    INTRODUCTION

    A harmonic of a wave is a

    component frequency of the

    signal that isan integer multiple of

    the fundamental frequency,

    i.e. if the fundamentalfrequency is f, the harmonics

    have frequencies 2f, 3f, 4f, . . .

    etc

    http://en.wikipedia.org/wiki/Wavehttp://en.wikipedia.org/wiki/Frequencyhttp://en.wikipedia.org/wiki/Integerhttp://en.wikipedia.org/wiki/Fundamental_frequencyhttp://en.wikipedia.org/wiki/Fundamental_frequencyhttp://en.wikipedia.org/wiki/Integerhttp://en.wikipedia.org/wiki/Frequencyhttp://en.wikipedia.org/wiki/Wave
  • 7/28/2019 5th March Sud Khatri

    2/15

  • 7/28/2019 5th March Sud Khatri

    3/15

  • 7/28/2019 5th March Sud Khatri

    4/15

    PROBLEM

    1) East Bus harmonic filter experienced failureof fifth harmonic reactor, fuses, and capacitor

    cans. 2) West Bus harmonic filter experienced

    failure of fuses and capacitor cans.

  • 7/28/2019 5th March Sud Khatri

    5/15

    SOLUTION

    The East Bus fifth harmonic filter may not be

    filtering properly for several possible reasons.

  • 7/28/2019 5th March Sud Khatri

    6/15

    REASONS GIVEN

    First, measurements have shown an unbalance inthe phase currents to the entire filter shown anunbalance in the phase currents bank of 12.7%13.1%. Phase-B current is 282 A, while Phase-A

    and Phase-C are 347 and 343 A, respectively, onaverage. So some capacitors were underratedand some were overrated.

  • 7/28/2019 5th March Sud Khatri

    7/15

    REASONS GIVEN

    Second, the inductance of the East Bus fifth

    harmonic was estimated to be 25 mH, which

    gives a tuned frequency of 3.9th harmonic.

    No design data were available from the

    manufacturer, and the rewind shop did not

    conduct an inductance test on either the

    rewound or undamaged reactors

  • 7/28/2019 5th March Sud Khatri

    8/15

    REASONS

    Voltage rating of the capacitors was

    underrated for applications at 13.8 kV, putting

    undue stress on the for applications at 13.8

    kV, putting undue stress on the capacitors in

    the steady state and providing no margin for

    transient conditions. Since the rating of

    voltages had increased since installation.

  • 7/28/2019 5th March Sud Khatri

    9/15

    SOLUTION GIVEN

    The capacitors which were underrated ,were

    replaced by new capacitors.

    The inductance which was making filter to

    remove 5th harmonic,was dimensionally

    corrected to make it tuned to 5th harmonic.

  • 7/28/2019 5th March Sud Khatri

    10/15

    Problems Caused by

    Harmonics

    Transformer over-heating

    Circuit breaker trips

    Fuse blowing

    Equipment malfunction

    Increased KVA demand

    rms and peak

    Total Power Factor reduction

    Wasted energy

  • 7/28/2019 5th March Sud Khatri

    11/15

    OTHER POSSIBLE SOLUTIONS

    We can use harmonic filter at transformer

    end, so that transmission line is free from

    carrying harmonic current.

  • 7/28/2019 5th March Sud Khatri

    12/15

    OTHER POSSIBLE SOLUTIONS

    We can also use harmonic filter at the load

    end ,so that the harmonics which were

    introduced at transmission line can also be

    removed.

  • 7/28/2019 5th March Sud Khatri

    13/15

    OTHER POSSIBLE SOLUTIONS

  • 7/28/2019 5th March Sud Khatri

    14/15

    OTHER POSSIBLE SOLUTIONS

    We can use power quality meters at regular

    distances in system to measure wave

    distortion quantitatively.

  • 7/28/2019 5th March Sud Khatri

    15/15

    OTHER POSSIBLE SOLUTIONS

    The rating of inductance and capacitance

    used should be such that they can withstand

    the temporary surges, so that they do not

    damage during surges.