FIRE ALARM PANEL REPLACEMENTBROWER STUDENT CENTER
AS SHOWN SC SF
E101-BSCTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-306-E101 - BrowerSC.dwg, 5/3/20 at 4:53 AM By SGOWERS - Last Printed: 5/4/20 at 5:26 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLANS03E101
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELExisting Honeywell XLS3000 Non-Addressable Fire Alarm ControlPanel And Honeywell FS90 Intermediary Fire Alarm Control PanelWith Exposed Conduit Located Within Basement Electrical Room
Drawing:Detail:
Scale:NTSFIRE ALARM RISER (ZONE)
01E101
HoneywellXLS 3000
FACP
Ground
DISPLAY
Battery
120V
KEYPLAN VERTICAL KEY
BASEMENT
1st FLOOR
2nd FLOORROOF
N
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
BPS
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
120V
FARA
FFFFF F
FFFF FWP
FIRE ALARM PHOTOS
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Fire Alarm Devices Located Throughout The
Building
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
To Main Distribution Frame
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Enough Capacity To Accommodate Total Device Count And Will Monitor Existing Honeywell FACP System.2) New Honeywell FACP Would Monitor Existing Honeywell FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Brower Student Center Is Currently Covered By Fire Notification And Detection / Initiation Devices From a Honeywell XLS 3000 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours OfOperation Without Normal Power And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both EndsWith Listed Hardware. See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) SpareCircuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater CertifiedFire Alarm Technician.
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
Remote LED / Test StationRTS
F
To All Existing Zone Fire Alarm Devices OnSignaling Line Circuit
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
WF
TSTamper Switch
(As Required)
Flow Switches For Sprinkler System(As Required)
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
EMT And JumperTo FACP
Kitchen Hood Suppression System (As Required)
Corning WCH-02PFiber Enclosure(Existing)
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1ST FLOOR
BASEMENT
FIRE ALARM SCHEDULEDESCRIPTIONMARK
EXISTING FIRE ALARM DEVICES, PANEL, CIRCUITS, Etc
CO DETECTOR ( WITH LOCAL VISUAL AND AUDIO )
FIRE ALARM MONITOR MODULE
CO
MM
POWER OR SIGNALING LINE CIRCUIT
BPS BOOSTER POWER SUPPLY
MM
COCOCO
CO Device Communication Loop MMMM
BPS
120V
CO Device Power Loop
(If Required)
1 2KEY NOTES (SYMBOLS , , ETC.)
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments. ProvideInstallation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
6. CO Detectors To Provide Local Audio Visual And Supervisory At FACP And LSMS Control Station.
GENERAL NOTES
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Fire Alarm Control Panel
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
Connect To Existing
Photo Tag
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. Provide New CO Devices Connected To New Panel. See Sheet E102 For Approximate Location.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
MTG ROOM
BSC ASSTMANAGER
105ERESTAURANT102
FS LOCKERS107C
MENS
WOMEN
STAGE103
GAME ROOM1-L7
COLD PREP
107G
MTG ROOM101
CATERINGPANTRY
112STORAGE
116
MECH
VESTIBULE
ATRIUM
FOOD COURT
GLOBALCORNER
1-L6
NORTHATRIUM
CORRIDOR
BOX OFFICE105A
RECEIVING
CORRIDOR
BSC MGR105F
OFFICE105B
RECEPTION105
ELEC
LOBBY
SOUTHWESTLOUNGE
1-L2
VESTIBULE
1-C1
RECYCLING108
IT
IT
ELEC
ELEVWALK INCOOLERS
107H
DRYSTORAGE
115
JAN107E
WALK INCOOLERS
HOT PREP107B
EVENT ROOM EAST100E
AV REPAIR114
ELEC105C
MACH
CATERINGSTORAGE
CORRIDOR107
AV
OFFICE102E
DRYSTORAGE
102G
WALK-INFREEZER
102F
WARE WASH102J
RECEIVING102B
FINISHCOOKING
102I
PREP102H
CORR
IDO
R
LOBBY
CORRIDOR
AVCLO
TRASHJAN
TOILET
JAN
AV
EVENTLOBBY
CLO
FREEZER111
CATERINGDRY STO
MEDIACORNER
EVENT ROOM WEST100W
COPY105D
CORRIDOR
STORE102L
CLOSET
EVENT TERRACE
SOUTHWESTTERRACE
1-T2
RESTAURANT PATIO
NORTH TERRACE1-T4
WALK INCOOLERS
WALK INCOOLERS
WALK-INFREEZER
CO
CO CO
CO
CO
CO
1
TYP3
MECH005 MECH
001
ELEV MACH
STORAGE004
ELEV 1
FIRE PUMP001A
ELECTRICAL002
STORAGE003
1
DN
WOMEN OFFICE204
PRISM OFFICE205
AAA OFFICE206
UL OFFICE207
GREEK LIFE208
STUD. GOV.210
COLLEGEUNION
212
STUD.FINANCE
214 LEADERSHIPTRAINING
216
DEAN OFSTUDENTS
220CWORK ROOM
220B
ASSOC. DEAN220D
HEALTHWELLNESS
220E
DIR.CONDUCT
220G
LG MEETINGROOM
222
SM MEETINGROOM
221
SM MEETINGROOM
223
LG MEETINGROOM
224
MULTI-PURPOSEROOM WEST
225WMECH2-M3
SARECEPTION
201
OFFICE201A
OFFICE201B
OFFICE201C
CONF.201E
VP STUD.AFFAIRS
201D
CONF.220F
RECEPTION220
WORK ROOM201G
MECH2-M2
STUDENTORG LOUNGE
2-L1
ELEV 2
AV2-AV1
IT2-IT1
STORAGE225A
SAFE214A
OFFICE202ABSU OFFICE
203
WOMEN
MENJAN
ELEC2-E3
TOILET
ASST DIR.STUD. COND.
220H
OPEN OFFICE220J
CORRIDOR
2-C1
STO220A
A.D. GREEK LIFE208A
CORRIDOR
MULTI-PURPOSEROOM EAST
225E
ELEC2-E1
OPEN TOBELOW
OPEN TOBELOW
OFFICE209A
209
OFFICE209C
STO225C
STO225B
AV
MECH PENT2-M1
OFFICE202B
202
COPY209B
GREEK LIFE208B
BALCONY
FIRE ALARM - EXISTING LAYOUTBROWER STUDENT CENTER
AS SHOWN SC SF
E102-BSCTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-306-E102 - BrowerSC.dwg, 1/15/20 at 8:54 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
BASEMENT
1st FLOOR
2nd FLOORROOF
N
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1/32"=1'-0"Drawing:Detail:
Scale:FIRST FLOOR LAYOUT02E102
1/32"=1'-0"Drawing:Detail:
Scale:SECOND FLOOR LAYOUT03E102
3/32"=1'-0"Drawing:Detail:
Scale:BASEMENT LAYOUT01E102
1 2KEY NOTES (SYMBOLS , , ETC.)
1.
2.
3.
Existing Fire Alarm Control Panel.
Existing Gas Kitchen Equipment.
New CO Detector.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Fire Alarm Ansul System
New Carbon Monoxide Detector WithLocal Audio And Visual Notification.
Photo Location IndicatorX
CO
AREA OF WORK
2143
MDF3
FIRE ALARM PANEL REPLACEMENTBUSINESS BUILDING
AS SHOWN SC SF
E101-BUSTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-307-E101 - Business.dwg, 5/1/20 at 6:21 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
PHOTO A - SIMPLEX FIRE ALARM CONTROL PANELSimplex 4010 Addressable Fire Alarm Control Panel With Exposed
Conduit Located Within Lower Level Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
Ground120V
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Simplex4010FACP
DISPLAY
Battery
Addressable
FIRE ALARM PHOTOS
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
PHOTO B - HONEYWELL FIRE ALARM CONTROL PANELExisting Honeywell Intermediary Fire Alarm Control Panel With
Exposed Conduit Located In The Lower Level Telecom Room
1 2KEY NOTES (SYMBOLS , , ETC.)
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Connect To Existing
Photo Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Simplex End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Monitor Existing Simplex FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. The Business Building Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Simplex 4010 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - FIRST FLOOR04E101
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
x10
POE1
FIRE ALARM - EXISTING LAYOUTBUSINESS BUILDING
AS SHOWN SC SF
E102-BUSTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-307-E102 - Business.dwg, 1/15/20 at 8:55 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
1/16"=1'-0"Drawing:Detail:
Scale:LOWER LEVEL LAYOUT01E102
1/16"=1'-0"Drawing:Detail:
Scale:FIRST FLOOR LAYOUT02E102
1/16"=1'-0"Drawing:Detail:
Scale:SECOND FLOOR LAYOUT03E102
1/16"=1'-0"Drawing:Detail:
Scale:THIRD FLOOR LAYOUT04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1 2KEY NOTES (SYMBOLS , , ETC.)
1. Existing Fire Alarm Control Panel.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
AREA OF WORK
12
34
MDF3
FIRE ALARM PANEL REPLACEMENTCENTENNIAL HALL
AS SHOWN SC SF
E101-CENTTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-308-E101 - Cent.dwg, 5/1/20 at 6:20 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/16"=1'-0" 8' 16' 32'4'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER (ZONE)
01E101
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell FS90 Addressable Fire Alarm Control Panel With
Exposed Conduit Located Within Lower Level Electrical Room
KEYPLAN VERTICAL KEY
1st FLOOR
3rd FLOOR
N
ROOF
2nd FLOOR
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
FIRE ALARM PHOTOS
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Enough Capacity To Accommodate Total Device Count And Will Monitor Existing Honeywell FACP System.2) New Honeywell FACP Would Monitor Existing Honeywell FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Centennial Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From a Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
HoneywellFS90FACP
Ground
DISPLAY
Battery
120V
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
BPS
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
120V
FARA
FFFFF F
FFFF FWP
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
Remote LED / Test StationRTS
F
To All Existing Zone Fire Alarm Devices OnSignaling Line Circuit
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
WF
TSTamper Switch (As Required)
Flow Switches For Sprinkler System(As Required)
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
MM
COCOCO
CO Device Communication Loop MMMM
BPS
120V
CO Device Power Loop
(If Required)
FIRE ALARM SCHEDULEDESCRIPTIONMARK
EXISTING FIRE ALARM DEVICES, PANEL, CIRCUITS, Etc
CO DETECTOR ( WITH LOCAL VISUAL AND AUDIO )
FIRE ALARM MONITOR MODULE
CO
MM
POWER OR SIGNALING LINE CIRCUIT
BPS BOOSTER POWER SUPPLY
1 2KEY NOTES (SYMBOLS , , ETC.)
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments. ProvideInstallation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.\
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
6. CO Detectors To Provide Local Audio Visual And Supervisory At FACP And LSMS Control Station.
GENERAL NOTES
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Fire Alarm Control Panel
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
Connect To Existing
Photo Tag
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. Provide New CO Devices Connected To New Panel. See Sheet E102 For Approximate Location.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
1
1
1
POE
x2
3
2
CO
CO TYP5CO
4
FIRE ALARM - EXISTING LAYOUTCENTENNIAL HALL
AS SHOWN SC SF
E102-CENTTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-308-E102 - Cent.dwg, 1/15/20 at 8:55 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
1st FLOOR
3rd FLOOR
N
ROOF
Drawing:Detail:
Scale:NTSFIRST FLOOR LAYOUT
01E102 Drawing:
Detail:Scale:NTSSECOND FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSTHIRD FLOOR LAYOUT
03E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1.
2.
3.
4.
5.
Device To Be Added.
Pull Station Required Along Path Of Egress.
Existing Fire Alarm Control Panel.
Gas Generator.
New CO Detector.
PHOTO A - GAME ROOM
Additional Smoke Detector To Be Added To Game Room ForFull Coverage
PHOTO B - SMOKE DETECTION
Replace Smoke Detection In Kitchens With Heat Detection
2nd FLOOR
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
Fire Alarm Booster Panel
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
No Access
New Smoke Detector
New Manual Pull Station
New Strobe
New Horn / Strobe
Photo Location IndicatorX
New Carbon Monoxide Detector WithLocal Audio And Visual Notification.
CO
AREA OF WORK
MDF3
1
AREA OF WORK
23 4
56
FIRE ALARM PANEL REPLACEMENTCROMWELL HALL
AS SHOWN SC SF
E101-CROMTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-309-E101 - Cromwell.dwg, 5/4/20 at 4:46 PM By SGOWERS - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN B - LOWER LEVEL04E101
PHOTO A - INTERMEDIARY FIRE ALARM CONTROL PANEL
LOWER LEVEL
B
Honeywell FS90 Intermediary Fire Alarm Control Panel WithExposed Conduit Located Within Lower Level Storage Room
PHOTO B - SIEMENS FIRE ALARM CONTROL PANEL
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN A - LOWER LEVEL03E101
Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
Siemens MXL Addressable Fire Alarm Control Panel With ExposedConduit Located Within Lower Level Generator Room
CM
MM
MM
BPS
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
To Electric Fire Pump And / Or Jockey Pump Controller(s)
RTS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
Heat Detector
MM
F
FFF FWP
SiemensMXLFACP
Ground
Tamper Switch (As Required)
DISPLAY
Monitor Module
Battery
120V
FARA
H
F
F
120V
FFFF
FIRE ALARM PHOTOS
F
NewFACP
Ground
Battery
AddressableAddressable
MM
MM
120V
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Photo Tag
MM
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
1 2KEY NOTES (SYMBOLS , , ETC.)
Connect To Existing
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Network (TCNJ IT)Access
Fire Alarm Control Panel(FACP)
Wall-mounted ConnectorHousing (WCH)
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
5th FLOOR
6th FLOOR
A
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Siemens End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Monitor Existing Siemens FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Cromwell Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Siemens MXL System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. New Life Safety Management System Server And Cabling To Connect To LSMS Network In IT ServerRoom Location. See Specifications And Cable Infrastructure Package A Set For Additional Details.
6. Provide New Fire Alarm Network Switch And Fiber Patch Cords As Required For New Life SafetyManagement System Network Architecture. Coordinate With TCNJ IT Department For Connection OfSwitch To Fiber Network.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
Clean Agent Discharge SystemMonitor Module MM
FIRE ALARM - EXISTING LAYOUTCROMWELL HALL
AS SHOWN SC SF
E103-CROMTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-309-E103 - Cromwell.dwg, 1/15/20 at 8:56 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
5th FLOOR
6th FLOOR
Drawing:Detail:
Scale:NTSFOURTH FLOOR LAYOUT
01E103 Drawing:
Detail:Scale:NTSFIFTH FLOOR LAYOUT
02E103
Drawing:Detail:
Scale:NTSSIXTH FLOOR LAYOUT
03E103
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
AREA OF WORK
243
1
MDF3
FIRE ALARM PANEL REPLACEMENTCROMWELL / DECKER GARAGE
AS SHOWN SC SF
E101-DGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-310-E101 - Decker Grg.dwg, 5/1/20 at 6:25 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - FIRST FLOOR03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
3rd FLOOR
4th FLOOR
PHOTO B - INTERMEDIARY FIRE ALARM CONTROL PANELHoneywell FS90 Intermediary Fire Alarm Control Panel And Booster Panel
With Exposed Conduit Located Within First Floor Electrical Room
PHOTO A - SIMPLEX FIRE ALARM CONTROL PANELSimplex 4020 Addressable Fire Alarm Control Panel And Booster Panel
With Exposed Conduit Located Within First Floor Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
Ground120V
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Simplex4020-8001
FACP
DISPLAY
Battery
Addressable
FIRE ALARM PHOTOS
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
1 2KEY NOTES (SYMBOLS , , ETC.)
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Connect To Existing
Photo Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Simplex End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Monitor Existing Simplex FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Decker Garage Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Simplex 4020-8001 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
POE
1
FIRE ALARM - EXISTING LAYOUTCROMWELL / DECKER GARAGE
AS SHOWN SC SF
E102-DGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-310-E102 - Decker Grg.dwg, 1/15/20 at 8:56 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
3rd FLOOR
4th FLOOR
Drawing:Detail:
Scale:NTSFIRST FLOOR LAYOUT
01E102 Drawing:
Detail:Scale:NTSSECOND FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSTHIRD FLOOR LAYOUT
03E102 Drawing:
Detail:Scale:NTSFOURTH FLOOR LAYOUT
04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. Existing Fire Alarm Control Panel.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
AREA OF WORK
13
24
MDF3
FIRE ALARM PANEL REPLACEMENTDECKER HALL
AS SHOWN SC SF
E101-DECKTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-311-E101 - Decker.dwg, 5/1/20 at 6:38 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
5th FLOOR
6th FLOOR
PHOTO A - SIMPLEX FIRE ALARM CONTROL PANELSimplex 4020 Addressable Fire Alarm Control Panel And HoneywellFS90 Intermediary Fire Alarm Control Panel With Exposed Conduit
Located Within Lower Level Fire Pump Room
FIRE ALARM PHOTOS
SIMPLEX FIRE ALARM DEVICESExisting Simplex Addressable Fire Alarm Devices Located
Throughout The Building
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Connect To Existing
Photo Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NLOWER LEVEL PART PLAN03E101
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
Ground120V
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Simplex4020-8001
FACP
DISPLAY
Battery
Addressable
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Simplex End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Monitor Existing Simplex FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Decker Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Simplex 4020-8001 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
To Main Distribution Frame 1 2KEY NOTES (SYMBOLS , , ETC.)
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
7. A Portion Of This Work Will Be Occurring In The Path Of An Emergency Egress Route. During All PhasesOf This Project, A Protected Emergency Egress Route Must Be Maintained Through Each AffectedEmergency Egress Route, Allowing Retreat From The Building. Approval From The Division OfCommunity Affairs Is Required To Close Or Re-Direct An Egress Route.
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
GENERAL NOTES
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NFIRST FLOOR PART PLAN04E101
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
ELEVATOR MACHINE ROOM (ON ROOF)
x2
FIRE ALARM - EXISTING LAYOUTDECKER HALL
AS SHOWN SC SF
E103-DECKTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-311-E103 - Decker.dwg, 1/15/20 at 8:57 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
5th FLOOR
6th FLOOR
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
Drawing:Detail:
Scale:NTSFIFTH FLOOR LAYOUT
02E103Drawing:
Detail:Scale:NTSFOURTH FLOOR LAYOUT
01E103
Drawing:Detail:
Scale:NTSSIXTH FLOOR LAYOUT
03E103
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
AREA OF WORK
3
13107107
12 W07
Electrical Service /Fire Alarm Panel
41 2
MDF3
FIRE ALARM PANEL REPLACEMENTELY-ALLEN-BREWSTER
AS SHOWN SC SF
E101-EABTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-312-E101 - EAB.dwg, 5/1/20 at 6:37 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
PHOTO A - INTERMEDIARY FIRE ALARM CONTROL PANELHoneywell FS90 Intermediary Fire Alarm Control Panel With Exposed
Conduit Located Within Basement Electrical Room.
PHOTO B - SIMPLEX FIRE ALARM CONTROL PANELSimplex 4020 Addressable Fire Alarm Control Panel With Exposed Conduit
Located Within Basement Electrical Room.
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
Ground120V
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Simplex4020-8001
FACP
DISPLAY
Battery
Addressable
FIRE ALARM PHOTOS
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
1 2KEY NOTES (SYMBOLS , , ETC.)
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Simplex End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Monitor Existing Simplex FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Ely-Allen-Brewster Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Simplex 4020-8001 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Connect To Existing
Photo Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
FIRE ALARM - EXISTING LAYOUTELY-ALLEN-BREWSTER
AS SHOWN SC SF
E102-EABTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-312-E102 - EAB.dwg, 1/15/20 at 8:57 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
Drawing:Detail:
Scale:NTSELY HALL - LOWER LEVEL LAYOUT
01E102 Drawing:
Detail:Scale:NTSELY HALL - FIRST FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSELY HALL - SECOND FLOOR LAYOUT
03E102 Drawing:
Detail:Scale:NTSELY HALL - THIRD FLOOR LAYOUT
04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
FIRE ALARM - EXISTING LAYOUTELY-ALLEN-BREWSTER
AS SHOWN SC SF
E103-EABTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-312-E103 - EAB.dwg, 1/15/20 at 8:57 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
Drawing:Detail:
Scale:NTSBREWSTER HALL - LOWER LEVEL LAYOUT
01E103 Drawing:
Detail:Scale:NTSBREWSTER HALL - FIRST FLOOR LAYOUT
02E103
Drawing:Detail:
Scale:NTSBREWSTER HALL - SECOND FLOOR LAYOUT
03E103 Drawing:
Detail:Scale:NTSBREWSTER HALL - THIRD FLOOR LAYOUT
04E103
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
13107107
12 14
1615
W07 W07
Electrical Service /Fire Alarm Panel
POE
1
DRAWING ROOM
101 103
102 W07
TOILET
106101 112 118
107
202TOILET
201203 205 207 209 211
212210208206 214
213215 217
218
TOILET
202TOILET
201203 205 207 209 211
212210208206 214
213215 217
218
TOILET
FIRE ALARM - EXISTING LAYOUTELY-ALLEN-BREWSTER
AS SHOWN SC SF
E104-EABTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-312-E104 - EAB.dwg, 1/15/20 at 8:57 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
Drawing:Detail:
Scale:NTSALLEN HALL - LOWER LEVEL LAYOUT
01E104 Drawing:
Detail:Scale:NTSALLEN HALL - FIRST FLOOR LAYOUT
02E104
Drawing:Detail:
Scale:NTSALLEN HALL - SECOND FLOOR LAYOUT
03E104 Drawing:
Detail:Scale:NTSALLEN HALL - THIRD FLOOR LAYOUT
04E104
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
1. Existing Fire Alarm Control Panel.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide.
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
AREA OF WORK
3POE 41 2
MDF3
FIRE ALARM PANEL REPLACEMENTEDUCATION BUILDING
AS SHOWN SC SF
E101-EDUTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-313-E101 - Education.dwg, 5/1/20 at 6:37 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell XLS 1000 Addressable Fire Alarm Control Panel And Booster
Panel With Exposed Conduit Located Within Lower Level Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Addressable
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. The Education Building Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell XLS 1000 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Fire Shutter System (As Required)CMControl Module
Corning WCH-02PFiber Enclosure(Existing)
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
MM
COCOCO
CO Device Communication Loop MMMM
BPS
120V
CO Device Power Loop
(If Required)
FIRE ALARM SCHEDULEDESCRIPTIONMARK
EXISTING FIRE ALARM DEVICES, PANEL, CIRCUITS, Etc
CO DETECTOR ( WITH LOCAL VISUAL AND AUDIO )
FIRE ALARM MONITOR MODULE
CO
MM
POWER OR SIGNALING LINE CIRCUIT
BPS BOOSTER POWER SUPPLY
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. Provide New CO Devices Connected To New Panel. See Sheet E102 For Approximate Location.
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments. ProvideInstallation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
6. CO Detectors To Provide Local Audio Visual And Supervisory At FACP And LSMS Control Station.
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Fire Alarm Control Panel
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
Connect To Existing
Photo Tag
Fire ShuttersMonitor Module MM
x2
x11
POE
1
COCO 23
2430
2454
2430
2460
AIR IN
FIRE ALARM - EXISTING LAYOUTEDUCATION BUILDING
AS SHOWN SC SF
E102-EDUTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-313-E102 - Education.dwg, 1/15/20 at 8:58 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
Drawing:Detail:
Scale:NTSLOWER LEVEL PLAN
01E102 Drawing:
Detail:Scale:NTSFIRST FLOOR PLAN
02E102
Drawing:Detail:
Scale:NTSSECOND FLOOR PLAN
03E102 Drawing:
Detail:Scale:NTSTHIRD FLOOR PLAN
04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
1.
2.
3.
Existing Fire Alarm Control Panel.
Gas Generator.
New CO Detector.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
No Access
New Smoke Detector
New Manual Pull Station
New Strobe
New Horn / Strobe
New Carbon Monoxide Detector WithLocal Audio And Visual Notification.
Photo Location IndicatorX
CO
FIRE ALARM - EXISTING LAYOUTEDUCATION BUILDING
AS SHOWN SC SF
E103-EDUTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-313-E103 - Education.dwg, 1/15/20 at 8:58 AM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
Drawing:Detail:
Scale:NTSFOURTH FLOOR LAYOUT
01E103
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
AREA OF WORK
1 243
MDF3
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101
1 2KEY NOTES (SYMBOLS , , ETC.)
FIRE ALARM PANEL REPLACEMENTEICKHOFF HALL
AS SHOWN SC SF
E101-ECKTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-314-E101 - Eickhoff.dwg, 5/1/20 at 6:36 PM By MHABIB - Last Printed: 5/4/20 at 5:27 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF3rd FLOOR
Honeywell FS90 Addressable Fire Alarm Control Panel And Fire AlarmRemote Annunciator Panel Located Within Front Entrance Vestibule.
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANEL
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
MM
CM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFF FFF
FFFWP
F F
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Addressable
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Eickhoff Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
Fire Alarm Control Panel
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Connect To Existing
Photo Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
7. Remove Pull Station Surround And Glass At Each Of The Existing Pull Stations.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
EMT And JumperTo FACP
Kitchen Hood Suppression System (As Required)Monitor Module MM
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
COORDINATE FACP LOCATION WITH VENDOR
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - THIRD FLOOR04E101
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
1
AREA OF WORK
2 3 4
FIRE ALARM PANEL REPLACEMENTFORCINA GARAGE
AS SHOWN SC SF
E101-FGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-315-E101 - Forcina Garage.dwg, 5/1/20 at 6:35 PM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELExisting Honeywell FS90 Addressable Fire Alarm Control Panel With
Exposed Conduit Located Within Lower Level Electrical Room
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
N
FIRE ALARM PHOTOS 1 2KEY NOTES (SYMBOLS , , ETC.)
Fire Alarm Control Panel
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Connect To Existing
Photo Tag
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments. ProvideInstallation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Drawing:Detail:
Scale:NTSFIRE ALARM RISER (ZONE)
01E101
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Enough Capacity To Accommodate Total Device Count And Will Monitor Existing Honeywell FACP System.2) New Honeywell FACP Would Monitor Existing Honeywell FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Forcina Garage Is Currently Covered By Fire Notification And Detection / Initiation Devices From a Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
HoneywellFS90FACP
Ground
DISPLAY
Battery
120V
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
BPS
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
120V
FARA
FFFFF F
FFFF FWP
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
Remote LED / Test StationRTS
F
To All Existing Zone Fire Alarm Devices OnSignaling Line Circuit
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
WF
TSTamper Switch (As Required)
Flow Switches For Sprinkler System(As Required)
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
1
FIRE ALARM - EXISTING LAYOUTFORCINA GARAGE
AS SHOWN SC SF
E102-FGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-315-E102 - Forcina Garage.dwg, 1/15/20 at 8:58 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
Drawing:Detail:
Scale:NTSLOWER LEVEL LAYOUT
01E102
Drawing:Detail:
Scale:NTSFIRST FLOOR LAYOUT
02E102
N
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
1. Existing Fire Alarm Control Panel.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
4
AREA OF WORK
3
5
21
MDF3 6
FIRE ALARM PANEL REPLACEMENTGREEN HALL
1/8" = 1'-0" SC SF
E101-GRNTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-316-E101 - Green.dwg, 5/4/20 at 4:47 PM By SGOWERS - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/16"=1'-0" 8' 16' 32'4'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELExisting Honeywell FS90 Addressable Fire Alarm Control Panel With
Exposed Conduit Located Within Lower Level Electrical Room
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
N
2nd FLOORROOF
FIRE ALARM PHOTOS
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Not Be Compatible With The New FACP.
1) Install New FACP With Enough Capacity To Accommodate Total Device Count And Will Monitor Existing Honeywell FACP System.2) New Honeywell FACP Would Monitor Existing Honeywell FACP For Alarm, Tamper, Trouble, And Other Points That Are Currently Monitored By The Front End At a Minimum.3) This Building Would NOT Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Green Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
HoneywellFS90FACP
Ground
DISPLAY
Battery
120V
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
BPS
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
120V
FARA
FFFFF F
FFFF FWP
NewFACP
Ground
Battery
120V
Addressable
MM
MM
MM
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
Remote LED / Test StationRTS
F
To All Existing Zone Fire Alarm Devices OnSignaling Line Circuit
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
End Of Line Resistor
WF
TSTamper Switch (As Required)
Flow Switches For Sprinkler System(As Required)
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
To Main Distribution Frame
GENERAL NOTES
1 2KEY NOTES (SYMBOLS , , ETC.)
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
7. A Portion Of This Work Will Be Occurring In The Path Of An Emergency Egress Route. During All PhasesOf This Project, A Protected Emergency Egress Route Must Be Maintained Through Each AffectedEmergency Egress Route, Allowing Retreat From The Building. Approval From The Division OfCommunity Affairs Is Required To Close Or Re-Direct An Egress Route.
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Per-terminated On Both Ends At the MDFbetween required interconnection points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. New Life Safety Management System Server And Cabling To Connect To LSMS Network. SeeSpecifications And Cable Infrastructure Package A Set For Additional Details.
6. Provide New Fire Alarm Network Switch And Fiber Patch Cords As Required For New Life SafetyManagement System Network Architecture. Coordinate With TCNJ IT Department For Connection OfSwitch To Fiber Network.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
MMMonitor Module For Security System
MMMonitor Module For Clean Agent Discharge System
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
Fire Alarm Control Panel
Connect To ExistingPhoto Tag
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
Assoc. DirDirector
Data Res.Admin.
Assoc. Dir
Manager
Director
Info
. Spe
c.
LoanProcessor
Assoc. Dir.
Assoc. Dir
LoanProcessor
ClerkTypist
Sec'y.Dean
Conf.Room
Assoc. Dir.
Director
ProgramAss't.Sec'y.
Ass't. Dean
Assoc. Dir.
Files Coffee /Work Area
Programmer
Storage
x4
x2
POE POE POE
POEPOE
1
2
Vacant
New Hire
Publ Rel &Comm
Publ Rel &Comm
FIRE ALARM - EXISTING LAYOUTGREEN HALL
AS SHOWN SC SF
E102-GRNTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-316-E102 - Green.dwg, 1/15/20 at 8:58 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
N
2nd FLOORROOF
Drawing:Detail:
Scale:NTSLOWER LEVEL LAYOUT
01E102 Drawing:
Detail:Scale:NTSFIRST FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSSECOND FLOOR LAYOUT
03E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
1.
2.
Existing Fire Alarm Control Panel
UPS Power Panel. Provide 20A Receptacle ForServer Power UPS / Generator Backed Power.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Beam Detector
Clean Agent Control Panel
Existing Wall Mounted ConnectorHousing
AREA OF WORK
1 23 4
MDF3
FIRE ALARM PANEL REPLACEMENTHAUSDOERFFER HALL
1/8" = 1'-0" SC SF
E101-HAUSTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-317-E101 - Hausdoerffer.dwg, 5/1/20 at 6:34 PM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - FIRST FLOOR03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
ATTIC
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell XLS 1000 Addressable Fire Alarm Control Panel With
Exposed Conduit Located Within First Floor Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Addressable
1 2KEY NOTES (SYMBOLS , , ETC.)
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Be Connected To The Campus Life Safety Management System.
2. Equipment
A. Hausdoerffer Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell XLS 1000 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
5. Provide New CO Devices Connected To New Panel. See Sheet E102 For Approximate Location.
MM
COCOCO
CO Device Communication Loop MMMM
BPS
120V
CO Device Power Loop
(If Required)
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments. ProvideInstallation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
6. CO Detectors To Provide Local Audio Visual And Supervisory At FACP And LSMS Control Station.
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Fire Alarm Control Panel
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
Connect To Existing
Photo Tag
FIRE ALARM SCHEDULEDESCRIPTIONMARK
EXISTING FIRE ALARM DEVICES, PANEL, CIRCUITS, Etc
CO DETECTOR ( WITH LOCAL VISUAL AND AUDIO )
FIRE ALARM MONITOR MODULE
CO
MM
POWER OR SIGNALING LINE CIRCUIT
BPS BOOSTER POWER SUPPLY
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
x3x2
POE
1
CO32 CO
3
FIRE ALARM - EXISTING LAYOUTHAUSDOERFFER HALL
AS SHOWN SC SF
E102-HAUSTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-317-E102 - Hausdoerffer.dwg, 1/15/20 at 8:59 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
ATTIC
1/16"=1'-0"Drawing:Detail:
Scale:FIRST FLOOR LAYOUT01E102
1/16"=1'-0"Drawing:Detail:
Scale:SECOND FLOOR LAYOUT02E102
1/16"=1'-0"Drawing:Detail:
Scale:THIRD FLOOR LAYOUT03E102
1/16"=1'-0"Drawing:Detail:
Scale:ATTIC LAYOUT04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
No Access
New Smoke Detector
New Manual Pull Station
New Strobe
New Horn / Strobe
New Carbon Monoxide Detector WithLocal Audio And Visual Notification.
Photo Location IndicatorX
CO
1.
2.
3.
Existing Fire Alarm Control Panel.
Existing Gas Fired Water Heater.
New CO Detector.
AREA OF WORK
1 23 4
3MDF
FIRE ALARM PANEL REPLACEMENTKENDALL HALL
1/8" = 1'-0" SC SF
E101-KENTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-318-E101 - Kendall.dwg, 5/1/20 at 6:33 PM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell FS90 Addressable Fire Alarm Control Panel With
Exposed Conduit Located Within Lower Level Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal) To Electric Fire Pump And / Or Jockey Pump Controller(s)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit
Notification Appliance Circuit With Booster Power SupplyRemote Annunciator
Heat Detector
Monitor Module Tamper Switch (As Required)MM
120V
FARA
H
F
FFF FF F
FF FF F
FIRE ALARM PHOTOS
WP
NewFACP
Ground
Battery
120V
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Addressable
Fire Alarm Control Panel
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Connect To Existing
Photo Tag
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Be Connected To The Campus Life Safety Management System.
2. Equipment
A. Kendall Hall Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
1 2KEY NOTES (SYMBOLS , , ETC.)
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
x6POE
2
TCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-318-E102 - Kendall.dwg, 1/15/20 at 8:59 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
FIRE ALARM - EXISTING LAYOUTKENDALL HALL
AS SHOWN SC SF
E102-KEN
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
2nd FLOOR
LOWER LEVEL
1st FLOOR
N
ROOF
Drawing:Detail:
Scale:NTSLOWER LEVEL LAYOUT
01E102 Drawing:
Detail:Scale:NTSFIRST FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSSECOND FLOOR LAYOUT
03E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. Smoke Detection To Be Added To Top Of Stairwell.
Existing Fire Alarm Control Panel.
1
1.
2.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Beam Detector
Fire Curtain
Existing Wall Mounted ConnectorHousing
AREA OF WORK
1 23 4
MDF3
FIRE ALARM PANEL REPLACEMENTGITENSTEIN LIBRARY
1/8" = 1'-0" SC SF
E101-LIBTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-319-E101 - Library.dwg, 5/1/20 at 6:33 PM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - LOWER LEVEL03E101
1 2KEY NOTES (SYMBOLS , , ETC.)
Drawing:Detail:
Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell XLS1000 Addressable Fire Alarm Control Panel And Booster
Panel With Exposed Conduit Located Within Lower Level Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
HONEYWELL FIRE ALARM DEVICESExisting Honeywell Addressable Fire Alarm Devices Located
Throughout The Building
Addressable
Fire Alarm Control Panel
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Connect To Existing
Photo Tag
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Gitenstein Library Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell XLS 1000 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
7xx2
1
Drawing:Detail:
Scale:NTSLOWER LEVEL LAYOUT
01E102
FIRE ALARM - EXISTING LAYOUTGITENSTEIN LIBRARY
AS SHOWN SC SF
E102-LIBTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-319-E102 - Library.dwg, 1/15/20 at 8:59 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
Drawing:Detail:
Scale:NTSFIRST FLOOR LAYOUT
02E102
Drawing:Detail:
Scale:NTSSECOND FLOOR LAYOUT
03E102 Drawing:
Detail:Scale:NTSTHIRD FLOOR LAYOUT
04E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. Existing Fire Alarm Control Panel.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Beam Detector
Pre-Action Valve
Existing Wall Mounted ConnectorHousing
FIRE ALARM - EXISTING LAYOUTGITENSTEIN LIBRARY
AS SHOWN SC SF
E103-LIBTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-319-E103 - Library.dwg, 1/15/20 at 9:01 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
GENERAL NOTES
KEYPLAN VERTICAL KEY
LOWER LEVEL
1st FLOOR
2nd FLOOR
N
ROOF
3rd FLOOR
4th FLOOR
Drawing:Detail:
Scale:NTSFOURTH FLOOR LAYOUT
01E103
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of Entry
Duct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Beam Detector
Pre-Action Valve
AREA OF WORK
13 4
2
FIRE ALARM PANEL REPLACEMENTMETZGER GARAGE
1/8" = 1'-0" SC SF
E101-MGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-320-E101 - Metzger Grg.dwg, 5/1/20 at 6:32 PM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1/8"=1'-0" 2' 4' 8' 16'Drawing:Detail:
Scale: NPARTIAL FLOOR PLAN - FIRST FLOOR03E101Drawing:
Detail:Scale:NTSFIRE ALARM RISER
01E101
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
3rd FLOOR
4th FLOOR
PHOTO A - HONEYWELL FIRE ALARM CONTROL PANELHoneywell FS90 Addressable Fire Alarm Control Panel With Exposed
Conduit Located Within First Floor Electrical Room
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)
Flow Switches For Sprinkler System (As Required)
Duct Smoke Detector
Manual Fire Alarm Box
Smoke Detector
To All Existing Addressable Fire AlarmDevices On Signaling Line Circuit
To Associated HVAC Unit Motor Starter For Shutdown (As Required)
Remote LED / Test Station
To Audio / Visual and Visual Only Indicating Devices(As Indicated On Plans)WP
To Electric Fire Pump And / Or Jockey Pump Controller(s)Monitor Module(One For Each: Running, Loss Of Phase, Phase Reversal)
RTS
CM
MM
MM
BPS
WF
Control Module
Monitor Module
Notification Appliance Circuit With Booster Power Supply
Notification Appliance Circuit
Remote Annunciator
Heat Detector
Tamper Switch (As Required)Monitor Module MM
120V
FARA
H
F
FFFFF F
FFFF FWP
FIRE ALARM PHOTOS
NewFACP
Ground
Battery
120V
Addressable
1 2KEY NOTES (SYMBOLS , , ETC.)
Fire Alarm Control Panel
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
Connect To Existing
Photo Tag
Drawing:Detail:
Scale:NTSFIRE ALARM FIBER ENCLOSURE INSTALLATION
02E101
Fire Alarm Control Panel(FACP)
Threaded Hub Adapter AttachedFire Alarm Panel Enclosure. PunchEnclosure As Required
2" LB At All 90-degree Bends,Or Long-radius Sweep For UpTo Two (2) Bends
One (1) 2" EMT ConduitFrom Fiber Enclosure ToFire Alarm Panel. InstallPull Strings
Threaded Hub AdapterAttached To Customer SideOf Enclosure. PunchEnclosure As Required
Network (TCNJ IT)Access
Wall-mounted ConnectorHousing (WCH)
Existing Fire Alarm Control Panel
Existing Wall-Mounted ConnectorHousing
Existing Equipment
New Equipment
NOTES:1. General
A. The Riser Above Depicts A "Honeywell" Basis of Design With A New Honeywell FACP. All Existing Honeywell End Devices Would Be Compatible With The New FACP.
1) Install New FACP With Capacity Noted Below.2) New Honeywell FACP Would Communicate The Point Identification Of Each Device To The New Front End.3) This Building Would Be Considered A Fully Addressable Building.
B. The Schematic Riser Diagram Is Intended As An Overview Of The Fire Alarm System Including The General Configuration And Type Of Devices Found Throughout The Building.
C. The FACP Shall Connect The Campus Life Safety Management System.
2. Equipment
A. Metzger Garage Is Currently Covered By Fire Notification And Detection / Initiation Devices From An Addressable Honeywell FS90 System.
B. Fire Alarm Fiber Jumper Is To Be Brought Into Wall Mounted Connector Housing In The Vicinity Of The FACP.
3. Wiring
A. The FACP Power Supply Shall Be Derived From A Dedicated, Lockable Electrical Circuit (Colored Red) As Well As An Internal Battery Sized To Provide 15 Minutes Of Alarm Condition After 24 Hours Of Operation Without NormalPower And Include 20% Additional Spare Capacity.
B. The FACP Ground Shall Consist Of An #8 AWG Conductor In 3/4" Conduit From The Fire Alarm Control Panel (FACP) To The Building's Grounding Electrode System. Bond To Metallic Conduit On Both Ends With Listed Hardware.See Sheet E102 For Location Of Main Electric Room.
C. The Fire Alarm System's Wiring Method Shall Be Class A Rated Between Panels (Where Applicable) And Class B Rated For Detection Devices And Notification Appliances.
D. The New FACP Shall Contain A Minimum Of 30% Spare Capacity Above The Total Amount Of Existing Devices Connected To The Existing FACP Provide Fire Alarm Panel With Hardware For Two (2) Spare Circuits.
E. Surge Protector To Be Provided For Each 120V Power Supply Circuit, Refer To Specifications For Further Information.
4. Testing
A. Perform A Final Acceptance Test Of The Entire Fire Alarm System In Accordance With All Applicable Codes Including The International Building Code (IBC) And NFPA 72 By NICET Level II Or Greater Certified Fire AlarmTechnician.
1. The Fire Alarm Plan Shows The General Layout And Intent Of The Fire Alarm System. It Does NotNecessarily Reflect Exact Quantities Required By Code. The Contractor Shall Determine The ActualQuantity And Location Of Devices Required Based Upon Actual Field Conditions Required As Per NFPA72.
2. The Fire Alarm System Shall Comply With NFPA 72 And All Local Codes And Amendments.
3. Fire Alarm Cabling That Cannot Be Concealed Shall Be Neatly Surface Mounted Utilizing Wire Mold InFinished Areas Or EMT In Non-Finished Areas. All Exposed EMT Shall Be Prepped And Painted To MatchAdjacent Wall Surface.
4. Panel Board Circuit Breaker Supplying Fire Alarm Control Panel and Associated Equipment Shall Have AHandle "Lock On" Device .
5. Provide Installation Testing Per NFPA 72 By NICET Level II Or Greater Certified Fire Alarm Technician.
6. When Replacing An Existing FACP It Is The Contractors Responsibility To Transfer All Systems That AreCurrently reporting To The Existing Panel. There Are Certain Panels That Monitor Accessory SystemsSuch As Security, Fire Shutters Clean Agent Systems, CO Detectors, Access Control Etc. Contractor ShallSurvey The Buildings And Include All Accessory Systems And Intermediary Devices Required To IntegrateSaid Systems On Their Shop Drawings.
FACP Fire Alarm Control Panel
EMT Electrical Metallic Tubing
CM Control Module
MM Monitor Module
WCH Wall-Mounted Connector Housing
EMT And JumperTo FACP
Corning WCH-02PFiber Enclosure(Existing)
GENERAL NOTES
To Main Distribution Frame
NOTES:1. Coordinate Position Installation Of EMT Into FACP Enclosure With Respect To Fiber Termination Connections In FACP Enclosure, And With TCNJ/IT2. Install 2" EMT From Fiber Enclosure To FACP Enclosure. Use LBs At Each 90-Degree End Unless Swept Long-Radius Bends Can Be Installed. No More Than (2)
90-degree Bends Are Permitted Before An Accessible Pulling Point Shall be Furnished.3. Install Fiber Jumpers Between WCH And FACP.
1. Provide A New Fire Alarm Panel, Or ReplaceExisting Fire Alarm Panel, Or Replace ExistingFire Alarm System To Enable AddressableCommunication With The New Campus FrontEnd. To Count As One Of The Fully AddressableBuildings, Each Device Point Must BeCommunicated To The Front End System.
2. Provide UL Listed Alarm System Loop CircuitSurge Protection For Each 24V Alarm SystemLoop Circuits In A Field-Replaceable Module.Includes Hardwired Mounting Base For EachModule.
3. Provide Two Duplex Fiber Jumper CablesPre-terminated On Both Ends, Between TheExisting WCH And Fire Alarm Control Panel AsPer Detail 2. Also Provide Duplex Fiber Jumper Cables Pre-terminated On Both Ends At the MDFBetween Required Interconnection Points. Contractor Shall Coordinate And Confirm Jumper ConnectionTypes, Fiber Type, Length, Routing Conditions, Etc With Field Conditions. Coordinate With TCNJ ITDepartment For Fiber Connection And Labeling Information.
4. Provide Branch Circuit For The New Fire Alarm Panel From Existing Electrical Panel In Electric Room ThatCurrently Supplies The Existing Fire Alarm Panel. Utilize 2#12, #12G In 3/4" Conduit And Provide New20Amp Circuit Breaker (Red And Clearly Identify FACP Circuit). Match Existing Type/Ratings For CircuitBreaker.
WCH
EMT
To Campus Life Safety Management System(Monitored 24/7 By Campus Police)
POE
1
FIRE ALARM - EXISTING LAYOUTMETZGER GARAGE
AS SHOWN SC SF
E102-MGRGTCNJ - CAMPUS FIRE ALARM PROJECTPART B - HARDWARE & SOFTWARE UPGRADES2000 PENNINGTON ROAD,EWING NJ, 08618Anthony Laskosky
dlb associates265 Industrial Way West, Eatontown, N.J. 07724
CONSULTING ENGINEERS, P.C.
Confidential and Proprietary / ©DLB Associates 20205/03/2020
Questions For DLB Call:This
Draw
ing
Is T
he P
rope
rty
Of D
LB A
ssoc
iate
s Con
sulti
ng E
ngin
eers
, PC.
It W
as P
repa
red
Excl
usiv
ely
For T
his P
artic
ular
Pro
ject
And
Is L
imite
d To
Thi
s Pro
ject
Onl
y. U
naut
horiz
ed R
epro
duct
ion
Or O
ther
Use
Of T
hese
Dra
win
gs O
r Ide
as Is
Pro
hibi
ted.
Last Saved: \\w-fs\Vol3\47\472\47211 - TCNJ Campus Fire Alarm\47211-320-E102 - Metzger Grg.dwg, 1/15/20 at 8:59 AM By MHABIB - Last Printed: 5/4/20 at 5:28 PM By Gowers, Scot
project
DLB Project ID: 47211ITEM DATE ISSUE DESCRIPTION DATE ISSUE DESCRIPTION
A
ITEM
B C D E F G H I J K L M N O P Q R30
x42
3
4
5
6
7
8
9
10
11
12
13
14
title
scale checked bydrawn by date
dwg. no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
CAMPUS KEY
GREEN LN
PENNINGTON RD
N
1 05/01/2020 ISSUED FOR BID
Phone: 732-927-5038
1 2KEY NOTES (SYMBOLS , , ETC.)
GENERAL NOTES
KEYPLAN VERTICAL KEY
1st FLOOR
2nd FLOOR
N
3rd FLOOR
4th FLOOR
1/32"=1'-0"Drawing:Detail:
Scale:SECOND FLOOR LAYOUT02E102
1/32"=1'-0"Drawing:Detail:
Scale:FOURTH FLOOR LAYOUT04E102
1/32"=1'-0"Drawing:Detail:
Scale:FIRST FLOOR LAYOUT01E102
1/32"=1'-0"Drawing:Detail:
Scale:THIRD FLOOR LAYOUT03E102
Drawings Based On Visual Inspection Site Walk ThroughCompleted During Nov 2017 - March 2018
1. Existing Fire Alarm Control Panel.
1. This Drawing Is Provided For Reference Only And Includes Existing Fire Alarm Devices Noted During AVisual Walk Through To Provide An Understanding Of The Existing Level Of Detection Within EachBuilding. The Intent Of This Reference Drawing Is To Provide A Baseline Or Minimum Level Of ProtectionThat Shall Be Maintained In Within The Building. It Is Not Intended To Depict The Requirements For AComplete System Replacement Or Layout Of New Devices For This Building.
CO Detector
DescriptionIdentifier DescriptionIdentifier
PARTIAL SYMBOLS & ABBREVIATIONS
FACP Fire Alarm Control Panel
CO Carbon Monoxide
POE Point Of EntryDuct Mounted Smoke Detector
Heat Detector, Combination FixedTemperature And Rate Of Rise
Fire Alarm Control Panel
Fire Alarm Remote AnnunciatorPanel
No Access
Smoke Detector (ER IndicatesElevator Recall)
Manual Pull Station
Strobe Only
Horn/Strobe
Smoke Detector
Fire Sprinkler Tamper Switch
Fire Sprinkler Flow Switch
Smoke Detector With SounderBase
New Smoke Detector
New Manual Pull Station
Photo ID Tag
New Strobe
New Horn / Strobe
Fire Alarm Booster Panel
Existing Wall Mounted ConnectorHousing