68DCCAT
Transcript of 68DCCAT
-
8/9/2019 68DCCAT
1/44
Features
• High reliability
• Simple installation and operation
• LCD display for self-guided controller operation
• RS232 interface for remote operation
• Intelligent battery management:
• Temperature compensation
(requires optional cables)
• Programmable battery load testing with
data logging
• Symmetry (requires optional cables)
• Programmable low voltage disconnect
• Optional Ethernet (SNMP compatible) interface
module
• Natural convection cooling - no fans
• International standards compliance
Description
PPS 7 modular DC power shelf systems
provide large power system features in
cost-effective, rack-mounted form factors.
These shelf power solutions provide
rectification, system management, and
power distribution while maintaining high
reliability and offering flexibility for future
expansion. The PPS 7 systems are based
on hot-swappable rectifier modules output
power available at 450, 560 or 670W per
module.
System management is accomplished
through messages and alarms displayed
on the system controller’s (PCU) LCD
screen and can also be displayed
remotely via the PC-based PowComTM
software package.
PPS 7 Power SystemShelf System
www.power-one.com
-
8/9/2019 68DCCAT
2/44
An all-in-one 3U high shelf system that can be
installed in both 19” and ETSI telecom cabinet
solutions. The system subrack can
accommodate up to three rectifier modules, a
supervision module (PCU) and DC distribution
with a single battery breaker and six load
breakers.
PPS 7-2100 System
An all-in-one 3U high shelf system that can be
installed in both 19” and ETSI telecom cabinet
solutions. The system subrack can
accommodate up to four rectifier modules, a
supervision module (PCU) and DC
distribution with a single battery breaker and a
single load breaker.
PPS 7-2800 System
An all-in-one 6U high shelf system that can be
installed in 23” standard telecom cabinet
solutions. The system subrack can
accommodate up to six rectifier modules, a
supervision module (PCU) and DC distribution
with up to two battery breakers and twenty
four load breakers.
PPS 7-4200 System An all-in-one 6U high shelf system that can be
installed in 19” and ETSI telecom cabinet
solutions. The system subrack can
accommodate up to five rectifier modules, a
supervision module (PCU) and DC distribution
with up to two battery breakers and twenty
load breakers.
PPS 7-3500 System
System Configurations
-
8/9/2019 68DCCAT
3/44
Rectifier Features
Model VoltagePower (max.)
Current(max.)
PMP 5.24 SIC 110* 24V DC 448W 16A
PMP 5.48 SIC 110* 48V DC 448W 8A
PMP 7.24 SIC 24V DC 560W 20A
PMP 7.48 SIC 48V DC 672W 12A
PMP 7.60 SIC 60V DC 635W 9A
The PPS 7 system utilizes plug-in rectifier modules that are
based on a soft-switching approach. Features include 3 LEDs
for rectifier status indication, thermal shutdown, and input
overvoltage disconnection with an automatic reset (only on
PMP 7 modules).
• Menu guided operation
• RS232 interface for remote operation
• Battery management and testing
• Low voltage battery disconnect (LVBD)• Temperature compensation
• Battery symmetry measurement
• Optional Ethernet interface through SNMP and/or TCP/IP
• Partial load disconnection (PLD)
PCU Features
Rectifier Modules
Advanced system supervision is accomplished using a
microprocessor based control module that allows both local
and remote system monitoring.
Supervision Modules
*110V AC input
System Components
PPS 7 Power SystemShelf System
-
8/9/2019 68DCCAT
4/44
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model PPS 7-2100 PPS 7-2800 PPS 7-3500 PPS 7-4200
Input
230/400V 3-phase
208-240V 1-phase
Site configurable
230/400V 3-phase
208-240V 1-phase
Site configurable
230/400V 3-phase
208-240V 1-phase
Site configurable
230/400V 3-phase
208-240V 1-phase
Site configurable
Inputs (max.) Single input Single input Single input Single input
Rectifier Modules (max.) 3 4 5 6
Battery Outputs 1 1 2 2
Load Outputs 6 1 20 24
24V DC Version Yes N/A N/A N/A
48V DC Version Yes Yes Yes Yes
60V DC Version Yes (on request ) Yes (on request) Yes (on request) Yes (on request)
Supervision PCU PCU PCU PCU
Battery Symmetry Inputs(max.)
1 1 3 3
Low Voltage Battery
Disconnection (LVBD)Yes Yes Yes Yes
Dimensions (WxHxD) 485x133x305mm 485x133x305mm 485x133x305mm 582x266x305mm
Mounting
19”, ETSI, or flush
ETSI mount
(site configurable)
19”, ETSI, or flush
ETSI mount
(site configurable)
19”, ETSI, or flush
ETSI mount
(site configurable)
23”
Cable Entry Top Top Top Top
Temp. Comp. Charge Yes Yes Yes Yes
Ethernet Network
InterfaceYes Yes Yes Yes
Modem Interface Yes Yes Yes Yes
www.power-one.com
Shelf System
11V0005-036 PPS7 SY V3.0
PPS 7 Power System
-
8/9/2019 68DCCAT
5/44
Description
The Power-One PMP 5 rectifier moduleprovides a cost-effective power solutionin a high density footprint. Built on thelatest advances in the resonance switchmode approach (soft-switching), the
PMP 5 is the next evolution in our smallconvection cooled rectifier series.
Optimized for telecom applications, themodule is designed to work in amultitude of different subrack/shelf configurations incorporating the Power-One PCU controller and variousdistribution options.
Features• 115/230 VAC input
• 24V, or 48VDC output
• Power factor correction
• Active load sharing
• Hot-swappable
• International standards compliance
• Natural convection cooling
• Low weight
PPS 5/7 SystemShown
PMP 5Rectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
6/44
Input
Model PMP 5.24 PMP 5.48
PMP
5.24-110
PMP
5.48-110
Input
Voltage
161-276V AC single
phase, (44-66Hz)
80-138V AC single
phase, (44-66Hz)
Current
(max.)87% >87%
Tolerance Vout +/- 1%
Transient
Response
+/- 5% at load variation 10-90% or 90-10%,
recovery time 10ms
Load Sharing
-
8/9/2019 68DCCAT
7/44
Description
The Power-One PMP 7 rectifier moduleprovides a cost-effective power solutionin the highest possible density. Built onthe latest advances in the resonanceswitch mode approach (soft-switching),the PMP 7 is the next evolution in our small convection cooled rectifier series.
Optimized for telecom applications, themodule is designed to work in a multitudeof different subrack/shelf configurationsincorporating the Power-One PCUcontroller and various distributionoptions.
Features• 208/240 VAC input
• 24V, 48V, or 60V DC output
• Input overvoltage disconnection
• Thermal protection
• Active load sharing
• Hot-swappable
• Up to 92% efficient
• International standards compliance
• Natural convection cooling
• Low weightPPS 7 3500 SystemShown
PMP 7Rectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
8/44
Input
Model PMP 7.24 PMP 7.48 PMP 7.60
Input
Voltage
205-250V AC ±10% single phase,(44-66Hz) (-15% for PMP7.60)
185-160V at reduced output power
Current
(max.)
-
8/9/2019 68DCCAT
9/44
The PCU 5/ 7Controllers are usedin PPS5 and PPS7
Power Systems.
DescriptionThe Power-One Control Unit (PCU 5/7) provides monitoring and control for the PPS 5 and PPS 7
power systems. These hot-swappable controller modules supervise output voltages, currents, rectifier
performance, battery condition, and breaker status. Visual notification of an alarm condition is
provided with an LED. A description of the exact alarm condition is provided through an LCD.
Additionally, four Form “C” contacts are provided to indicate a failure.
Features
User controls and interfaces:
• Simple menu-guided operation using front panelmounted pushbuttons and an LCD
• User-selectable alarm parameters
• Data logging of last 40 events
• SNMP interface adapter available
• RS232 interface and Form “C” dry alarm contacts
• Compatible with PowComTM PC-based software
PCU 5/7Controller
www.power-one.com
Intelligent battery management:
• Temperature compensation with programmablecompensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
-
8/9/2019 68DCCAT
10/44
Input
Voltage 18-72V DC
Current
-
8/9/2019 68DCCAT
11/44
Description
The Power-One PPR 5/7 3 and 6position rectifier backplane provides acost-effective power solution in a highdensity wall-mounted footprint. Thesepower solutions provide rectification,
system management, and power distribution while maintaining highreliability and offering flexibility for future expansion. The PPS 5/7 3 & 6Position systems are based on hot-swappable rectifier modules outputpower available at 450, 560 or 670W per module.
Features• 115/230 VAC input
• 24V, or 48VDC output
• Serial or parallel alarm configurations
• Active load sharing
• Hot-swappable
• International standards compliance
• Natural convection cooling
• Systems can be paralleled
• Individual rectifier output adjustment6 Position SystemShown
PPR 5/73 & 6 Position Power Systems
www.power-one.com
-
8/9/2019 68DCCAT
12/44
www.power-one.com11V0005-065 PPR 5/7 V3.0
PPR 5/73 & 6 Position Power Systems
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Features
Model PPR 5/7 3-Position PPR 5/7 6-Position
Input115 or 230VAC single phase
(Depending on rectifier
module)"
115 or 230VAC single phase
(Depending on rectifier
module)"
Input Connections 3x4mm² terminal blocks 3x4mm² terminal blocks
Rectifier Modules (max.) 3 6
Load Outputs 2x10mm² - Qty 3 2x10mm² - Qty 6
24V DC Version Yes Yes
48V DC Version Yes Yes
Alarms
Common alarm for High Voltage/ Shutdown, Low Voltage/
Module Failure, Unequal Load Sharing Normally Opened
or Normally Closed.
Dimensions (WxHxD) 271x193.5x305mm 484.4x193.5x305mm
Weight 1.2kg (2.65lbs.) 2.5kg (5.5lbs.)
Mounting Wall Mount Wall Mount
Model Voltage Power (max.) Current (max.)
PMP 5.24 24V DC 448W 16A
PMP 5.24 SIC 110* 24V DC 448W 16A
PMP 5.48 SIC 110* 48V DC 448W 8A
PMP 7.24 SIC 24V DC 560W 20A
PMP 7.48 SIC 48V DC 672W 12A
*110V AC input
Available Rectifiers
-
8/9/2019 68DCCAT
13/44
Features
• High reliability
• Simple installation and operation
• Natural convection cooling - no fans
• RS232 interface for remote operation
• Form “C” dry alarm contacts
• Intelligent battery management
• Pluggable controller and DC distribution
modules
• Optional Ethernet (SNMP compatible) interface
module• International standards compliance
Description
The Galero™ Power System provides
large power system features in cost-
effective, rack-mounted form factors.
These power solutions provide
rectification, control and power
distribution all in one compact system
while offering extensive local and remote
power system and battery monitoring.
System management is accomplished
through the system controller (GMC).Status indication is made via LED’s, while
detailed information and remote operation
are accomplished through the PC-based
PowComTM software package.
Galero™ Power System
www.power-one.com
Shelf System
-
8/9/2019 68DCCAT
14/44
All-in-one 125 mm high shelf system for integration into standard
19” or ETSI cabinets.
Complete subrack for five rectifier modules, supervision module
and DC distribution with battery breakers (1-2) and load breakers
(9-10).
Galero 1750 System
All-in-one 125 mm high shelf system for integration into
standard 19” or ETSI cabinets.Complete subrack for seven rectifier modules, supervision
module and DC distribution including battery breakers (1-2) and
load breakers (2-3).
Galero 2450 System
System Configurations
-
8/9/2019 68DCCAT
15/44
Rectifier Features
Model VoltagePower (max.)
Current(max.)
CMP 3.48 48V DC 364W 6.5A
The Galero Shelf System utilizes plug-in rectifier
modules based on a soft-switching approach.
Features include 2xLED for rectifier status indication,
thermal protection with de-rating and input over-
voltage disconnection with automatic reset.
• Advanced system monitoring
• RS232 interface for remote operation
• Battery management and testing
• Automatic testing
• Low voltage battery disconnect (LVBD)
• Temperature compensation
• Battery symmetry measurement
• Monthly logging of battery parameters including “temperature-hours”
• Site programmable Flash EPROM
• Programmable alarms
• Programmable logic circuit
• Optional Ethernet interface through SNMP and/or TCP/IP
GMC Features
Rectifier Module
Advanced system supervision is accomplished using a
microprocessor based module that allows both local and
remote system monitoring.
Supervision Module - GMC
System Components
Galero™ Power SystemShelf System
-
8/9/2019 68DCCAT
16/44
Note: All specifications are subject to change without notification.
Input
Output
Mechanical
Options
Features
Battery
Model Galero 1750 Galero 2450
Input
230/400V AC 3-phase
205-240V AC 1-phase
Site configurable
230/400V AC 3-phase
205-240V AC 1-phase
Site configurable
Inputs (max.) Single input Single input
Rectifier Modules (max.) 5 7
Battery Outputs 1 2 1 2
Load Outputs 10 9 3 2
48V DC Version Yes Yes
Supervision GMC GMC
Battery Symmetry Inputs (max.) 2 2
Low Voltage Battery
Disconnection (LVBD)Yes Yes
Temp. Comp. Charge Yes Yes
Dimensions (WxHxD) 483x125x280mm 483x125x280mm
Mounting 19”, ETSI 19”, ETSI
Cable Entry AC - Rear
DC and signals -Top
AC - Rear
DC and signals -Top
Temp. Comp. Charge Yes Yes
Battery SymmetryMeasurement
Yes Yes
Ethernet Network Interface Yes Yes
Partial Load Disconnect N/A N/A
Integrated Surge Arrestors N/A N/A
www.power-one.com11V0005-033 Galero SY V3.0
Galero™ Power SystemShelf System
-
8/9/2019 68DCCAT
17/44
Description
The Power-One CMP 3.48, for use in theGalero™ series of power systems, is thenext evolution in our convection cooledrectifier series. This module provides thelatest advances in resonance switch modetechnology (softswitching). An onboard
microcontroller and an RS 485 data busprovide monitoring of basic functions, statusand identification information to the systemcontroller (GMC).
The CMP 3.48 rectifier module is optimizedfor telecom applications and is designed towork in numerous subrack/shelf configurations incorporating the GMCcontroller and varying distribution options.
Features• 208/240 VAC input
• 48 VDC output
• Input over-voltage disconnection
• Thermal protection, with de-rating
• Active load sharing
• Hot-swappable
• Up to 91% efficient
• Natural convection cooling
• Low weight
• International Standards Compliance
Galero™ Power
System
CMP 3.48Rectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
18/44
Input
Model CMP 3.48
Input Voltage
205-240V AC +10% single phase,
44-66Hz
(185-160V at reduced power output)
Current (max.) 91%
Tolerance Vout +/- 1.0%,
Transient
Response
+/- 5% at load variation
10-90% or 90-10%
recovery time 10ms
Load Sharing Typical 250VAC.
Indications
Green LED
Red LED
Power ON
High output
voltage/ shut down
Low voltage/
module failure
Audible
Noise
-
8/9/2019 68DCCAT
19/44
Description
The Galero™ Microprocessor Controller (GMC) from Power-One provides comprehensive monitoring and
control of the Galero power system. This digital controller monitors total system conditions including DC
voltage, rectifier current, rectifier temperature, system capacity, battery parameters and circuit breaker
status.
The GMC enables data storage of system configuration information such as battery type, installation date
and system commission date. Visual notification of alarm and warning conditions are indicated by front
panel LEDs, while descriptions of the alarms are provided through RS232 communication using PC-based
PowCom™ software package.
To meet individual site requirements, the GMC contains a Programmable Logic Unit that can be
programmed to monitor and control specified requirements. This allows actions to be set, alarms to be
triggered and outputs to be activated based on internal and external signal monitoring, comparing and
processing.
Features
User controls and interfaces:
• User-selectable alarm parameters
• 40 event data logging
• Password controlled environment
• RS232 Interface and Form “C” dryalarm contacts
• Programmable routing alarm
• Programmable logic unit
GMCController Module
www.power-one.com
Intelligent battery management:
• Temperature compensation withprogrammable compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
• Optional plug-in Ethernet interface (PNI module)
-
8/9/2019 68DCCAT
20/44
Input
Voltage 30-60V DC
Current
-
8/9/2019 68DCCAT
21/44
-
8/9/2019 68DCCAT
22/44
-
8/9/2019 68DCCAT
23/44
-
8/9/2019 68DCCAT
24/44
-
8/9/2019 68DCCAT
25/44
Description
The Power-One Xscend™ rectifier providesextremely reliable DC power in the highestpossible density. The module incorporatesthe latest in power monitoring solutionsthrough an internal microprocessor giving up
to the second updates to the systemcontroller and adjacent rectifiers. Thisguarantees tightly controlled load sharingamong rectifiers, and providing status andidentification information to the controller.
At only two rack units high, these compactrectifiers provide up to 1350W and fit up tofive rectifier modules in a 23in. rack or four modules in a 19in. rack. Designed withdiversity in mind, the Xscend rectifier is ableto operate in a complete range of indoor andoutdoor applications.
Features• Compact 2 rack unit height
• Front or mid-mountable• 208/240 single phase input
• Hot-swappable
• No adjustments required
• 90% typical efficiency
• Active and droop current sharing
• International Standards Compliance
Xscend Power
System
XR1448Rectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
26/44
Input
Model XR1448
Input Voltage 180-264VAC (47-63Hz)
Current (max.) 9.3A @180VAC
Inrush Current 25A @ 25°C
Power Factor >0.98 typical
Fuse 12.5A- line, 12.5A- neutral
Connection FCI power connector™
EMCEN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B
Output
Model XR1448
Output Voltage 42-58VDC
Power (max.) 1350W
Current 25A
Efficiency 90% typical
ToleranceVout +/- 1.0%, constant
voltage regulation
Transient
Response+/- 4% recovery time 2ms
Load Sharing +/- 5%
Ripple
-
8/9/2019 68DCCAT
27/44
DescriptionThe Power-One Xscend™ Controller System (XCS) provides comprehensive monitoring
and control for Power-One’s Xscend DC power systems. This digital controller monitors
total system conditions including DC voltage, rectifier current, rectifier temperature,
system capacity, battery parameters and circuit breaker status.
The XCS enables data storage of system configuration information such as battery type,
installation date and system commission date. Visual notification of alarm and warning
conditions are indicated by front panel LEDs, while descriptions of the alarms are provided
through an LCD, or as an option, may be accessed remotely through a modem or a
Network Interface (PNI) module.
To meet individual site requirements, the XCS contains a logic operator that can be
programmed to monitor and control specified requirements. This allows actions to be set,
alarms to be triggered, and outputs to be activated based on internal and external signal
monitoring, comparing and processing.
FeaturesUser controls and interfaces:
• Simple menu-guided operation using frontpanel mounted pushbuttons and an LCD
• User-selectable alarm parameters
• 40 event data logging
• Password controlled environment
• Multiple language options
• RS232 Interface and Form “C” dryalarm contacts
XCSController
www.power-one.com
Intelligent battery management:
• Temperature compensation withprogrammable compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
• Monthly data logging
-
8/9/2019 68DCCAT
28/44
Input
Voltage 18-72V DC
Current
-
8/9/2019 68DCCAT
29/44
-
8/9/2019 68DCCAT
30/44
Breaker Panels• Twenty positions for 5 to 100A
breakers
• Two positions for 125 to 250Abreakers
• A single position for a 450A or 525Abreaker
Low Voltage Disconnect• Optional Feature
• Provides protection against deepdischarge of batteries
• Emergency Power Off (EPO) switchprovided for emergency shutoff
• Remote contacts for EPO
Rectifier Shelves
• Interfaces with controller • 23” shelf allows up to 4rectifiers each
• Active current sharing• Single or three-phase input
DMAC Controller • Single point system voltage adjust
• Programmable timer for battery testor equalization
• Digital meters and test pointsmonitor plant voltages and current
• User-adjustable set points forunder/over voltage and low voltage
disconnect
NHS Rectifiers• 4 Rectifiers into each 3U 23” shelf• Available in 24 or 48VDC
• Thermal protection
• Fan cooled modules• Hot swappable• Low weight
• High reliability
System Components
Temperature Compensation• Works in conjunction with the DMAC
controller
• Automatically adjusts the float
voltage according to the ambienttemperature
• Sets off alarms when batterythermal runaway or sensor failure is
indicated
-
8/9/2019 68DCCAT
31/44
The Compac Power System is available in three different configurations, allowing customers to choose
the solution that is right for them. Each system uses the same basic components, systems include:
System Configurations
Compac Rack System™
Power System
48VDC 1200A System
The Compac full rack system
allows for up to 1200Aat 48V in a
single bay by using combinations
of distribution options. Each
rack is capable of holding up to
six rectifier shelves, a DMAC
controller panel, variousdistribution options and rear
connection points for external
battery strings.
48VDC 400A System
The Compac full rack system
with battery shelves allows for up
to 400A at 48V in a single bay.
Each rack is capable of holding
up to five battery trays for 100 to
150 Ah battery reserve strings.
24VDC 800A System
The Compac full rack system
without battery shelves allows for
up to 800A at 24V in a single bay.
Each rack is open at the bottom
to allow room for user installed
equipment.
-
8/9/2019 68DCCAT
32/44
-
8/9/2019 68DCCAT
33/44
Description
The Power-One NHS rectifier modulesprovide extremely reliable DC power output for use in our Compac™ series of power systems. NHS rectifier modulesare hot-swappable and provide a completeset of interface signals.
At only 3 rack units high, these compact
rectifiers allow for up to four modules ineach 23in. rack and provide up to 50A at48V or up to 100A at 24V. With full power available up to 50°C, these rectifiers areideal for any indoor and outdoor applications.
Features
• Compact 3 rack-unit height
• 24V and 48V rectifiers
• 50A output at 48V
• 100A output at 24V
• 180-264 single or three phase inputs
• Hot-Swappable, plug-and-play rectifiers
• High power density (9.8W/in3)
• High reliability, >700,000 hours MTBF
• Power factor correction
• Active current sharing
• International Standards Compliance
NHSRectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
34/44
Input
Model NHS24/100 NHS48/50
InputVoltage 180 - 264V AC single phase, (50-60Hz)
Current 15A @ 230V 15A @ 230V
Soft Start 0.99 (50-100% load)
AC
Transient3000V, 2 Joules
Output
Mechanical
Dimensions5 x 5 x 12.25 in.
(12.7 x 12.7 x 31.1cm )
Weight 12.6 lbs.
Cooling Fan
Other Technical Data
Model NHS24/100 NHS48/50
Power (max.) 2400W 2400W
Output
Voltage25-29V DC 51-59V DC
Current (max.) 100A 50A
Efficiency(@ 40-90%Load)*
>86% >86%
Voltage
Regulation+/- 0.4%
TransientResponse
+/- 4% at load variation 10-90%or 90-10%, recovery time 10ms
Load Sharing
-
8/9/2019 68DCCAT
35/44
Features• Single point system voltage adjust
• Programmable timer for battery test orequalization
• Digital meters and test points monitor plantvoltages and current
• User-adjustable set points for under/over voltageand low voltage disconnect
DMACController
Description
The Power-One Digital Meter, Alarm and Control Panel (DMAC) provides comprehensivemonitoring and control for Power-One’s Compac™ power systems. This digital controller
monitors system conditions including DC voltage and load current, while providing a
variety of alarm and control functions.
DMAC features include user-configurable battery testing, measurement of battery voltage
and current & battery equalization.
Front panel LED’s for alarms, including:• Equalize alarm
• OV/UV alarm• Major alarm• Minor alarm• Rectifier fail
• Breaker alarm
www.power-one.com
-
8/9/2019 68DCCAT
36/44
Temperature Compensation
Other Technical Data
Operating
Temperature-0 to +50°C
Storage
Temperature-50 to +85°C
Humidity10-90% RH, operating, 5-95%
storage, non-condensing
Altitude
Range
13,000 ft., derate 7°C/100 ft.
above 8000 ft.
Overview
The temperature
compensation panel works in
conjunction with the DMACcontroller. Temperature
compensation automatically
adjusts the float voltage
according to the ambient
temperature.
Temperature
Compensation
Alarms
Alarms include temperature
delta, which indicates battery
thermal runaway and sensor
failure. In the event of a
sensor or panel failure, the
compensation defaults to the
normal float voltage set by thecontroller.
Interface
Note: All specifications are subject to change without notification.
Display Digital amp and digital volt meters
Digital Meters 3.5 digits, +/-2% accuracy
UV/OV
Adjustment
22V/29V for 24VDC +/- 1.5V
44V/58V for 48VDC +/- 1.5V
Equalization &
Battery Test
Timer Range
0.5 seconds to 130 hours
Current
Measurement
DC Shunt
1200A:50mA
User Controls
Timer reset button
System voltage adjustment
Normal/Bypass test switch
Equalize/Battery test switch
Equalize Under/Over voltage adjustment
Undervoltage/Overvoltage
Connection
Points
System voltage test points
System amperage test points
www.power-one.com11V0005-050 DMAC V3.0
DMACController
Alarms
Alarms
Equalize alarm
OV/UV alarm
Major alarm
Minor alarm
Rectifier fail
Breaker alarm
-
8/9/2019 68DCCAT
37/44
-
8/9/2019 68DCCAT
38/44
-
8/9/2019 68DCCAT
39/44
-
8/9/2019 68DCCAT
40/44
-
8/9/2019 68DCCAT
41/44
Description
The Power-One PMP 25 rectifier providesextremely reliable DC power in a compactmodule. Digital interfaces areincorporated using an RS485 data bus tocommunicate with the system controller and adjacent rectifiers guaranteeingtightly controlled load sharing amongrectifiers, and providing status andidentification information to the controller.
At only 4 rack units high, these compactrectifiers allow for up to five modules ineach 23in. rack (4 units in 19in. rack)providing up to 250A at 48V or up to 550Aat 24V. With full power available up to65°C, these rectifiers are ideal for bothindoor and outdoor applications.
Features
• Compact 4 rack-unit height
• 24V and 48V rectifiers
• 50A output at 48V
• 110A output at 24V
• 208 / 240 single phase input
• Hot-swappable rectifiers• No adjustment required
• High efficiency, up to 91%
• Active current sharing
• International standards compliance
Integrity-One™ Full
Height System
PMP 25Rectifier Module
www.power-one.com
-
8/9/2019 68DCCAT
42/44
Input
Model PMP 25.24 PMP 25.48
Input
Voltage
196 - 250V AC ±10% single phase,(44-66Hz)
176-160V AC at reduced output power
Current
(max.)
-
8/9/2019 68DCCAT
43/44
FeaturesUser controls and interfaces:
• Simple menu-guided operation using frontpanel mounted pushbuttons and an LCD
• User-selectable alarm parameters
• 40 event data logging
• Password controlled environment
• Multiple language options
• RS232 Interface and Form “C” dryalarm contacts
PCSController
Description
The Power-One Power Controller System (PCS) provides comprehensive monitoring and control for
a broad range of Power-One’s DC power systems. This digital controller monitors total system
conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery
parameters and circuit breaker status.
The PCS enables data storage of system configuration information such as battery type, installation
date and system commission date. In addition, the PCS is capable of monitoring up to 128 rectifiers
and 128 sub-controllers within a power system. Visual notification of alarm and warning conditions
are indicated by front panel LEDs, while descriptions of the alarms are provided through an LCD or
as an option may be accessed remotely through a modem or a Network Interface (PNI) module.
To meet individual site requirements, the PCS contains a logic operator that can be programmed to
monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and
outputs to be activated based on internal and external signal monitoring, comparing and processing.
Intelligent battery management:
• Temperature compensation withprogrammable compensation factor
• Automatic and manual load testing
• Battery voltage and symmetry monitoring
• Capacity testing
• Low voltage disconnect
• Monthly data logging
www.power-one.com
-
8/9/2019 68DCCAT
44/44
Input
Voltage 18-72V DC
Current