230kV-substation-seminar-eric.ppt

69
230 KV SUBSTATION 230 KV SUBSTATION

Transcript of 230kV-substation-seminar-eric.ppt

  • 230 KV SUBSTATION

  • House Rules

    Observe silence Raise hand to question Avoid side discussions Turn off your cellular phones or keep it in silent mode

    230 kV Substation Seminar

  • Seminar Objectives

    This seminar takes an in-depth look into the

    components used in the transmission of electricity

    Learn typical configurations of switchyards

    and substation

    Learn the operation of transformers, circuit breakers,

    disconnects, current and potential transformers and

    lightning arresters

    Learn the components which make up a typical

    substation and how it feeds a distribution network

    that supplies customers with electricity

    230 kV Substation Seminar

  • Seminar Outline

    I. Introduction

    I.1 Power Substation

    I.2 Transmission Lines

    II. HV Outdoor Switchyard

    II.1 Types of Substation Configuration

    II.2 Outdoor HV Circuit Breakers

    II.3 HV Disconnect Switches

    II.4 HV Current Transformers

    II.5 HV Capacitor Voltage Transformer (CVT)

    II.6 Surge Arresters

    II.7 Power Systems Communications

    II.8 Typical HV Outdoor Substation Layout

    230 kV Substation Seminar

  • Seminar Outline

    III. Gas Insulated Substation

    III.1 Sulfur Hexaflouride (SF6) Gas

    III.2 Types of HV Substation

    IV. Power Transformer

    III.1 Classifications of transformer

    III.2 Cooling Methods

    230 kV Substation Seminar

  • Introduction

    1. Uses of Power Substation:

    Line termination Switching Protection Metering and voltage transformation Control and stabilization between the

    generating plant to the customers terminal

    230 kV Substation Seminar

  • Introduction

    2. Transmission Lines

    The transmission lines serves as the linkage

    between power generation and the power

    substations which serve as a voltage

    transformation point or switching or both.

    The delivery capability of the substation is

    dependent on the capacity of the transmission

    lines.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    1. Types of Substation Configuration

    The arrangement of outdoor switchyard installation is

    influenced by economic considerations, in particular the

    adaptation to space availability and the operational

    requirements of reliability and ease of operations.

    a) Single bus system

    b) Single bus system with by-pass bus

    c) Duplicate bus system

    d) Duplicate bus system with by-pass bus

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    1. Types of Substation Configuration

    e) Multiple bus system

    f) Multiple bus system with by-pass bus

    g) H-shape system

    h) Three breaker system

    i) Ring-bus system

    j) Polygon system

    k) One-and-a-half breaker system

    l) Two breaker system

    230 kV Substation Seminar

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    2. Outdoor HV Circuit Breakers

    2.1 Dead-tank circuit breakers

    A North American design using bulk oil

    (old design) or SF6 (new design) as the

    Interrupting medium.

    SF6 power circuit breaker utilize the puffer

    Principle of arc interruption. This principle

    utilizes compressing SF6 during the opening

    Stroke and exhausting compressed SF6

    through the breaker contacts to extinguish the

    Arc.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    2. Outdoor HV Circuit Breakers

    2.2 Live-tank circuit breakers

    A European design using SF6 as the

    Interrupting medium. Its difference with the

    Dead-tank design is the absence of a CT as an

    Integral part of the breaker.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    3. HV Disconnect Switches

    Disconnect switches or disconnectors are

    mechanical swinging devices which in the open

    position provide an isolating distance.

    They are used primarily for isolation and

    sectionalizing electric circuits such as buses,

    lateral circuits or portions of main circuits, and

    for special purposes such as testing and

    Maintenance.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    3. HV Disconnect Switches

    Types of disconnect switches:

    a) Vertical-break

    b) Side-break

    c) Center-break

    230 kV Substation Seminar

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    4. HV Current Transformer

    A separate units of HV current transformers are

    Required in live-tank circuit breakers installations.

    They provide the necessary interface between the

    HV and LV systems where protection, metering,

    and control signals are obtained.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    5. HV Capacitor Voltage Transformers (CVT)

    Capacitor voltage transformers or CVT are

    installed in high voltage systems with

    transmission voltages from 66 kV up to the

    highest voltages in the EHV range.

    Functions:

    a) Metering

    b) Protection

    c) Sychronizing

    d) Indication

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    5. HV Capacitor Voltage Transformers (CVT)

    They are often used simultaneously for coupling

    carrier frequencies to power lines for purposes

    of telecommunication, remote metering, selective

    line protection and control.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    5. HV Capacitor Voltage Transformers (CVT)

    The CVT has a distinct economic advantages

    at higher voltages over the conventional

    electromagnetic voltage transformers. At

    voltages of 100 kV and above, the selection

    of a CVT over the conventional VT is

    economically motivated by its duality of

    function: as a standard voltage transformer

    and as a coupler for high frequency

    power line carrier system.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    6. Surge Arresters

    Surge arresters in outdoor substations are used

    for limiting over voltages. The protection zone of

    the arrester is limited due to the traveling phenomena.

    To ensure that the voltage across the protected

    equipment is more or less equal to the surge

    arresters protective level, it is necessary to maintain

    a certain separation distance between the arrester

    and the protected equipment.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    6. Surge Arresters

    For rated voltages of 123 kV, the arrester should

    not be farther than 15-meter from the

    protected apparatus

    For 245 kV up to 525 kV, the maximum distance

    is 20-meter.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    7. Power System Communications:

    Power line carrier (PLC) systemUse of fibre optic communication

    PLC System

    Carrier links using the HV transmission lines

    or PLC systems are used by many power

    utilities as the form of its communications.

    They cater to the different communication

    tasks required by the power utility which

    includes the following: signals for telephony,

    line protection, telemetering, remote control, etc.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    7. Power System Communications:

    Fibre Optic Communication

    The use of fibre optic communication has

    continuously gained ground in recent years.

    The reasons are mainly due to the growing needs

    for increased transmission capacity as well as

    the enormous advantages of optical fibres over

    copper cables.

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    8. Typical HV Outdoor Substation Layout

    230 kV Substation Seminar

  • HV Outdoor Switchyard

    8. Typical HV Outdoor Substation Layout

    230 kV Substation Seminar

  • Gas Insulated Substation

    Gas-insulated substation or GIS is usually of

    modular construction. All components such as

    busbars, disconnectors, circuit breakers,

    instrument transformers and cable terminations

    are housed in a grounded metallic enclosures

    in which the primary insulating medium is

    a compressed gas, usually SF6.

    230 kV Substation Seminar

  • Gas Insulated Substation

    Advantages:

    1) Compact size

    2) Low weight

    3) High reliability

    4) Safety against touch contact

    5) Low maintenance

    On-site erection time is short due to the extensive

    prefabrication and factory testing of large assemblies

    or complete bays.

    230 kV Substation Seminar

  • Gas Insulated Substation

    1. Sulfur Hexaflouride (SF6) Gas

    Sulfur hexaflouride gas or SF6 is employed as

    insulation in all parts of the GIS installation and

    likewise used as the interrupting medium of the

    circuit breakers.

    SF6 is a highly electronegative gas (it readily

    absorbs electrons to form negative ions) and has

    A dielectric strength of about 89 kV/cm-bar in a

    uniform field or about 3 times that of air.

    230 kV Substation Seminar

  • Gas Insulated Substation

    2. Types of HV Substation

    There are several principal types of designs

    for HV substations. They can be conventional

    outdoor or indoor, gas insulated substation or

    GIS, or can be a hybrid as summarized on

    Table III.2.1.

    230 kV Substation Seminar

  • Gas Insulated Substation

    Table III.2.1

    Principal Types of Designs

    For HV Substation Installations

    (*) special cases only

    (**) station conversion, expansion or upgrading

    Basic DesignInsulating MediumVoltage Level, kVApplicationConventionalAir52-123Outdoor/ ndoorConventionalAir123-800outdoorGISSF652-800Indoor/outdoor*Hybrid**Air/SF6245-500outdoor

    230 kV Substation Seminar

  • Power Transformers

    One of the most important apparatus in the electrical

    system is the transformer. This is used to transfer

    power by electromagnetic induction between two or

    more circuits at the same frequency. The power

    transfer is usually accompanied with a change of

    voltage and current.

    230 kV Substation Seminar

  • Power Transformers

    1. Classification according to size

    1.1 Distribution transformer

    Distribution transformers are used for

    transferring power from the primary

    distribution circuit to a secondary distribution

    circuit.

    rated 5 kVA up to 500 kVA inclusive

    230 kV Substation Seminar

  • Power Transformers

    1. Classification according to size

    1.2 Power transformer

    Power transformers are used for

    transferring power in any part of the system

    between the generator down to the primary

    distribution system.

    rated 500 kVA above

    230 kV Substation Seminar

  • Power Transformers

    100 MVA Power Transformer

    230 kV Substation Seminar

  • Power Transformers

    100 MVA Power Transformer

    230 kV Substation Seminar

  • Power Transformers

    100 MVA Power Transformer

    230 kV Substation Seminar

  • Power Transformers

    2. Classification according to insulation

    2.1 Liquid-immersed transformers

    Liquid-immersed transformers are those whose

    core and coils are immersed in an insulating

    liquid. The insulating liquid can either be

    mineral or synthetic oil. Non-flammable

    liquid-immersed transformers are required for

    indoor installations

    230 kV Substation Seminar

  • Power Transformers

    2. Classification according to insulation

    2.2 Dry-type transformers

    Dry-type transformers are those whose

    core and coils are gaseous or dry compound

    insulating medium. These type of transformers

    are basically applied in LV up to MV systems

    Power Transformers

    230 kV Substation Seminar

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.1 Indoor transformers

    An indoor transformer is one which,

    because of construction, must be

    protected from weather. They are usually

    dry-type or the non-flammable oil-

    immersed type.

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.2 Outdoor transformers

    An outdoor transformer is of the weather-

    resistant construction suitable for service

    without the additional protection from the

    Weather. They are usually of the mineral

    oil-immersed type.

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.3 Station type transformers

    Station type transformers are those designed

    for installation in a power station or substation.

    They are usually those that have voltages

    above 34.5 kV in any of the windings.

    230 kV Substation Seminar

  • Power Transformers

    3.5 MVA Station Transformer

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.4 Padmounted transformer

    A padmounted transformer is an outdoor

    type used as a part of an underground

    distribution system. The high and low

    voltage bushings are provided with

    enclosed compartments with the

    corresponding cable systems entering from

    below. They are mounted on a foundation

    pad.

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.5 Pole-type transformers

    A pole-type transformer is one which is

    suitable for mounting on a pole or similar

    structure.

    230 kV Substation Seminar

  • Power Transformers

    3. Classification according to location

    3.5 Pole-type transformers

    A pole-type transformer is one which is

    suitable for mounting on a pole or similar

    structure.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    Excessive heat is a catalyst to the rapid

    degradation of the transformer insulation system.

    It reduces the mechanical and dielectric strength

    of the paper insulation. The loss of the insulation

    means the loss of life of the transformer.

    To safeguard the early retirement (failure) of

    transformers, several factors must be taken into

    consideration when loading. Each kVA rating of

    a transformer is based on its rated temperature rise

    of either 55oC or 65oC for oil-immersed and 55, 80,

    115 and 150oC for dry type.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    ANSI and IEC differs in identifying the various

    transformer cooling methods.

    4.1 ANSI standard

    The various types of transformer cooling

    methods as provided by the ANSI

    standard are identified by the type letters

    as shown on Table 4.1.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    4.1 ANSI standard

    The type letter identify by a slash

    indicates an upgraded capacity with

    forced-cooling. It is possible that the

    self-cooled rating can be raised to a

    higher rating of one or two steps

    depending on the number of auxiliary

    cooling stages and capacity.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    4.1 ANSI standard

    The Three phase transformer upgraded

    capacity with forced cooling is given as

    follows:

    501 - 2499 kVA1st stage = 1.5 self-cooled rating

    2500 11999 kVa1st stage = 1.25 self-cooled rating

    12000 kVa1st stage = 1.33 self-cooled rating

    2nd stage = 1.66 self-cooled rating

    230 kV Substation Seminar

  • Power Transformers

    Table 4.1

    230 kV Substation Seminar

    1.psd
  • Power Transformers

    4. Cooling Methods

    4.2 IEC standard

    The identification of the type of cooling of

    IEC standard transformers are identified by

    four-letter symbols as described on Table 4.2.

    The four-letter symbol indicating the type

    of cooling is governed by the order of

    arrangement of the letters given on Table 4.2.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    4.2 IEC standard

    The first two symbols indicate the cooling

    medium that is in contact with the windings.

    The last two symbols indicate the cooling

    medium that is in contact with the external

    cooling system.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    4.2 IEC standard

    An example of an IEC cooling designation is

    ONAN which can be interpreted as follows:

    ONANthe 1st letter O indicates that the

    cooling medium in contact with the

    winding is mineral oil.

    230 kV Substation Seminar

  • Power Transformers

    4. Cooling Methods

    the 2nd letter N indicates that the

    kind of circulation of the cooling

    medium in contact with the winding is

    natural.

    the 3rd letter A indicates that the

    kind of cooling medium in contact

    with the external cooling system is air.

    the 4th letter N indicates that the

    kind of circulation of the external

    cooling medium is natural.

    230 kV Substation Seminar

  • Power Transformers

    Table 4.2

    230 kV Substation Seminar

  • 230 kV Substation Seminar

    Learn from yesterday, live for today, hope for tomorrow. The important thing is not to stop questioning.
    Albert Einstein

  • Thank You

    230 kV Substation Seminar