Air Flow Measurements
Transcript of Air Flow Measurements
![Page 1: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/1.jpg)
Air Flow Measurements
Paul Morin
![Page 2: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/2.jpg)
In accordance with the Department of Labor and
Industry’s statute 326.0981, Subd. 11,
“This educational offering is recognized by the
Minnesota Department of Labor and Industry as
satisfying 1 hour of credit toward Building
Official and Residential Contractors continuing
education requirements.”
For additional continuing education approvals,
please see your credit tracking card.
![Page 3: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/3.jpg)
Agenda
» Why is measuring airflow important
» How much energy is being delivered to a room
» Commonly used devises for measuring air flow
» Describe lab setup used for this study
» Which devises are the most accurate and why
» Approximate cost of each devise
![Page 4: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/4.jpg)
Why is measuring airflow important
» To confirm we are delivering the designed air flow
» To trouble shoot comfort issues» Because we are required to do so
![Page 5: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/5.jpg)
How much energy is being delivered to a room
» BTU = 1.07 x air flow in CFM x ∆T in F⁰
• ∆T = temperature difference between the air coming out of the register and the temperature in the center of the room
![Page 6: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/6.jpg)
Commonly used devices
» Rule of thumb» Your hand» Garbage bag» Pitot tube / hot wire anemometer» Rotating vane anemometer» Balometer – flow hoods» Powered capture hoods
![Page 7: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/7.jpg)
Methods of Measuring Airflow
» Time to inflate a known volume• Stopwatch and a plastic bag on a hanger
![Page 8: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/8.jpg)
Methods of Measuring Airflow
» Flow through an orifice » 1.07 x area (sq. inches) x √pressure (Pa)
![Page 9: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/9.jpg)
Methods of Measuring Airflow
» Flow through an orifice • Exhaust fan flow meter
![Page 10: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/10.jpg)
Methods of Measuring Airflow
» Flow through an orifice • Blower door• Duct Blaster®
![Page 11: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/11.jpg)
Methods of Measuring Airflow
» Flow through an orifice • Duct calibration plate
![Page 12: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/12.jpg)
Methods of Measuring Airflow
» Measure velocity and area• Pitot tube in a duct• 2 tubes – static pressure and total pressure• Need to take measurements in multiple locations• Long lengths of rigid duct (6” duct = 10’ duct)• Velocity in feet per minute x square feet = CFM
![Page 13: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/13.jpg)
Methods of Measuring Airflow
» Measure velocity and area• Rotating Vein Anemometer
• Directly measures velocity• Allows you to input duct cross sectional area• Allows for timed or multi point averages
![Page 14: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/14.jpg)
Methods of Measuring Airflow
» Measure velocity and area• TrueFlow Air Handler Flow Meter
![Page 15: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/15.jpg)
» Flow Hoods and Powered Flow Hoods
Methods of Measuring Airflow
![Page 16: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/16.jpg)
Goals of the Research
» Measure the insertion loss» Measure accuracy as it relates to
positioning the measurement device over the source
![Page 17: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/17.jpg)
Devices Tested
» ACIN Flowfinder Mk2®• powered capture hood
![Page 18: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/18.jpg)
Devices Tested
» Alnor® Loflow Balometer®• capture hood
![Page 19: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/19.jpg)
Devices Tested
» Testo™ 417 • vane anemometer with funnel set
![Page 20: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/20.jpg)
Devices Tested
» TEC Flow Blaster®• powered capture hood
![Page 21: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/21.jpg)
Devices Tested
» TSI™ Accubalance® 8375 • Capture hood
![Page 22: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/22.jpg)
Lab Setup
![Page 23: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/23.jpg)
Test Setup
The transition assembly and fan were calibrated using our calibration chamber
![Page 24: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/24.jpg)
Test Setup
A flow conditioner was added in the duct where the branch and trunk meet
![Page 25: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/25.jpg)
Test Setup
An Iris damper was added to
![Page 26: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/26.jpg)
Insertion Loss Test
» Duct Blaster fan set to cruise 400 CFM» Flow through each register is 100 CFM
+/- 2 CFM» TECLOG3 was used to measure and
record pressures and flows» Methods were devised to get repeatable
results with each devise
![Page 27: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/27.jpg)
Devices Test Method
» ACIN Flowfinder Mk2®• Results varied based on when the device was told to start displaying real-time flow data
» Procedure used: • Place on register and allow it to equalize• When the “zero pressure” reading on the Flowfinderscreen stopped fluctuating, the device was triggered and allowed to spin up and begin taking flow measurements.
![Page 28: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/28.jpg)
» Alnor® Loflow Balometer®• directly observed for 30 seconds and, because of the stability of their displayed measurements, an average decided upon with an uncertainty of ±1cfm
Devices Test Method
![Page 29: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/29.jpg)
» Testo™ 417 • A 30 second time-average option was used because there was quite a bit of variability from one instantaneous measurement to the next
Devices Test Method
![Page 30: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/30.jpg)
» TEC Flow Blaster®• Results were recorded directly by
TECLOG3
Devices Test Method
![Page 31: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/31.jpg)
» TSI™ Accubalance® 8375 • directly observed for 30 seconds and, because of the stability of their displayed measurements, an average decided upon with an uncertainty of ±1cfm
Devices Test Method
![Page 32: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/32.jpg)
Insertion Loss Test
» Device was centered over each of the four registers and averaged
![Page 33: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/33.jpg)
-40.0
-30.0
-20.0
-10.0
0.0
10.0
20.0
30.0
Alnor Flowblaster Flowfinder Testo TSI
Err
or
in C
FM
Flow Measurement Device
COMPARISON OF CAPTURE HOOD DEVICES @
100CFM
Error (cfm) Average change in flow at measured station
![Page 34: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/34.jpg)
Insertion Loss Conclusions
» Powered Flow Hoods minimize insertion loss and read very accuracy
» The Alnor hood had minimal insertion loss, but consistently read 9 CFM too low
» The TSI hood had virtually no insertion loss but measured almost 20 CFM high
» The Testo had 31 CFM of insertion loss and read 9 CFM too high
![Page 35: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/35.jpg)
Orientation Tests
![Page 36: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/36.jpg)
Orientation Tests
» Tested at 50 CFM and 100 CFM» Tests were all performed at register 4
![Page 37: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/37.jpg)
30
35
40
45
50
55
60
65
70
Alnor Flowblaster Flowfinder Testo TSI
SCFM
Device
Capture Hood Orientation Test @48cfm
Centered Top Edge Side Edge Top Corner
Bottom Corner 45deg CW Baseline Flow Actual Flow
![Page 38: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/38.jpg)
60
70
80
90
100
110
120
130
140
Alnor Flowblaster Flowfinder Testo TSI
SCFM
Device
Capture Hood Orientation Test @100cfm
Centered Top Edge Side Edge Top Corner
Bottom Corner 45deg CW Baseline Flow Actual Flow
![Page 39: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/39.jpg)
Orientation Test Conclusions
» Fan assisted devises are the most consistently accurate
» Capture hoods are affected by hood orientation
» Testo devise is not affected much by orientation
![Page 40: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/40.jpg)
Orientation Test Conclusions
» Fan assisted devises are the most consistently accurate
» Capture hoods are affected by hood orientation
» Testo devise is not affected much by orientation
![Page 41: Air Flow Measurements](https://reader033.fdocuments.net/reader033/viewer/2022042600/589eda2d1a28ab7c4a8bffc5/html5/thumbnails/41.jpg)
Approximate cost of devises
» Testo 417 w/ hood $725» Flow Blaster accessory $1140
• With fan and DG-700 $2765
» Alnor Loflow $1595» TSI Accubalance $2500» ACIN Flowfinder $3950