Capcitance Switching With Vacuum Circuit Breaker

9
Technical collection H. Schellekens 2008 - Conferences publications Capacitor Bank Switching with Vacuum Circuit Breakers

description

Type Test Procedure for Vacuum Circuit Breaker

Transcript of Capcitance Switching With Vacuum Circuit Breaker

Page 1: Capcitance Switching With Vacuum Circuit Breaker

Technical collection

H. Schellekens

2008 - Conferences publications

Capacitor Bank Switching with

Vacuum Circuit Breakers

Page 2: Capcitance Switching With Vacuum Circuit Breaker

2008 China International Conference on Electricity Distribution (CICED 2008) 1

Capacitor Bank Switching with Vacuum Circuit Breakers

Hans Schellekens

Schneider Electric, Power SBU, Medium Voltage Development, Usine 38V, ZAC Champ Saint-Ange, Varces, France

Abstract: After interruption of a capacitive current sometimes Non Sustained Disruptive Discharges (NSDDs) are observed when

using vacuum circuit breakers. According to network calculations, NSDDs generate significant over-voltage on the terminal of the

capacitor bank to ground and across the circuit breaker (CB) terminals. In a full scale experiment at 12kV on an 8Mvar capacitor

bank artificial NSDDs are produced using a Triggered Vacuum Gap. The over-voltage depends on the momentary voltage

difference across the breaker and, hence, varies with the phase angle. The over-voltage on the terminal of the capacitor bank to

ground varies from 1.5 to 4.2 pu, and to maximum 5.2 pu. across the CB terminals. The effectiveness of surge arrestors on the

limitation of the over-voltages is measured. The over-voltages are limited to 2.2 pu. on the terminals of the capacitor bank to

ground and 3.2 pu. across the CB terminals. A single surge arrestor on the neutral point of the capacitor bank yields the same level

of protection and, therefore, is a cost effective alternative. An application guide for switchgear and arrestors is presented.

1. INTRODUCTION

The capacitive current switching duty is characterised

by frequent, day to day or hour by hour, switching of low to

moderate currents in industrial or public networks, and by a

low rate of rise of recovery voltage. Modern circuit breakers

(CB’s) which claim a long mechanical but also electrical life

without maintenance seem to be best adapted to this

switching duty [1,2,3]. Yet the behaviour of vacuum CB’s is

rather different from that of gas CB’s.

Today, the circuit breaker envisioned for capacitor bank

switching is either a vacuum or SF6 circuit breaker or a

vacuum or SF6 contactor. All these devices are known for

their long service life. The circuit breaker offers a protection

against short circuit currents with an electrical life between

10.000 and 30.000 operations at nominal current. Contactors

offer an electrical life up to 1 million operations depending on

load conditions. SF6 CB’s, in the past referred to as “restrike

free” breakers, are according to the new IEC62271-100 class

C2 breakers with proven “very low restrike probability” [4].

Field experience indicates that the restrike probability even

for the electrically very stressed 36 kV networks is lower than

1/50.000.

For vacuum CB’s, the physical processes during the

capacitive switching duty have been studied by [5]. They

found that the pre-ignition at contact closing and the

subsequent inrush current heavily eroded the contacts leading

to detached particles. These particles cause late breakdowns

which appear as NSDDs1. Breakdown frequencies of typically

3/1000 where found under the experimental conditions

studied. The probability of breakdown depends on the

dielectric conception or contact stroke of the vacuum

interrupter. So for the same voltage rating different designs

lead to different probabilities of occurrence of NSDD. Fig. 1

shows the experimentally found relation between dielectric

conception, based on contact gap, and the probability of a

NSDD during an operation. It shows that a minimum contact

distance of 16 mm is necessary to reduce this probability

below 1/500.

The overvoltage produced by a NSDD differs notably

from the overvoltage produced by a restrike. A restrike can

generate an overvoltage of 3 pu. between the terminals of

the capacitor bank, whereas a NSDD causes a sudden voltage

shift of the neutral capacitor bank voltage, which leaves the

voltage across the capacitor unchanged, but creates an

overvoltage between 1.5 and 5 pu. on the terminal of

capacitor bank to ground and between 2.5 and 6 pu. across the

CB terminals. Due to this high overvoltage a second NSDD in

the adjacent phases becomes more likely.

When two NSDDs occur simultaneously, the

phenomenon turns into a restrike. Typically, a vacuum CB

with a contact gap of about 16 mm has a probability of about

1 NSDD or non-sustained disruptive discharge [7] is a disruptive discharge associated with current interruption that does not result in the resumption of power frequency current or, in the case of capacitive current interruption does not result in current in the main load circuit.

Schneider Electric 2008 - Conferences publications

Page 3: Capcitance Switching With Vacuum Circuit Breaker

2 2008 China International Conference on Electricity Distribution (CICED 2008))

1/500 for producing a NSDD and belongs to the class C2 with

proven “very low restrike probability”.

Fig.1 : Experimentally found dependence between probability of a

NSDD and nominal contact stroke of vacuum interrupter.

Due to the rare occurrence and the random nature of the

phenomenon, the relation between NSDD and overvoltage is

not evident. Therefore in this paper this question is addressed

in section II using a numerical network simulation. By this

the worst case overvoltage for different voltage levels is

determined. Then in section III an experiment designed to

verify the simulation results is shown. Here the NSDD is

created artificially, which permits to measure the influence of

phase angle and network parameters. A good understanding of

the origin of the overvoltage enables the definition of

protective measures adapted to the switchgear and capacitor

bank. In section IV protection schemes based on surge

arrestors are tested and compared on their effectiveness.

Finally in section V the results are discussed and an

application guideline is presented for the choice of switchgear

and arrestor.

2. ORIGIN OF OVERVOLTAGES

2.1 Numerical simulation The simplified electrical circuit, Fig. 2, will be used

here to simulate the phenomena associated with a NSDD; the

NSDD is simulated as a temporary loss of dielectric strength

in the vacuum interrupter of a vacuum CB.

Fig. 2 : Electric circuit used to calculate overvoltage on capacitor

bank during a NSDD. TVG see section III.

The source side of the network is represented by:

- a generator with a driving voltage of U

- a short circuit impedance of value Ls

- a TRV network as defined by IEC for short circuit

conditions

- a capacitor Cp to account for parallel feeders

The load side of the network is represented by:

- a 8Mvar capacitor bank with floating neutral

- single phase cables between CB and the bank.

The load and the source side of the network are

connected to each other by the CB. The CB is treated as an

ideal breaker with a NSDD some time after current

interruption. The moment of NSDD has been chosen in order

to create the worst possible case. The CB is allowed to

recover immediately at the first occurring current zero. At a

NSDD, on the R phase for the case illustrated by Fig. 2, the

voltage across the breaker moves as a travelling wave through

the line impedance towards the capacitor bank. The capacitor

bank being a high frequency short circuit allows the wave to

pass on to the neutral point of the bank. At the neutral point

the wave splits itself and continues its propagation in the

neighbouring phases towards the healthy CB poles. These

healthy poles are in fact open terminals for the incoming

wave causing it to reflect by doubling the voltage. After

reflection the wave travels back to the failing CB pole. Here it

creates a current zero passage on which the breaker can

interrupt. The frequency of this current is typically of the

order of 100 kHz for cable connected capacitor banks. Fig. 3

shows the voltage swing on the bank terminals with respect to

ground. Note that

Fig. 3 : The voltage on all 3 capacitor bank terminals during current

interruption (at 0.1s) followed by a NSDD (at 0.13s) in R phase in a

12kV network.

- For each of the three bank terminals the voltage

jumps to a new value, which means that the neutral point of

the bank attains also a different value.

- The voltage difference between terminals remains

Schneider Electric 2008 - Conferences publications

Page 4: Capcitance Switching With Vacuum Circuit Breaker

2008 China International Conference on Electricity Distribution (CICED 2008) 3

unchanged. The capacitors themselves are not stressed by the

breakdown.

- The maximum terminal voltage to earth attains a

high value (see table I). This is a dc voltage, so all parts of the

installation are stressed during a long period.

- The CB is stressed by the composed voltage of

network voltage and capacitor bank terminal voltage.

- The capacity of the bank itself is of no significance

for the phenomenon.

Table 1: Compilation of voltages associated with

capacitor bank switching for nominal network voltages

Um US U C-bank UVCB BIL Power

frequency

kVrms kVrms kV kV kV kVrms

12 10 47 55 75 28

24 20 93 110 125 50

36 30 140 164 170 70

2.2. Identification of zones at risk In table I the maximum possible overvoltage produced

by a NSDD is shown for three commonly used classes of

network voltages. For each voltage class column 2 gives Us

the nominal network voltage. Column 3 gives the maximum

overvoltage on the capacitor bank terminal to ground and

column 4 the maximum overvoltage across the CB terminals.

For reference the BIL and power frequency withstand

voltages of the equipment are given. For all three voltage

classes both overvoltages exceed the peak value of the power

frequency withstand voltage. For the CB the overvoltage

comes very close to the rated BIL voltage for 36 kV class

networks.

2. EXPERIMENTAL VERIFICATION

3.1 Test procedure The objective was to create in a reproducible way

NSDD type breakdowns in a capacitive current interruption

test. This allowed to minimize the number of tests to obtain

the desired NSDD. NSDDs do not occur frequently and are

therefore difficult to reproduce. A triggered vacuum gap

(TVG) parallel to the R-phase of the VCB is used to create an

artificial NSDD in a controllable way. A separate experiment

confirmed that the TVG was able to interrupt high frequency

currents of, for instance, 300A at 100kHz and 10 A at 900

kHz at the first current zero. Hence, the duration of the

“artificial” NSDD is determined by the circuit topology and

only one half cycle of high frequency current will pass

through the TVG. Numerical modelling showed that this will

lead to the highest possible overvoltage. Using the TVG

provided a measurement window with high frequency

sampling centred at the time of breakdown allowing precise

measurements to be made.

Full scale tests are performed in a direct test circuit fed

by a generator 2000 MVA at 12 kV with short circuit current

limited at 14 kA. The capacitive load was a 8 Mvar capacitor

bank; nominal current of 430 A. The detailed characteristics

of the test circuit are given in Fig. 4 and table II.

Fig. 4 : 3-phase test circuit with generator and 8 Mvar capacitor bank.

3.2 Test results Fig. 5a shows an oscillogram of a normal interruption

with NSDD. The first phase to interrupt, R, creates a dc

voltage on the capacitor bank terminal of 1.5 pu. Then 30

milliseconds after current interruption a NSDD is generated in

phase R at a maximum voltage difference across the CB. At

this moment the voltages on all C-bank terminals change

suddenly and settle to a new constant value. The highest

overvoltage is found in phase T. The instant of occurrence of

the NSDD was varied by firing the TVG at a predetermined

Schneider Electric 2008 - Conferences publications

Page 5: Capcitance Switching With Vacuum Circuit Breaker

4 2008 China International Conference on Electricity Distribution (CICED 2008))

moment to see the influence of the phase angle on the nature

and the value of the over-voltage. The waveform of the

overvoltage is a dc voltage and is the same for all tested phase

angles.

Fig.5a: Normal interruption of capacitive current followed by NSDD in R phase after 30 ms.

Fig.5b: As Fig. 5a Surge arrestor in phase T limits the overvoltage.

For each phase (R, S, T). Red : Source side voltage on CB. Green : Load side voltage on CB and capacitor bank terminal.

Blue : Current through CB. Time scale: 1ms/div.

Fig. 6a shows the measured voltage on the capacitor

bank terminal in phase T to ground after the NSDD in phase

R. Before the NSDD the voltage is about 0.89 pu. The voltage

jump is between 0.6 and 3.2 pu. leading to an over-voltage of

maximum 4.1 pu. The height of the overvoltage varies

harmonically with the phase angle.

Fig. 6a : Variation of over-voltage in phase T expressed in pu

due to instant of occurrence (phase angle) of the

NSDD in 1st phase R to interrupt.

In order to investigate whether the above condition is

the most severe one, the experiment was repeated by keeping

the first phase to clear in phase R and generating the NSDD in

phase T. The highest overvoltage is now found in phase R.

The instant of occurrence of the NSDD was varied by firing

the TVG at a predetermined moment to see the influence of

the phase angle on the nature and the value of the

over-voltage. The waveform of the overvoltage is a dc voltage

and is the same for all tested phase angles. Fig. 6b shows the

measured voltage on the capacitor bank terminal in phase R to

ground after the NSDD in phase T. Before the NSDD the

voltage is about 1.5 pu. The voltage jump is between 0 and

2.5 pu. resulting into an over-voltage of maximum 4.0 pu.

The height of the overvoltage varies harmonically with the

phase angle.

Fig. 6b : Variation of over-voltage in phase R expressed

in pu due to instant of occurrence (phase angle)

of the NSDD in 2nd phase T to interrupt.

Note that the over-voltage is the addition of the original

capacitor bank voltage after current interruption and a voltage

jump due to the NSDD. The amplitude of the voltage jump

depends on two factors :

● the voltage across the breaker at the instant of

breakdown, which varies with time or phase angle, and which

is maximum 2.5 pu. (see Fig. 5a).

● an amplitude multiplication K-factor (section IIIC)

The voltage difference at breakdown is transmitted

integrally to the neighbouring phases as predicted by the

numerical simulation. Except for a reduced amplitude factor

the behaviour found is identical to the simulation. Moreover,

the most severe overvoltage is produced by a NSDD in the

first phase to interrupt at the moment of the largest voltage

difference across the CB.

3.3 Influence of TRV circuit The influence of the TRV circuit on the high frequency

behaviour of the breakdown has been studied with the

following circuits:

Schneider Electric 2008 - Conferences publications

Page 6: Capcitance Switching With Vacuum Circuit Breaker

2008 China International Conference on Electricity Distribution (CICED 2008) 5

TRV-1 : The standard TRV circuit composed of 2

branches see Fig. 2.

TRV-2 : No TRV circuit; only stray capacitance between

Generator and CB.

TABLE III : Influence TRV circuit on peak

value of overvoltage

TRV-1 TRV-2

Voltage jump

K-theoretical

K-Immediate

K-Late

Damping time

2

1.6

1.3

16.5µs

2

1.7

1.6

13.5µs

Frequency NSDD current

Current

150 kHz

28 A

28 kHz

6 A

Results are shown in table III. The voltage jump after

breakdown can be characterised by :

● A peak voltage immediately after the NSDD: with K

factor : K-immediate.

● A dc voltage after a transition period: K-late. The

transition is characterised by a time constant here called

“damping time”.

● The frequency of the NSDD current.

Fig. 7 shows an oscillogram of the voltage on both sides of

the CB during the NSDD for TRV-2 circuit. During the

NSDD, between 12 and 30 µsec, both voltages are identical as

an arc in the CB allows for current to pass from the source

side to the load side. Due to the small TRV capacitance, the

source side voltage collapses at 12 µsec and joins the load

side voltage. During the current flow the voltage makes an

oscillation around the driving voltage (the source voltage

before the NSDD). When this reaches a new maximum at 30

µsec the current passes through zero and interruption takes

place. After interruption, the source voltage is subject to the

Fig. 7 Zoom at voltage behaviour at NSDD in R phase with TRV-2.

Green (1) : Load side voltage on CB and capacitor bank terminal.

Red (2) : Source side voltage on CB. Time scale 10µs/div.

TRV generated by the driving voltage of the generator and the

TRV circuit. The load side voltage settles to a new dc voltage

level. Numerical simulation suggests voltage doubling with a

K-factor equal to 2. Therefore the reduced value of

K-immediate is attributed to damping of the high frequency

current at NSDD.

4. PROTECTION BY SURGE ARRESTORS

Arrestors are commonly proposed as means to protect

the capacitor bank against excessive overvoltages due to

restrikes [6]. In such a case the overvoltage rise-time is of the

order of milliseconds. Yet in case of an NSDD the

overvoltage rise-time is only several microseconds. In order

to verify the effectiveness of the surge arrestor the following

two cases are investigated.

4.1 Surge arrestors on all three phases to ground Test conditions are similar as under section IIIA but

with surge arrestors on the load side of the CB to ground. On

initiation of a NSDD in phase R, the highest overvoltage of

2.2 pu. was in phase T due to immediate limitation of the

overvoltage by the surge arrestor in phase T; the associated

oscillogram is shown in Fig. 5b. A significant current flows

through the surge arrestor: 890 A during 1 ms; representing an

energy of about 8 kJoule. This current is determined by :

1. The series impedance of two branches R and T of the

capacitor bank and the series inductance of phase R and the

resistance to ground of the generator.

2. The voltage difference across the capacitor prior to

breakdown minus the voltage of the arrestor.

Notice, that during the limitation of an overvoltage due

to a NSDD only one surge arrestor is conductive and

dissipates the energy. Due to the random nature of current

interruption the maximum overvoltage can be in any of the

three phases. Therefore, surge arrestors have to be installed on

all three phases.

4.2 Surge arrestor on neutral to ground Test conditions are similar as under section IIIA but

with a single surge arrestor on the neutral point of the

capacitor bank. If a NSDD was initiated in phase R, the

highest overvoltage of 2.1 pu. was in phase T due to

immediate limitation of the overvoltage by the surge arrestor.

A significant current flows through the surge arrestor: 575 A

during 2.5 ms; representing an energy of about 13 kJoule.

This current is determined by

1. The series impedance of one branch of the capacitor

bank, the inductance of one phase of the circuit and the

resistance to ground of the generator.

Schneider Electric 2008 - Conferences publications

Page 7: Capcitance Switching With Vacuum Circuit Breaker

6 2008 China International Conference on Electricity Distribution (CICED 2008))

2. The voltage difference across the capacitor prior to

breakdown minus the voltage of the arrestor.

The energy dissipated in the arrestor is higher than

under IV-A due to the lower COV of the arrestor. Yet here the

arrestor will function regardless the phase in which the

maximum overvoltage will occur. This limits the number of

surge arrestors to install to one.

Table IV : Choice of continuous operating voltage

of the arrestor and the resulting overvoltage protection level

depends on network operation conditions and arrestor location.

Arrestor location

Continuous Operating Voltage

Overvoltage protection

level [pu] or Un√(2/3)

CB terminals Un/ 3 2.2 networks with high-

ohmic insulated neutral system and automatic earth fault clearing

Neutral point 0.5*Un/ 3 2.1

CB terminals 1.5*Un/ 3 3.3 networks with earth

fault compensation or with a high-ohmic insulated neutral system

Neutral point 1*Un/ 3 3.2

4.3 Choice of the surge arrestor The surge arrestor limits effectively the overvoltage by

suppressing the high frequency (150 kHz) peak overvoltage.

The absolute value of the remaining overvoltage depends

though on the choice of the surge arrestor. The voltage

limitation is effective at a level of 3.1 times the rated

continuous operating voltage of the surge arrestor. The choice

of the rated voltage of the surge arrestor must take into

account abnormal circuit conditions as well. In table IV two

common situations are compared.

● For networks with high-ohmic insulated neutral

system and automatic earth fault clearing the nominal voltage

of each phase is fixed at Un/√3 and the neutral point of the

capacitor bank has 0 (zero) voltage. The continuous operating

voltage of the surge arrestor can be chosen accordingly. The

surge arrestor with associated continuous operating voltage

(COV) gives a protection of 2.2 pu. During a normal breaking

operation the neutral point attains a peak voltage of

0.5*Un√(2/3), which lasts until discharging of the capacitor

bank; this corresponds to a COV of 0.5*Un/√3; the resulting

level of protection is 2.1 pu.

● For networks with earth fault compensation or with a

high-ohmic insulated neutral system a possible persistent

single phase earth failure increases the nominal voltage of the

healthy phases a factor √3, and the voltage on the neutral

point of the capacitor bank increases to 1 pu. These more

severe conditions determine the continuous operating voltage

of the surge arrestor. For arrestors on the circuit-breaker

terminals the nominal voltage can reach 1.5*Un/√3; the

resulting level of protection is 3.3 pu. For a single arrestor on

the neutral of the bank the continuous voltage can reach

Un/√3; the resulting level of protection is 3.2 pu. During

interruption of the capacitive current the voltage of the neutral

can increase slightly more. Yet, the surge arrestor is capable

of dealing with this temporary overvoltage under this rare

abnormal network condition.

5. DISCUSSION

The main results of this study are summarized in table V.

An important difference is found between the numerically and

experimentally obtained overvoltage values. The measured

overvoltage on the bank terminal to ground is significantly

lower than calculated. This is due to natural damping of the

high frequency phenomena by dissipative elements in the

circuit and by the very small capacitance on the source side

due to the absence of parallel feeders. The peak over-voltage

has a limited duration of about 10µs. Surge arrestors

effectively limit these overvoltages to values as low as 2.2 pu

between terminal and ground. The capacitors themselves are

stressed neither by the NSDD nor by the action of the surge

arrestors during limitation, as the discharge current is a single

phase current flowing towards ground.

TABLE V : Over-voltages in capacitor bank switching

Situation Capacitor

bank terminal Across CB

1 Normal Interruption 1.5 pu 2.5 pu

2 NSDD : Predicted 6.0 pu 7.0 pu

3a NSDD (K-Late = 1.3) 4.2 pu 5.2 pu

3b NSDD (K-Immediate = 1.7) 5.2 pu 6.2 pu

4 Surge arrestors on all terminals 2.2 pu 3.2 pu

5 Surge arrestor on C-bank neutral 2.2 pu 3.2 pu

In the introduction it was outlined that NSDDs are a

common phenomenon in vacuum interrupters and that the

simultaneous occurrence of NSDDs in 2 phases give rise to a

restrike. The frequency of occurrence of a NSDD is related to

design parameters like the contact opening stroke. Hence it is

possible to design a vacuum CB according to the

requirements of either “low restrike probability” class C1 or

“very low restrike probability” class C2 of [7]. For 24 kV

Class C2 vacuum CBs with “very low restriking probability”

this leads to a nominal contact gap of 16 mm, see Fig. 1. For

voltages of 36 kV and above [8] proposes to use two vacuum

Schneider Electric 2008 - Conferences publications

Page 8: Capcitance Switching With Vacuum Circuit Breaker

2008 China International Conference on Electricity Distribution (CICED 2008) 7

interrupters in series. Although these measures are effective

from a normative point of view, they do not contribute to an

economically conclusive and reliable solution as shown by

the following numerical example. For instance, contactors

which allow for frequent operations have a small contact

opening stroke. Even with a NSDD frequency of only 1/500

they will produce over 2000 NSDDs in their entire lifespan.

Therefore, only the application of surge arrestors is an

effective solution to suppress overvoltages and eliminate any

risk for equipment: capacitor bank, circuit breaker and switch

board. The application guide in table VI summarises this

recommendation relating the choice of switchgear to the

application duty. If the CB is used only occasionally for

energizing and de-energizing the capacitor bank a vacuum CB

with class C1 or C2 can be used. Yet for daily operation of the

capacitor bank a protection by surge arrestor is recommended,

and in this case a class C1 rating is sufficient, as the

suppression of overvoltage during a NSDD reduces

significantly the probability of a second simultaneous NSDD,

and hence the risk of a restrike. For more than daily operation

a vacuum contactor with surge arrestor is an economical

viable solution in series with a vacuum CB for protection.

Table VI : Application guide

Capacitive switching duty

Protection and Occasional operation

Daily operation Frequent operation

Vacuum-CB

Class C1 or C2 Class C1 +

Surge arrestors —

Vacuum-Contactors

— Surge arrestors Surge

arrestors

When applying surge arrestors, special attention must

be given to the energy dissipation in the arrestor. It is

proposed to dimension the arrestor to be capable to carry out

3 consecutive protective actions without cooling down.

Furthermore the dimensioning is related to the reactive power

of the capacitor bank, Sk. Guidelines are given by [6, 9] in the

case of restriking CBs, in which case the arrestor has to be

dimensioned for an energy of 6*Sk/ω, where ω : angular

frequency of the network. Transposing this approach to a

protection against NSDD the guidelines as presented in table

VII dimension the energy dissipation capability of the arrestor.

Hence, for the protection against NSDDs the arrestor can be

designed 3 to 6 times smaller.

Table VII : the requested energy dissipation

capability of the arrestor

Protection against NSDD

Arrestor on CB terminals to ground 1 * Sk/ω

Arrestor on C-bank neutral to ground 2 * Sk/ω

I. CONCLUSION

This study focussed on the interaction of the vacuum

circuit breaker with a capacitor bank during switching

operation. The occurrence of a NSDD leads to a shift of the

voltage of the neutral point of the bank. Although the

phenomenon in itself is rare, the over-voltages produced are

deterministic and depend on the recovery voltage of the phase

in which the NSDD occurs and on the moment of breakdown.

The experimental study shows that the overvoltage after

NSDD is limited to about 4.2 pu. on the capacitor bank

terminals. Surge arrestors are shown to be an effective

means to limit this overvoltage. As cost efficient solution it is

proposed to use a single surge arrestor on the neutral point of

the capacitor bank. Guidelines are presented to dimension

these arrestors.

REFERENCES

[1] T. Yokoyama, Y. Matsui, K. Ikemoto and M. Inoyama

“ Technique on Overvoltage Phenomenon Analysis for

Vacuum Switching Equipment ” by, Meiden Review

Series No. 78,1986

[2] Y. Sunada,N.Ito, S. Yanabu, H. Awaji, H. Okumura and Y.

Kanai, “ Research and Development on 13.8kV 100kA

Vacuum CB with Huge capacity and Frequent

Operation ”, CIGRE, Paris, 1982

[3] P. Huhse and E. Zielke, “ 3AF Vacuum CBs for Switching in

Capacitor Banks ”, Siemens Power ENGENEERING III

(1981) No 8-9

[4] D. Koch, “Control equipment for MV capacitor banks”,

ECT142, Schneider-Electric, Grenoble, 1992

[5] T. Kamakawaji, T. Shioiri, T. Funahashi, Y. Satoh, E.

Kaneko and I. Oshima, “ An Investigation into Major

Factors in Shunt Capacitor switching Performances By

Vacuum CBs With Copper Chromium Contacts ”, IEEE

Power Engeneering 1993 winter meeting Columbus

OHIO

[6] L. Gebhardt, B. Richter, ”Surge arrestor application of

MV-capacitor banks to mitigate problems of switching

restrikes”, paper 0639, 19th CIRED, 2007, Vienna.

[7] International Standard IEC 62271-1, 2008, “High Voltage

Schneider Electric 2008 - Conferences publications

Page 9: Capcitance Switching With Vacuum Circuit Breaker

8 2008 China International Conference on Electricity Distribution (CICED 2008))

Switchgear and Controlgear – Part 1: Common specifications ”

[8] E. Dullni, W. Shang, D. Gentsch,I. Kleberg and K.

Niayesh, “ Switching of Capacitive Currents and the

Correlation of Restrike and Pre-ignition Behavior” , IEEE

trans. on dielectrics and electrical insulation, vol. 13, n 1,

pp. 65-71, 2006

[9] R. Rudolph and B. Richter, “Dimensioning, testing and

application of metal oxide surge arrestors in medium

voltage networks”, open document ABB, Wettingen, 1999

About the author

Hans Schellekens (54) received the Ph.D. degree in

technical engineering from the Technical University of

Eindhoven, The Netherlands, in 1983, with a specialization in

plasma physics. He worked at the HOLEC Research

Laboratory from 1978 to 1982 and at KEMA testing

laboratories from 1983 to 1985. From 1986 to 1993, he was

responsible for the development of vacuum interrupters and

vacuum circuit breakers at HOLEC. Since 1994, he is

involved in the development of vacuum interrupters for

Schneider Electric Medium Voltage SBU (formerly

Merlin-Gerin) at Grenoble in France. He has been active in

the Dutch Brazing Soc. as well as in the CIGRE Working

Group 13.01 from 1985 to 1993. Dr. Schellekens is a member

of the Current Zero Club.

E-mail of author: [email protected]

Schneider Electric 2008 - Conferences publications