and the same as
the suspension crane does.
- When column’s span is more than 12m:
1.1 – for the bridge crane which works very hard
5.9.2 The horizontal assumed load of the bridge crane must be multiplied by the live
coefficient = 1.1 for the bridge crane which works very hard.
VIETNAM STANDARD TCVN 2737:1995
299
5.9.3 The live coefficient is 1 for other cases.
5.9.4 When we define the durability of structure, the sagging of a bridge crane’s
beam, the transpose of column and the local effect of the vertical concentrated
load to each wheel, the coefficient does not need to be considered.
5.10 When we define the durability and stability of a bridge crane’s beam, we need to
consider the vertical load caused by two bridge cranes or suspension cranes
and their disadvantage effect.
5.11 To define the durability, stability of frame, column, floor and foundation of
house which has bridge crane with several spans (There is only storey at every
span), the vertical load caused by two bridge cranes with disadvantage effect
on each crane-way. When we calculate a combination of bridge cranes at
different spans, we must consider the vertical load which the four bridge cranes
cause the most disadvantageously.
5.12 To define the durability and stability of frame, column, rafter, rafter supporting
structure, floor and foundation bed of house in which the hoist is placed at one
or several spans, the vertical load caused by two bridge cranes with
disadvantage effect must be considered to each crane-way. When we calculate
a combination of suspension cranes at different spans, the vertical load must be
taken:
- For two suspension cranes: to column, steel frame-supporting structure, floor
and foundation of outside marginal row when there are two crane-ways in a
span
- For 4 suspension cranes:
+ To column, rafter supporting structure, floor and foundation of middle
row
+ To column, rafter supporting structure, floor and foundation of
marginal row when there are three crane-ways in a span.
+ To steel frame-supporting structure when there are two or three crane-
ways in a span.
5.13 The said number of cranes which is used to calculate the durability, stability
caused by the vertical and horizontal load of the cranes when arranging 2 or 3
crane-ways in one span, when the hoist and crane travel at the same span or
when using suspension cranes to transfer goods from this crane to others, must
be based on the function design.
5.14 When doing calculation the durability and stability of the mobile bridge girder,
column, frame, rafter, rafter supporting structure, floor and foundation bed,
determination of the horizontal load needs to be mentioned to the most
disadvantageous effect of not over two cranes at the same crane-way or at the
VIETNAM STANDARD TCVN 2737:1995
300
different one, but in the same line. So, we only mention a load (vertical or
horizontal) for each crane,
5.15 When we determine vertical sag, horizontal sag of the bridge girder and
horizontal transposition of column, we only define the effect of one most
disadvantageous crane.
5.16 When doing calculation basing on one bridge crane, the vertical and horizontal
loads, it is suggested to entirely be counted, no reduction. With two bridge
cranes, that load must be multiplied by the aggregate coefficient:
nth = 0.85 for the bridge crane which works lightly or averagely.
nth = 0.95 for the bridge crane which works hard and very hard
When doing calculation for 4 bridge cranes, the load caused by them must be
multiplied by the aggregate coefficient:
nth = 0.7 for the bridge crane which works few and averagely.
nth = 0.8 for the bridge crane which works hard and very hard
5.17 If there is one bridge crane working in one crane-way while the second one
does not during usage of project, the only load of the bridge crane is
considered.
5.18 When we define the fatigues strength of the bridge crane’s beam and their
relationship to the force-resistant structure, reduction of standard load needs to
be taken as the article 2.3.4.8. When we check a fatigues of beam’s abdomen at
the area where the vertical concentrated load effects to at one wheel of bridge
crane, the standard reduced value of a wheel’s vertical pressure needs to be
increased by multiplying the coefficient as noted in the article 5.8.
The bridge crane’s operation mode is decided by the design standard when
fatigue strength of structure is calculated.
6. Load of wind
6.1 Load of wind on projects consists of such elements as: pressure of normal (We),
frictional force (Wf) and pressure of normal (Wi). Load of wind on projects is
also considered as two elements – pressure of normal Wx and Wy.
6.1.1 Pressure of normal (We) on the exterior surface of projects and other
components’ structure.
6.1.2 The frictional force (Wf) has a tangency of exterior of the project and is in ratio
to an area of a flat-plan (for the saw-tooth roof, corrogate roof and roof with a
lantern or in ratio to a vertical plan (to the wall with part of balcony and other
same structure).
6.1.3 Pressure of normal Wf effects to the interior of walled – unclose house or house
with doorway whose door closes and opens occasionally or often opens
VIETNAM STANDARD TCVN 2737:1995
301
6.1.4 Pressure of normal Wx, Wy is defined basing on the resistibility plane of the
work under the direction of the axis X, Y. The work’s resistibility plane is a
projection of the work into the planes which are perpendicular to the
corresponding axis.
6.2 Load of wind includes two elements: static and live elements:
When we determine pressure of interior (Wf) as well as when we do calculation
for the multi-stories house whose height is less than 40m and a one story
industrial house whose height is less than 36m with a height ratio in a small
span which is less that 1.5 and built at the area of A, B, the live element of load
of wind does not need to be considered.
6.3 The static element’s standard value of wind load (W) at the height (Z) versus
the standard is determined as the formula:
W = W o x k x c (5)
With:
Wo – value of pressure of wind is referred to the appendix D, article 6.4
k – The coefficient for a change of wind pressure basing on the height which is
referred to table 5
c – The pneumatic coefficient is referred to table 6
The reliable coefficient of load of wind (γ) is 1.2
6.4 Value of wind pressure (Wo) in the table 4
The appendix D shows the zoning of pressure of wind in Vietnam. The bold
interruptive lines is a border of the zone which is considered to be impacted by
storm lightly or heavily (accompanying with zone code is a sign of A or B)
The appendix E shows zoning of pressure of wind according to geographic
name.
The appendix F shows value of wind pressure with different supposed usage
time for different projects defined by the meteorological observation station in
mountain and island zone.
Table 4 – Value of wind pressure in the zoning map of wind pressure in Vietnam
Wind pressure zones in the map I II III IV V
Wo (daN/m2) 65 95 125 155 185
6.4.1 To the zone which is defined to be impacted by storm lightly (appendix D),
pressure of wind (Wo) is reduced 10 daN/m2 for the zone 1-A, 12daN/m
2 for
the zone II-A and 15 daN/m2 for the zone III-A.
VIETNAM STANDARD TCVN 2737:1995
302
6.4.2 To the zone I, the value of wind pressure (Wo) is referred to the table 4, which is
used for house and project which are built at the mountain, hill, plain and
valley area
Other complicated area refer to the article 6.4.4
6.4.3 House and projects which are built at the mountain and island area with the
same height, terrain and at the meteorological observation station in the
appendix F, value of wind pressure calculated accordance with different
supposed usage time is taken under independent numeric value of this station
(table F1 and F2, appendix F)
6.4.4 House and project which are built at the complicated terrain (ravine, between
two parallel mountain ranges, mountain pass’s gates…), value of wind pressure
is used from the data of the meteorological observation station or the observed-
site result which is processed, including experience of project usage. So, the
value of pressure of wind (Wo(daN/m2) is defined as the formula:
W o = 0,0613 x V2
o (6)
With: V0 – speed of wind at the 10 meter height versus the standard (average
speed of 3 seconds surpass the standard one time for 20 years) is tantamount to
the terrain of B and Its unit is meter/second.
6.5 Value of the coefficient (k) which mentions change of pressure of wind based on
the height versus standard point and type of terrain refers to the table 5.
The terrain of A is a desolate one which has no or very few of high obstacles
which are not over 1.5 meter (airy beach, river, big lake, field of salt, field
without high trees…).
The terrain of B is a quite desolate one which has some scattered high obstacles,
which are not over 10 meters (suburb with a few houses, town, village, thin
forest or planted-newly forest, thinly planted area…)
The terrain of C is a thickly-obstacle one, has thick –set obstacles whose height
is from 10 meters onwards (in city, thick forest…)
What type of terrains the project is determined to belongs to if that terrain’s
nature does not change within a distance of 30h with h ≤60 meters and 2km with
h >60 meters, which is defined from wind facing plane of project (h is a height
of project)
Table 5 – the coefficient (k) on the change of wind-pressure versus the height and
terrain.
Type of terrain
Altitude Z, m A B C
3 1.00 0.80 0.47
5 1.07 0.88 0.54
VIETNAM STANDARD TCVN 2737:1995
303
10 1.18 1.00 0.66
15 1.24 1.08 0.74
20 1.29 1.13 0.80
30 1.37 1.22 0.89
40 1.43 1.28 0.97
50 1.47 1.34 1.03
60 1.51 1.38 1.08
80 1.57 1.45 1.18
100 1.62 1.51 1.25
150 1.72 1.63 1.40
200 1.79 1.71 1.52
250 1.84 1.78 1.62
300 1.84 1.84 1.70
350 1.84 1.84 1.78
≥400 1.84 1.84 1.84
Note:
1) For the average height, the coefficient (k) is defined by interpolating linearly
the value of table 5.
2) When we determine load of wind for a certain project, different direction of
wind may have different terrains.
6.6 When the ground around the house and project is not flat, the standard point to
define height is determined as the appendix G.
6.7 Diagram of wind-load distribution on house, project or components and
pneumatic coefficient are defined as the instruction of table 6. The intermediate
value can be defined by a linear interpolation.
The arrow in the table 6 shows a direction of wind to house, project or segments. The
pneumatic coefficient is defined as follow:
6.7.1 To the individual faces or points of house and project, it is applied as the
pressure coefficient stated (from the diagram 1 to 33 of table 6).
The positive value of the pneumatic coefficient indicates that the direction of
wind-pressure goes into surfaces of project. The negative one goes out of the
project.
6.7.2 To the structures and components (in the diagram 34 to 43 of table 6); we use
the frontispiece drag coefficient cx and cy when we define an object’s general
VIETNAM STANDARD TCVN 2737:1995
304
resistant elements whose effects perpendicular to the wind way and correspond
the object’s projection area to the wind perpendicular plane; we use the lifting
coefficient cz when we determine the vertical elements of the object’s general
drag which is corresponding the object’s projection area to horizontal plane.
6.7.3 To the structure whose face meets wind at an angle of α versus a direction of
wind, it is counted the same as a coefficient (cn and ct) when we determine the
general obstacle elements of objects based on their axis direction and their area
of wind-met surfaces.
To the cases which have not included in the table 6 yet (other houses and
projects with the different direction of wind, the general obstacle elements of
objection with different directions), the pneumatic coefficient is followed to the
experimental data or specific instructions.
6.8 To the house and project with an open frame (window, door, ventilator, heaven’s
gate stated from the diagram 2 to 26 are distributed uniformly over the perimeter
or to the house with the fibre-cement wall and material through which the air can
go (not depend on the embrasures’ presence); when doing calculation of
structure of external wall, column, wind beam, glass transombar, value of the
pneumatic coefficient for the external wall is:
C = +1 with positive pressure
C = - 0.8 with negative pressure
The assumed load of wind for the internal wall is 0.4xWo; the load for the light
partition whose weight is not over 100 daN/m3
is 0.2xWo (but not less than
10daN/m3)
6.9 When doing calculation for the horizontal frame of the house whose lantern
directs longitudinally or is at the zenith with a > 4h (diagram 9, 10, 25, table 6),
load of wind which effects to the windward or leeward columns, frames as well
as the horizontal elements which load of wind impacts on the lantern is
considered.
To the house with saw-tooth roof (diagram 24, table 6) or with the lantern at the
zenith with a ≤ 4h, the frictional force (Wf) which replaces elements of
horizontal force and impacts on the second and more windward lantern is must
be counted. The frictional force (Wf) is defined as the formula:
W f = W o x c f x k x S (7) With:
Wo – wind pressure seen in the table 4, unit is daN/m2
cf - the frictional coefficient given in the table 6
k – the coefficient as the table 5
S – the flat projection area (for saw-tooth roof, corrugated roof or roof with
lantern) or the vertical projection area (for the wall with balcony’s part and the
same structure). Unit is m2.
VIETNAM STANDARD TCVN 2737:1995
305
Drawing of house, projects,
components and diagram of load of
wind
Instruction for determination of the coefficient of motive air Remarks
1.
a) The vertical planes:
- Facing with the wind
- sheltered from the wind
b) The vertical planes or the sloping
plane with an angle of 15o inside the
house of many lanterns or inside the
house with many different
complicated surfaces (if there is not
included in the equivalent diagram in
this table)
- A marginal or middle surface
emerging:
Facing with wind
Sheltered from the wind
- Other middle surfaces:
Facing with the wind
Sheltered from the wind
C = +0.8
C = - 0.6
C = +0.7
C = -0.6
C = -0.5
C = -0.5
VIETNAM STANDARD TCVN 2737:1995
306
2. The house with a saddle roof
3. The house with a closed saddle
roof capsizing close to the ground
h1/l Coefficient degree
0 0.5 1 ≥2
Ce1 0
20
40
60
0
+0.2
+0.4
+0.8
-0.6
-0.4
+0.3
+0.8
-0.7
-0.7
-0.2
+0.8
-0.8
-0.8
-0.4
+0.8
Ce2 ≤60 -0.4 -0.4 -0.5 -0.8
b/l Value of ce3 as h1/l is
≤0.5 1 ≥2
≤1
≥2
-0.4
-0.5
-0.5
-0.6
-0.6
-0.6
α 0o 30o ≥60o
Ce1 0 +0.2 +0.8
- When wind blows to
gable, planes of roof
refers to ce = -0.7
- When we define the
coefficient (v) as the
article 6.15, h = h1 + 0.2
x l x tgα
VIETNAM STANDARD TCVN 2737:1995
307
4. The dome closed roof capsizing
close to the ground
f/l Ce1
0.1
0.2
0.5
+0.1
+0.2
+0.6
5. A dome or arch-likely roof (a bow-
likely shape)
6. The close house with a shed roof
Coefficient h1/l f/l
0.1 0.2 0.3 0.4 0.5
Ce1 0
0.2
≥
+0.1
-0.2
-0.8
+0.2
-0.1
-0.7
+0.4
+0.2
-0.3
+0.6
+0.5
+0.3
+0.7
+0.7
+0.7
Ce2 -0.8 -0.9 -1 -1.1 -1.2
α Ce1
≤15o
30o
≥60o
-0.6
0
+0.8
When determination of
the coefficient (v) as the
article 6.15, h = h1 + 0.7.f
7. The close house with semi-roof
h1/h2 Co
- When b1 ≤ b2 and 0 ≤ β ≤ 30
o, co is applied as
VIETNAM STANDARD TCVN 2737:1995
308
1.2
1.4
1.6
1.8
2.0
2.5
3.0
≥4.0
-0.5
-0.3
-0.1
10
+0.2
+0.4
+0.6
+0.8
this table.
- When b1 > b2, Co
follows the diagram 2
- Value of Ce1, Ce2, Ce3
refers to the diagram 2
8. The one span house with the
lantern along the length of the house
- Value of Ce1, Ce3 follow the diagram 2
- The pneumatic coefficient for surfaces of lantern is -0.6
- The pneumatic coefficient for a windward surface of lantern at
an angle of less than 20o is -0.8
- When we calculate the
vertical frame for house
with a lantern as the
diagram 8 and with a gate
valve, the total pneumatic
coefficient on the lantern
and gate valve is 1.4
- When determining the
coefficient v as the article
6.15, h = h1
9. House with many spans and a
lantern along the length of the house
- Refer to the pneumatic coefficient of the diagram 8
- If the house is in the section AB, Its coefficient ce uses the
same as the diagram 8.
- To the lantern in the section BC when λ ≤ 2, Cx = 0.2
When 2 ≤ λ ≤ 8, cx = 0.1λ
- To the windward wall,
the leeward wall and any
walls, the pneumatic
coefficient is determined
as the diagram 2
- When we define the
VIETNAM STANDARD TCVN 2737:1995
309
When λ > 8, Cx = 0.8
When λ a/(h1 – h2)
- To the rest, Ce = -0.5
coefficient (v) based on
the article 6.15, h = h1
10. Houses with many spans, a
lantern along the length of house and
oblique height
- Refer to the instruction of coefficient in the diagram 8.
- The coefficient C”e1, C
’e1, Ce2 is seen the same as the diagram 2
when we determine Ce2 basing on h1 (the height of windward
wall)
- To the section AB, the coefficient Ce is determined the same as
the section BC in the diagram 9 when the height of a lantern is
(h1 –h2)
Refer to the notes in the
diagram 9.
11. The close house with two bays, a
saddle roof
- The coefficient Ce1 follows as the diagram 2
12. The close house with two bays, a
saddle roof and different height.
- The coefficient Ce1 follows as the diagram 2
VIETNAM STANDARD TCVN 2737:1995
310
13. The close house with three bays,
saddle roof and different height
- The coefficient follows as the diagram 2
- The coefficient is counted as follow: Ce2 = 0.6 x (1 – h1/h). If
h1>h, Ce2 = -0.6
14. The close house with a lantern
and one half-roofed area
The pneumatic coefficient is referred to the next diagram
15. The house with a lantern and two
half-roofed areas
The pneumatic coefficient is referred to the next diagram
VIETNAM STANDARD TCVN 2737:1995
311
16. The close house with three bays
and a lantern at middle of and along
the house
- The coefficient Ce1 follows the diagram 2
- The coefficient Ce2 follows: Ce2 = 0.6 x (1 – 2h1/h)
If h1 > h, Ce2 = - 0.6
17. The close house with two bays
and a lantern along the house
The coefficient is counted as follow:
When a ≤ 4h, Ce1 = +0.2
When a > 4h, Ce1 = +0.6
18. The close house with bulkhead
wall and saddle roof
The pneumatic coefficient is referred to the next diagram
19. The close house with a dome and
subterranean lantern
The pneumatic coefficient is referred to the next diagram
VIETNAM STANDARD TCVN 2737:1995
312
20. The close house with a dome, two
bays and subterranean lantern
The pneumatic coefficient is referred to the next diagram
21. The close house with one bay, a
lantern and gate valve
The pneumatic coefficient is referred to the next diagram
22. The close house with two bays, a
lanterm and gate valve
The pneumatic coefficient is referred to the next diagram
23. The close house with the light The coefficient is counted as follow:
VIETNAM STANDARD TCVN 2737:1995
313
corrugated or wrinkly roof
- If f/b ≤ 0.25, refer to the diagram 2
- If f/b > 0.25, refer to the diagram 9
24. The house with saw-tooth roof
- The coefficient Ce1 and Ce2 are referred as the diagram 2
- The frictional force Wf is counted for the case which the
direction of wind goes with the arrow’s direction as well as is
perpendicular to the drawing’s plane
- The frictional force
which is as the same
direction of wind, Cf =
0.04
- Refer to the note of the
diagram 9
25. The house with zenith - The coefficient Ce1 and Ce3 is referred to the diagram 2
- The frictional force is counted as the diagram 24
- Refer to the note of the
diagram 9
VIETNAM STANDARD TCVN 2737:1995
314
26. The close house with many
complicated bays
The coefficient Ce1 is counted as follow:
When a ≤ 4h, ce1 = +0.2
When a > 4h, Ce1 = +0.6
27. The house with one open surface
(open partly or completely)
µ is called wind-osmoses of the wall. It is defined by ration
between the open door’ area and the area of the wall.
- When µ ≤ 5%, ci1 = Ci2 = ±0.2 (depending on the windward or
leeward)
- When µ ≥ 30%, Ci1 – Ce3, defined as the diagram 2 and ci2 =
+0.8
- The case which the house has one completely open surface, it is
referred the same as when µ ≥ 30%
- The coefficient Ce
follows the diagram 2
- To the close house; Ci =
0. To the houses stated in
the article 6.1.2, the
standard value of external
pressure on the light
partition (when their
surface density is less
than 100kg/m2)is 0.2Wo,
but the density is not less
VIETNAM STANDARD TCVN 2737:1995
315
than 10kg/m2.
- To each wall, the sign
“+” or “-“of Ci1 when µ
≤5% is defined from the
experimental condition of
the most disadvantageous
load methods.
28. The house with two opposite
open surfaces
- The coefficient Ce1, Ce2 and Ce3 follows as the diagram 2
29. The house with three open faces - The coefficient Ce1, Ce2 and Ce3 follows the diagram 2.
- The coefficient Ce4 to the wind-met face is +0.8 and to the
wind-hidden face is Ce3
VIETNAM STANDARD TCVN 2737:1995
316
30. The house with many terraces
- To the horizontal or
incline roof’s parts (α <
15o), the pneumatic
coefficient at the height h1
and h2 is referred the same
as the one of the vertical
roof’s part.
- When l1 > h1, length of
the section turning into
negative pressure is h1/2.
- The pneumatic
coefficient for the
concavity of house (in the
length a) which parallels
to the wind is considered
VIETNAM STANDARD TCVN 2737:1995
317
the same as the windward
face.
- When b > a the length of
the section turning into
negative pressure is a/2
31. Eaves
Type of
diagram
Α
(degree) Ce1 Ce2 Ce3 Ce4
I
10
20
30
0.5
1.1
2.1
-1.3
0
0.9
-1.1
0
0.6
0
-0.4
0
II
10
20
30
0
1.5
2
-1.1
0.5
0.8
-1.5
0
0.4
0
0
0.4
III
10
20
30
1.4
1.8
2.2
0.4
0.5
0.6
IV
10
20
30
1.3
1.4
1.6
0.2
0.3
0.4
- The value of the
coefficient Ce1, Ce2, Ce3,
ce4 is used to calculate
the total pressure on and
beneath the eaves.
- To the negative value of
Ce1, Ce2, Ce3, Ce4; the
direction of pressure in
the diagram will be in the
reverse direction.
- To the corrugated roof,
if the wind goes along the
roof, it is included the
frictional force (Wf) with
Cf = 0.04
32. Globe
β(degree) 0 15 30 45 60 75 90
Ce +0.1 +0.8 +0.4 -0.2 -0.8 -1.2 -1.25
β(degree) 105 120 135 150 175 180
VIETNAM STANDARD TCVN 2737:1995
318
ce -1.0 -0.6 -0.2 +0.2 +0.3 +0.4
Cx = 1.3 as Re < 105
Cx = 0.6 as 2 x 102 ≤ 3 x 10
5
Cx = 0.2 as 4 x 105 >Re
With Re = 0,88 x d x yzkW ×× )(0 × 10 5
d – diameter of globe (m)
Wo – wind pressure follows as the table 4 (daN/m2)
k(z) – the coefficient of live pressure’s change versus the height
(table 5)
yγ – the reliable coefficient follows the article 6.3
VIETNAM STANDARD TCVN 2737:1995
319
33. The projects with their round
cylinder-shaped surrounding surfaces
(container, cooling town, chimney)
and with or without roof
Cel = k1 x cβ with k1 = 1 as cβ > 0
h1/d 0.2 0.5 1 2 5 10 25
k1 as
cβ <0
0.8 0.9 0.95 1.0 1.1 1.15 1.2
cβ is used when Re > 4 x 105 as the follow table:
Value of Ce2 as h1/d is Type of roof
1/6 1/3 ≥ 1
Plane, cone as α
≤ 5o; globe as
f/d ≤ 0.1
-0.5 -0.6 -0.8
h1/d 1/6 1/4 1/2 1 2 ≥ 5
c1 -0.5 -0.55 -0.7 -0.8 -0.9 -1.05
- The coefficient Re is
defined as the formula of
the diagram 32 and z = h1
- The coefficient c1 is
counted for both with and
without opening roof.
- When we determine the
coefficient v as the article
6.15, b = 0.7d and h = h1
+ 0.7f
VIETNAM STANDARD TCVN 2737:1995
320
34. The prism-shaped project with the
square- and polygonal- shaped plane
The obstructing factor of front face cx and cv follows:
Cx = k x Cx∞; Cv = k x Cv∞
Table 6.1
λe 5 10 20 35 50 100 ∞
k 0.6 0.65 0.75 0.85 0.9 0.95 1
λe is defined as the table 6.2. In the table 6.2, there is λ = l/b with
l, b are corresponding to the biggest and smallest dimension of
the project or its parts in the wind-met plane
Table 6.2
λe = λ/2 λe = λ λe = 2λ
Table 6.3
Section – the wind β (degree) l/b Cx∞
Rectangle 0 ≤ 1.5 2.1
- When the wind parallel
to the wall which has part
of balcony, cf = 0.1; to
corrugated roof, cf = 0.04
- To the house with
rectangle plane (table
6.3); when l/b = 0.1 ÷ 0.5
and β = 40o ÷ 50
o, cf =
0.75. When load of wind
is distributed uniformly
and placed at the point 0,
the eccentricity e =
0.15b.
- The coefficient Re is
defined accordance with
the formula of the
diagram 32, with z = h1
and d is the
circumscribed circle.
- When determining the
coefficient v as the article
6.12, h is the height of
the project, b is
dimension of the project
at the y axis
VIETNAM STANDARD TCVN 2737:1995
321
40 ÷ 50
≥ 3
≤ 0.2
≥ 0.5
1.6
2.0
1.7
Lozenge
0 ≤ 0.5
1
≥ 2
1.9
1.6
1.1
Equilaterla
triangles
0
180
2
1.2
Table 6.4
Section – the wind β (degree) n(number of
sides)
C∞ as Re >
4x105
Regular polygon
Any 5
6 ÷ 8
10
12
1.8
1.5
1.2
1.0
35. The projects with their round
cylinder-shaped surrounding surfaces
(container, cooling town, chimney),
cable, conduit and the close and
round tube-shaped structure
components
Cx = k x cx∞
With:
- The coefficient k is defined as the table 6.1 of the diagram 34
- The coefficient cx∞ is defined as the below chart of rough
surfaces (by concrete, steel, wood…)
- The coefficient Re is
defined as the formula of
the diagram 32 with Z =
h and d is the project’s
diameter.
- Value of ∆: to the wood
VIETNAM STANDARD TCVN 2737:1995
322
structure, ∆ = 0.005m; to
brick construction, ∆ =
0.01m; to ferro-concrete,
∆ = 0.005m; to steel
structure, ∆ = 0.001m; to
the conduit and cable
with diameter d, ∆ =
0.01d; to the surface
whose slope had a height
b, ∆ = b.
- To the corrugated roof,
cf = 0.04
- The wire way with
value cx is referred as
follow:
To the conduit and cable
whose diameter is more
than 20mm, cx is reduced
10%
36. The shaped steel with different
section of trussed frame
When the wind is perpendicular to the line shaft of segments, cx
= 1.4
VIETNAM STANDARD TCVN 2737:1995
323
41. The structured multi-step frame
- This chart is used for the structured multi-step frame which
there is no wall or any built work on
- The coefficient c follows as the diagram 38.
42. The span rope and the tube-
shaped components which slope in
the plane of wind.
Cxα = cx x sin2α
With cx is defined as the date of the diagram 35
43. The cone and cylinder-shaped
project with round bottom
1 – The cone and cylinder-shaped project with their round
bottom on the ground
VIETNAM STANDARD TCVN 2737:1995
324
1) The cone and cylinder- shaped
project with their round bottom on
the ground:
2) The cone and cylinder-shaped
project in the space:
- The cone one: cx = 0.7
cz = -0.3
- The cylinder one
cx = 1.2
cz = -0.3
2 – The cone in space:
a/ Its top is at the windward
- The cone has no bottom as α = 30o; cx = 0.35
- The cone has no bottom as α = 60o; cx = 0.5
b/ Its tops is at the leeward: values cx is used as Re > 105
- The cone has no bottom: cx = 1.4
- The cone has bottom: cx = 1.2
VIETNAM STANDARD TCVN 2737:1995
325
6.10 At the area next to the outline of roof rim, ridge rim and roof foot, edges which
are contiguous between horizontal wall and vertical wall; if the external pressure
has a negative value; the local pressure needs to be included (figure 1)
Figure 1: Areas whose roof is effected by the local pressure
The coefficient of local pressure D follows the table 7.
Table 7 – Coefficient of local pressure D
Areas with local pressure Coefficient D
- Area 1: has a width “a” which is calculated from
the roof rim, ridge rim, roof foot and corner
- Area 2: a width “a” which connects to the area 1
2
1.5
Note:
1) At the area with the local pressure, the pneumatic coefficient C needs to be
multiplied by the coefficient of the vertical pressure D
2) When we define the collective force which effects to project, a wall or roof, the
coefficient of the local pressure is not used.
3) Width a is the smallest value in three values as follow: 0.1b; 0.1l and 0.1h, but
not over 1.5m. The dimension of, l, h refers to the figure 1
4) The coefficient of the local pressure is only applied for the house with a
sloping roof (α > 10o)
5) When there is cornice, the area of roof includes the area of the cornice. The
pressure of the cornice equals the pressure of the wall right under the rising-
out roof.
VIETNAM STANDARD TCVN 2737:1995
326
6.11 The live element of load of wind must be included when we do calculation for the cylindrical, pyramidal project, chimney, lamp-post, column-shaped equipment, conveyer’s corridor, outdoor scaffold, the many-storied house whose height is over 40 meters, horizontal frame of the one-storied and span industrial house whose height is over 36 meters and ratio between the height and the span is over 1.5.
6.12 To the project which is high and has soft structure (chimney, cylinder, pyramid…), needs to be checked the instability of the pneumatic.
The calculation and solution instruction of the oscillation’s loss of structure is defined by the specific studies based on pneumatic experimental data.
6.13 The standard value of wind-load’s motive elements (Wp) at the height Z is defined as follow:
6.13.1 To the project and its structure components whose specific basic oscillatory frequency f1 (Hz) is more than the limited value of the specific oscillatory frequency fL stated in the article 6.14 is defined as the follow formula:
W p = W × ξ × v (8)
With:
W – The standard value of wind load’s static elements at the defined height is determined as the article 6.3
ξ– The live pressure’s coefficient of load of wind at the height Z bases on the table 8
V – the correlation coefficient between a space and pressure for load of wind is defined as the article 6.15
Table 8 – The motive pressure’s coefficient of load of wind ξ
The live pressure’s coefficient versus types of terrain Height Z, m
A B C
≤ 5 0.318 0.517 0.754
10 0.303 0.486 0.684
20 0.289 0.457 0.621
40 0.275 0.429 0.563
60 0.267 0.414 0.532
80 0.262 0.403 0.511
100 0.258 0.395 0.496
150 0.251 0.381 0.468
VIETNAM STANDARD TCVN 2737:1995
327
200 0.246 0.371 0.450
250 0.242 0.364 0.436
300 0.239 0.358 0.425
350 0.236 0.353 0.416
≥ 480 0.231 0.343 0.398
6.13.2 To the project (and its structure components) whose calculation drawing is a free level system (The horizontal frame of the one-storied industrial house, water town…); when f1 < fL, it is defined as the follow formula:
W p = W × ζ × ξ × v (9)
With:
ξ – the coefficient of motive power is defined by the chart in the figure 2, depending on a parameter غ and logarithms reduction of oscillation.
ε = 1
0
940 f
W
×
×γ (10)
γ – The reliable coefficient of load of wind is 1.2
Wo – The value of wind-load (N/m2) is defined as the article 6.4
Figure 2: The coefficient of motive power
The curved line 1 – to the ferro-concrete and brick-stone project, even the steel frame projects covered by structure (δ = 0.3)
The curved line 2 – to the steel pyramid, the steel cylinder, chimney, column-shaped equipments with ferro-concrete platform (δ = 0.15)
6.13.3 The houses with symmetric surfaces which has f1 < fL and the project has f1 < fL < f2 (f2: the project’s second specific oscillating frequency) are defined as follow formula:
VIETNAM STANDARD TCVN 2737:1995
328
W p = m × ξ × ψ × v (11)
With:
M – Mass of project’s parts whose center of gravity has height Z.
ξ - the coefficient of motive power, refer to the article 6.13.2
y – Horizontal set-over of the project at the height Z, which is corresponding to the first specific oscillating type (for house with symmetric planes, it is allowed that y is the set-over caused by the static placed and uniformly distributed horizontal load).
Ψ – The coefficient is defined by dividing the project into r of parts with a condition that load of wind will not be changed at each part.
ψ = ∑
∑
=
=
×
r
k
kk
r
k
pkk
My
Wy
1
2
1 (12)
With
Mk – mass of the kth part of the project
Yk – The horizontal set-over of the kth part’s center of gravity which is corresponding to the first free vibration.
Wpk – The uniformly distributed motive constituent of load of wind at the kth part of the project is defined the same as the formula (8).
To the house with many stories, which has no change in its hardness, mass and width of met-wind surface versus the height, the follow formula is to define a standard value of load of wind’s motive constituent at the height Z:
W p = 1,4 × h
Z × ξ W ph (13)
With:
Wph – The standard value of wind-load’s motive constituent at the height h of the project is determined as the formula (8).
6.14 The limited value of free vibration frequency fL (Hz) does not need to calculate force of inertia generated during the project oscillates in the equivalent free vibration. The value is defined in the table 9, depending on value of vibration’s derate δ.
6.14.1 To the ferro-concrete and brick-stone project, the steel frame project with protected construction, δ = 0.3
VIETNAM STANDARD TCVN 2737:1995
329
6.14.2 To the town, cylinder, steel chimney, steel column-shaped equipments with its ferro-concrete platform, δ = 0.15
Table 9 – The limited value of free vibration frequency fL
fL
Hz Area of wind pressure
δ = 0.3 δ= 0.15
I
II
III
IV
V
1.1
1.3
1.6
1.7
1.9
3.4
4.1
5.0
5.6
5.9
To the cylinder-shaped project as f1 < fL, it is needed to check the stability of
the pneumatics.
6.15 The space-interrelating coefficient of wind pressure’s live elements (v) is defined
basing on the assumed plane surface of the project, which we can define the
live interrelation.
The assumed surface consists of the wall’s windward faces, wall’s leeward face,
side-wall, roof and other same structure, through which wind pressure goes to
the structure components of the project.
If the assumed surfaces have a square-shape and they are placed parallel with the
basic shafts (see figure 3), the coefficient (v) is defined as the table 10,
depending on parameter ρ and χ. The parameter ρ and χ are defined as the table
11.
Figure 3 – the system of axes when determining of the interrelation coefficient v
VIETNAM STANDARD TCVN 2737:1995
330
Table 10 – the interrelation coefficient between space and wind-load’s motive
pressure v
Ρ, m Coefficient ν as χ (m) is
5 10 20 40 80 160 350
0.1
5
10
20
40
80
160
0.95
0.89
0.85
0.80
0.72
0.63
0.53
0.92
0.87
0.84
0.78
0.72
0.63
0.53
0.88
0.84
0.81
0.76
0.70
0.61
0.52
0.83
0.80
0.77
0.73
0.57
0.59
0.50
0.76
0.73
0.71
0.68
0.63
0.56
0.47
0.67
0.65
0.64
0.61
0.57
0.51
0.44
0.56
0.54
0.53
0.51
0.48
0.44
0.38
Table 11 – The parameter ρ and χ
The basic co-ordinate plane parallels to the
assumed surfaces ρ χ
Zoy
Zox
Xoy
b
0.4a
b
h
h
a
6.16 The project with fs > f L needs to be counted a motive power, including the first
oscillation s (s is defined with a condition: fs < fL < f s+1)
6.17 To the house and project whose supposed usage time is 50 years, the reliable
coefficient γ for load of wind is 1.2. When the supposed time changes, the assumed
value of load of wind must be change by multiplying by the coefficient given in the
table 12.
Table 12 – the adjustment coefficient of load of wind versus the different
projects’ supposed usage time.
The supposed usage time
(year) 5 10 20 30 40 50
The adjustment
coefficient of load of
wind
0.61 0.72 0.83 0.91 0.96 1
VIETNAM STANDARD TCVN 2737:1995
331
Appendix A
The determination methods of the assumed internal force
in the basic and special load aggregate
A.1 When at least two of basic load aggregate are considered, the total value of the
assumed internal force X caused by those loads (moment of flexure or axial
torque, longitudinal force or cutting strength) is defined as the follow formula:
X = ∑=
m
i
tciX1
+ ∑=
−×m
i
tcix1
2
1
2 )1(γ (A.1)
With:
Xtci – the internal force is defined basing on the standard value of each load,
including the aggregate coefficient as the instruction of the article 2.4.3
gi – the reliable coefficient of each load
m- Number of loads effecting simultaneously
A.2 If load simultaneously generates two or three different internal force (X,Y,Z)
which are included during calculation (for example normal inner-force and
moment flexure one or two directions), at each aggregate, three methods (X,
ZY , ), (Y, XZ , ), Z, YX , ) will be considered if there are three inner forces or two
(X, Y), (Y, X) if there are two ones.
To the method (X, ZY , ), the inner forces are defined as the follow formula:
X = ∑=
±m
i
tciX1
∑=
−×m
i
itciX1
22 )1(γ (A.2)
−
Y = ∑=
±m
i
tciY1
∑
∑
=
=
−×
−××
m
i
itci
m
i
itcitci
X
YX
1
22
1
2
)1(
)1(
γ
γ
(A.3)
−
Z = ∑=
m
i
tciZ1
±
∑
∑
=
=
−×
−××
m
i
itci
m
i
itcitci
X
ZX
1
22
1
2
)1(
)1(
γ
γ
(A.4)
VIETNAM STANDARD TCVN 2737:1995
332
With:
X, ZY , – The total assumed inner force generated when there is simultaneous
effect of several temporary loads.
Xtci, Ytci, Xtci – inner forces are defined according to the standard value of
each load, including the aggregate coefficient. To the short-term load, it is
referred to the article 1, 4, 3. It is referred to the article 5.13 if the live element of
load of wind is included.
M, gi – the same as the formula (A.1)
To the methods (Y, XZ , ) and (Z, YX , ), the inner force is defined as the
formula (A.2), (A.3) and (A.4) under the cyclic permutation of signs (X, Y, Z)
In the formulas (A.2), (A.3) and (A.4), a minus will be used for the case which
absolute value of the inner force is de-rated, which is defined under the formula
(A.2) is risky. So, all three formulas must use the same sign.
When establishing the assumed aggregate, in the case that when the temporary
load is calculated, it must be sure that the extreme value of one of the inner
forces must be in the section and the value of the other inner force will certainly
exist through the result of this calculation. So, the assumed extreme inner force
should be defined as the formula (A.2), its corresponding inner force follows the
formula (A.3) and (A.4). For example when establishing the aggregate (Nmin, M
corresponding), Nmin should be defined as the formula (A.2) and the
corresponding m follows the formula (A.3).
Note: Depending on the type of the aggregate, the inner force which is caused
the frequent load with the more or less reliable coefficient (refer to the article
3.2), should be added
VIETNAM STANDARD TCVN 2737:1995
333
Appendix B
Table of list of cranes and its operation status
Table B1
Crane’s operation status List of electrical cranes
Workshop which uses
crane with the mentioned
working status
Light
Average
Hard
Very Hard
Type of crane with a goods
-suspending hook
Type of crane with goods-
suspending hook,
including tackles with
trolley hoist
Type of crane with goods-
suspending hook, types of
crane using for casting,
forging metal
Type of clamshell, of
electromagnet, type of
clamshell with purling,
type which is made from
magnet to prop the casting
block, type used to smash
material
Repairing workshop,
machinery building of
thermoelectric plant
Mechanic and assembly
block of the factories with
average-scale mass
production, mechanical
repair block, packet
loading and unloading area
Workshops of the factory
which have a large-scale
mass production, goods
loading and unloading
area, several workshops of
metallurgical work
Workshops of metal mill
Note – The electric running hoist with the average operation status and the hand-pull
crane with the light operation status.
VIETNAM STANDARD TCVN 2737:1995
334
Appendix C
Load caused by collision between the crane and the chock at the end rail
The standard horizontal load Py (10 KN) along the crane-way generated by collision
between the crane and the end-rail chock is defined as formula:
P y = f
vm 2× (C.1)
With:
v – Speed of crane at the time of collision is as half as the rated speed, its unit is
meter/second.
f – The most sag of a damper which is able to be generated is 0.1m for the crane
with a soft rigging and the lifting capacity of below 500 KN under its
operation status – light, average and hard. It is 0.2m for the others.
m – Mass of crane is defined as the formula (its unit is ton - 10KN):
m = g
1 × 2
MP + (P
T + KQ) ×
k
k
L
lL − (C.2)
With:
g – the gravity is 9.81m/s2
PM – the weight of crane’s rod (its unit is ton – 10KN)
PT – the weight of trolley (its unit is ton – 10KN)
Q – the lifting capacity of crane (its unit is ton – 10KN)
k – The coefficient is 0 for the crane with a soft rigging and it is 1 for the crane
with the hard one.
Lk – the bay of crane (its unit is meter)
l – Distance between the trolley and the chair (its unit is meter)
The assumed value of load is included the reliable coefficient as the article 5.8. It
is not more than the value of the follow table (C.1):
Table C.1
Crane’s characteristic The critical load,
10KN
1. The suspension hoist with manual or electrical control
2. The multi-purposes electric crane with the operation
status (middle and hard) and a crane for casting shop
3. The multipurpose electric crane with the operation status
(light)
4. The multipurpose electric crane with the operation status
(very hard) used for metallurgy work or special work.
- With soft hook
- With hard hook
1
15
5
25
50
VIETNAM STANDARD TCVN 2737:1995
335
Appendix E
Table E1 – The pressure of wind at the administrative geographic name
Place-name Area Place-name Area
1. Ha Noi capital:
- Inner Ha Noi
- Dong Anh district
- Gia Lam district
- Soc Son district
- Thanh Tri district
- Tu Liem district
2. Ho Chi Minh city:
- Inner city
- Binh Chanh district
- Can Gio district
- Cu Chi district
- Hoc Mon district
- Nha Be district
- Thu Duc district
3. Hai Phong city: - Inner city
- Do Son town
- Kien An town
- An Hai district
- An Lao district
- Cat Hai district
- Dao Bach Long Vi district
- Kien Thuy district
- Thuy Nguyen district
- Tien Lang district
- Vinh Bao district
3. An Giang:
- Long Xuyen town
- Chao Doc town
- An Phu town
II.B
II.B
II.B
II.B
II.B
II.B
II.A
II.A
II.A
I.A
II.A
II.A
II.A
IV.B
IV.B
IV.B
IV.B
IV.B
IV.B
V.B
IV.B
III.B
IV.B
IV.B
I.A
I.A
I.A
- Chau Thanh district
- Chau Phu district
- Cho Moi district
- Phu Tan district
- Tan Chau district
- Tinh Bien district
- Thoai Son district
- Tri Ton district
5. Ba Ria – Vung Tau:
- Vung Tau city
- Chau Thanh district
- Con Dao distict
- Long Dat district
- Xuyen Moc district
6. Bac Thai:
- Thai Nguyen city
- Bac Can town
- Song Cong town
- Cho Don district
- Bach Thong district
- Dai Tu district
- Dinh Hoa district
- Dong Hy district
- Na Ri district
- Pho Yen district
- Phu Binh district
- Phu Luong district
- Vo Nhai district
7. Ben Tre:
- Ben Tre town
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
II.A
II.A
III.A
II.A
II.A
II.B
I.A
II.B
I.A
I.A
II.A
I.A
I.A
I.A
II.B
II.B
I.A
I.A
II.A
VIETNAM STANDARD TCVN 2737:1995
336
Table E1 (cont.)
Place-name Area Place-name Area
- Ba Tri district
- Binh Dai district
- Chau Thanh district
- Cho Lach district
- Giong Trom district
- Mo Cay district
- Thanh Phu district
8. Binh Dinh: - Quy Nhon city
- An Nhon district
- An Lao district
- Hoai An district
- Hoai Nhon district
- Phu Cat district
- Phu My district
- Tay Son district
- Tuy Phuoc district
- Van Canh district
- Vinh Thanh district
9. Binh Thuan: - Phan Thiet town
- Bac Binh district
- Duc Linh district
- Ham Tan district
- South Ham Thuan district
- North Ham Thuan district
- Phu Quy district
- Tanh Linh district
- Tuy Phong district
10. Cao Bang:
- Cao Bang town
- Ba Be district
- Bao Lac district
- Ha Quang district
- Ha Lang district
- Hoa An district
- Ngan Son district
- Nguyen Binh district
II.A
II.A
II.A
II.A
II.A
II.A
II.A
III.B
III.B
II.B (I.A)
II.B
III.B
III.B
III.B
II.B (I.A)
III.B
II.B
I.A
II.A
II.A (I.A)
I.A
II.A
II.A
I.A (II.A)
III.A
I.A
II.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
- Quang Hoa district
- Thach An district
- Thong Nong district
- Tra Linh district
- Trung Khanh district
11. Can Tho:
- Can Tho city
- Chau Thanh district
- Long My district
- O Mon district
- Phung Hiep district
- Thot Not district
- Vi Thanh district
12. Dac Lac:
- Buon Ma Thuat town
- Cu Giut district
- Cu M’ga district
- Dac Min district
- Dac Nong district
- Dac Rlap district
- E Ca district
- E H’leo district
- E Sup district
- Krong Ana district
- Krong Bong district
- Krong Cuc district
- Krong Nang district
- Krong No district
- Krong Pac district
- Lac district
- Mo Drac district
13. Dong Nai:
- Bien Hoa city
- Vinh An town
- Dinh Quan district
- Long Khanh district
- Long Thanh district
- Tan Phu district
I.A
I.A
I.A
I.A
I.A
II.A
II.A
II.A
II.A (I.A)
II.A
I.A
II.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A(II.A)
II.A
I.A
VIETNAM STANDARD TCVN 2737:1995
337
Table E1 (cont)
Place-name Area Place-name Area
- Thong Nhat district
- Xuan Loc district
14. Dong Thap:
- Cao Lanh town
- Cao Lanh district
- Chau Thanh district
- Hong Ngu district
- Lai Vung district
- Tam Nong district
- Tan Hong district
- Thanh Binh district
- Thanh Hung district
- Thap Muoi district
15. Gia Lai:
- Play Cu town
- A Dun Pa district
- An Khe district
- Chu Pa district
- Chu Prong
- Chu Se
- Duc Co
- K bang
- Krong Chro
- Krong Pa
- Mang Giang
16. Ha Bac:
- Bac Giang
- Bac Ninh
- Gia Luong
- Hiep Hoa
- Lang Giang
- Luc Nam
- Luc Ngan
- Que Vo
- Son Dong
- Tan yen
- Tien Son
- Thuan Thanh
I.A
I.A
I.A
I.A
II.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
- Viet Yen district
- Yen Dung district
- Yen Phong district
- Yen The district
17. Ha Giang:
- Ha Giang town
- Bac Me district
- Bac Quang district
- Dong Van district
- Hoang Su Phi district
- Meo Vac district
- Quan Ba district
- Vi Xuyen district
- Xin man district
- Yen Minh district
18. Ha Tay:
- Ha Dong town
- Son Tay town
- Ba Vi district
- Chuong My district
- Dan Phuong district
- Hoai Duc district
- My Duc district
- Phu Xuyen district
- Phuc Tho district
- Quoc Oai district
- Thach That district
- Thanh Oai district
- Thuong Tin district
- Ung Hoa district
19. Ha Tinh:
- Ha Tinh town
- Hoang Linh town
- Can Loc district
- Cam Xuyen district
- Duc Tho district
- Huong Khe district
- Huong Son district
II.B
II.B
II.B
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
II.B
IV.B
IV.B
IV.B
III.B(IV.B)
II.B
I.A(II.B)
I.A(II.B)
VIETNAM STANDARD TCVN 2737:1995
338
Table E1 (cont)
Place-name Area Place-name Area
- Ky Anh district
- Nghi Xuan district
- Thach Ha district
20. Hai Hung:
- Hai Duong town
- Hung Yen town
- Cam binh district
- Chau Giang district
- Kim Mon district
- Kim Thi district
- My Van district
- Chi Linh district
- Nam Thanh district
- Ninh Thanh district
- Phu Tien district
- Tu Loc district
21. Hoa Binh:
- Hoa Binh town
- Da Bac district
- Kim Boi district
- Ky Son district
- Lac Thuy district
- Lac Son district
- Luong Son district
- Mai Chau district
- Tan lac district
- Yen Thuy district
22. Khanh Hoa:
- Nha Trang city
- Cam Ranh district
- Dien Khanh district
- Khanh Son district
- Khanh Vinh district
- Ninh Hoa district
- Truong Sa district
23. Kien Giang:
- Rach Gia town
- An Bien district
- An Minh district
III.B(IV.B)
IV.B
IV.B
III.B
III.B
III.B
II.B
II.B
III.B
II.B
II.B
III.B
III.B
III.B
III.B
I.A
I.A
II.B
I.A
II.B
II.B
II.B
I.A
I.A
II.B
II.A
II.A
II.A
I.A
I.A
II.A
III.B
I.A
I.A
I.A
- Chau Thanh district
- Giong Rieng district
- Go Quao district
- Ha Tien district
- Hon Dat district
- Kien Hai district
- Phu Quoc district
- Tan Hiep district
24. Kon Tum:
- Kom Tum town
- Dac Giay district
- Vinh Thuan district
- Dac To district
- Kon Plong district
- Ngoc Hoi district
- Sa Thay district
25. Lai Chau:
- Dien Bien Phu town
- Lai Chau town
- Dien Bien district
- Muong Lay district
- Muong Te district
- Phong Tho district
- Tua Chua district
- Tuan Giao district
- Sin Ho district
26. Lam Dong:
- Da lat city
- Bao Loc district
- Cat Tien district
- Di Linh district
- Da Hoai district
- Da Te district
- Don Duong district
- Duc Trong district
- Lac Duong district
- Lam Ha district
27. Lang Son:
- Lang Son town
I.A
II.A
II.A
I.A
I.A
II.A
III.A
I.A
I.A
I.A
II.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
VIETNAM STANDARD TCVN 2737:1995
339
Table E1 (cont)
Place-name Area Place-name Area
- Bac Son district
- Binh Gia district
- Cao Loc district
- Chi Lang district
- Dinh Lap district
- Huu Lung district
- Loc Binh district
- Trang Dinh district
- Van Lang district
- Van Quan district
28. Lao Cai: - Lao Cao town
- Bac Ha district
- Bao Thang district
- Bao Yen district
- Bat Xat district
- Muong Khuong district
- Sa Pa district
- Than Uyen district
- Van Ban district
29. Long An:
- Tan An town
- Ben Luc district
- Can Duoc district
- Can Giuoc district
- Chau Thanh district
- Duc Hoa district
- Duc Hue district
- Moc Hoa district
- Tan Thanh district
- Tan Tru district
- Thach Hoa district
- Thu Thua district
- Vinh Hung district
30. Minh Hai:
- Bac Lieu town
- Ca Mau town
- Cai Nuoc district
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
II.A
II.A
II.A
II.A
II.A
I.A
I.A
I.A
I.A
II.A
I.A
II.A
I.A
II.A
II.A
II.A
- Dam Doi district
- Gia Rai district
- Hong Dan district
- Ngoc Hien district
- Thoi Binh district
- Tran Van Thoi district
- U Minh district
- Vinh Loi district
31. Nam Ha:
- Nam Dinh city
- Ha Nam town
- Binh Luc district
- Duy Tien district
- Hai Hau district
- Kim Bang district
- Ly Nhan district
- Nam Ninh district
- Nghia Hung district
- Thanh Liem district
- Vu Ban district
- Xuan Thuy district
- Y Yen district
32. Nghe An:
- Vinh city
- Anh Son district
- Con Cuong district
- Dien Chau district
- Do Luong district
- Hung Nguyen district
- Ky Son district
- Nam Dan district
- Nghi Loc district
- Nghia Dan district
- Que Phong district
- Quy Chau district
- Quy Hop district
- Quynh Luu district
- Tan Ky district
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
IV.B
III.B
III.B(IV.B)
III.B
IV.B
III.B
III.B
IV.B
IV.B
III.B
IV.B
IV.B
IV.B
III.B
I.A
I.A
III.B
II.B
III.B
I.A
II.B
III.B
II.B
I.A
I.A
I.A
III.B
I.A
VIETNAM STANDARD TCVN 2737:1995
340
Table E1 (cont)
Place-name Area Place-name Area
- Thanh Chuong district
- Tuong Duong district
- Yen Thanh district
33. Ninh Binh:
- Ninh Binh town
- Tam Diep town
- Gia Vien district
- Hoa Lu district
- Hong Long district
- Kim Son district
- Tam Diep district
34. Ninh Thuan:
- Phan Rang-Thap Cham town
- Ninh Hai district
- Ninh Phuoc district
- Ninh Son district
35. Phu Yen:
- Tuy Hoa town
- Dong Xuan district
- Song Cau district
- Song Hinh district
- Son Hoa district
- Tuy An district
- Tuy Hoa district
36. Quang Binh:
- Dong Hoi town
- Bo Trach district
- Le Thuy district
- Minh Hoa district
- Quang Ninh district
- Quang Trach district
- Tuyen Hoa district
37. Quang Nam-Da Nang:
- Da Nang city
- Tam Ky town
- Hoi An town
- Duy Xuyen district
- Dai Loc district
II.B
I.A
II,B
IV.B
IV.B
III.B
III.B
III.B
IV.B
IV.B
II.A
II.A
II.A
I.A
III.B
II.B
III.B
I.A
I.A
III.B
II.B(III.B)
III.B
I.A(II.B)
I.A(II.B,III.B)
I.A
I.A(II.B,III.B)
III.B
II.B
II.B
II.B
III.B
II.B
II.B
- Dien Ban district
- Giang district
- Hiep district
- Hiep Duc district
- Hoang Sa district
- Hoa Vang district
- Nui Thanh district
- Phuoc Son district
- Que Son district
- Tien Phuoc district
- Thanh Binh district
- Tra My district
38. Quang Ngai:
- Quang Ngai town
- Ba To district
- Binh Son district
- Duc Pho district
- Minh Long district
- Mo Duc district
- Nghia Hanh district
- Son Ha district
- Son Tinh district
- Tra bong district
- Tu Nghia district
39. Quang Ninh:
- Cam Pha town
- Hon Gai town
- Uong Bi town
- Ba Che district
- Binh Lieu district
- Cam Pha district
- Dong Trieu district
- Hai Ninh district
- Hoanh Bo district
- Quang Ha district
- Tien Yen district
- Yen Hung district
II.B
I.A
I.A
II.B
V.B
II.B
III.B
I.A
II.B
II.B
III.B
I.A
III.B
I.A
III.B
III.B
II.B
III.B
II.B
I.A
II.B
I.A
II.B
III.B
III.B
II.B
II.B
II.B
IV.B
II.B
III.B
II.B
IV.B
II.B
IV.B
VIETNAM STANDARD TCVN 2737:1995
341
Table E1 (cont.)
Place-name Area Place-name Area
40. Quang Tri:
- Dong Ha district
- Quang Tri district
- Cam Lo district
- Gio Linh district
- Hai Lang district
- Huong Hoa district
- Trieu Phong district
- Vinh Linh district
41. Soc Trang:
- Soc Trang town
- Ke Sach district
- Long Phu district
- My Tu district
- My Xuyen district
- Thanh Tri district
- Vinh Chau district
42. Song Be:
- Thu Dau Mot town
- Ben Cat district
- Binh Long district
- Bu Dang district
- Dong Phu district
- Loc Ninh district
- Phuoc Long district
- Tan Uyen district
- Thuan An district
43. Son La:
- Son La town
- Bac Yen district
- Mai Son district
- Moc Chau district
- Muong La district
- Phu Yen district
- Quynh Nhai district
- Thuan Chau district
- Song Ma district
- Yen Chau district
II.B
II.B
II.B
II.B
II.B
I.A
III.B
II.B
II.A
II.A
II.A
II.A
II.A
II.A
II.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
44. Tay Ninh:
- Tay Ninh town
- Ben Cau district
- Chau Thanh district
- Duong Minh Chau dist.
- Go Dau district
- Hoa Thanh district
- Tan Bien district
- Tan Chau district
- Trang bang district
45. Thai Binh: - Thai Binh town
- Dong Hung district
- Kien Hung district
- Hung Ha district
- Quynh Phu district
- Thai Thuy district
- Tien Hai district
- Vu Thu district
46. Thanh Hoa: - Bim Son district
- Thanh Hoa district
- Sam Son district
- Ba Thuoc district
- Cam Thuy district
- Dong Son district
- Ha Trung district
- Hau Loc district
- Hoang Hoa district
- Lang Chanh district
- Nga Son district
- Ngoc Lac district
- Nong Cong district
- Nhu Xuan district
- Quan Hoa district
- Quang Xuong district
- Tich Gia district
- Thach Thanh district
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
IV.B
IV.B
IV.B
IV.B
IV.B
IV.B
IV.B
IV.B
IV.B
III.B
IV.B
II.B
II.B
III.B
III.B
IV.B
IV.B
II.B
IV.B
II.B
III.B
II.B
I.A
III.B
III.B
III.B
VIETNAM STANDARD TCVN 2737:1995
342
Table E 1 (end)
Place-name Area Place-name Area
- Trieu Yen district
- Tho Xuan district
- Thuong Xuyen district
- Trieu Son district
- Vinh Loc district
47. Thua Thien – Hue:
- Hue city
- A Luoi district
- Huong Tra district
- Huong Thuy district
- Nam Dong district
- Phong Dien district
- Phu Loc district
- Phu Vang district
- Quang Dien district
48. Tien Giang:
- My Tho city
- Go Cong town
- Cai Lay district
- Cai Be district
- Chau Thanh district
- Cho Gao district
- East Go Cong district
- West Go Cong district
49. Tra Vinh:
- Tra Vinh town
- Cang Long district
- Cau Ke district
- Cau Ngang district
- Chau Thanh district
- Duyen Hai district
- Tieu Can district
- Tra Cu district
50. Tuyen Quang:
- Tuyen Quang town
- Chiem Hoa district
III.B
II.B
II.B
II.B
III.B
II.B
I.A
II.B
II.B
I.A
III.B
II.B
III.B
III.B
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
I.A
I.A
- Ham Yen district
- Na Hang district
- Son Duong district
- Yen Son district
51. Vinh Long:
- Ving Long town
- Binh Minh district
- Long Ho district
- Mang Thit district
- Tam Binh district
- Tra On district
- Vung Liem district
52. Vinh Phu:
- Viet Tri city
- Phu Tho town
- Vinh Yen town
- Doan Hung district
- Me Linh district
- Lap Thach district
- Phong Chau district
- Song Thao district
- Tam Dao district
- Tam Thanh district
- Thanh Hoa district
- Thanh Son district
- Vinh Lac district
- Yen Lap district
53. Yen Bai:
- Yen Bai town
- Luc Yen district
- Mu Cang Chai district
- Tram Tau district
- Tran yen district
- Van Chan district
- Van Yen district
- Yen Binh district
I.A
I.A
I.A
I.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
II.A
I.A
II.A
II.A
II.A
I.A
II.B
II.B
I.A
I.A
II.B
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
I.A
Note: For the district belonging to two or three areas (in the bracket), in order to get
the accurate value and area for design, it is suggested to refer to the office which
wrote this stadard.
VIETNAM STANDARD TCVN 2737:1995
343
Appendix F
Wind pressure for the meteorological observation station at the mountain and
island area
The independent value of the meteorological observation station given in the
appendix F (table F1 and F2) is the assumed wind pressure versus the supposed usage
time of the 5, 10, 20 and 50 year project.
Table F1 – The assumed wind pressure of several meteorological observation
stations at the mountain and island area, applied for the article 6.4.3
Wind pressure versus the repetitive cycle, da N/m2 The
meteorological
observation
stations
5 years 10 years 20years 50 years
1. An Khe
2. Bac Can
3. Bac Son
4. Bao Loc
5. Chiem Hoa
6. Con Cuong
7. Da Lat
8. Dac Nong
9. Ha Giang
10. Hoa Binh
11. Hoi Xuan
12. Huong Khe
13. Kon Tum
14 .Lac Son
15. Luc Ngan
16. Luc Yen
17. M’Drac
18. PlayKu
19. Phu Ho
20. Sinh Ho
21. Tua Chua
22. Than Uyen
23. That Khe
24 Tuyen Hoa
25.Tuong Duong
26. Yen Bai
59
67
49
45
60
42
47
48
58
55
57
58
40
59
70
65
70
61
60
64
41
62
60
62
52
58
69
78
57
52
70
47
53
54
68
65
66
67
46
69
83
76
81
70
69
75
47
73
73
72
61
68
80
90
65
59
81
54
60
60
79
74
76
77
53
79
97
88
93
79
79
87
53
85
87
83
71
77
95
107
76
69
97
63
70
69
94
88
91
91
61
96
117
104
109
93
92
404
62
102
107
98
86
91
VIETNAM STANDARD TCVN 2737:1995
344
Table F2 – The assumed wind pressure of the meteorological observation
stations at the island area, applied for the article 6.4.3
Wind pressure versus the repetitive cycle, da N/m2 The meteorological
observation stations 5 years 10 years 20 years 50 years
1. Bach Long Vi
2. Co To
3. Con Co
4. Con Son
5. Hon Dau
6. Hon Ngu
7. Hoang Sa
8. Phu Quoc
9. Phu Quy
10.Truong Sa
147
130
95
81
131
94
86
103
83
103
173
153
114
94
154
110
102
123
97
119
201
177
135
108
178
128
120
145
110
136
241
213
165
128
214
153
145
175
130
160
VIETNAM STANDARD TCVN 2737:1995
345
Appendix G
The determination method of standard mark to define
the height of the house and project.
When we determine the coefficient k as the table 5, if the ground surrounding the
house and project is not flat, the standard mark for calculation of height z is
defined as follow:
G.1 When the ground has an incline which is small comparing with the horizontal
direction i ≤ 0.3, the height z is defined from the ground at where the house and
project is placed to the defined position.
G.2 When the ground with an incline (0.3 ≤ i ≤ 2), the height z is defined from the
stipulated height-ground Zo which is lower than the real ground to the defined
position.
The stipulated height-ground Zo is defined as the figure G.1
Figure G1
Left of A: Zo = Z1
In the section BC: Zo = H(2 – i)/1.7
Right of D: Zo = Z2
In the section AB and CD: Using the linear interpolation method to define Zo
G.3 When the ground with an incline (i ≥ 2), the stipulated height ground Zo for
determination of the height z which is lower than the real ground is defined as
the figure G2.
Figure G2
Left of C: Zo = Z1
Right of D: Zo = Z2
In the section CD: defining Zo by the linear interpolation method
VIETNAM STANDARD TCVN 2737:1995
346
Unit of measurement conversion
1-Multiple and Submultiple of unit system SI
Name Symbol Value Discription
Giga G 109
1,000,000,000
Mega M 106
1,000,000
Kilo k 103
1,000
Hecto h 102
100
Deca da 10 10
Deci d 10-1
0.1
Centi d 10-2
0.01
Mili m 10-3
0.001
Micro µ 10-6
0.000,001
Nano n 10-9
0.000,000,001
2- Conversion of normal unit
Quantity Name Symbol Conversion
Length
kilometer
meter
decimeter
centimeter
milimeter
km
m
dm
cm
mm
= 100m
1m = 10dm = 100cm = 1000mm
= 0.1m
= 0.01m
= 0.001
Area
Square meter
Hectare
Square meter
Square decimeter
Square centimeter
km2
ha
m2
dm2
cm2
= 1,000,000m2 = 100ha = 10,000a
= 10,000m2 = 100a
= 100dm2
= 100cm2
= 100mm2
Volume
Cubic meter
Cubic decimeter
Hectoliter
Decaliter
liter
m3
dm3
hl
dal
l
= 1,000dm3 = 1,000,000cm
3 = 1,000 liters
= 1 liter
= 10dal = 100 liters
= 10 liters
Speed Kilometer/hour
Meter/second
Km/h
m/s = 0.278 m/s
Mass
Ton
Kilogramme
Gramme
miligramme
T
Kg
g
mg
= 10 quintals = 1000kg = 1,000,000 g
= 1,000 grammes
= 1,000 miligrammes
= 0.001 grammes
VIETNAM STANDARD TCVN 2737:1995
347
Quantity Name Symbol Discription Force
Mass x acceleration
Mega Newton
Kilometer
Newton
MN
kN
N
= 1,000,000N
= 1,000N; 1Tf = 9.81KN ≈10KN
1kgf=9.81N≈10N= 1kg.m/s2
Pressure, stress force/area Pascal
Atmosphere
Pa =1N/m2; 1kgf/cm
2=9.81.10
4N/m
2
≈0.1MN/m2; 1kgf/m
2=9.81N/m
2
= 9.81Pa
≈ 10N/m2 = 1daN/m
2
= 1kgf/cm2 = 10Tf/m
2 =1 10 meter
water column with horizontal area
(1.2meter) at 4oC
Weight of volume 1kgf/m3 = 9.81N/m
3 ≈ 10N/m
3
1Tf/m3 = 9.81KN/m
3 ≈ 10KN/m
3
Temperature
Kelvin degree
Celcius degree
oK
oC
= 273.15oK
Power, work, calory Megajoule
Kilojoule
Juie
Milijoule
kilocalory
MJ
kJ
J
mJ
Kcal
= 1,000,000J
= 1,000J = 0.239 Kcal
= 1Nm
= 0.001J
= 427kgm = 1.1636Wh; one
housepower/hour = 270,000kgm =
632Kcal
Power capacity/time Megawatt
Kilowatt
Horsepower
Watt
miliwatt
MW
kW
hp
W
mW
= 1,000,000W
= 1,000W = 1,000J/s = 1.36hp
= 0.239 Kcal/s
= 0.745kW
= 1 J/s
= 0.001W
Frequency(cycle/second) hec Hz = 1s-1
3 – Conversion of British unit system into SI system: Quantity Name Symbol Conversion
Length
Mile
Yard
Foot
Inch
Mile
yd
ft
in
= 1,609m
= 0.9144m
= 0.3048m
= 2.54cm
Area
Square mile
Acre
Square yard
Square foot
Sq.mile
ac
sq.yd
sq.ft
= 259 ha = 2,590,000m2
= 4,047m2
= 0.836m2
= 0.0929m2
Volume
Cubic yard
Cubic foot
Cubic inch
cu.yd
cu.ft
cu.in
= 0.7646m3
= 28.32dm3
= 16.387cm3
Mass
Long ton
Short ton
Pound
Ounce
tn.lg
tn.sh
lb
oz
= 1,016kg
= 907.2kg
= 0.454kg
= 28.350g
VIETNAM STANDARD TCVN 2737:1995
348