AESO Export Capability Workshop February 16, 2006 Metropolitan Centre, Calgary
description
Transcript of AESO Export Capability Workshop February 16, 2006 Metropolitan Centre, Calgary
AESO Export Capability Workshop
February 16, 2006
Metropolitan Centre, Calgary
AB to BC Transfer BCTC perspective
Calgary, Alberta - Feb 16, 2006
Feb. 16, 2006 Page 3
The BC Transmission System
Snapshot:• 18,000 km circuit transmission
lines• 287 switching, distribution and
capacitor stations• Control Centers
• 1 System Control Center• 4 Area Control Centers
• 244 microwave and repeater sites
• Transmission rights-of-way• Interconnected to Alberta and
the Pacific Northwest for over three decades
Feb. 16, 2006 Page 5
BCTC Bulk Transmission System Overview (export to US)
NICSEL
KLY
REV
WSN
MCA
CBK
ACK
VAS
GMS/PCN
LM & VI
SEL area gen
5L925L94
5L91
5L965L98
5L81 & 5L82
5L51 & 5L52
5L875L76 & 5L79
2L112
BPA
Feb. 16, 2006 Page 6
BCTC Bulk Transmission System Overview(import from US)
NICSEL
KLY
REV
WSN
MCA
CBK
ACK
VAS
GMS/PCN
LM & VI
SEL area gen
5L925L94
5L91
5L965L98
5L81 & 5L82
5L51 & 5L52
5L875L76 & 5L79
2L112
BPA
Feb. 16, 2006 Page 7
Transmission Line Forced Outage (3 pole) Approx Data
Notes:1. SPR provided
in late 2002
2. SPR provided in mid 2003
3. SPR to be provided in 2006
4. SPR provided in 2005
5. Include sequential ctgs in less than 5 minutes
6. * SPR provided
500kV LinesCircuit Length
(km)3 Phase forced
outages Data Years
Forced outage per
year
5L76 (note 1 ) 118 65 22 2.98
5L79 (note 2) 118 70 21 3.35
5L81 * 264 55 22 2.52
5L82 * 248 62 22 2.84
5L91 (note 3) 223 181 22 8.29
5L92 * 180 62 22 2.84
5L94 * 319 146 20 7.30
5L98 (note 4) 302 381 22 17.45
5L51 & 5L52 36 / 36 1 22 0.05
5L91 & 5L98 3 (note 5) 22 0.14
5L76 & 5L79 4 22 0.18
5L81 & 5L82 3 22 0.14
5L1/2/3/4/7 double contingencies approx 278 14 22 0.64
5L11/12/13 double contingencies approx 330 12 22 0.55
Feb. 16, 2006 Page 8
BCTC RAS
• RAS arms generation shedding, line tripping, reactive equipment switching, and calculates transfer limits
• RAS armed in real time dynamically
• RAS arming based on actual flows
• TSA runs every 4 minutes
• TSA arms RAS
• RAS armed automatically
Feb. 16, 2006 Page 9
Feb. 16, 2006 Page 10
Questions?