Motor Protection against overload
Thermal overload relays
Motor
• economic motor protection
against overload
• , small extensive
• possibilities for remote reset
• , small variety = low store costs
• cooperate design to contactors
©A
BB
Gro
up -
3-
30-A
pr-0
7
� EN 60-947-4-1 Motor overload protection EN 60-947-4-1.
� / Phase failure protection.
� Manual and automatic reset.
� Reset push-button adjustible
� Reset only
� 95-96Reset and opening tripping contact 95-96
� Setting knob for nominal current
� –25 °C ~ 55 °C Ambient temperature -25 to 55 °C
� Class 10/10ATripping class 10/10A
Functions
Thermal overload relays
©A
BB
Gro
up -
4-
30-A
pr-0
7
Strategies for Motor Protection
M
TOL
Therm. Overload-relay TOL
M
EOL
Electron. Overload-relay EOL
M
I >
Manual MotorStarter
M
ECD�
CM-LWNMotor-monitoringRelais CM-LWN
M
I >
C
CM-MSEThermistor-Protection Custorapid
Wiring Diagrams
©A
BB
Gro
up -
5-
30-A
pr-0
7
Protections Strategies
Thermal Overload Relay
acc. IEC60947-4-1
Protection against:
• thermal overload
• phase failure
• manual rest
• automatic start
Electronic Overload Relay
acc. IEC60947-4-1
Protection against:
• thermal overload
• phase failure
• manual rest
• automatic start
• high accuracy
• less energy need
••high temperature
Manual Motor Starter
acc. IEC60947-4-1
Protection against:
• thermal overload
• phase failure
• manual rest
• automatic start
••short circuit protection
• remote stop
Cos - Protec.
Cos Cos - monitoring
Protection against:
• thermal overload
• phase failure
• manual rest
• automatic start
Thermistor Custorapid
temp. monitoring
Protection against:
• thermal overload
• manual rest
• automatic start
• remote functions
Features
©A
BB
Gro
up -
6-
30-A
pr-0
7
Motor Protection
12 * Ie
Magnetic Release
3 Phase
2 Phase
Thermal Release
Magnetic Release
12 * Ie
Thermal Release to be
Provided by e.g. Thermal Overload Relay
Time Time
Tripping Curves
©A
BB
Gro
up -
7-
30-A
pr-0
7
1.2 * Ie 7.2 * Ie
1.05 x Ie No Tripping at 1.05 Ie within 2 hours
1.2 x Ie Tripping at 1.2 * Ie within 2 hours
Class 30 9 - 30 sec
Class 20 6 - 20 sec
Class 10 4-10 secMS325: Class 10A 2-10 sec
Ie – Ie = Adjusted Current
– Tripping Classes - Basic Data for Thermal Release
IEC 947-4-1
Please refere to IEC947-4-1 for exact data and characteristic
TIME
©A
BB
Gro
up -
8-
30-A
pr-0
7
Tripping curves
Tripping class : 10 / 10A Tripping class : 30
0.8 1 2 3 4 6 8
1
2
4
10
20
401
2
4
10
20
40
120
2-Phase
Tripping current, as multiple of set current
cold
3-Phase
warm
10
Tri
ppin
g tim
e
T 450 DU, DU 900 DUMin
utes
Seco
nds
3 4 6 8
cold
warm2-Phase
3-Phase
©A
BB
Gro
up -
9-
30-A
pr-0
7
Tripping Times, according to EN 60 947-4-1
1.5( )Max.
Tripping time at 1.5x setting current (warmstate)
1.05 At 1.05xsetting current
10 A 10 20 30Tripping classes
7.2( )Tripping time at 7.2x
setting current (cold state)
120 240 480 720
2 ... 10 6 ... 20 9 ... 30
no tripping
4 ... 10
©A
BB
Gro
up -
10-
30-A
pr-0
7
(IEC 60947-4-1)Tripping Curve acc. to Trip Classes (IEC 60947-4-1)
Thermal Overload Relays
Tripping time
Minutes
Class
Class
Seconds
Multiple of rated current
ABB :ABB Thermal Overloads with
• single phase protection
• temp. compensation
©A
BB
Gro
up -
11-
30-A
pr-0
7
Thermal Overload Relays
T 7 DU : up to 5,5 kW / 400 V
Label carrier
Test
2 4 6 98 96
97 95
Reset H
A
(integrated)
(push: stop, 95/96 opens
pull : stop until reset, 95/96 opens,97/98 closes)
Test
(NO)Signalling contact (NO)
Setting
(for rated motor current)
Selection and reset
(autom./hand reset,push: hand-reset)
(NC)Tripping contact(NC)(for contactor coil)
for contactor typesB6 / B7
©A
BB
Gro
up -
12-
30-A
pr-0
7
Thermal Overload Relays
ABB Assortment
TA25 to TA750,1 to 80 A
TA80 to TA20029 to 200 A
TA450 to T900130 to 850 A
©A
BB
Gro
up -
13-
30-A
pr-0
7
TA Overload Relays TA...
�� �� � ����
� �� �
�� � �� � �� � � � � � �� � �� �� �
� � �
� �� �
� �� �
� �� � �
©A
BB
Gro
up -
14-
30-A
pr-0
7
Overload Relays
Types
M~3
©A
BB
Gro
up -
15-
30-A
pr-0
7
Products
ABB– TA80 DU ... TA 200 DU..TA 450..T 900
©A
BB
Gro
up -
16-
30-A
pr-0
7
Products
ABB TA 450 SU ...T 900 SUABB Thermal Overload Relays – T A450 SU ... T 900 SU
With Current Transformers,
Class 30
���� Type TA 450 SU���� A210 A260 A300
���� 8 , 40 310 .8 setting ranges from 40 to 310 A
���� Type T 900 SU���� AF400 AF460 AF580 AF750
���� 4 , 265 850 4 setting ranges from 265 to 850 A
©A
BB
Gro
up -
17-
30-A
pr-0
7
Contactors with fitting relays
Thermal Overload Relays
Type A2611kW
Type A110 55 kWType B6 / B7
5,5 kW
©A
BB
Gro
up -
18-
30-A
pr-0
7
Motor protection
How to plan with thermal overload relays?
2 4 6 9896
97
Reset
Test
H
A
Motor
2 4 6 9896
97
Reset
Test
H
A
Motor
2 4 6 9896
97
Reset
Test
H
A
Motor
2 4 6 9896
97
Reset
Test
H
A
Motor
Circuit breaker
©A
BB
Gro
up -
19-
30-A
pr-0
7
Motor protection
How to plan with circuit breakers?
Motor Motor Motor Motor
0
1
0
1
0
1
0
1
Tmax
©A
BB
Gro
up -
20-
30-A
pr-0
7
Thermal Overload Relays
Principle of Phase Failure Sensitivity
- -----
b1, b2, b3
c,d
e
x
©A
BB
Gro
up -
21-
30-A
pr-0
7