3.Application of Dist Prot With KD Appendix

download 3.Application of Dist Prot With KD Appendix

of 41

Transcript of 3.Application of Dist Prot With KD Appendix

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    1/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Application of Distance ProtectionJay Gosalia

    Vice President of Marketing

    Doble Engineering Company

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    2/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection

    3 Zones of protection

    Zone 1 operates with no intentional time

    delay

    Zone 2 provides back up protection to Zone

    1 and operates with some time delayZone 3 typically has offset characteristic

    and has a time delay longer then Zone 2

    Zone 2 and Zone 3 are used in pilotscheme if employed

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    3/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    General Application Rules

    Zone 1 protects 80-85% of line length AB

    Zone 2 protects line AB + 50% of line BC Zone 3 Protects AB + Line BC + 20-30% of line CD + 20-30%

    of line behind terminal A

    Zone 1 protects 80-85% of line length AB

    Zone 2 protects line AB + 50% of line BC

    Zone 3 Protects AB + Line BC + 20-30% of line CD + 20-30%

    of line behind terminal A

    AB DC

    Time

    Zone 1

    Zone 2Zone 3

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    4/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reach Setting Criteria : Zone 1

    Zone 1 should never over reach for the faults on or

    beyond remote terminal

    Considering 5% accuracy of CTs and PTs maximum

    reach of Zone 1 can be 90% of line length AB

    Considering accuracy of Zone 1 protection 5% and safety

    margin of 5% Zone 1 reach can be 80% of the line length. In some instances based on the previous practices Zone

    1 is set to 90% of line length

    It is safe to set Zone 1 reach 80% of line length in general

    A BDC

    Zone 1

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    5/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone 1: Requirements

    Should cover the protected circuit and shouldprovide good fault resistance coverage Fast operation for limiting the system disturbance Directional discrimination for security and reliability

    AB

    DC

    Zone 1

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    6/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reach Setting Criteria : Zone 2

    Zone 2 should always over reach for the faults on or

    beyond remote terminal Zone 2 should always reach beyond the remote terminal andcover at least 50% of next line section

    Zone 2 time delay should be larger then the operating timeof Protection + CB (at terminal C of line CD) + safety margin

    Breaker fail timer co ordination is required

    Zone 2 is used in the pilot aided trip scheme to provideinstantaneous protection for faults anywhere on line BC

    AB C

    D

    Zone 2

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    7/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone 2 Time Delay : Criteria

    Determine Zone 2 time if Breaker fail protection is employed

    Breaker fail protection clears the fault by tripping back up breaker ifthe primary breaker fails to clear the fault after the protection trip

    For fault on line CD, protection at breaker 5 will see the fault andissues a trip command to breaker 5 and at the same time initiatesbreaker fail protection

    If breaker 5 trip it resets the breaker fail protection

    The fault is seen by the protection at breaker 3, in Zone 2.

    If breaker 5 fails then Breaker fail protection trip all breakers at bus C

    What should be the Zone 2 time delay for protection at breaker 3?

    1 2 3 4 5 6

    B CA D

    Zone 2

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    8/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Breaker Fail Scheme

    Breaker fail scheme principle Consists of a timer, high speed pick up/drop out over

    current protection and lock out protection

    Some time re-trip protection is employed Needs 52a breaker input to sense breaker status

    When protection operates it initiates breaker fail

    scheme Timer is starts and seals in with the high speed over

    current protection

    Issues re trip command to second trip coil of the breaker

    If breaker trips then 52a resets the timer and at the sametime over current protection.

    If breaker fails to trip then timer times out and picks up lockout protection to trip the back up breakers connected to the

    bus

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    9/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Breaker Fail Protection Logic

    OR62X

    62Y

    AND50 Timer86

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    10/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Timing Diagram : Normal Operation

    Operating

    Time of CB: 2Cy.

    Protection

    Trip: 1Cy.

    Drop out time

    Of current prot : 1 Cy.

    Margin: 5 Cy.

    Breaker fail timer time delay : 7 Cy.

    Breaker fail protection start

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    11/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Timing Diagram : Failed CB

    Operating

    Time of CB: 2Cy.

    Protection

    Trip: 1Cy.

    Drop out time

    Of current prot : 1 Cy.

    Margin: 5 Cy.

    Margin

    7 Cy.

    Operating

    Time of CB: 2 Cy.Breaker fail

    Protection trip : 0.5 Cy

    Breaker fail timer time delay : 7 Cy.

    Breaker fail protection start

    Remote Zone 2 Back up protection operation time :say 20 Cy.

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    12/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Reach Criteria Zone 3

    Zone 3 is a back up protection and last resort for the

    isolation of the fault if everything fails

    Time Delayed protection. Time delay is longer thenZone 2 delay

    When a very long line is following the short line Zone

    3 reach may be very long Can interfere with load on the line

    Lens characteristic is a potential solution

    It is used in the pilot aided protection when blocking

    scheme is employed to detect the fault direction

    Typically set in the offset mode to cover the reverse

    fault

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    13/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone 3 : Load Encroachment

    Load

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    14/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone 1 Reach : 3 Terminal Line

    X

    Y

    ZIx

    Iy

    Ix + Iy

    F

    Fault voltage at X = VF

    = Ix*ZF

    + Iy* (1-d)ZFFault current at X = Ix

    Apparent Impedance at X =VF/IF= VF/Ix =ZF + Iy/Ix (1-d)ZFAdditional impedance due to in feed = Iy/Ix (1-d)ZFFault will be seen farther: Protection will not trip

    Fault voltage at X = VF = Ix*ZF + Iy* (1-d)ZFFault current at X = Ix

    Apparent Impedance at X =VF/IF= VF/Ix =ZF + Iy/Ix (1-d)ZFAdditional impedance due to in feed = Iy/Ix (1-d)ZFFault will be seen farther: Protection will not trip

    d

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    15/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Zone 1 Reach : 3 Terminal Line

    X

    Y

    ZIxF

    Lets Set the reach considering maximum in feed so protection tripsNow say breaker at Y is out for maintenance

    Now the fault in the next line section will be seen as internal

    Protection will trip for the external fault

    Lets Set the reach considering maximum in feed so protection trips

    Now say breaker at Y is out for maintenance

    Now the fault in the next line section will be seen as internal

    Protection will trip for the external fault

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    16/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Rules for Zone 1 and Zone 2 Reach

    Zone 1 should never overreach and Zone 2 shouldalways over reach the remote terminal

    For 3 terminal line set the

    Zone 1 Reach As if there is no in feed

    Set the Zone 1 only up to tap point

    Zone 2 Reach

    Set the Zone 2 reach considering maximum in feed

    General rule and good practice for Zone 1 Its better not to trip for an internal fault then to trip for the

    external fault

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    17/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Phase to Phase Fault

    Phase to phase fault MHO is an ideal characteristic Fault resistance is arc resistance

    Fault current = V/(Zs+ZL+ Rarc)

    Arc resistance inversely proportional to current and directlyproportional to line spacing

    Rarc = (8750 * L)/ I1.4

    For strong source: lower Zs, creates high fault current,

    produces lower arc resistance For weak source : higher Zs, creates lower fault current,

    produces higher arc resistance

    For phase to phase fault MHO characteristic adjusts basedon the source impedance

    A

    B

    C

    GZs

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    18/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Arc Resistance

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    19/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Phase to Phase Fault: Fault Resistance

    Phase-Phase faultsconsist only of arcresistance Earth faults consist ofarc and tower footingresistance

    A i t C

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    20/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Arc resistance Coverage

    ZR

    Zs

    Rarc

    ZR

    Zs

    Rarc

    Strong source, Lower Zs, smaller Rarc, lower expansion = Good Rarc coverage

    Weak source, Higher Zs, larger Rarc, higher expansion = Good Rarc coverageStrong source, Lower Zs, smaller Rarc, lower expansion = Good Rarc coverage

    Weak source, Higher Zs, larger Rarc, higher expansion = Good Rarc coverage

    P S i

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    21/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing

    Variation in power flow Sudden removal of fault

    Loss of synchronism between ends of power system

    Change in the direction of power flow

    Protection on the system may see the impendencemoving from load condition to its operating zone.

    During transient condition Protection should not trip

    Only protection that requires system disconnectionat suitable point should trip

    To prevent tripping some type of sensing need to

    be employed to distinguish between power swingand actual fault

    Requires Power Swing Blocking Protection

    P S i

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    22/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing

    Power Flow from A to B EA leads EB by angle

    Total impedance : Z=ZSA +ZL+ZSB

    Current I = (EA-EB)/Z

    Voltage E at the Relay = EA-I*ZSA

    Power Flow from A to B EA leads EB by angle

    Total impedance : Z=ZSA +ZL+ZSB

    Current I = (EA-EB)/Z

    Voltage E at the Relay = EA-I*ZSA

    A B

    EA EB

    21

    ZsBZL

    ZsA

    E

    I

    P S i N l C diti

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    23/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing : Normal Condition

    ZR=E / I

    B

    EA EB

    21

    ZsBZL

    ZsA

    E

    I

    EB

    I I*ZSA

    EA

    E

    EA - EB

    EA - EB

    P S i Ab l C diti

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    24/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing : Abnormal Condition

    ZR is much smaller then ZR

    E is small

    EA-EB is large due large

    ZR is much smaller then ZR E is small

    EA-EB is large due large

    I

    EB

    I*ZSAEA

    E EA - EB

    ZR=E / I

    B

    EA EB

    21

    ZsBZL

    ZsA

    E

    I

    Power Swing

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    25/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing

    EB

    II*ZSA

    EA

    E

    EA - EB

    EA - EBEB

    I*ZSAEA

    E EA - EB

    Power Swing : Locus

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    26/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Power Swing : Locus

    P.S. LOCUS

    LOAD

    R

    PSB

    ZSB

    Z L

    ZSA

    O

    Z

    X

    MHO Characteristic : Power Swing

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    27/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    MHO Characteristic : Power Swing

    P.S. LOCUS

    LOAD

    R

    ZSB

    Z L

    ZSA

    X

    QUAD Characteristic : Power Swing

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    28/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    QUAD Characteristic : Power Swing

    P.S. LOCUS

    LOAD

    R

    ZSB

    Z L

    ZSA

    X

    Switch ON to Fault

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    29/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Switch ON to Fault

    Ensures inst. Trip under switch on to fault condition whenline is energized with earthing clamps connected tobreaker terminals

    Need for SOTF

    Protection against close up 3 Phase Faults when line

    VTs are used When used with Bus PT pre fault memory polarization

    can provide tripping through distance protection

    Distance Protection: Switch ON to

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    30/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Fault

    Distance Protection: VT Supervision

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    31/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: VT Supervision

    Condition shall be Detected when;3Vo > 20% of VN (L-N) & 3Io < 20% of IN

    FUSE FAILURE WILL CAUSE VOLTAGE UNBALANCEAND HENCE VO(V2) BUTNO CURRENT UNBALANCE IO(I2)UNBALANCED FAULTS CAUSE BOTH VOLTAGE/CURRENTUNBALANCE,PREVENTING VTS OPERATIONFUSE FAIL SUPERVISION IS BLOCKED FOR 150 TO 300ms FOLLOWING LINEENERGIZATION IN ORDER NOT TO OPERATE FOR UNEQUAL POLE CLOSING &ALSO DURING AUTO-RECLOSING

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    32/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    33/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    34/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    35/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    36/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    37/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    Distance Protection: Setting Criteria

    PERMISSIVE OVERREACHING SCHEMES AREADOPTED FOR SHORT LINES ( ALSO CALLEDDIRECTIONAL COMPARISON SCHEMES) ADVANTAGESARE; BETTER PERFORMANCE FOR HIGH RESISTANCEFAULTS. SUPERIOR TO PILOT WIRE AS DIGITAL DECISIONSARE EXCHANGED AND NOT ANALOGUE SUPERIOR TO PHASE COMPARISON WHICHREQUIRES FAITHFUL TRANSMISSION OF PHASEINFORMATION.

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    38/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    g

    Communication signal is sent to remoteend when the fault is detected in the reversedirection. Tripping is achieved when thisblocking signal is not received within a timeT0 (20-40 ms) and the local relay hasdetected a fault in the forward direction.

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    39/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    g

    Distance Protection: Setting Criteria

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    40/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery

    g

    BLOCKING SCHEMES ARE USED WHENCOMMUNICATION SIGNALS SHALL NOTBE TRANSMITTED OVER FAULTY LINEFOR RELIABILITY REASONS

  • 8/6/2019 3.Application of Dist Prot With KD Appendix

    41/41

    Knowledge Is PowerSMApparatus Maintenance and Power Management

    for Energy Delivery