Lot 5 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. 360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825 24 June 2017 The Bathla Group 17 Gilba Road Girraween NSW 2145 Dear Mr Bijan Afsar RE: BUILDIG CODE OF AUSTRALIA REPORT PROPERTY: LOT 5 - 1086 RICHMOND ROAD MARSDEN PARK NSW Please find enclosed our BCA 2016 of Australia Report in relation to the proposed residential flat buildings at the above property. Should you require further information in relation to the above, please do not hesitate to contact the undersigned. Regards, Greg Evans Director Accredited Certifier BPB 1870 360 Certification 360 Certification M: 0422 688 491 [email protected] Mosman NSW 2088

Transcript of 360 Certification M: 0422 688 491 [email protected] … ·  · 2017-09-252.1 – BUILDING...

Page 1: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

Lot 5 – 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017.

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

24 June 2017 The Bathla Group 17 Gilba Road Girraween NSW 2145 Dear Mr Bijan Afsar

RE: BUILDIG CODE OF AUSTRALIA REPORT

PROPERTY: LOT 5 - 1086 RICHMOND ROAD MARSDEN PARK NSW Please find enclosed our BCA 2016 of Australia Report in relation to the proposed residential flat buildings at the above property. Should you require further information in relation to the above, please do not hesitate to contact the undersigned. Regards,

Greg Evans Director Accredited Certifier BPB 1870 360 Certification

360 Certification M: 0422 688 491

[email protected] Mosman NSW 2088

Page 2: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 1 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

BCA 2016 CODE REPORT

LOT 5 – 1086 RICHMOND ROAD MARSDEN PARK

Date: 24 JUNE 2017

Our Re: C2017057

Page 3: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

TABLE OF CONTENTS

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 3 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

CONTENTS Page No.

1.0 – EXECUTIVE SUMMARY ............................................................ 3

1.1 DESIGN CONSIDERATIONS ....................................................................... 3

2.0 – PROPERTY DESCRIPTION ....................................................... 4

2.1 – BUILDING LOCATION ........................................................................... 4

2.2 – BASIS OF ASSESSMENT ......................................................................... 4

2.3 – REPORT PURPOSE ............................................................................... 5

2.4 – REPORT METHODOLOGY........................................................................ 5

2.5 – EXCLUSIONS ...................................................................................... 5

2.6 – BUILDING DESCRIPTION ....................................................................... 6

3.0 - BCA 2016 OF AUSTRALIA ASSESSMENT ................................. 7

3.1 – STRUCTURAL & FIRE RESISTANCE (SECTION B & C OF NCC) ......................... 7

3.2 – ACCESS & EGRESS (SECTION D, NCC) .................................................. 13

3.3 – SERVICES AND EQUIPMENT (SECTION E, NCC) ........................................ 19

3.4 – HEALTH & AMENITY (PART F, NCC) ..................................................... 23

3.6 – ENERGY EFFICIENCY. (PART J, NCC) ..................................................... 26

4.0 – FIRE SAFETY AND OTHER MEASURES .................................. 30

5.0 – CONCLUSION ........................................................................ 31

6.0 – REFERENCES & PLANS .......................................................... 32

© Mosman Certifiers Pty Ltd. All rights reserved. 360 Certification (Mosman Certifiers Pty Ltd) has prepared this document for the sole use of the Client and for a specific purpose, each as expressly stated in the document. No other party should rely on this document without the prior written consent of 360 Certification. 360 Certification undertakes no duty, nor accepts any responsibility, to any third party who may rely upon or use this document. This document has been prepared based on the Client’s description of its requirements and 360 Certification’s experience, having regard to assumptions that 360 Certification can reasonably be expected to make in accordance with sound professional principles. 360 Certification accepts no liability for information provided by the Client and other third parties used to prepare this document or as the basis of the analysis. Subject to the above conditions, this document may be transmitted, reproduced or disseminated only in its entirety. Document History

Revision Date Prepared & Approved

DRAFT 24 June 2017 Greg Evans, Accredited Certifier BPB 1870, 360 Certification

Revision 1 Greg Evans, Accredited Certifier BPB 1870, 360 Certification

Page 4: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

1.0 – EXECUTIVE SUMMARY

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 3 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

1.0 – Executive Summary This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 76 apartments and basement carparking for 130 vehicles. The assessment of the documentation has revealed that the building is primarily capable of complying with the Deemed-to-Satisfy [herein ‘DTS’] provisions of the BCA 2016 Code 2016 (Volume 1, Class 2-9 Buildings) [herein ‘BCA 2016’], and where necessary the Performance Requirements, without modification that require a development consent to be modified.

1.1 Design Considerations

No.

Recommendation

DTS Clause

1 The proponent has indicated that they intend to reduce the FRL’s of the Class 7b parts to 120 minutes, via a performance solution based on fire engineering analysis.

Clause 3 of Spec. C1.1, C2.8, C2.9,

C2.10

2 The total floor area and volume of the Class 7a & 7b parts is more than the maximum 5,000m2 permitted - approximately 5300m2. The proponent has indicated that they intend to address the slightly enlarged fire compartment via a performance solution based on fire engineering analysis.

C2.2

3 The spandrels are capable of complying provided the horizontal spandrels extend past either side of the opening by 450mm.

C2.6

5 The public corridors are greater than 40 metres in length and therefore must be smoke separated in accordance with Clause 2 of Specification C2.5. Currently the corridor between grid line B & F is not smoke separated like the corridor between grid line G and N. Additional smoke separation to be show on the plans.

C2.14

6 The exit travel distances within the basement do not comply with this clause, as:

- occupants have 45m to a point of choice instead of 20m; and, - 45m to one of the exits instead of 40m.

A third exit from the basement towards grid line N would resolve this matter. If a third stair is not proposed the proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.

C2.14

7 The exit travel distances on the roof does not comply with this clause, as: - occupants have 22m to a point of choice instead of 20m between grid line J & L;

and, The proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.

D1.4

8 The direct distance between alternative exits within the basement is 60m as required. However, if measured from first exit door to the point of choice to the second exit door, the distance increases to approximately 62m. Also, the distance between the alternative exits on the roof is greater than the maximum 45m and is approximately 60m. The proponent has indicated that they intend to address this via a performance solution based on fire engineering principles.

D1.5

9 The fire isolated stair at grid line N must have a doorway leading to outside, and the living room window of UG15 protected on the inside as required by D1.7(c) and as per C3.4

D1.7

10 The exit doors swing in the direction of egress as required, except the two sets of double doors from the ground floor hallways and the garbage exit door.

D2.20

11 Direct access must also be provided to the sprinkler valve set at basement level one between grid line I-J, which requires a minor layout change to this area.

E1.5

Page 5: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

2.0 – PROPERTY DESCRIPTION

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 4 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

2.0 – Property Description

2.1 – Building Location

The site is currently located on Lot 51, Deposited Plan No. 1196583. This building is to be located on proposed Lot 5, 1086 Richmond Road, Marsden Park NSW. Existing farmland and farm type buildings currently adjoins subject property. Site plan: 1086 Richmond Road Marsden Park NSW © NSW Government.

2.2 – Basis of Assessment

This BCA 2016 Report has been prepared based of the following:-

I. The Deemed-to-Satisfy and the Performance Requirements of BCA 2016 including NSW Variations and relevant Australian Standards;

II. Plans prepared by the Bathla Group, dated May 2017;

III. The Environmental Planning & Assessment Act 1979;

IV. Disability (Access to Premises — Buildings) Standards 2010;

Page 6: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

2.0 – PROPERTY DESCRIPTION

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 5 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

2.3 – Report purpose

This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 76 apartments and basement carparking for 130 vehicles. The BCA 2016 Report will: a) compare the proposed building against the Deemed-to-Satisfy provisions of

BCA 2016 including NSW Variations and relevant Australian Standards;

b) Identify DTS breaches that can be altered to comply with the DTS provisions of BCA 2016;

c) Identify DTS breaches and relevant performance requirements to be considered for Performance Solutions by the fire engineering and other consultants.

2.4 – Report methodology

This BCA 2016 report initially relies upon the plans of the proposed building, and a review of the structure against Deemed-to-Satisfy provisions of BCA 2016 and adopted Australian Standards. Consideration can be given to the Performance Requirements of BCA 2016 where appropriate. Where relevant the assessment can include the following categories – ▪ Structural; ▪ Fire resistance and compartmentation; ▪ Occupant Access/Egress; ▪ Fire Safety/Protection Services ▪ Health & Amenity; ▪ Energy Efficiency. Where compliance is not achieved with the relevant Deemed-to-Satisfy provisions, recommendations will be made to comply with the DTS or the relevant performance requirements.

2.5 – Exclusions

The report is limited to the proposed buildings and excludes the existing structures. This report does not imply, nor make reference to structural design or operating capability or design of any electrical, fire, hydraulic or mechanical services. Furthermore, limited reference is made to the Disability (Access to Premises — Buildings) Standards 2010 and the Disability Discrimination Act 1992 (Cth).

Page 7: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

2.0 – PROPERTY DESCRIPTION

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 6 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

2.6 – Building Description

Building Residential flat building.

Use/Classifications

Storey Description Classification(s)

Basement Carpark 7a and 7b

Ground Floor Carpark 7a and 7b

First Floor RFB 2

Second Floor RFB 2

Third floor RFB 2

Roof Floor RFB 2

Note: The basement storage is more than 10% of the floor area of the storey. The storage is

Class 7b, which requires higher FRL’s.

Rise in Storeys The proposed building has a rise in storeys of five as per Clause C1.2.

Note: The lift lobby on the roof causes that level to be a storey.

Storeys contained The proposed building will contain seven storeys.

Floor Area The total floor area and volume of the Class 7a & 7b parts is more than

the maximum 5,000m2 permitted - approximately 5,300m2.

Volume The volume of the Class 7a and 7b part is less than the maximum permitted

for type A Construction of 30,000m3.

Effective Height The building will have an effective height of approximately 12.00 m.

Car parking Spaces 130 on the basement level.

Type of Construction The proposed building requires Type ‘A’ Construction.

Primary FRL’s Class 2 – 90 minutes;

Class 7a – 120 minutes; Class 7b – 240 minutes.

Fire Compartments The carpark on basement 1 & 2 is one fire compartment. Ground, Level 1,

level 2, level 3 and roof are effectively separate fire compartments. The

apartments are fire separated – not separate fire compartments.

HBCF Insurance HBCFI is NOT applicable as the building has a rise in storeys of five (as

defined by the Home Building Regulation 2014, being levels: ground, level

1, level 2, level 3 and the roof level. As such, the building is considered a multi-storey building under clause 54 of the Home Building Regulation 2014). The basements have been excluded as they are wholly beneath the

ground and therefore not counted in the rise in storeys.

Zoning R3 - Medium Density Residential:

RE1 - Public Recreation: Local Open Space

SP2 - Infrastructure: Classified Road

SP2 - Infrastructure: Local Road

Flood Prone No

Acid Sulphate Soils No

Heritage No

Conservation Area No

Bushfire Prone Land Yes. Far western corner is located within buffer zone.

Page 8: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 7 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

3.0 - BCA 2016 of Australia Assessment

3.1 – Structural & Fire Resistance (Section B & C of NCC)

Clause Description Clause Requirements/Comments Compliance

Yes/No Part B Structural Provisions B1.0 Deemed-to-satisfy provisions Part applicable. Note only.

B1.1 Resistance to actions. Subject to geotechnical and structural

engineering.

Yes

B1.2 Determination of individual

actions.

Subject to geotechnical and structural

engineering.

Yes

B1.3 ***** Blank clause. N/A

B1.4 Determination of structural resistance of materials and

forms of construction.

Subject to geotechnical and structural engineering.

Yes

B1.5 Structural software. Note only. Note only.

B1.6 Construction of buildings in flood

hazard areas.

Property not identified as flood prone. N/A

Clause Description Clause Requirements/Comments Compliance Yes/No

Part C1 Fire Resistance and Stability C1.0 DtS Provisions. Applicable performance requirements

for building solutions. Note only

C1.1 Type of construction required. Type ‘A’ construction required to

comply with Clause 2 and 3 of Specification C1.1.

The majority of building elements

must be non-combustible, including: external walls, lifts and fire resisting

internal walls.

Internal load bearing walls must be of

concrete, masonry or fire protected timber.

The roof does not require an FRL, but must be non-combustible.

The buildings’ required FRL’s.

Class 2 – 90 minutes;

Class 7a – 120 minutes; Class 7b – 240 minutes.

The proponent has indicated that they

intend to reduce the FRL’s of the Class 7b parts to 120 minutes, via a

performance solution based on fire

engineering analysis. REFER TO DESIGN CONSIDERATIONS

Yes,

subject to fire engineering

Page 9: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 8 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

C1.2 Calculation of rise in storeys. The proposed building has a rise in storeys of five, as per Clause C1.2 of BCA 2016. The building contains seven

storeys including the basement.

Yes

C1.3 Buildings of multiple

classifications.

The building contains Class 2, 7a and

7b parts. For this clause only, the

building is identified as a five storey Class 2 building which requires Type

‘A’, construction. Note: The basement storage is more than 10% of the floor area of the storey. As such, the storage is Class 7b, which requires higher FRL’s.

Yes

C1.4 Mixed type of construction. The building is not subject to mixed types of construction.

N/A

C1.5 Two storey Class 2, 3 or 9c buildings.

Not applicable as the Class 2 has a rise in storeys of five.

N/A

C1.6 Class 4 parts of buildings. No Class 4 parts. N/A

C1.7 Open spectator stands and

indoor sports stadiums.

Not applicable N/A

C1.8 Lightweight fire rated

construction.

If proposed, lightweight fire rated

construction is to comply with this clause and manufactures

specifications.

Yes

C1.9 ***** Blank clause. N/A

C1.10 Fire hazard properties NSW Variations NSW C1.10(a)(v) NSW C1.10(b) NSW C1.10(c)(xiii).

The fire hazard properties of floor linings, floor coverings, wall

linings, ceiling linings and air-handling ductwork, are capable of complying

with this clause.

As the Class 2 part of the building will

not be sprinklered, the floor linings are to achieve a critical radiant flux not less than 2.0 and a smoke development rate of not less than 750

percent minutes.

Wall and ceiling linings are assumed to

be plasterboard and will comply with this clause.

Yes

C1.11 Performance of external walls in

fire.

Not applicable as the building not

proposed to be constructed with concrete panels.

N/A

C1.12 Non-combustible materials Noted. Note only

C1.13 Fire-protected timber: Concession

Not proposed to comply with requirements for fire protective

timber.

N/A

Part C2 Compartmentation and Separation

C2.0 DtS Provisions. Applicable performance requirements for building solutions.

Note only

C2.1 Application of Part. Applicable Yes or No Applicable

C2.2 General floor area and volume

limitations.

The total floor area and volume of the

Class 7a & 7b parts is more than the

Yes,

Page 10: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 9 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

maximum 5,000m2 permitted -

approximately 5300m2. The proponent has indicated that they intend to

address the slightly enlarged fire compartment via a performance solution based on fire engineering analysis. REFER TO DESIGN CONSIDERATIONS The volume of the carpark is less than

the maximum 30,000m3 permitted.

The area and volume limitations do not apply to the Class 2 parts.

Subject to fire

engineering

C2.3 Large isolated buildings. Not a large isolated building. N/A

C2.4 Requirements for open space

and vehicular access.

Not a large isolated building.

N/A

C2.5 Class 9a and 9c buildings. NSW Variations NSW C2.5(b).

Not a Class 9a or 9c building. N/A

C2.6 Vertical separation of openings in external walls.

Spandrel protection is required.

All spandrels must achieve an FRL of 60/60/60or 90/90/90 if load bearing.

Vertical spandrels must be: (A) is not less than 900 mm in height; and

(B) extends not less than 600 mm above the upper surface of the intervening floor; and

(C) is of non-combustible material having an FRL of not less than 60/60/60; or Horizontal spandrels must be:

a slab or other horizontal construction that— (A) projects outwards from the external face of the wall not less than 1100 mm; and (B) extends along the wall not less than 450 mm beyond the openings concerned; and (C) is non-combustible and has an FRL of not less than 60/60/60

In this instance the spandrels are capable of complying provided the

horizontal spandrels extend past either

side of the opening by 450mm. REFER TO DESIGN CONSIDERATIONS

Yes

C2.7 Separation by fire walls. At present no fire walls, as defined by the BCA, proposed or required.

N/A

C2.8 Separation of classifications in the same storey.

The basement storage is more than 10% of the floor area of the storey. As

Yes,

Page 11: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 10 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

such, the basement levels must have

an FRL of 240 minutes or the Class 7b parts must be fire separated from the

Class 7a parts.

As this fire separation is not practical or cost effective, the proponent has

indicated that they intend to reduce

the FRL’s of the Class 7b parts to 120 minutes, via a performance solution

based on fire engineering analysis. REFER TO DESIGN CONSIDERATIONS

The ground floor, first floor, second

floor, third floor and the roof only

have a classification of 2. As such this clause does not apply to those parts.

subject to fire

engineering

C2.9 Separation of classifications in

the different storey.

The basement storage is more than

10% of the floor area of the storey. As such, the basement levels must have

an FRL of 240 minutes or the Class 7b parts must be fire separated from the

Class 7a parts.

Assuming the basement levels FRL’s

are reduced to 120 minutes, via a performance solution based on fire

engineering analysis, the ground floor slab must have an FRL of 120

minutes, being the higher FRL

between the Class 7a/7b and 2 parts. REFER TO DESIGN CONSIDERATIONS

Yes,

subject to fire engineering

C2.10 Separation of lift shafts. Assuming the basement levels FRL’s are reduced to 120 minutes, via a

performance solution based on fire

engineering analysis, the lift is to be fire isolated with construction

achieving an FRL of 120 minutes on the basement levels and 90 minutes

on the Class 2 parts. Doorways to the

lift are to have an FRL of --/60/--. REFER TO DESIGN CONSIDERATIONS

Yes, subject to fire

engineering

C2.11 Stairways and lifts in one shaft. The lift and stairs are within separate fire isolated shafts as required.

Yes

C2.12 Separation of equipment. The following equipment must be fire

separated from the building: - (i) lift motors and lift control panels; or

(ii) emergency generators used to sustain emergency equipment operating in the emergency mode; or (iii) central smoke control plant; or (iv) boilers; or

(v) a battery or batteries installed in the building that have a voltage

Yes

Page 12: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 11 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

exceeding 24 volts and a capacity exceeding 10 ampere hours. (vi) on-site fire pumps must comply with the requirements of AS 2419.1 Where required, fire separating construction must achieve an FRL of

120/120/120 with doorways achieving

an FRL of --/120/30.

At present the hydrant pump room on ground floor and MSB, are fire

separated as required.

C2.13 Electricity supply system. The proposed fire pumps and main electrical distribution board serving the

pump or FIP are to be fire separated with fire rated construction achieving

an FRL of 120/120/120 with doorways

achieving an FRL of --/120/30.

The emergency switchgear must be separated from non-emergency

switchgear as per Clause C2.13(d).

Yes

C2.14 Public corridors in Class 2 and Class 3 buildings.

The public corridors are greater than 40 metres in length and therefore

must be smoke separated in accordance with Clause 2 of

Specification C2.5.

Currently the corridor between grid

line B & F is not smoke separated like the corridor between grid line G and

N. Additional smoke separation to be

show on the plans. REFER TO DESIGN CONSIDERATIONS

Yes subject to minor change.

Part C3 Protection of Openings C3.0 DtS Provisions. Applicable performance requirements

for building solutions. Note only

C3.1 Application of part. Applicable Yes or No. Note only

C3.2 Protection of openings in external walls.

No windows require protection as per Clause C3.2.

N/A

C3.3 Separation of external walls and

associated openings in different fire compartments.

No external walls in different fire

compartments are exposed to each other. As such, clause not applicable.

N/A

C3.4 Acceptable methods of

protection.

See Clause 3.2 above. N/A

C3.5 Doorways in fire walls. No fire walls. As such, not applicable. N/A

C3.6 Sliding fire doors. No sliding fire doors. N/A

C3.7 Protection of doorways in horizontal exits.

No horizontal exits. N/A

C3.8 Openings in fire isolated exits. Doorways to the fire isolated stairs are

to have self-closing fire doors achieving an FRL of --/60/30.

Yes

C3.9 Service penetrations in fire

isolated exits.

Fire isolated stairs must not be

penetrated with any plumbing or

Yes

Page 13: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 12 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

electrical services, except fire services,

including exit signs, emergency lighting and hydrants.

C3.10 Openings in fire isolated lift shafts.

The doorways to the lift shaft must be protected by –/60/– fire doors that—

(i) comply with AS 1735.11; and

(ii) are set to remain closed except when discharging or receiving

passengers, goods or vehicles.

Yes

C3.11 Bounding construction: Class 2, 3, 4 & 9b buildings NSW Variation NSW C3.11(d).

The doorways to the residential sole occupancy units, must be self-closing

fire door sets, achieving an FRL of --/60/30 as the building

requires Type A construction.

Yes

C3.12 Openings in floors and ceilings for services.

Openings in the ground, first floors, and enclosed roof parts are required

to be protected as they require an FRL with respect to integrity and

insulation.

Yes

C3.13 Openings in shafts. In a building of Type A construction, an opening in a wall providing access to a

ventilating, pipe, garbage or other service shaft must be protected by—

(a) if it is in a sanitary compartment — a door or panel which, together with

its frame, is noncombustible or has an

FRL of not less than –/30/30; or

(b) a self-closing –/60/30 fire door or

hopper; or

(c) an access panel having an FRL of

not less than –/60/30; or

(d) if the shaft is a garbage shaft — a

door or hopper of non-combustible construction.

Yes

C3.14 ***** Blank clause. N/A

C3.15 Openings for service installations Where an electrical, electronic,

plumbing, mechanical ventilation, air-conditioning or other service

penetrates a building element (other than an external wall or roof) that is

required to have an FRL with respect

to integrity or insulation or a resistance to the incipient spread of fire, that installation must be fire stopped as per this clause.

Yes

C3.16 Construction joints. Construction joints to be fire stopped

as per this clause.

Yes

C3.17 Columns protected with

lightweight construction to

achieve an FRL.

Columns proposed to be protected

with lightweight fire rated construction

to comply with this clause.

Yes

Page 14: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 13 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

3.2 – Access & Egress (Section D, NCC)

Clause Description Clause Requirements/Comments Compliance Yes/No

Part D1 Provisions for Escape D1.0 DtS Provisions Applicable performance requirements

for building solutions. Note only.

D1.1 Application of Part Part applicable Note only.

D1.2 Number of exits required NSW Variation NSW D1.2(d)(vii).

The basements have two exits as required.

The Class 2 parts require at least one

exit as per this clause.

[Note: Additional exits are required for exit travel distance].

Yes

D1.3 When fire-isolated stairways and ramps are required.

Stair Description Fire Isolated

Y/N

1 Stair 1 serving the basements at grid line C.

Yes, as the stair connects two basement levels.

2 Stair 2 serving the basements at grid line J.

Yes, as the stair connects two basement levels.

3 Stair serving first, second, third and roof levels at grid line C.

Yes, as the stair connects four storeys and bypasses a fifth.

4 Stair serving ground, first, second, third, and roof at grid line E.

Yes, as the stair connects four storeys.

5 Stair serving first, second, third and roof levels at grid line J.

Yes, as the stair connects four storeys and bypasses a fifth.

6 Stair serving first, second, third levels at grid line N.

Yes, as the stair connects four storeys.

Yes

D1.4 Exit travel distances The exit travel distances within the basement do not comply with this

clause, as: - occupants have 45m to a point

of choice instead of 20m; and,

- 45m to one of the exits instead of 40m.

A third exit from the basement

towards grid line N would resolve this matter. If a third stair is not proposed

the proponent has indicated that they

intend to address this via a performance solution based on fire

engineering principles. REFER TO DESIGN CONSIDERATIONS

Yes, subject to fire

engineering

Page 15: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 14 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

The exit travel distances within the Class 2 parts on the ground and first

floor are 6m from an exit or from a point from which travel in different

directions to 2 exits is available as per Clause D1.4(a)(i)(A).

The exit travel distances on the roof does not comply with this clause, as:

- occupants have 22m to a point of choice instead of 20m

between grid line J & L; and,

The proponent has indicated that they intend to address this via a

performance solution based on fire engineering principles. REFER TO DESIGN CONSIDERATIONS

D1.5 Distance between alternative exits

The direct distance between alternative exits within the basement is

60m as required. However, if measured from first exit door to the

point of choice to the second exit door,

the distance increases to approximately 62m.

The proponent has indicated that they

intend to address this via a performance solution based on fire

engineering principles. REFER TO DESIGN CONSIDERATIONS

The distance between alternative exits on the ground and first floor complies

with this clause as they are more than 9m apart and less than 45m apart as

required.

The distance between the alternative

exits on the roof is greater than the maximum 45m and is approximately

60m.

The proponent has indicated that they

intend to address this via a performance solution based on fire

engineering principles. REFER TO DESIGN CONSIDERATIONS

Yes, subject to fire

engineering

D1.6 Dimensions of exits and paths of

travel NSW Variations NSW D1.6(f)(vii) NSW D1.6(i)

The dimensions of exits and paths of

travel to exits generally complies with this clause and is subject to detailed

design at construction certificate

stage.

Yes

D1.7 Travel via fire-isolated exits. Excluding fire isolated stair at grid line

N, the discharge of the fire isolated

Yes

Page 16: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 15 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

stairs complies with this clause.

The fire isolated stair at grid line N must have a doorway leading to

outside, and the living room window of UG15 protected on the inside as

required by D1.7(c) and as per C3.4. REFER TO DESIGN CONSIDERATIONS

D1.8 External stairways or ramps in

lieu of fire-isolated exits

No external stair in lieu of a fire

isolated stair required or proposed.

N/A

D1.9 Travel by non-fire-isolated

stairways or ramps.

No non-fire isolated stairs, as all fire

isolated.

N/A

D1.10 Discharge from exits NSW Variation NSW D1.10(f).

The discharge of the exits complies with this clause. Details are required at

construction certificate stage to ensure

that compliance with this clause, D1.7(c), and D2.12.

Yes

D1.11 Horizontal exits. No horizontal exits are provided / required.

N/A

D1.12 Non-required stairways, ramps

or escalators.

No non-required stairways, ramps or

escalators.

N/A

D1.13

Number of persons accommodated. NSW Variation NSW Table D1.13.

The building is likely to approximately less than 160 occupants.

Yes

D1.14 Measurement of distances Note only. Note only.

D1.15 Method of measurement Note only. Note only.

D1.16 Plant rooms and lift machine rooms: Concession.

The plant rooms and lift rooms are entitled to comply with the

concessions for egress using ladders

complying with this part.

Yes

D1.17 Access to lift pits The lift pits will be less than 3m in

depth and therefore access to the lift

pit will be via the lowest landing doors.

Yes

Part D2 Construction of Exits D2.0 DtS Provisions. Applicable performance requirements

for building solutions. Note only.

D2.1 Application of part NSW Variation NSW D1.2(c).

Part applies.

Note only.

D2.2 Fire-isolated stairways and ramps.

The fire isolated stairs must be constructed with non-combustible

materials, so that if there is local

failure it will not cause structural damage to, or impair the fire-

resistance of, the shaft.

Yes

D2.3 Non-fire-isolated stairways and

ramps.

No non-fire isolated stairs. N/A

D2.4 Separation of rising and descending stair flights.

No rising and descending stair flights provided the basement stairs at grid

line C and J are separated from the

stairs serving the level 1, 2, 3 and the roof.

Yes

D2.5 Open access ramps and balconies.

No open access ramps or balconies used to comply with the requirements

of Table E2.2a.

N/A

D2.6 Smoke lobbies. No smoke lobbies utilised. N/A

Page 17: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 16 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

D2.7 Installations in exits and paths

of travel.

Electrical distribution boards that are

located within a path of travel to an exit must be contained within non-

combustible construction (metal cabinet) and smoke sealed.

Yes

D2.8 Enclosure of space under stairs

and ramps.

No cupboards beneath the non-fire

isolated stairs proposed.

N/A

D2.9 Width of stairways. Stairways greater than 2m in width

only count for 2m of exit width.

Note only.

D2.10 Pedestrian ramps. No internal pedestrian ramps serving as exits.

N/A

D2.11 Fire-isolated passageways. The fire isolated passageway on the

ground floors are assumed to be load bearing and therefore must be

concrete or masonry.

Yes

D2.12 Roof as open space. The roof is not utilised as open space for the purpose of this clause.

N/A

D2.13 Goings and risers. NSW Variation NSW 2.13(a)(ix), (x), xi

The goings and the risers are capable of complying with this clause.

Yes

D2.14 Landings. The proposed landings are capable of complying with this clause and are

subject to detailed design at construction certificate stage.

Yes

D2.15 Thresholds. NSW Variation NSW D2.15(d)(e).

The proposed thresholds are capable

of complying with this clause and are subject to detailed design at

construction certificate stage.

Yes

D2.16 Balustrades or other barriers. NSW Variation D2.16(g)(iv) & (v).

The proposed balustrades capable of complying with this clause and are

subject to detailed design at construction certificate stage.

Yes

D2.17 Handrails. Hand rails will be required to all stairs

and they are capable of complying with this clause.

Yes

D2.18 Fixed platforms, walkways’

stairways and ladders.

No fixed platforms, walkways and

ladders proposed or required.

N/A

D2.19 Doorways and doors. NSW Variation NSW D2.19(b)(v).

No revolving, sliding or tilt up doors

proposed in an exit or in the path of

travel to an exit.

Nonetheless, should an automatic sliding door be proposed, it must be

able to be opened manually under a force of not more than 110 N if there

is a malfunction or failure of the power

source; and if it leads directly to a road or open space it must open

automatically if there is a power failure to the door or on the activation of a

fire or smoke alarm anywhere in the

fire compartment served by the door.

Yes

D2.20 Swinging doors. The exit doors swing in the direction of

egress as required, except the two sets of double doors from the ground

Yes, subject to

minor change

Page 18: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 17 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

floor hallways and the garbage exit

door. REFER TO DESIGN CONSIDERATIONS

D2.21 Operation of latch. NSW Variation NSWD2.21(c)& (d).

Excluding the internal doors of the residential units, door hardware must

be a single hand downward action on

a single device which is located between 900 mm and 1.1 m from the

floor and if serving an area required to be accessible by Part D3—

(A) be such that the hand of a person who

cannot grip will not slip from the

handle during the operation of the latch; and

(B) have a clearance between the handle

and the back plate or door face at the

centre grip section of the handle of not less than 35 mm and not more than 45

mm.

Yes

D2.22 Re-entry from fire-isolated exits. Building not >25m in effective height. N/A

D2.23 Signs on doors. The doorways opening into the fire

isolated stairs and the smoke doors in the hallways must have the following

signage:

“FIRE SAFETY DOOR DO NOT

OBSTRUCT DO NOT KEEP OPEN”;

The doorways leading from the fire

isolated stairs that open to outside must have signage that states:

“FIRE SAFETY DOOR DO NOT

OBSTRUCT”;

Yes

D2.24 Protection of openable windows.

Class 2, 3, 4 or 9b building.

http://www.legislation.nsw.gov.

au/#/view/act/2015/50/part6/div3/sec118

The bedroom windows on the first

floors that have a sill height of less than 1.7 metres and do not open to a

balcony, require protection as per this

clause.

BCA 2016 applies to bedroom windows only, 2m above the ground

with a sill less than 1.7m in height. They MUST be fixed into that position

or have the screen that can withstand

250 Newtons (25kg).

Section 118 of the Strata Schemes

Management Act 2015 requires ALL windows accessible from an

apartment, 2m above the ground

with a sill less than 1.7m in height.

Yes

Page 19: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 18 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

They MUST have the child lock, but do

not have to be fixed, or have the screen that can withstand 250

Newtons (25kg).

D2.25 Timber stairways: Concession No applicable as no timber stairs

proposed within the fire isolated

stairway.

N/A

NSW

D2.101

Doors in path of travel in an

entertainment venue.

Not an ‘entertainment venue’, as

defined by the EP & A Regs. 2000.

N/A

Part D3 Access for People with Disabilities

D3.0 DtS Provisions. Applicable performance requirements for building solutions.

Note only.

D3.1 General building access

requirements.

Disabled access is a requirement of

BCA 2016 and Federal legislation.

In this instance, disabled access must be provided from the principal

pedestrian entry to the: - accessible car parking places

on basement levels;

- waste bins on ground level; - entry doors of the residential

units on all levels; - External common spaces

including the roof.

The building appears capable of

complying with this clause subject to detailed design.

Yes

D3.2 Access to buildings. An accessway is provided from the

boundary of the property, to the principal pedestrian entrances.

Yes

D3.3 Parts of buildings to be

accessible.

Accessible hand rails, tactiles, nosing’s,

will be required to all non-fire isolated stairs to 1428.1-2009.

Yes

D3.4 Exemptions. Disabled access need not be provided

to service areas / metres rooms etc. - Gas metre room;

- Water metre room; - Electricity metre room;

- Fire hydrant pump room.

Yes

D3.5 Accessible car parking. Two accessible car parking space are required and provided. The space must

comply with AS/NZS 2890.6.

Vertical clearance of not less than

2500mm must be provided above each dedicated space and adjacent shared

area, when measured in accordance with AS 2890.1: 1993 Clause 5.3. (AS

2890.6: 2009 Clause 2.4) (Figure 4).

Yes

D3.6 Signage. Braille and tactile signage complying with Specification D3.6 must: -

Yes

Page 20: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 19 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

(ii) identify each door required by E4.5 to be provided with an exit sign and state— (A) "Exit"; and (B) "Level" ; and either (aa) the floor level number; or (bb) a floor level descriptor; or (cc) a combination of (aa) and (bb).

In addition to the above, where a

pedestrian entrance is not accessible, directional signage incorporating the

international symbol of access, in accordance with AS 1428.1 must be

provided to direct a person to the location of the nearest accessible

pedestrian entrance.

D3.7 Hearing augmentation. Hearing augmentation not required. N/A

D3.8 Tactile indicators. If non fire isolated stairs proposed, and form part of the accessible path,

they must have tactiles in accordance with sections 1 and 2 of AS/NZS

1428.4.1.

Yes

D3.9 Wheelchair seating in Class 9b assembly buildings.

No fixed seating proposed as part of the development.

N/A

D3.10 Swimming Pools. No pools proposed. N/A

D3.11 Ramps. The accessible ramps must comply with AS 1428.1-2009 and must not

have a vertical rise of more than 3m.

Yes

D3.12 Glazing on an accessway. On an accessway, where there is no chair rail, handrail or transom, all

frameless or fully glazed doors, sidelights and any glazing capable of

being mistaken for a doorway or

opening, must be clearly marked in accordance with AS 1428.1.

Yes

3.3 – Services and Equipment (Section E, NCC) Clause &

Description Requirements/Comments Compliance Yes/No

Part E1 Fire Fighting Equipment E1.0 DtS Provisions Applicable performance requirements

for building solutions Note only

E1.1 ***** Blank clause. N/A

E1.2 ***** Blank clause. N/A

E1.3 Fire hydrants. Fire hydrant coverage is required in accordance with AS 2419.1-2005.

Internal hydrants are required to the

fire isolated stairs to provide coverage

Yes

Page 21: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 20 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

to the building and so hose reels are

not passing though smoke doors.

If the booster is likely to be within 10m of the building, the booster must be

protected 2m either side and 3m above the booster must achieve an

FRL of 90/90/90.

Direct access must be provided to the

fire hydrant pump room, which can be from a fire isolated stair.

Further details are required from the hydraulic engineer to confirm

compliance.

E1.4 Fire hose reels. Fire hose reels are not required for the

Class 2 parts.

The Class 7a and 7b parts must have

fire hose reels, which will be located within 4m of the two fire isolated

stairs. Coverage is from a 36m hose

and 4m spray.

Yes

E1.5 Sprinklers NSW Variation NSW Table E1.5

Sprinklers are required to the carpark

as more than 40 vehicles are permitted.

Direct access must also be provided to the sprinkler valve set at basement

level one between grid line H-I, which requires a minor layout change to this

area. REFER TO DESIGN CONSIDERATIONS

Yes, subject to

minor design change

E1.6 Portable fire extinguisher. Portable fire extinguishers will be

installed in accordance with this clause and additional PFE’s are required to

serve the Class 2 part not provided

with hose reel coverage.

Yes

E1.7 ***** Blank clause. N/A

E1.8 Fire control centres. Not required or proposed. N/A

E1.9 Fire precautions during construction.

Not less than one fire extinguisher to suit Class A, B and C fires and

electrical fires must be provided at all

times on each storey adjacent to each required exit or temporary stairway or

exit.

Yes

E1.10 Provision for special hazards. Not required or proposed.

N/A

Part E2 Smoke Hazard Management E2.0 DtS Provisions Applicable performance requirements

for building solutions Note only

E2.1 Application of Part. Part applies. Applicable

E2.2 General requirements. The building will require an automatic smoke detection and alarm system

Yes

Page 22: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 21 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

(BOWS) complying with NCC Clause

E2.2a, Clause 3 or 4, & 6 of Spec. E2.2a, AS 3786-2014.

This will require:

- At least one hard wired smoke alarm within each residential

unit; and

- hard wired and interconnected smoke alarms on ground, first,

second, third and roof, so that if one alarm detects smoke, all

smoke alarms in the common

area activate to form the building occupant warning

system; - speaker to the carpark that

activates if the above smoke alarms in the common areas

detect smoke activate.

The carpark ventilation system

requires compliance with Clause E2.2a, Clause 5.5 of AS 1668.1-2015 & AS

1668.2-2012. This requires:

- smoke detectors to the mechanical supply air parts;

- auto shutdown of the supply air on detection of smoke by

the supply air smoke detectors;

- auto full ventilation rate where

smoke detection or sprinklers installed activated by thermals

in accordance with AS 1670.1-2015;

- Override control switch at the

designated building entry point or the at the FDCIE (aka FIP).

E2.3 Provision of special hazards. NSW variations NSW Table E2.2a NSW Table E2.2b

The building is not considered to be

subject to the provision of special hazards.

N/A

Part E3 Lift Installations E3.0 DtS Provisions Applicable performance requirements

for building solutions. Note only

E3.1 Lift installations. The electric passenger lift must

comply with Specification E3.1.

Yes

E3.2 Stretcher facility in lifts. A stretcher facility is NOT required as the effective height of the building is

NOT more than 12 metres, based on three metres per storey. Check

effective height at CC stage.

N/A

Page 23: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 22 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

E3.3 Warnings against the use of lifts

in fire.

Signage will be provided to comply

with this clause.

Yes

E3.4 Emergency lifts. An emergency lift is not required or

proposed.

N/A

E3.5 Landings. Landings to the lift comply with this clause.

Yes

E3.6 Passenger lifts. The passenger lift will comply with this

clause. The required disabled access provisions.

a) Hand rail to AS 1735.12; b) Lift floor of 1400 (w) x 1600 (d);

c) Lifts doors that have passenger protection to AS 1735.12;

d) Lift landing doors at the upper

landing; e) Lift car control buttons to AS

1735.12; f) Lighting to AS 1735.12;

g) Automatic audible information,

visual indicators to identify the level and when the lift stops.

h) Emergency button to call centre

Yes

E3.7 Fire service controls. The passenger lift does NOT require

fire service controls as it has effective

height less than 12m.

N/A

E3.8 Aged care buildings. Not an aged care building. N/A

E3.9 Fire service recall operation

switch.

The passenger lift does NOT require

fire service controls as it has effective height less than 12m.

N/A

E3.10 Lift car service drive control

switch.

The passenger lift does NOT require

fire service controls as it has effective height less than 12m.

N/A

Part E4 Emergency Lighting, Exit Signs and Warning Systems

E4.0 DtS Provisions Applicable performance requirements for building solutions.

Note only.

E4.1 ***** Blank clause. N/A

E4.2 Emergency lighting

requirements.

Emergency lighting is required to be

installed to all internal and external

stairs that are part of the path of travel to the road in accordance with

this clause, including the rooftop.

Yes

E4.3 Measurement of distance. Noted. Note only.

E4.4 Design and operation of

emergency lighting.

Emergency lighting must be installed

in accordance with AS 2293.1-2005.

Yes

E4.5 Exit signs. Exit signs to be installed on all levels above or adjacent to the exit.

Yes

E4.6 Direction signs. NSW Variation NSW E4.6

If the exit is not readily apparent,

additional directional exit signs must be installed to guide occupants to the

exit.

Yes

E4.7 Class 2 & 3 buildings and Class

4 parts: Exemption.

The Class 2 parts are entitled to use

the with the word “EXIT” in capital

letters 25 mm high in a colour

Yes

Page 24: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 23 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

contrasting with that of the background, on the side remote from the exit or balcony of every exit door.

E4.8 Design and operation of exit signs.

Every required exit sign must comply with—

AS 2293.1; or for a photoluminescent exit sign, Specification E4.8; and

be clearly visible at all times when the building is occupied by any person

having the right of legal entry to the

building.

Yes

E4.9 Sound systems and intercom

systems for emergencies

Not a class 3, a Class 9b building

having a RIS of 3 or more, or over

25m in Effective Height building.

N/A

3.4 – Health & Amenity (Part F, NCC) Clause Description Clause Requirements/Comments Compliance

Yes/No Part F1 Damp and Waterproofing F1.0 DtS Provisions Applicable performance requirements

for building solutions. Note only

F1.1 Stormwater drainage. The stormwater will comply with AS/NZS 3500.3-2015.

Yes

F1.2 ***** Blank clause N/A

F1.3 ***** Blank clause N/A

F1.4 External above ground membranes.

Where external membranes are proposed, they must comply with AS

4654.1 & 2.

Yes

F1.5 Roof coverings. The new roof coverings must comply

with this clause. If metal deck roofing

is proposed it must comply with AS 1562.1.

Yes

F1.6 Sarking New sarking will comply with this

clause and AS/NZS 4200.1 & 2.

Yes

F1.7 Waterproofing of wet areas in

buildings.

Waterproofing of all wet areas will be

in accordance with this clause and AS

3740-2010.

Yes

F1.8 ***** Blank clause. N/A

F1.9 Damp-proofing New damp-proofing will comply with

this clause.

Yes

F1.10 Damp-proofing of floors on the

ground.

New damp-proofing on the ground will

comply with this clause.

Yes

F1.1 Provision of floor wastes. New floor wastes will be provided to the Class 2 parts within the bathrooms

and laundries.

Yes

F1.12 Sub-floor ventilation. New sub-floor ventilation must be upgraded to comply with this part.

Yes

F1.13 Glazed assemblies. New glazed members will comply with

this clause.

Yes

Part F2 Sanitary and Other Facilities F2.0 DtS Provisions Applicable performance requirements

for building solutions. Note only

Page 25: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 24 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

F2.1 Facilities in residential buildings. Each SOU will be provided with a

kitchen, bathroom, toilet, shower.

Laundry facilities are proposed via a washing machine. Clothes drying will

be via dryer or 7.5m of clothes lines on balconies.

A cleaner’s toilet is required and is provided as the building has more than

10 units, as per Table F2.1.

Yes

F2.2 Calculation of number of occupants and facilities.

Population loads: Approximately less than 160.

Noted

F2.3 Facilities in Class 3-9 buildings. Facilities not required for the Class 7a or 7b parts as no employees.

N/A

F2.4 Accessible sanitary facilities. If common sanitary facilities are

utilised within building, this must be an accessible bathroom.

Yes

F2.5 Construction of sanitary

compartments.

The construction of sanitary

compartments will comply with this clause.

Yes

F2.6 Interpretation: Urinals and

washbasins.

Noted only. Yes

F2.7 Microbial.

NSW Variation NSW F2.7

Not applicable in NSW. N/A

F2.8 Waste management. Not Class 9a N/A

Part F3 Room Heights F3.0 DtS Provisions Applicable performance requirements

for building solutions. Applies

F3.1 Height of rooms and other spaces.

The height of rooms are required to be 2.4 meters in height in habitable

rooms and 2.1m in non-habitable rooms. It is noted that that normal

internal heights are 2.4 metres or

more.

Yes

Clause Description Clause Requirements/Comments Compliance Yes/No

Part F4 Light and Ventilation F4.0 DtS Provisions Applicable performance requirements

for building solutions. Applicable

F4.1 Provision of natural light. Natural lighting is provided to all habitable rooms within Class 2 parts.

Yes

F4.2 Methods and extent of natural

lighting.

Compliant natural lighting is provided

to all habitable rooms within Class 2 parts.

Yes

F4.3 Natural light borrowed from

adjoining room.

Borrowed light not required as direct

natural lighting provided.

N/A

F4.4 Artificial lighting. In non-habitable rooms, artificial

lighting will comply with this clause, the BASIX certificate and Part J6 and

AS 1680.0-2009.

Yes

F4.5 Ventilation of rooms. NSW Variation F4.5(b).

Excluding the basement and some bathrooms, the building is primarily

provided with natural ventilation. Parts

Yes

Page 26: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 25 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

that are mechanical ventilated must

comply with the BASIX certificate, Part J5 and AS 1668.2-2012.

F4.6 Natural ventilation. Excluding the basement and some bathrooms, the building is primarily

provided with natural ventilation. Parts

that are mechanical ventilated must comply with the BASIX certificate, Part

J5 and AS 1668.2-2012.

Yes

F4.7 Ventilation borrowed from adjoining room.

Borrowed ventilation may be relied upon for small study / non-habitable

rooms. However, it is likely that the non-habitable components will be

mechanically ventilated.

Yes

F4.8 Restriction of position of water closets and urinals.

Toilet doors open to hallways or the like or must be mechanical ventilated

to comply with Clause F4.9(a)(ii).

Yes

F4.9 Airlocks. Toilet doors open to hallways or the like or must be mechanical ventilated

to comply with Clause F4.9(a)(ii).

Yes

F4.10 ***** Blank clause. N/A

F4.11 Carparks The basement carpark part must be

mechanically ventilated as per AS 1668.2-2012.

Some supply is detailed, however, exhaust is not detailed on the current

plans, which is subject to detailed engineering design that is co-ordinated

with other engineering disciplines.

Yes

F4.12 Kitchen and local exhaust ventilation.

No commercial kitchens. N/A

Part F5 Sound Transmission and Insulation

F5.0 DtS Provisions Applicable performance requirements for building solutions.

Noted.

F5.1 Application of Part. Applies to Class 2 parts. Applies

F5.2 Determination of airborne sound

insulation ratings.

Airborne sound insulation requirement. Noted

F5.3 Determination of impact sound insulation ratings.

Airborne sound insulation ratings must be determined in accordance with

Clause F5.2(a) or comply with

Specification F5.2.

Noted

F5.4 Sound insulation of floors. The residential floors must have an Rw

+ Ctr (airborne) not less than 50 and an Ln,w (impact) not more than 62.

Yes

F5.5 Sound insulation of walls.

The walls separating Units must have

an Rw + Ctr (airborne) not less than 50.

Discontinuous construction is required

around the lift shafts, garage rooms, and other rooms which are habitable

and back on to non-habitable areas.

Yes

Page 27: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 26 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

F5.6 Sound insulation of internal

services.

Pipework, including stormwater pipes,

must have an Rw + Ctr (airborne) not less than—

(i) 40 if the adjacent room is a habitable room (other than a kitchen);

or

(ii) 25 if the adjacent room is a kitchen

or non-habitable room.

Yes

F5.7 Sound insulation of pumps. A flexible coupling must be used at the point of connection between the

service pipes in a building and any

circulating or other pump.

Yes

3.6 – Energy Efficiency. (Part J, NCC) Note 1: The residential Class 2 part of the building is to be designed to comply with the requirements of two MANDATORY points for energy efficiency. They are:

• A, BASIX assessment and a BASIX certificate will be required to be lodged with the

development application.

• In addition to the BASIX certificate compliance with NSW J (A) is required for the Class

2 part. The relevant/applicable sections of NSW J (A) are to be complied with. The clauses within Section J (A) are listed below.

• NSW J(A) 1.0 – Building Fabric,

• NSW J(A) 2.0 – Building Sealing

• NSW J(A) 3.0 – Air Conditioning and ventilating systems

• NSW J(A) 4.0 – Hot Water Supply

• NSW J(A) 5.0 – Access for Maintenance

Clause Description Clause

Requirements/Comments Compliance

Yes/No

NSW PART J(A)1

Building Fabric

NSW J(A)1.1(a)

&(b)

Application of Part. NSW J(A)1.1(a)&(b). The DTS provisions do not apply as the

Development Consent

D/2015/326/C, does NOT require

the installation of insulation.

N/A

NSW

J(A)1.1(c)

Application of Part. The Deemed-to-Satisfy provisions of

this Part for thermal breaks apply to

all Class 2 buildings

Part applies

Page 28: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 27 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

NSW

J(A)1.2

Compliance with BCA provisions

The sole-occupancy units of the

Class 2 parts must comply with the national BCA provisions of J0.2(b) to

(e), as stated below, excluding J1.2 if the DA does not mandate

insulation.

(b) for general thermal construction, comply with J1.2; and

(c) for thermal breaks, comply with J1.3(d) and J1.5(c); and

(d) for compensating for a loss of ceiling insulation, comply with J1.3(c), other than where the house energy rating software used can automatically compensate for a loss of ceiling insulation; and

(e) for floor edge insulation, comply with J1.6(c) and J1.6(d); and

Part applies

NSW PART J(A)2

Building Sealing

NSW

J(A)2.1

Application of Part. Parts applies as Class 2 parts have

air conditioning.

Part applies

NSW

J(A)2.2

Compliance with BCA

provisions

Class 2 parts must comply with the

following national BCA provisions, as

applicable—

(a) J3.2 Chimneys and flues; and

(b) J3.3 Roof lights; and

(c) J3.4 Windows and doors; and

(d) J3.5 Exhaust fans; and

(e) J3.6 Construction of roofs, walls

and floors; and

(f) J3.7 Evaporative coolers.

Subject to Section J Report

NSW PART J(A)3

Air-Conditioning & Ventilation Systems

NSW J(A)3.1 Application of Part. Parts applies to Class 2 parts. Part applies

Page 29: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 28 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

NSW J(A)3.2 Compliance with BCA

provisions

Class 2 buildings and Class 4 parts of

buildings must comply with the following national BCA provisions, as

applicable—

(a) J5.2 (a) to (d) and (f) to (g) Air

conditioning systems; and

(b) J5.3 Mechanical ventilation

systems; and

(c) J5.4 Miscellaneous exhaust

systems.

Note: Compliance is not required

with the national BCA provisions of

J5.2(e) as those matters are

regulated under BASIX.

Subject to Section J Report

NSW PART J(A)4

Heated Water Supply

NSW J(A)4.1 Application of Part. Parts applies to Class 2 parts. Part applies

NSW J(A)4.2 Compliance with BCA

provisions

Class 2 buildings and Class 4 parts of

buildings must comply with the national BCA provisions of J7.2

Heated water supply.

Note: Compliance is not required

with the national BCA provisions of J7.3 and J7.4 as those matters are

regulated under BASIX.

Subject to Section J Report

NSW PART J(A)5

Heated Water Supply

NSW J(A)5.1 Application of Part. Applies to Class 2 common areas. Part applies

NSW J(A)5.2 Compliance with BCA

provisions

a) A building or sole-occupancy unit with a floor area of more than 500

m2 must have the facility to record the consumption of gas and

electricity. This will be provided as

required.

Yes

Page 30: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

3.0 – BUILDING CODE OF AUSTRALIA - ASSESSMENT

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 29 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

The following NCC Section J National provisions will be applicable to the Class 7a and 7b part.

Item Comment

Building Fabric

Should the basement be heated or cooled, or be a conditioned space, it

must be insulated in accordance with Part J1 of the NCC.

Glazing

No applicable as no windows to the basement levels.

Building Sealing

Should the basement be heated or cooled, or be a conditioned space, it

must be sealed in accordance with Part J3 of the NCC.

Air-Conditioning and Ventilation System

If proposed, the air-conditioning and ventilation system to the basement portion of the development must be designed to comply with Part J5 of

the NCC.

Artificial Lighting and Power

The Class 7a and 7b parts must maintain maximum lighting power levels and control systems as applicable. The design of lighting systems must

comply with NCC Part J6.

Hot Water Supply

Hot water supply systems must be installed in accordance with Part J7 of the NCC and AS/NZS 3500.4.

Access for Maintenance

The building is to have facilities for maintenance and energy monitoring

in compliance with NCC Part J8 and the NSW variations.

Page 31: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

4.0 – FIRE SAFETY AND OTHER MEASURES

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 30 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

4.0 – Fire Safety and Other Measures

4.1 – Proposed Fire Safety Measures The building will have the following fire safety measures: - Measure Standard of Performance

Access panels to fire-resisting shafts. BCA Clause C3.13

Alarm signalling equipment BCA Clause E1.5, Spec. E1.5, AS 2118.1-1999, AS 1670.3-2004

Automatic fire detection and alarms systems (BOWS)

BCA Clause E2.2a, Clause 3 or 4 & 6 of Spec. E2.2a, AS 3786-2014.

Automatic fire suppression (carpark sprinkler systems)

BCA Clause E1.5, Specification E1.5, AS 2118.1-1999.

Emergency lighting BCA Clause E4.2 & E4.4, AS 2293.1-2005

Exit signs BCA Clause E4.5, NSW E4.6, E4.7 & E4.8, AS 2293.1-2005

Fire doors BCA Spec C3.8, C3.11, AS 1905.1-2005

Fire engineering Fire Engineering Report by XYZ.

Fire hydrant systems BCA Clause E1.3, AS 2419.1-2005

Fire seals (protecting openings in fire resisting components of the building)

BCA Clause C3.15, and manufacturers specifications.

Mechanical air handling systems (carpark)

BCA Clause E2.2a, Clause 5.5 of AS 1668.1-2015 & AS 1668.2-2012, AS 1670.1-2015.

Portable fire extinguishers BCA Clause E1.6, AS 2444-2001

Wall wetting sprinklers (drenchers to U15) BCA Clause D1.7(c), AS 2118.2-2010

Warning and operational signage - Fire door signs; - Fire isolated stairway notices; - Lift notices - Hydrant, hose reel, PFE signs..

BCA Clause D2.23, D3.6, E1.3, E1.4, E1.6, E3.3, and EP&A Regs 2000.

Page 32: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

5.0 – CONCLUSION

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 31 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

5.0 – Conclusion This BCA 2016 Report has been prepared to assess the proposed plans appurtenant to the Development Application that is to be submitted to Blacktown Council for a new residential flat building with 75 apartments and basement carparking for 130 vehicles. The assessment of the documentation has revealed that the building is primarily capable of complying with the Deemed-to-Satisfy [herein ‘DTS’] provisions of the BCA 2016 Code 2016 (Volume 1, Class 2-9 Buildings) [herein ‘BCA 2016’], and where necessary the Performance Requirements, without modification that require a development consent to be modified. Prepared by:

Greg Evans Director Accredited Certifier BPB 1870 360 Certification Date: 24 June 2017

Page 33: 360 Certification M: 0422 688 491 greg@360certification.net … ·  · 2017-09-252.1 – BUILDING LOCATION ... Clause 3 of Spec. C1.1, C2.8, C2.9, ... Level 1, level 2, level 3 and

6.0 – REFERENCES

Lot 5, 1086 Richmond Road, Marsden Park, Version 1, 24 June 2017. Page 32 of 32

360 Certification [Mosman Certifiers Pty Ltd], MOSMAN NSW 2088 ABN: 24 606 570 825, ACN: 606 570 825

6.0 – References & Plans

See attached plans.