DMD & Associates Ltd. #12-17358 104A Avenue
Surrey, BC V4N 5M3 604/589-9010
Fax 604/589-9012
40600-RE-RPT-55075 Revision 0 February 2018 Lighting Impact Statement
Date: February 2018
To: Hemmera Envirochem Inc. 18th Floor, 4730 Kingsway Burnaby, BC V5H 0C6
From: Don McLean, DMD & Associates Ltd.
File: File: 5079-15
Re: Lighting Impact Statement - BHP Potash Export Facility at Fraser Surrey Docks
DMD & Associates Ltd. (DMD) was retained as a qualified lighting professional firm by Hemmera
Envirochem Inc. (Hemmera) to provide an impact statement for the proposed lighting design for the
proposed potash export facility (Project) at Fraser Surrey Docks (FSD) by BHP Billiton Canada Inc. (BHP).
This impact statement:
• Supports the Project application for a Project and Environmental Review (PER) permit that wouldbe issued by the Vancouver Fraser Port Authority (VFPA).
• Presents a summary of the review of general Project lighting design, light trespass, and lightpollution (based on drawings and luminaire information provided in Appendix A and D (AusencoLighting Drawings), Appendix B (Lighting Estimate Spreadsheet), and Appendix C (FixtureProduct Sheets) for consistency with the PER Guidelines - Lighting (VFPA 2015).
• Summarises the review of potential adverse effects of Project-related exterior lighting on adjacentresidential areas and general areas offsite.
The preliminary lighting design was prepared by Ausenco, the Project’s engineering firm. According to the
VFPA Guidelines: “Lighting Plans should be designed to minimise glare, light trespass, energy
conservation, and to maintain dark skies while ensuring safety and security.” (VFPA 2015)
The reference lighting specifications and consideration of best practices used for this impact statement are
presented as follows:
• BHP Electrical Design Criteria
• Canada Occupational Health and Safety Regulations (SOR/86-304) (COHSR).
1.1 GENERAL LIGHTING DESIGN
Table 1 summarises the preliminary design drawings for consistency with VFPA guidance on lighting locations and heights, illumination types, lighting intensity, controls, and cumulative lighting data.
BHP Billiton Canada Inc DMD Lighting Impact Statement - 2 - February 2018
Table 1 Lighting Plan Comparison with Vancouver Fraser Port Authority Lighting Guidance
VFPA Guidance BHP Ausenco Lighting Reference1 Comments Meets VFPA
Guidance?
Location of all current and proposed exterior lighting fixtures and proposed power source
Drawings 101051-03-EL-DWG-00101, 103, 104, 152, and 153 (Appendix A) Lighting Estimate Spreadsheet. (Appendix C) Power Distribution Drawings 101051-03-EL-DWG-00151 and 155 (Appendix D)
Mounting heights defined on lighting spreadsheet Yes
Type of illuminating devices, fixtures, lamps, supports, reflectors, and other devices – including the cut-off characteristics
Drawings 101051-03-EL-DWG-00101, 103, 104, 152, and 153 (Appendix A) Lighting Estimate Spreadsheet. (Appendix C) Fixtures are Type A to Type D as shown on the Lighting Drawings (Appendix A), the Fixture Product Sheets (Appendix B) and the Lighting Estimate Spreadsheet (Appendix C)
Most fixtures on conveyor are “hazardous location” rated (Type B and C mounted on stanchions) so they have no “full cut-off classification” (VFPA 2015); however, they will have an up-light shield as recommended to limit sky-glow. All floodlights that can be aimed (Type D) have upper visor to limit upward light trespass and sky-glow. Type A fixtures mounted on buildings will have full cut-off optics.
Yes
Lamp source type (e.g., high-pressure sodium, LED, etc.), lumen output, and wattage
Fixture Product Sheets (Appendix B) and the Lighting Estimate Spreadsheet (Appendix C)
All fixtures will be LED and 4000 Kelvin (K) for improved colour rendition
Yes
Expected change in wattage for site
Drawings 101051-03-EL-DWG-00101, 103, 104, 152, and 153 (Appendix A) Lighting Estimate Spreadsheet. (Appendix C)
6 high masts totaling 42 kW will be removed and approximately 26 kW of new lighting will be added, resulting in no significant additional load.
Yes
Fixture mounting height and orientation, with distance noted to the nearest property line
Drawings 101051-03-EL-DWG-00101, 103, 104, 152, and 153 (Appendix A) Lighting Estimate Spreadsheet. (Appendix C)
The closest property is 230 m to the east. Yes
Types of timing devices used to control the hours set for illumination, as well as the proposed hours when each fixture will be operated
Lighting Estimate Spreadsheet. (Appendix C)
Each fixture will have a timing device to control duration of illumination and hours of operation. Light fixtures will be photocell-activated to operate from dusk to dawn. Lighting will also be dimmed during periods of non-operation as set by the operators.
Yes
Cumulative lighting data for the overall lighting installation including design power consumption, average illumination, and uniformity levels
Drawings 101051-03-EL-DWG-00101, 103, 104, 152, and 153 (Appendix A) Lighting Estimate Spreadsheet. (Appendix C)
Uniformity1 level will be limited to 4:1 ratio (average to min). Yes
Notes: kW - kilowatt; LED - light-emitting diode; m – metre; For additional details, refer to: BHP Ausenco Lighting Drawings (Appendix A); Lighting Estimate Spreadsheet (Appendix B); Fixture Product Sheets (Appendix C); Ausenco Power Distribution Drawings (Appendix D)
1 Uniformity is the evenness of the light over a given area. Even (uniform) lighting throughout an area has a uniformity ratio of 1:1. In
this case 4:1 means a ratio between the average illumination calculation points over the given area and the minimum calculation point over that area. The goal being to create uniform lighting over given area.
BHP Billiton Canada Inc DMD Lighting Impact Statement - 3 - February 2018
The design follows general guidelines for shiploader lighting, as presented below:
• Walkways are illuminated for safety of personnel. Fixtures located along the handrail will direct light to the grated walking areas only, and will be controlled with motion sensors and timers to limit the time that they are turned on. Only main access ways will be equipped with automated lights, and secondary access platforms will require lights to be turned on manually. Lighting is designed to be switched on and off by an operator.
• The end of the loader spout in the hatch must be visible at night, and will be illuminated by an array of fixtures on the end of the loader boom. These fixtures will be 4-260W light-emitting diode (LED) (Type D) mounted above the spout, and will only turn on during loading.
• The shiploader travels on rails, and will have illumination around the wheel areas for safety of personnel. Shiploader lighting will be mounted to direct light downward and prevent light pollution. Type D (6 - 79W) fixtures will be mounted above the wheel to provide approximately 300 Lux of illumination at the wheels for worker safety. In addition, both leading and trailing legs of the shiploader will have warning strobes (amber) that will flash when the machine is moving.
• The top of the shiploader mast will be equipped with aviation hazard indicator lights, but no other lights will be used on the mast to avoid creating a visual nuisance.
1.2 DESIGN CRITERIA
The Project site lighting must meet COHSR, Part VI, Schedule B for worker safety, which define target
levels of 100 lux for frequently used stairways and 10 lux for outside areas where activity is low. BHP design
criteria highlighted in Table 2 have been used for Project design to meet the COHSR while ensuring that
the site will not be overly lighted. Motors and moving parts, as described in the BHP Electrical Design
Criteria, is a defined area and activity for this Project, and is therefore included in the design criteria in
Table 2; however, the COHSR has no specific reference for motors and moving parts. The 300 lux lighting
design criteria highlighted in Table 1 is considered reasonable for this activity for the following reasons:
• These areas make up a very small percentage of the overall lighting.
• Lighting will be directed downwards to very specific areas.
The documents provided in the appendices define the basis of the Project lighting design. For offsite
lighting effects, the light levels are reduced via full cut-off optics and visors. In addition, lighting will be
turned off or dimmed when the facility is not in use. The Project Electrical Design Criteria (BHP 2017)
listed in Table 2 are suitable for the site and activities being undertaken.
BHP Billiton Canada Inc DMD Lighting Impact Statement - 4 - February 2018
Table 2 Project Electrical Design Criteria
Area or Facility Target Level (Lux)
Minimum Level (Lux)
Office Areas
Regular office work, active filing, reading good reproductions, writing, etc. 500 300
Areas not involving prolonged reading such as conference rooms, inactive files 300 100
Corridors and Stairways 100 500
Computer and Control Rooms
Lighting shall be regulated to maintain suitable contrast. Track lighting with dimming control shall be provided. 500 300
Operational Areas
Process Areas (Inactive) and mine areas as required 50 20
Motors and Moving Parts/ Active areas 300 200
Stairways 100 50
Electrical Rooms 300 200
Cable Pull Rooms 75 50
Shops
Active Traffic Areas 200 150
Bench and machine Work 5001 300
Storage Areas and Warehouses
Inactive 50 20
Active (rough bulky) 100 50
Active (medium) 200 100
Laboratory 7501 500
Outdoor Lighting
Parking Lot 10 5
Roads Around Buildings 10 5
General 10 5
Note: 1 Target level to be implemented by task lighting as required.
BHP Billiton Canada Inc DMD Lighting Impact Statement - 5 - February 2018
1.3 LIGHT SPILL AND TRESPASS
To assess potential light trespass effects from Project lighting on local residents, it is appropriate to define
the level of spill light (lux) offsite at local residences and any defined areas of environmental sensitivity.
Spill light level limits are defined in Table 26.5 of the Illuminating Engineering Society of North America
(IESNA) Lighting Handbook (DiLaura et al. 2011)). For this assessment, no additional lighting around the
rail loop is anticipated to be required. For the Project site, local residences were determined to be a Lighting
Zone 3, which limits spill light to 3 Lux or less in the vertical plane at the local residences.
Impacts on fish and wildlife have been reviewed and assessed. However, research is limited with respect
to two key factors: dosage (amount of light) and duration (how long lighting is on for) as it relates to impacts
on a given species. Effects of lighting on fish and wildlife are much more difficult to assess than effects on
humans, therefore the impact on the majority of species are not well known with respect to dosage and
duration. That said, based on the additional lighting proposed for the site the dosage on the shoreline and
Fraser River would be very low and therefore is considered insignificant.
Light trespass from the proposed lighting will be very limited, given that it will be:
• Located 230 metres (m) or more from local residences
• Equipped with light shields
• Directed away from local residences.
1.4 SKY GLOW
Urban sky glow is a factor that can affect views of the night sky as well as sensitive receptors (e.g., wildlife),
and thus influence their behaviour. Species potentially sensitive to light were reviewed by Hemmera in the
aquatics assessment (see Attachment 4.2-W of the Application) and the terrestrial assessment
(Attachment 4-2.X of the Application). Based on Hemmera’s assessment of wildlife potentially sensitive to
lighting, no adverse effects were identified. The majority of fixtures shown on the Project lighting drawings
(Appendix A) will be aimed downwards to limit up-light2. Where floodlights are proposed, visors will be
added as per the recommendations in IESNA RP-33 Lighting Exterior Environments. Light will be reflected
off surfaces, such as pavement and steel structures, and redirected into the sky; however, this is common
for lighting installations. The visors are effective in minimising sky-glow to the greatest extent practical.
2 Uplight – The percentage of lumens distributed above the luminaire between 90 and 180 degrees vertical (IESNA
RP-33-14)
BHP Billiton Canada Inc DMD Lighting Impact Statement - 6 - February 2018
Luminaires with optical systems which limit up-light have been proposed for the Project. These limiting
systems are referred to as full cut-off optics.
Light will be reflected off surfaces, such as pavement and steel structures, and redirected into the sky,
however this is common for lighting installations. The use of full cut-off optics is effective in minimizing sky-
glow to the greatest extent practical.
1.5 SUMMARY AND CONCLUSIONS
The Project Lighting Plan and design meets VFPA guidance for the following:
• Location of all current and proposed exterior lighting fixtures on the premises, as well as the location of the proposed power source
• Type of illuminating devices, fixtures, lamps, supports, reflectors, and other devices – including the cut-off characteristics
• Lamp source type (e.g. high-pressure sodium, LED, etc.), lumen output, and wattage
• Expected change in wattage for site
• Mounting height with distance noted to the nearest property line for each fixture, with orientation noted
• Types of timing devices used to control the hours set for illumination, as well as the proposed hours when each fixture will be operated
• Cumulative lighting data for the overall lighting installation including design power consumption, average illumination, and uniformity levels.
BHP Billiton Canada Inc DMD Lighting Impact Statement - 7 - February 2018
DMD concludes that the lighting design and proposed operation for the Project is consistent with VFPA
guidance and industry practice, utilises energy-efficient LED sources, and minimises the potential for
adverse lighting effects to the greatest extent practical while also taking into account worker safety
requirements.
We trust that this report is satisfactory to your requirements.
Yours sincerely, DMD & Associates Ltd.
Don McLean Attached Lighting Drawings (Appendix A) Fixture Cut Sheets (Appendix B) Fixture Spreadsheet (Appendix C) Power Drawings (Appendix D)
BHP Billiton Canada Inc DMD Lighting Impact Statement - 8 - February 2018
1.6 REFERENCES
BHP Billiton Canada Inc. Design Criteria Electrical Rev. 2 (40001-EL-DES-40003).
DiLaura, D.L., K.W. Hauser, R.G. Mistrick, and G.R. Steffy. The Lighting Handbook. 10th Edition. Reference
and Application. Illuminating Engineering Society. 1,328 pp. ISBN-13: 978-0-87995-241-9.
Vancouver Fraser Port Authority (VFPA). 2015. Project and Environmental Review: Guidelines – Lighting.
July 2015. Available at https://www.portvancouver.com/wp-content/uploads/2015/05/PER-
Lighting-Guidelines-Final-2015-07-08.pdf. Accessed October 2017.
APPENDIX A Lighting Drawings
W
W
E
T
T
T T T T T T T T T T T T T T T T T T T T
E E E EE E E E
E E E EE E E E
E
E
E
E
E
EE
E
EE
EE
EE
E E EE E E
E
E
E
E
E
E
E
E
E EE
E
E
E E
EE
E
E
E
E
E
E
E
E
E E EE E EE E EE E E EE E E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
EE
E
E
E
E
E
E
E
E E
EE
EE
EE
E E
E
EE
E
E
E
E
E
E
E
E
E
E E
E
E
EE
EE
EE
E
E E E
EE
E E E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
EE
E
EE
E
EE
E
E
E
E
E
E
E
E
EE
EE
E E
E
E
E
E E E
E E E
E E
E
E E
E E E
E
E
EE
E
E
E
E E
E E EE
EE
E E E
E E E
EE
E
EE
EE
EE
EE
E
E E E
EE
E
E E E
E E
EE
E E E E E E
E
E
E E E E
E
E
E
EE
E
E
E
E E E E E E E E E E
E E E
EEE
EE
E
EE
POTASH STORAGEBUILDING (NOTE 3)
LEGEND:REMOVE LIGHT FIXTURES, POLES AND WIRING(NOTE 5)
NOTES:
1. COVERED CONVEYOR: STANCHION MOUNTED LIGHT FIXTUREc/w SWIVEL POLES, MOUNTED EVERY 9m ALONG WALKWAY ONBOTH SIDES OF CONVEYOR.
2. TRANSFER TOWER: STANCHION (c/w SWIVEL POLES) ORCEILING MOUNTED LIGHTS AT STAIR LANDING.
3. BUILDINGS: WALL MOUNTED LIGHT FIXTURES ABOVE DOORENTRANCES. INTERIOR LIGHT FIXTURES NOT SHOWN FORCLARITY.
4. SHIPLOADER c/w LIGHTS, SEE DWG. 40600-EL-DWG-00104.
5. EXISTING HIGH MAST LIGHTS, POLES AND WIRING TO BEREMOVED.
6. THIS PORTION IS UNDERGROUND,
F R A S E R S U R R E Y D O C K S
CANADIAN NATIONAL RAILWAYBURLINGTON NORTHERN RAILWAY
LED WALL MOUNTED FIXTURES, SEE NOTE 3(HOLLOPHANE PLED2)
B
NOTE 5(TYP. 3 )
LED STANCHION/CEILING MOUNTED LIGHT FIXTURES,SEE NOTE 1 & 2 (HOLLOPHANE PLED2)
C
LED STREET LIGHT MOUNTED AGAINST BUILDING(HOLLOPHANE ATB2)
A
DUMPER PIT CONVEYOR(NOTE 1, TYP.)
OUTFEED CONVEYOR STORAGEFEED CONVEYOR
SHIPLOADER(NOTE 4)
OUTLOADINGCONVEYOR
WHARF CONVEYOR
RAIL CAR UNLOADINGSTATION (NOTE 3)
ELECTRICAL ROOM 1(NOTE 3, TYP.)
ELECTRICAL ROOM 2
ELECTRICAL ROOM 3
TRANSFER TOWER 1(NOTE 2, TYP.)
TRANSFER TOWER 2
TRANSFER TOWER 3
TRANSFER TOWER 4
LED SMALL FLOOD LIGHT FIXTURES(HOLLOPHANE PSLED)
D
NOTE 5(TYP. 3 )
EXISTING HIGH MAST LIGHT FIXTURES
10 LUX - ROAD WAY
100 LUX - WALKWAYS/STAIRS
300 LUX - MOVING PARTS / MOTOR
LED MEDIUM FLOOD LIGHT FIXTURES(HOLLOPHANE PMLED)
E
NOTE 6
A
A
A
A
A
A
A
A
A
D
D
B
B
B
B
B
B
BB
A
A
STACKINGCONVEYOR
RECLAIMCONVEYOR
PORTALRECLAIM
RAILCAR DUMPER BUILDING - TYPICAL ELEVATIONSCALE 1:100
RAILCAR DUMPER BUILDING - TYPICAL SECTIONSCALE 1:100
℄ RAIL
11080
7400
6200
4971
5832110461 41000
466661000
RAILCAR DUMPER BUILDING - SECTION AT DISCHARGE ENDSCALE 1:100
℄ RAIL
RAILCAR GATE OPENER411310A-AC-00001
RAILCAR GATE VIBRATOR411310A-CVI-00001
DUMPER PIT FEEDER411410A-FD-00001
DUMPER PIT GRIZZLY411320A-SEP-00001
DUMPER PIT CONVEYOR411420A-CV-00001
RAILCAR GATE CLOSER411310A-AC-00002
RAILCAR GATE OPENER411310A-AC-00001
RAILCAR GATE VIBRATOR411310A-CVI-00001
DUMPER PIT FEEDER411410A-FD-00001
DUMPER PIT GRIZZLY411320A-SEP-00001
RAILCAR GATE CLOSER411310A-AC-00002
4700
6200
11080
DUMPER PIT CONVEYOR411420A-CV-00001
DUMPER PIT FEEDER411410A-FD-00001
NOTES:1. FOE LIGHTING LEGEND, SEE DWG 40600-EL-DWG-00152.
2. FLOODLIGHT FIXTURES TO PROVIDE LIGHTING AT TRAIN ENTRANCE AND EXIT.
3. INTERIOR LIGHTING NOT SHOWN FOR CLARITY.
RAILCAR GATE OPENER411310A-AC-00001
RAILCAR GATE CLOSER411310A-AC-00002
RAILCAR GATE VIBRATOR411310A-CVI-00001 (F/S)
7400
5590
4971
340
D NOTE 2 (TYP.)
D
STACKING CONVEYOR 412110A-CV-00003SCALE 1:500
STORAGE FEED CONVEYOR 411440A-CV-00002SCALE 1:500
DUMPER PIT CONVEYOR 411420A-CV-00001SCALE 1:500
BELT U/S
BELT U/S
T.O.C.REF. EL. -13,000m
NOM. GRADEREF. EL. 0,000m ℄ TAIL PULLEY
℄ HEAD PULLEY149688
2350
0
BELT TRAVEL
BELTTRAVEL
LOADINGZONE
HORIZONTALTAKE-UP
℄ TAIL PULLEY
BELT U/S
LOADINGZONE
237214
3000
0
3017
7
BELT U/S
℄ HEAD PULLEY
7.25°
NOM. GRADEREF. EL. 0,000m
NOM. GRADEREF. EL. 0,000m
BELT U/S
℄ TAIL PULLEY℄ HEAD PULLEY
BELT TRAVEL
LOADINGZONE
TAKE-UP
3163
℄ PULLEY℄ PULLEY
BELT U/S
TRIPPERMAINTENANCE POSITION
WEIGH SCALE - TO SHED411420A-FTW-00001
KEY PLANSCALE 1:2500
414120A-CV-00005
PORTAL RECLAIMERMAINTENANCE POSITION
GALLERY
GALLERY
1150
0
1200
0
3157
6
2683
7
TRANSFER TOWER 1411430A-BLD-00003
TRANSFER TOWER 1411430A-BLD-00003
TRANSFER TOWER 2411450A-BLD-00004
TRANSFER TOWER 2411450A-BLD-00004
413210A-CV-00004412110A-CV-00003 411440A-CV-00002
4114
20A-C
V-000
0141
4130
A-CV
-000
06
414150A-CV-00007
GALLERY
1. FOE LIGHTING LEGEND, SEE DWG 40600-EL-DWG-00152.
2. STANCHION MOUNT LIGHT FIXTURES, MOUNTED EVERY 9m ONBOTH WALKWAYS ON SIDE OF CONVEYOR. ONLY ONE SET OFLIGHTS SHOWN FOR CLARITY.
3. LIGHT FIXTURES MOUNTED ON STAIR PLATFORM AND ENTRANCE(TYP. FOR TRANSFER TOWERS).
4. INSIDE STORAGE BUILDING.
NOTES:
CONVEYER BELOW GROUND
C
NOTE 4
C
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
CC
C
NOTE 2 (TYP.)
5°
B
B
NOTE 3
x14
C
NOTE 3
x6
℄ HEAD PULLEY
TAKE-UP
RECLAIM CONVEYOR 413210A-CV-00004SCALE 1:750
4742659000℄ TAIL PULLEY TAKE-UP TOWER ℄ ℄
NOM. GRADEREF. EL. 0,000m
4000
4750 6150
449774 EST. PORTAL RECLAIMER LOADING ZONE
DRIVEBELT TRAVEL
262735
229362890173860 EST. TRIPPER TRAVEL DISTANCE
NOM. GRADEREF. EL. 0,000mBELT U/S
3950
1530
1574
0 EST
.
℄ HEAD PULLEY℄ TAKE-UP TOWER
℄ PULLEY ℄ PULLEY ℄ TAIL PULLEY
BELT TRAVEL
TAKE-UP
WHARF CONVEYOR 414150A-CV-00007SCALE 1:500
OUTLOADING CONVEYOR 414130A-CV-00006SCALE 1:500
BELT TRAVELLOADING
ZONE℄ TAIL PULLEY
NOM. GRADEREF. EL. 0,000m CLEAR FOR RAILCAR TRACKS
℄ HEAD PULLEY
℄ TAKE-UP
OUTFEED CONVEYOR 414120A-CV-00005SCALE 1:500
LOADINGZONE
206000
TAKE-UP TOWER ℄ ℄
46003000
℄ TAIL PULLEY
8°
4500
6000
NOM. GRADEREF. EL. 0,000m
℄ HEAD PULLEY
BELT TRAVEL
WEIGH SCALE - RECLAIM414120A-FTW-00002
OFF SPEC STORAGE
WEIGH SCALE - TO SHIPLOADER414130A-FTW-00003
MID-BELT PLOW - OFF SPEC TRANSFER414130A-CVBT-00001
3020001065
718903153130842129971542115766
1259
2
GALLERY - TYPICAL SECTIONSCALE 1:100
CABLE TRAYS(REF.)COVER(TYP.)ACCESS BOTH SIDES(TYP.)
℄ GALLERY
SPILL TRAY(TYP.) 15
00
1400
1500
TRANSFER TOWER 3414110A-BLD-00005
TRANSFER TOWER 3414110A-BLD-00005
TRANSFER TOWER 1411430A-BLD-00003
TRANSFER TOWER 4414140A-BLD-00006
1410
0
TRANSFER TOWER 4414140A-BLD-00006
COVER
GALLERY
GALLERY
NO CLADDING(TYP.)
BELT U/S
BELT U/S
5745OVERALL
4112
OVER
ALL
27000MAINTANCE AREA
NOTES:1. FOR LIGHTING LEGEND, SEE DWG 40600-EL-DWG-00152.
2. STANCHION MOUNT LIGHT FIXTURES, MOUNTED EVERY 9m ONBOTH WALKWAYS ON SIDE OF CONVEYOR. ONLY ONE SET OFLIGHTS SHOWN FOR CLARITY.
3. LIGHT FIXTURES MOUNTED ON STAIR PLATFORM AND ENTRANCE(TYP. FOR TRANSFER TOWERS).
4. INSIDE STORAGE BUILDING.
5. SHIPLOADER SHOWN TWICE TO INDICATE 2 POSSIBLEPOSITIONS.
C C C C C C C C C C C C C C C C
C C C C C C C C C C C C C C C C C C C
C
C
C
C
CC
C
CB
NOTE 3
x6
C
C
C
C
CC
CC C C C C C
C C C
NOTE 5NOTE 5
CC
CC
CC
CC C C C C C C C C C C
C C C C C C C C C C C C C C C C C C C C C CC
C
B
NOTE 3
Cx2
C C C C C
NOTE 4
C B
NOTE 3x4
x
x
x
x x x x x x x x x
xx
x x x x x x x x x
xx
xx
xx
xx
xx
xx
xx
xxxxxxxxxxxxxxxxxxxx
x
SHIPLOADER - GENERAL ARRANGEMENT - PLANSCALE 1:750
169800 EST. TRAVEL DISTANCE
TRANSFER TOWER 4414140A-BLD-00006
WHARF CONVEYOR414200-CV-00007
BELT TRAVEL
BELT TRAVEL
℄ SHIPLOADER CONVEYOR
24384 (80'-0")
SHIPLOADER - ELEVATION
24500SHIPLOADER SHUTTLE DIST.
℄ RAIL ℄ RAIL
TRANSFER TOWER 4414140A-BLD-00006
T.O. WHARF/ PILE CAPEL. 4.85m
℄ RAIL ℄ RAIL
SHIPLOADER414310A-SLS-00001
WHARF CONVEYOR TRIPPER414150A-CV-00007
CASCADINGCHUTE
82,000 DWT KAMSARMAXPARTIAL DRAFT
20,000 DWT HANDY SIZELOADED DRAFT
BELT U/SEL. +20.240m
T.O. DECKEL. +4.850m
EXISTINGBERTH
58350 EST. TRIPPER LENGTH
1872
0 EST
. STR
UCTU
RE H
EIGH
T
SECTION1:250
SECTION1:250
CC
CC
1. FOR LIGHTING LEGEND, SEE DWG 40600-EL-DWG-00152.
2. LIGHT FIXTURES MOUNTED ON WALKWAY & STAIRS ONSHIPLOADER.
3. LIGHTS MOUNTED TO PROVIDE LIGHTING TO TRAVELLINGSHIPLOADER WHEELS.
4. SHIPLOADER SPOUT LIGHTS, 4 LIGHT.
5. LIGHT FIXTURES SHOWN ON DWG. 40600-EL-DWG-00103.
NOTES:
NOTE 3
NOTE 5
D
NOTE 3
D
D D
NOTE 3 (TYP. )
E E
C C C C C C
NOTE 2
NOTE 4
x2x2
D
APPENDIX B Fixture Cut Sheets
APPENDIX C Fixture Spreadsheet
LED
Wattage
Mounting
Height (m)
High mast lighting E -6 --- Existing --- n/a 30 n/a Removed existing high mast lighting for storage bldg. & shiploader.
Qty: est. 6.
Existing light wattage: TBD (est. 4000 W).E-room #1 (substation & storage)) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
E-room #1 (substation & storage)) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
E-room #2 (conveying) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
E-room #2 (conveying) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
E-room #3 (shiploader) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
E-room #3 (shiploader) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 4 0 Above door
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.9 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.1 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 9.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-1 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.1 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.1 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 9.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.9 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 11.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 12.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 12.9 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 13.6 0 Covered conveyor - lights on both side of conveyor
NotesAngleInterior/
Exterior
Lighting Estimate - FSD
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 14.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 15.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 15.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 17.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 17.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 18.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 19.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 19.7 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 20.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 21.1 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 21.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 22.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 23.1 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 23.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 24.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 25.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 25.9 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 26.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 27.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 27.9 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 28.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 29.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 30.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 30.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 31.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-2 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 32.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 5.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-5 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.3 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 9.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 11.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 13.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 14.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.8 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 7.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 9.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.4 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 11.8 0 Covered conveyor - lights on both side of conveyor
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 13.2 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 14.6 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-6 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 16.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 3.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.5 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Conveyor BL-7 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.0 0 Covered conveyor - lights on both side of conveyor
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Transfer Tower Entrance
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Stairs Platform
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.2 0 Stairs Platform
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Stairs Platform
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.8 0 Stairs Platform
Transfer Tower TT-01 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 10.0 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Transfer Tower Entrance
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.2 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.7 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 11.0 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 13.2 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 15.5 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 17.8 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 20.0 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 22.2 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 24.5 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 26.7 0 Stairs Platform
Transfer Tower TT-02 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 29.0 0 Stairs Platform
Transfer Tower TT-03 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Transfer Tower Entrance
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
Transfer Tower TT-03 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Stairs Platform
Transfer Tower TT-03 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.2 0 Stairs Platform
Transfer Tower TT-03 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Transfer Tower Entrance
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 2.0 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 4.2 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 6.5 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 8.8 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 11.0 0 Stairs Platform
Transfer Tower TT-04 E 1 PLED2 10L 5K AS UN NA G L5 SH C 98 13.2 0 Stairs Platform
Storage Bldg n/a 0 - 0 0.0 Exterior: west side - use existing high-mast lighting
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Storage Bldg E 1 ATB2 40 40BLEDE10 MVOLT R2 A 133 10.0 0 Exterior: wall-mounted streetlight (north, east, south side of bldg.)
every 48 m.
Shiploader E 20 PLED2 10L 5K AS UN NA G L5 SH C 98 20.0 0 Shiploader - Stairs & Platform (assumption: 20 lights)
Shiploader E 6 PSLED PK2 MVOLT MFL 40K D 79 3.0 0 w/shieldsShiploader - Drive wheels (assumption: 6 lights)
Shiploader E 4 PMLED 6 4K 10A 55 E 261 18.0 0 w/shieldsShiploader - Loading Spout (assumption: 6 lights)
Rail Car Dumper (railcar entrance) E 1 PSLED PK2 MVOLT MFL 40K D 79 8.0 30 w/shieldsAbove railcar entrance & exit
Rail Car Dumper (railcar entrance) E 1 PSLED PK2 MVOLT MFL 40K D 79 8.0 30 w/shieldsAbove railcar entrance & exit
Rail Car Dumper (door) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 2.0 0 Above door
Rail Car Dumper (door) E 1 PLED2 10L 5K AS UN NA G L5 SH B 98 2.0 0 Above door
Total 508 26034
Lighting fixture location is based on Universal Transverse Mercator system. Zone is NAD 83.
Elevation is relative to ground.
LED
Wattage
Mounting
Height (m)
NotesAngleInterior/
Exterior
Fixture
TypeLocation Qty Fixture model (Americain Electric/Holophane)
(see https://en.wikipedia.org/wiki/Universal_Transverse_Mercator_coordinate_system)
Conveyor BL-1 is partially underground. Underground portion does not
contribute to light trespass
Annual hours - numbers of hours lights are switched on in a year.
Exterior: Photocell control - 12 hours / day. Total: 4380 hours
Interior: 24 hours / day. Total: 8760
Localized motion sensor to turn lights off when not in use. Assume 60% off.
Based on BHP Illumination Level table (Elect DC, Table 7-9), target vs minimum light level is 0.6 to 0.5. Local dimming of 0.6 is acceptable when area not active.
APPENDIX D Power Drawings
W
W
E
T
T
T T T T T T T T T T T T T T T
E E EE E E
E E EE E E
E E
E
E
EE
EE
E
E EE E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E EE EE EE E EE E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
E
EE
E
E
E
EE
E
E
E
E
E
E
E
E
E
EE
EE
E E
E
E E
EE
E
E
E
E
E
E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
EE
EE
EE
E
E
E
E
E
E
EE
E
E
E
E E
EE
E
E
E
E
E E
E
EE
E
E
E
E E
E
E
E
E
E
E
E E
EE
E E
E E
E E E EEE
EE
E E
EE
E E
E E
EE
E E E E
E
E
E
E
E
E
E
E
E
E
EE
E
EE
E
E E E
E
E
EE
E
E
E E E E E E E
E E
EE
W W W W WW
W
W
W
WW
WW
WW
W
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SAN
T
TT
E
E
E E
E
E
E
E
E
E E E
E
E
E
E
E
T
T
T
T
T
E
E
E
E
E
E
LEGEND:25kV POWER AND F/O CABLESIN UNDERGROUND DUCT BANKS
POTASH STORAGEBUILDING (NOTE 5)
PIT CONVEYOR
OUTFEED CONVEYOR
STORAGEFEED CONVEYOR
SHIPLOADER
OUTLOADINGCONVEYOR
WHARF CONVEYOR
RAIL CARUNLOADING STATION
ELECTRICAL ROOM 1(NOTE 3)
ELECTRICAL ROOM 2
ELECTRICAL ROOM 3
TRANSFER TOWER 1
TRANSFER TOWER 2
TRANSFER TOWER 3
TRANSFER TOWER 4
NOTES:
1. 4x155mm AND 4x78mm UNDERGROUND DUCTS FROM ELECTRICALROOM 1 TO CABLE BOXES AT ELECTRICAL ROOM 2.
2. 3x155mm AND 4x78mm UNDERGROUND DUCTS FROM CABLE BOXESTO ELECTRICAL ROOM 3.
3. 25kV UTILITY POWER CONNECTION TO ELECTRICAL ROOM 1.
4. AUXILIARY DUCT BANKS TO EQUIPMENT, NUMBER OF DUCTS VARIES.
5. EXISTING UNDERGROUND ELECTRICAL SERVICE IN WAY OF NEWSTORAGE BUILDING TO BE RELOCATED.
F R A S E R S U R R E Y D O C K S
CANADIAN NATIONAL RAILWAYBURLINGTON NORTHERN RAILWAY
NOTE 2
NOTE 1
4.16 & 0.6kV POWER AND CONTROLCABLES IN UNDERGROUND DUCT BANKS(NOTE 4)
NOTE 4 (TYP.)
STACKING CONVEYOR RECLAIM CONVEYOR PORTAL RECLAIM
W
W
E
T
T
T T T T T T T T T T T T T T T T T T T T
E E E EE E E E
E E E EE E E E
E
E
E
E
E
EE
E
EE
EE
EE
E E EE E E
E
E
E
E
E
E
E
E
E EE
E
E
E E
EE
E
E
E
E
E
E
E
E
E E EE E EE E EE E E EE E E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
EE
E
E
E
E
E
E
E
E E
EE
EE
EE
E E
E
EE
E
E
E
E
E
E
E
E
E
E E
E
E
EE
EE
EE
E
E E E
EE
E E E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
EE
E
EE
E
EE
E
E
E
E
E
E
E
E
EE
EE
E E
E
E
E
E E E
E E E
E E
E
E E
E E E
E
E
EE
E
E
E
E E
E E EE
EE
E E E
E E E
EE
E
EE
EE
EE
EE
E
E E E
EE
E
E E E
E E
EE
E E E E E E
E
E
E E E E
E
E
E
EE
E
E
E
E E E E E E E E E E
E E E
EEE
EE
E
EE
A
A
A
A
A
A
A
A
A
D
D
B
B
B
B
B
B
BB
A
A
LEGEND:REMOVE LIGHT FIXTURES, POLES AND WIRING(NOTE 5)
NOTES:
1. COVERED CONVEYOR: STANCHION MOUNTED LIGHT FIXTUREc/w SWIVEL POLES, MOUNTED EVERY 10m ALONG WALKWAYON BOTH SIDES OF CONVEYOR.
2. TRANSFER TOWER: STANCHION (c/w SWIVEL POLES) ORCEILING MOUNTED LIGHTS AT STAIR LANDING.
3. BUILDINGS: WALL MOUNTED LIGHT FIXTURES ABOVE DOORENTRANCES. INTERIOR LIGHT FIXTURES NOT SHOWN FORCLARITY.
4. SHIPLOADER c/w LIGHTS, SEE DWG. (TO COME).
5. EXISTING HIGH MAST LIGHTS, POLES AND WIRING TO BEREMOVED.
F R A S E R S U R R E Y D O C K S
CANADIAN NATIONAL RAILWAYBURLINGTON NORTHERN RAILWAY
LED WALL MOUNTED FIXTURES, SEE NOTE 3B
NOTE 5(TYP. 3 )
LED STANCHION/CEILING MOUNTED LIGHTFIXTURES (NOT SHOWN), SEE NOTE 1 & 2
C
LED STREET LIGHT MOUNTED AGAINST BUILDINGA
DUMPER PIT CONVEYOR(NOTE 1, TYP.)OUTFEED CONVEYOR
STORAGEFEED CONVEYOR
SHIPLOADER(NOTE 4)
OUTLOADINGCONVEYOR
WHARF CONVEYOR
RAIL CAR UNLOADINGSTATION (NOTE 3)
ELECTRICAL ROOM 1(NOTE 3, TYP.)
ELECTRICAL ROOM 2
ELECTRICAL ROOM 3
TRANSFER TOWER 1(NOTE 2, TYP.)
TRANSFER TOWER 2
TRANSFER TOWER 3
TRANSFER TOWER 4
LED FLOOD LIGHT FIXTURESD
NOTE 5(TYP. 3 )
POTASH STORAGEBUILDING (NOTE 3)
STACKING CONVEYOR RECLAIM CONVEYOR PORTAL RECLAIM