Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications...

11
Cast Resin Transformers 08B1-E-0004a

Transcript of Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications...

Page 1: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

Cast Resin Transformers

08B1-E-0004aInternet address : http://www.fujielectric.co.jpInformation in this catalog is subject to change without notice.

Printed on recycled paper

2013-10(J2013a/J2012)KO-H/CTP7M Printed in Japan

Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, JapanPhone : (03)5435-7111

1557 Hangnan Rd., Nanqiao Fengxian, Shanghai, THE PEOPLE’S REPUBLIC OF CHINAPhone : Tel +86-21-5718-7705

Page 2: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

Exported areas in percentage

●Maximum rating Three-phase 500 kVA Three-phase 500 kVA

Total loss comparison

Oil immersed transformer

Cast resin transformer

Mass, volume and space comparison

Oil immersedtransformer

Cast resintransformerMass

VolumeInstallation space

100%100%100%

65%48%39%

82%

100%

1 2

•Climatic class: C2•Environmental class: E2•Fire behavior class: F1

Fuji Electric Corporation has two cast resin transformer production bases:Chiba works in Japan, and Shanghai Fuji Electric Transformer Co., Ltd. in China.

1. Introduction ------------------------------------------------------12. Advantages of Cast Resin Transformer ------------------23. Features of Product--------------------------------------------34. Design Techniques --------------------------------------------55. Production Facilities -------------------------------------------66. Tests and Inspections -----------------------------------------67. Applications -----------------------------------------------------7

8. Standard Specifications ---------------------------------------99. 11 kV Series for IEC------------------------------------------10

10. 20 kV Series for IEC------------------------------------------1211. 22 kV Series for IEC------------------------------------------1412. Accessories -----------------------------------------------------1613. Inquiry Specification Sheet ---------------------------------17

Fuji Electric’s cast resin transformer works in Chiba was established in 1974, which became the first cast resin transformer works in Japan. Chiba works has produced over 90,000 cast resin transformers of which 3,000 units were exported to 55 countries all over the world.

Since the beginning of operation in 1998, Shanghai Fuji Electric Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers.

C O N T E N T S

Chiba works Shanghai Fuji Electric Transformer Co.,Ltd.

Epoxy resin is safe against fire since it has self-extinguishing properties and is fire resistant.Our cast resin transformer passed the all tests of IEC 60076-11 in 2006.

A sheet coil and wound core construction minimize total loss remarkably, thus reducing the electricity charges and saving energy.

Cast resin transformer is made smaller and lighter comparing with oil-immersed transformer. Thus it can be installed in slim type cubicle, which minimizes the installation space.

No insulation oil is required, so maintenance and inspection are easy.

42

Far EastAsiaNorth America

26

75 2 11

16

Primary voltage: 36 kV

Rated capacity: 24,000 kVA

Start of fire-test After test (completely extinguishing)

Works

Production records

IntroductionIntroduction Advantages of Cast Resin TransformerAdvantages of Cast Resin Transformer

Fire resistant

Energy saving effects Compact and light

Easy maintenance

OceaniaLatin America

AfricaMiddle Near EastEurope

Page 3: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

1.0

L

L

1 2 3

CS

CS: Series capacitance

CE

CE: Earth capacitance

123456789

242322212019181716151413

121110

1.64

3 4

Cast resin transformer is manufactured with vacuum casting method using metal pattern, its resin layer is thick and the surface is smooth. Thus it has following excellent characteristics.

(1) Weight reduction The aluminum winding weights approximately one half of the   copper winding.

Vacuum-casting method realizes highly reliable, voidless molded winding with excellent partial discharge characteristics.

Void-less

All winding conductors are molded. They have remarkable humidity resistance which prevents insulation materials from deteriorating due to dust and dirt during operation.

Resistance to humidity and dust

Molded winging is highly resistant to secondary short-circuit fault and surface cracking.

Robust construction

Vacuum-casting process is carried out automatically with advanced customized facilities, to manufacture highly reliable molded winging.

High reliability

Molded insulated parts are fire resistant since they have self- extinguishing properties.

Fire prevention

1. Vacuum-casting2. Aluminum winding3. Sheet-winding4. Partial discharge free5. Various product lineups6. Swift delivery

Standard typeHigh efficiency typeLow-noise typeFor rectifier

High vacuum conditionResin mold mouth

Inner pattern

Epoxy resin

Windings

Outer pattern

Cross section of molded winding(Arrangement of sheet winding)

Each part of aluminum sheet winding is sufficiently molded

Condition of molding epoxy resin

(3) Downsizing Sheet winding has high lamination factor.

(5) Surge stability Sheet winding is effective to reduce potential oscillation caused by surge voltage.

(4) High insulation reliability In case of sheet winding, the voltage between turns is only for one turn.

(2) Large mechanical strengthAluminum’s thermal expansion coefficient is close to resin, thus reducing thermal stress effectively.

Conductivity [%]Cross sectional area ratio

Gravity [g/cm3]Gravity ratio

Mass ratio

Copper : Aluminum

100 : 61 1 : 1.64

8.9 : 2.7 3.3 : 1

100 : 50

Material

Aluminum

Copper

Epoxy resin

Thermal expansion coefficient [mm/mm.h.℃]

2.3 x 10-5

1.6 x 10-5

3.3 x 10-5

Copper > Aluminum

Thermal stress acting

Aluminum sheet winding

Thermal stress acting on winding

Potential distribution Cylindrical winding

Sheet winding

Transformer winding

Surge voltage

Earth

Epoxy resin

Sheet winding Cylindrical winding

Sheet windingCylindrical winding

Company standard: ● All units are subject to partial discharge test. ● Applied voltage is twice the operating voltage.

● Partial discharge is less than 10 pC.

Aluminum winding

Sheet winding

Vacuum-casting

Features of ProductFeatures of Product

Partial discharge freeWe have developed the materials, structures and manufacturing systems that realize excellent partial discharge characteristics.From the viewpoint of cast resin transformer’s reliability, the excellent partial discharge characteristics is the most important. Thus we have adopted the following stricter standard than any other standards.

Comparison of the weight in the same resistance

Page 4: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

5 6

The insulation of cast resin transformer is composed of resin-air composite insulation.The distributed voltages of individual transformer parts depend on their respective dimensions.Thus, appropriate dimensions for insulation are designed with electric field analysis of the individual parts of the winding including air space.

Molded winding composed of conductor and insulating material (e.g regin) is subjected to thermal stresses due to the difference in the thermal expansion coefficient between conductor and resin, and the thermal distribution in the winding block, where the winding temperature varies with the load fluctuation of the transformer.The stress value obtained in thermal stress analysis is used to design optimum winding structure for high crack-resistance of winding.

a) Routine tests: ・Measurement of insulation resistance ・Measurement of winding resistance ・Measurement of voltage ratio and check of phase displacement ・Measurement of short-circuit impedance and load loss ・Measurement of no-load loss and current ・Separate-source AC withstand voltage test ・Induced AC withstand voltage test ・Partial discharge measurement

b) Type tests: ・Lightning impulse test ・Temperature-rise test ・Measurement of sound level

ISO9001Original registration: 23nd August 1994Registration date: 23nd August 2009

ISO14001Original registration: 24th March 1996Registration date: 24th March 2007

ISO certifications of Chiba works

Vacuum-casting plant High voltage foil winding machine

Core cutting machine Partial discharge measurement

Electric field analysis

The test items:

Design TechniquesDesign Techniques Production FacilitiesProduction FacilitiesTests and InspectionsTests and Inspections

Thermal stress analysis

ISO certification of Shanghai FujiElectric Transformer Co., Ltd.

Page 5: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

7 8

● Multistory buildings● Hospitals● Hotels● Laboratories● Shopping centers● Building complexes● Schools● Art galleries● Theaters● Underground shopping centers● Petrochemical plants● Industrial complexes● Underground railways● Railway substations● Tunnels● Cranes● Water and sewerage plants● Power supply for construction sites● Ships● Refuse disposal plants● Wind power sites

Sites where there are airborne contaminants and extremely severe environments (Chemicals, steels, automobiles, underground construction sites etc.)

Sites where compact size and light weight are required(Urban multistory buildings, etc.)

Sites where high reliability is required (Public facilities, etc.)

Sites where fire prevention is the highest priority(Stadiums, hospitals, underground shopping centers, hotels, etc.)

The exterior appearance of transformer (17000 kVA, 22/6.6 kV)

Sites where easy maintenance is required (Power stations, industrial complexes, buildings, underground railways, etc.)

Transformer cubicle for substation in building(5000 kVA)

Sites where high reliability and easy maintenance are required (Public facilities such as museums, airports, etc.)

The exterior appearance of transformer(2700 kVA, 33/0.59 kV)

Wind power site

ApplicationsApplications

Page 6: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

o a b c

1520

31.5

φ13

t3.5

Fig.1 Fig.2

1520

40

φ13

t8

2040

40

25

2-φ13

t8

Fig.3

4080

100

2040

25

4-φ14

t8

Fig.410050 25

5030

4-φ18

t8

Fig.5

50100

50100

2550

30

8-φ18

t8

Fig.6

50

M8

φ25

60° Lifting lug

Primary taps

Neutral terminal, Secondary terminalsNameplate

Primary terminals

Fans

Install hole

Grounding terminals

XSY

YSX

Z

109

※: Contact us for any other requests.

Standard

Normal servicecondition

Altitude [m]

Number of phases

Frequency [Hz]

Highest voltage [kV]

Separate-source voltage withstand

Lightning impulseinsulation class

Insulation class

Insulation system temp. [℃]

Average temp. rise limit [K]

Rated capacity [kVA]

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]

Connection symbolInsulation classInsulationlevels[kV]

IEC 60076-11: 2004

40

30/day, 20/year

−25 (Outdoor), −5 (Indoor)

Not more than 1000

3

50, 60

12

28

75

F

155

100

30

50

80

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

2500

3150

4000

5000

6300

8000

10000

12500

16000

20000

IEEE Std C57.12.01-1998

40

30/day

−30

Not more than 1000

3

60

15

31(34, 37)

60(95, 110)

150

90

15

30

45

75

112.5

150

225

300

500

750

1000

1500

2000

2500

3750

5000

7500

10000

12500

15000

20000

Highest [℃]

Average [℃]

Lowest [℃]

Standard [kV](Option)

Standard [kV](Option)

24

50

95(125)

36

70

145(170)

25

37(40, 50)

110(125, 150)

34.5

50(70)

150(200)

Rated capacity [kVA]

300 400 500 630 80010001250160020002500

Rated capacity [kVA]

300 400 500 630 80010001250160020002500

Total mass [kg]

1080130016001800210025002800350042005100

Dimensions [mm]X1190126815001600167016901740184020502050

No-load loss [W]

880110012001300150018002000250032003900

No-load current [%]

0.70.70.50.50.50.50.50.50.50.5

Impedance voltage [%]

3.6~4.4

5.4~6.6

Load loss [W]

3600 4200 5000 6400 7600 8900 9900117001560017000

IEC 60076-11: 2004

350F10.50-F10.25-R10.00-F9.75-F9.500.430, 50, 80, 100,125, 160, 200, 250,315, 400, 500Yyn0 (Dyn11)F28375

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Y 920 920 920 920 920 920 920117011701170

Z1239129913791400145016541700185419002010

XS 660 660 820 820 820 820 820107010701070

YS 840 820 820 820 820 820 820107010701070

Hole[φ]

15

20

TerminalsPFig-1

Fig-2

SFig-3

Fig-4

Fig-5

Fig-6

630, 800, 1000,1250,1600, 2000, 2500Dyn11 (Yyn0)

Standard specifications

Standard SpecificationsStandard Specifications 11 kV Serries for IEC11 kV Serries for IEC

Technical data

Dimensions and masses (without protection enclosure)

Page 7: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

ZR Z

X

1520

31.5

φ13

t3.5

Fig.1 Fig.2

1520

40

φ13

t8

2040

40

25

2-φ13

t8

Fig.3

4080

100

2040

25

4-φ14

t8

Fig.4

10050 25

5030

4-φ18

t8

Fig.5

50100

50100

2550

30

8-φ18

t8

Fig.6

50

M8

φ25

View window

Nameplate

Primary taps

ThermometerLifting lug (for intergral lifting)Nameplate

Primary terminals

Fans

Install hole

Neutral terminalSecondary terminals

Grounding terminalsEnclosure

Primary input hole

Secondary output hole

60°

XSYYS

B CA

cbao

YSY

XS

Z

X

Fig.1 Fig.2 Fig.3 Fig.4 Fig.5

20

2025 40

4080

501004060

25

2040

25

2550

30

50 50100

50100

2550

30

M8

2-φ13φ13 4-φ14 4-φ18 8-φ18 φ25

t6 t8 t8 t8 2-t8

60°o a b c

Neutral terminal

Lifting lug (for integral lifting)

Neutral terminalSecondary terminals

Nameplate

Primary terminals

Fans

Install hole

Grounding terminals

12

Technical data

20 kV Series for IEC20 kV Series for IEC

Standard specifications

Dimensions and masses (Without protection enclosure)

Rated capacity [kVA]

300 500 8001000150020002500

No-load loss [W]

1200140019002100300035004300

No-load current [%]

0.70.5

Impedance voltage [%]

5.4~6.6

7.2~8.8

Load loss [W]

3700 6600 860010300123001760020300

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]Connection symbolInsulation classInsulationlevels[kV]

IEC 60076-11: 2004

350F21.0-F20.5-R20.0-F19.5-F19.00.4315-2500Dyn11F503125

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Rated capacity [kVA]

300 500 8001000150020002500

Total mass [kg]

1500180024002800410051006500

Dimensions [mm]X1600160017001800200021002200

Y 920 920 9201100117011701170

Z1600165018001850210022002300

XS 820 820 820 820107010701070

YS 820 820 8201000107010701070

Hole[φ]

20

TerminalsPFig-1

SFig-2Fig-3

Fig-4Fig-5

11

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]

Connection symbolInsulation classInsulationlevels[kV]

Rated capacity [kVA]

300 400 500 630 80010001250160020002500

Rated capacity [kVA]

300 400 500 630 80010001250160020002500

Total mass [kg]

1400160020002200250030003300400049005800

Dimensions [mm]X1450190019001900200020002000220025002500

No-load loss [W]

880110012001300150018002000250032003900

No-load current [%]

0.70.70.50.50.50.50.50.50.50.5

Impedance voltage [%]

3.6~4.4

5.4~6.6

Load loss [W]

3600 4200 5000 6400 7600 8900 9900117001560017000

IEC 60076-11: 2004

350F10.50-F10.25-R10.00-F9.75-F9.500.430, 50, 80, 100,125, 160, 200, 250,315, 400, 500Yyn0 (Dyn11)F28375

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Y1250125012501250130013001300160016001600

Z1450220022002200220022002200220022002450

ZR1505225522552255225522552255225522552505

XS 660 660 820 820 820 820 820107010701070

YS1130113011301130118011801180148014801480

Hole[φ]

22

TerminalsPFig-1

Fig-2

SFig-3

Fig-4

Fig-5

Fig-6

630, 800, 1000,1250,1600, 2000, 2500Dyn11 (Yyn0)

Standard specifications

11 kV Serries for IEC11 kV Serries for IEC

Technical data

Dimensions and masses (with protection enclosure)

Page 8: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

cbao

A B C

YSY

Fig.1 Fig.2 Fig.3

Fig.4 Fig.5

20

2025 40

4080

50100

4060

25

2040

25

2550

30

50 50100

50100

2550

30

M8

2-φ13φ13 4-φ14

4-φ18 8-φ18 φ25

t6 t8 t8

t8 2-t8

60°

View windowThermometer

Lifting lug (for integral lifting)Nameplate

Primary terminals

Fans

Install hole

Grounding terminalsEnclosure

Neutral terminalSecondary terminals

Primary taps

Secondary input hole

View window

Primary output hole

Nameplate

XS

ZR Z

X

Lifting lug(for integral lifting)

Neutral terminal

Neutral terminalSecondary terminals

Nameplate

Primary terminals

Fans

Install hole

Grounding terminals

cbao

X

Z

60°

XSY

YS

Fig.1 Fig.2 Fig.3 Fig.4 Fig.5

20

2025 40

4080

501004060

25

2040

25

2550

30

50 50100

50100

2550

30

M8

2-φ13φ13 4-φ14 4-φ18 8-φ18 φ25

t6 t8 t8 t8 2-t8

14

Technical data

22 kV Series for IEC22 kV Series for IEC

Standard specifications

Dimensions and masses (Without protection enclosure)

Rated capacity [kVA]

300 500 8001000150020002500

No-load loss [W]

1200140019002100300035004300

No-load current [%]

0.70.5

Impedance voltage [%]

5.4~6.6

7.2~8.8

Load loss [W]

3600 6300 830010000120001720020200

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]Connection symbolInsulation classInsulationlevels[kV]

IEC 60076-11: 2004

350F21.0-F20.5-R20.0-F19.5-F19.00.4315-2500Dyn11F503125

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Rated capacity [kVA]

300 500 8001000150020002500

Total mass [kg]

1500180024002800410051006500

Dimensions [mm]X1600160017001800200021002200

Y 920 920 9201100117011701170

Z1600165018001850210022002300

XS 820 820 820 820107010701070

YS 820 820 8201000107010701070

Hole[φ]

20

TerminalsPFig-1

SFig-2Fig-3

Fig-4Fig-5

Technical data

20 kV Series for IEC20 kV Series for IEC

Standard specifications

Dimensions and masses (With protection enclosure)

Rated capacity [kVA]

300 500 8001000150020002500

No-load loss [W]

1200140019002100300035004300

No-load current [%]

0.70.5

Impedance voltage [%]

5.4~6.6

7.2~8.8

Load loss [W]

3700 6600 860010300123001760020300

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]Connection symbolInsulation classInsulationlevels[kV]

IEC 60076-11: 2004

350F21.0-F20.5-R20.0-F19.5-F19.00.4315-2500Dyn11F503125

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Rated capacity [kVA]

300 500 8001000150020002500

Total mass [kg]

2000230024003300480058007200

Dimensions [mm]X1900190021002100240025002600

Y1500150018001800190019002000

Z2200220022002200240025002600

ZR2255225522552255245525552655

XS 820 820 820 820107010701070

YS1380138016801680178017801880

Hole[φ]

22

TerminalsPFig-1

SFig-2Fig-3

Fig-4Fig-5

13

Page 9: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

Fig.1 Fig.2 Fig.3

Fig.4 Fig.5

20

2025 40

4080

50100

4060

25

2040

25

2550

30

50 50100

50100

2550

30

M8

2-φ13φ13 4-φ14

4-φ18 8-φ18 φ25

t6 t8 t8

t8 2-t8

YYS

CBA

o a b

ZZR

60°

c

XXS

Nameplate

Primary taps

View window

Thermometer

Grounding terminals

View window

Primary output hole

Lifting lug (for integral lifting)Nameplate

Primary terminals

Fans

Install hole

Neutral terminalSecondary terminals

Secondary output hole

Secondary input hole

16

Technical data

22 kV Series for IEC22 kV Series for IEC

Standard specificationsRated capacity [kVA]

300 500 8001000150020002500

No-load loss [W]

1200140019002100300035004300

No-load current [%]

0.70.5

Impedance voltage [%]

5.4~6.6

7.2~8.8

Load loss [W]

3600 6300 830010000120001720020200

Standard

Number of phasesFrequency [Hz]Rated primary voltage and tap voltage [kV]Rated secondary voltage [kV]Rated capacity [kVA]Connection symbolInsulation classInsulationlevels[kV]

IEC 60076-11: 2004

350F21.0-F20.5-R20.0-F19.5-F19.00.4315-2500Dyn11F503125

Separate-source Primaryvoltage withstand SecondaryLightning impulse Primary

Dimensions and masses (With protection enclosure)Rated capacity [kVA]

300 500 8001000150020002500

Total mass [kg]

2000230024003300480058007200

Dimensions [mm]X1900190021002100240025002600

Y1500150018001800190019002000

Z2200220022002200240025002600

ZR2255225522552255245525552655

XS 820 820 820 820107010701070

YS1380138016801680178017801880

Hole[φ]

22

TerminalsPFig-1

SFig-2Fig-3Fig-4

Fig-5

15

Nameplate The nameplate is easy to read with white letters on

a black background.

No-voltage tap changing terminals The tap voltage can be changed by switching the shorting bar connector.

Lifting lugs Four lifting lugs are provided as standard fixtures on the transformer body.

Protection enclosure An optional simplified protective enclosure can be installed.

Thermometer An optional Thermometer can be installed.

Earthing terminals with clamping bolts Two ground terminals are provided at the lower

frame ends: one on the primary side and one on the secondary side. (One of these ground terminals is in use.)

Warning label A danger label is attached to warn against contacting the surface of the high-potential winding.

AccessoriesAccessories

Page 10: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

Your Ref. No. : Date :

To. : Shanghai Fuji Electric Transformer Co., Ltd

Attn :

mail :

Tel. : (English, Chinese, Japanese)

Client requesting a quote

company name :

person in charge

e-mail :

Tel. : +

Request for Quotation (Cast Resin Transformer)This request for quotation consists of followings ;Item A. General SpecificationItem B. Technical Specification (If there are several type/specifications of cast resin transformers, Please add the sheets B)

17 18

A. General Specification

A.1.0 User information

A.1.1 Project Name

A.1.2 Name of end user

Country

A.1.3 Name of Distributor/SIer/General Contractor (if any)

Country

A.1.4 Name of competitors (if any)

A.1.5 Application Area (if any)

(will be selected one or more for

market survey and analysis.)

A.1.6 Purpose to use (if any)

(will be selected one or more for

market survey and analysis.)

A.2.0 Delivery & Transportation

A.2.1 Required delivery time(FOB Shanghai)

A.2.2 Trade Terms

as per "Incoterms 2012"

A.2.3 Transportation & Packing

A.3.0 Warranty Period

A.4.0 Currency:

A.5.0 Payment Terms

A.6.0 Validity

□ Utilities/Public Works □ Chemicals

□ Office Buildings □ Wind power plants

□ Shopping malls □ Solar Power

□ Colleges and universities □ Automotive

□ Hospitals/medical center □ Glass industry

□ Telecommunications □ Paper industry

□ Data center □ Mining industry

□ Banks □ Application with rectifiers

□ Railways & Metroway □ Variable speed drives

□ Airports □ Marine/Ships/off-shore

□ Steel & Iron □ Port/Industrial cranes

□ Oil & Gas □ Other

□ Fire-risk areas □ Environmentally sensitive areas

□ Urban substation □ Nearly maintenance free

□ Indoor and underground substations □ Other

Day Month Year

○ FOB Shanghai

○ Other

○ For export (By sea)

○ Other

18 months from the date of shipment from Shanghai port or 12 months from the date of

starting commercial operation, whichever comes earlier

US$

100% by T.T. remittance within 30 days after shipment of equipment with final drawings and

factory test report.

30 days

B. Technical Specification

Items

1.0 Number of units (Q'ty)

2.0 Rated voltage Primary [V]

Secondary [V]

3.0 Rated capacity [KVA]

4.0 Number of phases

5.0 Vector group (*)

(Dyn11 or Yyn0 will be checked.

Others will be specified.) Other

6.0 Impedance voltage[%] Manufacturer Standard

Other

7.0 K-Rating (if any)

8.0 Cooling method (**)

2.0 Insulation class Manufacturer Standard

Other

9.0 Standards

10.0 Ambient temperature

11.0 Altitude

12.0 Frequency

13.0 Tapping range of primary voltage

14.0 Overload

Tr-1 Tr-2 Tr-3 Tr-4 Tr-5

○ Dyn11 ○ Dyn11 ○ Dyn11 ○ Dyn11 ○ Dyn11

○ Yyn0 ○ Yyn0 ○ Yyn01 ○ Yyn0 ○ Yyn0

○ ○ ○ ○ ○

○ ○ ○ ○ ○

○      % ○      % ○      % ○      % ○      %

○ AN ○ AN ○ AN ○ AN ○ AN

○ AF ○ AF ○ AF ○ AF ○ AF

○ ANAF ○ ANAF ○ ANAF ○ ANAF ○ ANAF

○ F ○ F ○ F ○ F ○ F

○ ○ ○ ○ ○

○ IEC60076-11 ○ Other

○ Standard -5~40℃ ○ Other

○ Standard 0~1000m ○ Other

○ 50Hz ○ 60Hz ○ Other

○ ±2.5%×2 (Manufacturer Standard) ○ Other

○ Continuous 100% ○ 120%, 1min ○ Other

20.0 Optional accessories

20.1 Thermometer

20.2 Cooling fan

20.3 Wheels

20.4 Resistance thermometer bulb(Pt 100Ω)

20.5 Anti-vibration pads

20.6 Protection enclosure

if Yes, Degree of Protection will be selected

if Yes, cable entry will be selected

30.0 Special test

30.1 Temperature rise test

30.2 Lightning impulse test

30.3 Measurement of sound level

30.4 Witness testl

40.0 Other request item

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

□ IP20 □ IP23 □ Other

□ Buttom Cable □ Top Cable □ Bus Duct

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

○ No ○ Yes

Inquiry Specification Sheet for Cast Resin TransformerInquiry Specification Sheet for Cast Resin Transformer

<Option>

Remarks) (*) Dyn11=Δ(Delta)/Y(Star) with the neutral brought out. Yyn0=Y(Star)/Y(Star) with the neutral brought out. (**) AN; Naturally-air-cooled type AF; Forced-air-cooled type with cooling fan ANAF; Naturally-air-cooled/Forced-air-cooled type with cooling fan ANAF; Naturally-air-cooled/Forced-air-cooled type with cooling fan

Page 11: Cast Resin Transformers - Fujielectric€¦ · Transformer has been awarded various certifications including ISO 9001 and has produced over 10,000 cast resin transformers. C21TE1TS

Cast Resin Transformers

08B1-E-0004aInternet address : http://www.fujielectric.co.jpInformation in this catalog is subject to change without notice.

Printed on recycled paper

2013-10(J2013a/J2012)KO-H/CTP7M Printed in Japan

Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, JapanPhone : (03)5435-7111

1557 Hangnan Rd., Nanqiao Fengxian, Shanghai, THE PEOPLE’S REPUBLIC OF CHINAPhone : Tel +86-21-5718-7705