Calpeda control panel

27
CALPEDA TUTORIAL

description

Calpeda controlo panel: a biref tutorial

Transcript of Calpeda control panel

Page 1: Calpeda control panel

CALPEDA!TUTORIAL

Page 2: Calpeda control panel

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1CONTROL !PANELSpractice guide

Page 3: Calpeda control panel

SELECTION MENU

Page 4: Calpeda control panel

INSTALLATION

IGNITION

OPERATING MODE

STANDARD EMERGENCY TIMED

HOW TO CHANGE OPERATING MODE

STANDARD EMERGENCY TIMED

Page 5: Calpeda control panel

INSTALLATION

Page 6: Calpeda control panel

During installation do not damage the electronic cards and the other electrical components found inside of the box.Provide for enough space all around the control panel for natural cooling. !Do not install the control panel in places exposed to direct sunlight or near sources of heat. !!

1. INSTALLATION

selection menu

Page 7: Calpeda control panel

IGNITION

Page 8: Calpeda control panel

1. IGNITION

OFF

ON

OFF

ON

selection menu

next (2.ignition)

Page 9: Calpeda control panel

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

Firstly activate the pumps pushing the AUT/STOP bottoms

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

AUTSTOP

2. IGNITION

selection menu

next (3.ignition)

Page 10: Calpeda control panel

With a three-pashe motor check that the direction of rotation is as shown by the arrow on the pump casing, otherwise disconnect electrical power and reverse the connections of two phase.

!

selection menu

3. IGNITION

Page 11: Calpeda control panel

OPERATING MODE

Page 12: Calpeda control panel

TIMED3 EMERGENCY2

STANDARD1OPERATING MODE

selection menu

Page 13: Calpeda control panel

Each phase of the set operation is controlled by a electronic card that provides the following functions: • pump stop when there no water in the suction. • avoid pump starting in case of water hammering. • alarm activation when air cushion in the tanks drop. • pump stop when air cushion is over. • pump stop with too close starts and stops. !Flashing FAILURE red led: • insufficient air cushion in the tank. Continuous FAILURE red led: • Pump stopped when there is no air cushion in the tank.

1. STANDARD MODE

selection menu

Page 14: Calpeda control panel

ALARM TIME SETTING!

With the trimmer placed in the back side of the electronic card, it is possible to select a certain time to detect the drop of air cushion in the tanks, due to the membrane failure. !Example: 4 sec set delay time When the delay time between two following signals of the pressure switches is lower than 4 sec., the alarm for insufficient air cushion is detected. If the failure is not repaired, when the delay between the two following signals reaches 2 sec. (half the alarm time), the set stops (continuous FAILURE red led).After having the tanks repaired, reset the operation by pushing RESET pushbutton. !!!!

selection menu

next

Page 15: Calpeda control panel

!

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

Flashing FAILURE red led

Pre-alarm. Insufficient air cushion in

the tank

Continuous FAILURE red led

Alarm! Pump stopped when there is no air

cushion in the tank

The flashing or continuous FAILURE red led switches off only by pushing RESET pushbutton.

RESET

selection menu

Page 16: Calpeda control panel

2. EMERGENCY MODE!The operating mode is the same as the one described above with the only difference that the pump do not stop if there is no air cushion, but continue to run with starts and stops at intervals of a few seconds to ensure water supply also in emergency cases.

This mode must be used only in case of an emergency for short periods of time. The tank's air cushion must be restored as soon as possible. Prolonged operating in these conditions can lead to the burning of the electric motors and to the damaging of the contacts of the electromagnetic switches.

!

selection menu

Page 17: Calpeda control panel

3. TIMED MODE!

It is recommended to use operating mode 3 only with pump with a flat curve, as the pump may continue to run also with a zero flow rate.!

The back side of the electronic card features a TRIMMER with a scale ranging from 3 to 24 for setting the minimum running time for the pump.

3 4 9 13 18 22 24

30 minuti 40 m 90 m 130 m 180 m 220 m 240 m

Trimmer selection

Working time

selection menu

next

Page 18: Calpeda control panel

HOW TO CHANGE OPERATING MODE

Page 19: Calpeda control panel

By default the control panel is set in the standard mode

selection menu

Page 20: Calpeda control panel

TIMED3 EMERGENCY2

STANDARD1

selection menu

OPERATING MODE

Page 21: Calpeda control panel

STANDARD MODE

OFF

ON

OFF

ON

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1 1. Hold the AUT/STOP button down

AUTSTOP

2. Switch on (holding the AUT/STOP button down)

selection menu

next

Page 22: Calpeda control panel

FUNZIONAMENTO STANDARD

3. Wait until the flashing failure led flashes once

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

Release after the flash!selection menu

Page 23: Calpeda control panel

EMERGENCY MODE

OFF

ON

OFF

ON

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

AUTSTOP

selection menu

1. Hold the AUT/STOP button down

next

2. Switch on (holding the AUT/STOP button down)

Page 24: Calpeda control panel

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

!selection menu

EMERGENCY MODE

3. Wait until the flashing failure led flashes twice

Release after the flash

Page 25: Calpeda control panel

TIMED MODE

OFF

ON

OFF

ON

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

AUTSTOP

selection menu

1. Hold the AUT/STOP button down

next

2. Switch on (holding the AUT/STOP button down)

Page 26: Calpeda control panel

TIMED MODE

POWER ONPRESENZA RETE

FAILURE

MP 2000

AVARIA SISTEMA

NO WATERMANCANZA ACQUA

STOP

MAN

AUT

P2

STOP

MANRESET

AUT

P1

!selection menu

3. Wait until the flashing failure led flashes thrice

Release after the flash

Page 27: Calpeda control panel