Bus Protection Fundamentals - Relay...

17
Bus Protection Fundamentals Terrence Smith – GE Grid Solutions 2017 Texas A&M Protective Relay Conference

Transcript of Bus Protection Fundamentals - Relay...

Page 1: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Bus Protection Fundamentals

Terrence Smith – GE Grid Solutions

2017 Texas A&M Protective Relay Conference

Page 2: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

High bus fault currents due to large number of circuits connected:• CT saturation often becomes a problem as the CT may not be

sufficiently rated• Large dynamic forces associated with bus faults call for fast

clearing times in order to reduce damage due to a bus fault• High incident energy/arc flash

False trip by bus protection may create serious problems:• Service interruption to a large number of customers

(distribution and sub-transmission voltage levels)• System-wide stability problems (transmission voltage levels)• With both dependability and security important, preference

is always given to security

Bus Protection Requirements

Page 3: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Interlocking schemes

Overcurrent (unrestrained, unbiased) differential

Overcurrent percent (restrained, biased) differential

High-Impedance schemes

Low-Impedance microprocessor-based schemes

Bus Protection Techniques

Page 4: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

The Over-Current Problem

Downstream Fuse FS1

Phase TOC_ Upstream Relay 52-1

Phase TOC_ Downstream Relay 52-2

Phase IOC_ Upstream Relay 52-1

Phase IOC_ Downstream Relay 52-2

0 1000 2000 3000 40000

0.5

1

1.5

2

2.5

3

Fault current at 11 kV

Tim

e to

ope

rate

(s)

Gen

60 MVA11 kV

Bus1 Bus2

52-1 52-2

F60-1 F60-2

CT1 CT2F-1 F-2

F-3

Bus 3Load = 5 MVA

75 A

500 kVA11kV/.44 kV

LoadLoad Load

Load

FS1

F-4

F-2

Page 5: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

The Over-Current Problem

Page 6: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

The CT Problem

Page 7: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

The CT Problem

Fault with full DC offset:

Page 8: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

The Re-Configurable Bus Problem

NORTH BUS

SOUTH BUS

CT-8

B-5

B-6

CT-5

CT-6

S-5

S-6

B-4CT-4

S-3

S-4

B-3CT-3

S-1

S-2

B-2CT-2

CT-1

B-1

C-1 C-2 C-4

C-3 C-5

CT-7

B-7

Page 9: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Interlocking Schemes

• Blocking scheme typically used

• Short coordination time required

• Practically, not affected by CT saturation

• The blocking signal could be sent over communications ports

• This technique is limited to simple one-incomer distribution buses

50

50 50 50 50 50

BLO

CK

Page 10: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Overcurrent (unrestrained) Differential

• Differential signal formed by summation of the bus currents

• CT ratio matching may be required

• On external faults saturated CTs yield spurious differential current

• Time delay used to cope with CT saturation

• Instantaneous (unrestrained) differential OC function useful on integrated microprocessor based relays

51

Page 11: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Percent (restrained) Differential

• Percent characteristic used to cope with CT saturation

• Restraining signal can be formed in a number of ways

• No dedicated CTs needed

• Protection of re-configurable buses possible

87

nDIF IIII ...21

nRES IIII ...21

nRES IIII ...,,,max 21

Page 12: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Sloped Diff & CT Saturation Problem

diffe

rent

ial

restrainingt0

t2

Page 13: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Sloped Diff & CT Saturation Problem

diffe

rent

ial

restrainingt0

t2

Page 14: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

• No need for dedicated CTs

• High Internal CT ratio compensation

• Advanced algorithms supplement the percent differential protection function making the relay very secure

• Protection of re-configurable busbars becomes easy as the dynamic bus replica (bus image) can be accomplished without switching physically secondary current circuits

• Integrated Breaker Fail (BF) function can provide optimal tripping strategy depending on the actual configuration of a busbar

• Distributed architectures replace CT wires with fiber

Low Impedance Bus Protection

Page 15: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

High Impedance Bus Differential

High Impedance Bus Differential

Relay

CB nCB 3CB 2CB 1

I1 I2 I3 In

i1

i2

i3in

• I1 + I2 + I3 + …… + In = Id = 0 The vectorial sum of all primary currents in and out of the bus equals zero

• i1 + i2 + i3 + ……. + in = id = 0 The vectorial sum of all CT secondary currents (assuming same CT ratioand no CT saturation) in and out of the bus equals zero

• v1 +v2 + v3 + ……+ vn = vd = 0 The vectorial sum of all voltages induced on all CT secondary windingsduring normal load or external fault (no CT saturation) equals zero

vd = 0

id = 0

+ -- +

Page 16: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

• Fast, secure and proven

• Require dedicated CTs, preferably with the same CT ratio. Cannot handle nicely inputs from CTs set on different taps.

• Input from not fully distributed CT winding creates danger for the equipment, because of inducing very high voltages – autotransformer effect

• Can be applied to small buses

• Depending on bus internal and external fault currents, they may not provide adequate settings for sensitivity and security

• Cannot be easily applied to re-configurable buses

• Require a voltage limiting varistor capable of absorbing significant energy

• Does not provide benefits of a microprocessor based relay (e.g. metering, monitoring, oscillography, breaker fail)

High Impedance Bus Protection

Page 17: Bus Protection Fundamentals - Relay Conferenceprorelay.tamu.edu/.../sites/3/2017/04/Bus-Protection-Fundamentals.pdf · Bus Protection Fundamentals Terrence Smith – GE Grid Solutions

Thank You

Questions?