BNI PBS-202-000-Z001
BNI PBS-206-000-Z001
Short Guide

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
1 Notes for the user 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typografical conventions 2 1.3.1 Enumerations 2 1.3.2 Actions 2 1.3.3 Syntax 2 1.3.4 Cross references 2 1.4 Symbols 2 1.5 Abbreviations 2
2 Safety 2.1 Intended use 3 2.2 General safety notes 3 2.3 Meanings and warnings 3
3 Getting started 3.1 Connection overview, BNI PBS-202-000-Z001 4 3.2 Connection overview, BNI PBS-206-000-Z001 5 3.3 Mechanical connection 6 3.4 Electrical connection 6 3.4.1 Supply voltage 6 3.4.2 Profibus interface 7 3.4.3 Connecting actuators 8
4 Technical data 4.1 Dimensions 9 4.2 Mechanical data 9 4.3 Elektrical data 9 4.4 Operating conditions 9 4.5 Function indicators 10
5 Included material 5.1 Included material 11
6 Appendix 6.1 Ordercode / order informations 12

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 2
1 Notes for the user
1.1 About this guide The BNI EIP-… serves as a decentralized input/output module for connecting to a Profibus
network. 1.2 Structure of the
guide The guide is organized so that the sections build on one another.
Section 2: Basic safety information.
Section 3: Getting started.
Section 4: Technical data for the device.
Section 5: Included Material.
1.3Typografical
conventions The following typographical conventions are used in this Guide.
1.3.1 Enumerations Enumerations are shown in list form with bullet points.
- Entry 1, - Entry 2.
1.3.2 Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated
by an arrow. Action instruction 1.
Action result. Action instruction 2.
1.3.3 Syntax Numbers:
Decimal numbers are shown without additional indicators (e.g. 123).
Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).
1.3.4 Cross references Cross references indicate where additional information on the topic can be found (see
section 4 „Technical Data”).
1.4 Symbols Note Tip!
This symbol indicates general notes.
Note!
This symbol indicates a security notice which most be observed.
1.5 Abbreviations O port
BCD BNI EMV I-Port FE GSD file LSB MSB SELV PLC PELV
Profibus DP
Digital output port Binär coded switch Balluff Network Interface Elektromagnetische Verträglichkeit Digital input port Functions earth Geräte-Stamm-Daten-Datei (Generic Station Description) Least Significant Bit Most Significant Bit Safety Extra Low Voltage Process logic control Protective Extra Low Voltage -
Profibus DP: Profibus dezentrale peripherie

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 3
2 Safety
2.1 Intended use-
This guide describes The BNI PBS-… serves as a decentralized output module for
connecting to a Profibus network.
2.2 General safety notes
Installation and startup
Installation and startup are to be performed only by trained specialists. Any damage
resulting from unauthorized manipulation or improper use voids the manufacturer’s
guarantee and warranty.
The device is in accordance with EMC Class A. Such equipment may generate RF noise.
The operator must take precautionary measures accordingly.
The device must be powered only using an approved power supply (see section 4
“Technical data”). Only approved cable may be used.
Operating and testing
The operator is responsible for observing local prevailing safety regulations.
When defects and non-clearable faults in the device occur, take it out of service and secure
against unauthorized use.
Approved use in ensured only when the housing is fully installed.
2.3 Meanings
and warnings Note!
The pictogram used with word “Caution“ warns of a possible hazardous situation affecting the health of persons or equipment damage. Ignoring these warnings can result in injury or equipment damage.
Always observe the described measures for preventing this danger.

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 4
3 Getting started
3.1 Connection- overview
BNI PBS-202-…
Fig.: 3.1: Connection overview BNI PBS-202-…
1 Mounting hole 2 M12 Profibus IN 3 Address switch 4 Supply power POWER IN 5 Standard Output port 1, Pin 4 6 Standard Output port 3, Pin 4 7 Standard Output port 5, Pin 4 8 Standard Output port 7, Pin 4 9 Standard Output port 6, Pin 4
10 Standard Output port 4, Pin 4 11 Standard Output port 2, Pin 4 12 Standard Output port 0, Pin 4 13 Status LED module 14 Supply power Power OUT 15 Label 16 M12 Profibus OUT 17 Earth connection
1
2
3
5
6
7
8
1
10
9
11
13
14
16
12
15
4
17

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 5
3 Getting started
3.1 Connection overview
BNI PBS-206-…
Abb. 3.2: Connection overview BNI PBS-206-…
1 Mounting hole 2 M12 Profibus IN 3 Address switch 4 Supply power POWER IN 5 Standard Output port 1, Pin 2 / 4 6 Standard Output port 3, Pin 2 / 4 7 Standard Output port 5, Pin 2 / 4 8 Standard Output port 7, Pin 2 / 4 9 Standard Output port 6, Pin 2 / 4
10 Standard Output port 4, Pin 2 / 4 11 Standard Output port 2, Pin 2 / 4 12 Standard Output port 0, Pin 2 / 4 13 Status LED module 14 Supply power Power OUT 15 Label 16 M12 Profibus OUT 17 Earth connection
1
2
3
5
6
7
8
1
10
9
11
13
14
16
12
15
4
17

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 6
3 Getting started
3.3 Mechanical connection
The module is attached using 2 M6 screws and 2 washers.
3.4 Elektrische Anbindung
3.4.1 Supply voltage Power OUT (7/8“ Mini Change, 5-pin, female)
PIN Function
1 0 V
2 0 V
3 FE
4 Sensor / Bus communication supply
5 Actuator supply
Power Out (7/8” Mini-Change, 5-Pin, male)
PIN Function
1 0 V
2 0 V
3 FE
4 Sensor / Bus communication supply
5 Actuator supply
Connection of the IO
module 24 V DC.
Provide sensor/bus power and actuator power from separate power sources if
possible.
Total current <9A. The total current of all modules may not exceed 9A even when
daisy chaining the actuator supply.
Note!
The use of a Profibus hybrid cable is not allowed.
Function ground
Note Tip!!
The FE connection from the housing to the machine must be low-impedance and kept as short as possible.

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 7
3 Getting started
3.4.2 Profibus interface
The bus connection is made using the M12 sockets Profibus IN and Profibus OUT. The address is
set on the address switch.
Profibus OUT (M12, B-coded,female)
PIN Function
1 VP
2 RxD/TxD-N, A line (Green)
3 DGND
4 RxD/TxD-P, B line (Red)
5 n.c.
Thread: Shield
Profibus IN (M12, B-coded, male)
PIN Function
1 VP
2 RxD/TxD-N, A line (Green)
3 DGND
4 RxD/TxD-P, B line (Red)
5 n.c.
Thread: Shield
Connecting the Profibus
- Connect ground conductor to FE terminal - Connect incoming Profibus line to Profibus IN
- Connect continuing Profibus line to Profibus Out or screw termination resistor to the
continuing bus terminal
Note Tip!
Each Profibus segment end must be installed with a termination resistor. Unused sockets must be fitted with over caps to ensure IP67 protecting rating.
Addressing
The Profibus address is et directly on the BNI PBS- using two BCD switches Permissible address range: 0 … 99. Each Profibus node must have a unique address assigned to it. Any change to the address does not become effective until power is reset on the modules.

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 8
3 Getting started
3.4.3 Connecting
actuators
8 I/O ports are provided for connecting the actuators.
PIN Standard Output port
BNI PBS-202-000-Z001
Standard Output port
BNI PBS-206-000-Z001
1 + 24 V, 200mA + 24 V, 200 mA
2 - Output, 2A
3 0 V 0V
4 Output, 2A Output, 2A
5 FE FE
Note Tip!
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection rating.
Module Standard O ports
BNI PBS-202-000-Z001 8
BNI PBS-206-000-Z001 16

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 9
4 Technical data
4.1 Dimensions
4.2 Mechanical data
Housing material Die case zinc, matt nickel plated
Fieldbus Profibus: M12, B-coded (female and male)
Supply power 5-pin, 7/8“ (female and male)
I/O Ports M12, A-coded (8 x female)
Enclosure rating IP67 (only when plugged-in and threaded-in)
Weight ca.: 735 g
4.3 Electrical data
Operating voltage 18 ... 30 V DC
Ripple < 1 %
Current draw without load ≤ 200 mA
Service port Balluff
4.4 Operating conditions
Operating temperature Storage temperature
-5°C … 70°C -25°C….70°C
EMV - EN 61000-4-2/3/4/5/6 - EN 55011
- Severity level 4A/3A/4B/2A/3A - Gr. 1, Kl. A
Shock / vibration EN 60068 Teil2-6/27

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 10
4 Technical data
4.5 Function indicator
Status LEDs
LED Indicator Function
LED 1 Green US power supply sensor / bus communication ok
LED 2 Green UA power supply actuator ok
LED 3 Red US power supply sensor / bus communication under
voltage
LED 4 Red UA power supply actuator under voltage
LED 5 Green, solid
Green, blinking
BUS data transmission Profibus ok
BUS data transmission Profibus inactive
LED indicators
Standard I/O ports
Each M12 Port (digital output) is assigned to LED’s which indicate the operating states
Indicator
LED 6 (PIN 4)
Off Output = 0
Yellow Output = 1
Red I Output > Imax
LED 7 (PIN 2)
Off Output = 0
Yellow Output = 1
Red I Output > Imax
LED 6, Pin 4
LED 7, Pin 2
LED 1-5, Status

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 11
5 Included material
5.1 Included material
The BNI PBS … consists of the following components:
IO-block
4 blind plugs M12
Ground strap
Screw M4x6
20 labels.

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 12
6 Appendix
Order code BNI PBS-20x-000-Z001
Balluff Network Interface
Profibus
Functionen
202 = IP 67 Input module, 8 outputs
206 = IP 67 Input module, 16 outputs
Variante
000 = Standard version
Mechanical version
Z001 = Die-cast zinc housing
Material: Balluff housing version
Profibus ports: 1 x M12x1 internal thread, 1x M12 external thread
Power: 1 x 7/8“ external thread, 1x 7/8” external threads
IO-Ports: 8 x M12 internal thread
Order information Product ordering code Order code
BNI PBS-202-000-Z001 BNI002J
BNI PBS-206-000-Z001 BNI002K

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 13

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 14

Balluff Network Interface Profibus, BNI PBS-202/206-000-Z001
www.balluff.com 15