Page 1 of 73 WG - SERIES COMBINATION GAS/ELECTRIC WALL-MOUNT MODELS: WG242-A WG242-B WG243-C WG302-A WG302-B WG303-C WG362-A WG362-B WG363-C WG423-A WG423-B WG424-C WG482-A WG482-B WG483-C WG602-A WG602-B WG603-C Manual No.: 2100-365Q Supersedes: 2100-365P File: Volume III, Tab 20 Date: 05-05-08 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2004 WARNING READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION. THE INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION. IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS. FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY INJURY, OR DEATH. INSTALLATION INSTRUCTIONS

Transcript of 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS...

Page 1: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 1 of 73

WG - SERIES

COMBINATION GAS/ELECTRIC

WALL-MOUNT

MODELS:

WG242-A WG242-B WG243-C WG302-A WG302-B WG303-C WG362-A

WG362-B WG363-C WG423-A WG423-B WG424-C WG482-A WG482-B

WG483-C WG602-A WG602-B WG603-C

Manual No.: 2100-365Q

Supersedes: 2100-365P

File: Volume III, Tab 20

Date: 05-05-08

Bard Manufacturing Company, Inc.

Bryan, Ohio 43506

Since 1914...Moving ahead just as planned.

© Copyright 2004

WARNING

READ ALL INSTRUCTIONS CAREFULLY BEFORE

BEGINNING THE INSTALLATION.

THE INSTALLATION MUST COMPLY WITH THESE

INSTRUCTIONS AND THE REQUIREMENTS OF ALL

GOVERNING CODES AND ORDINANCES FOR THE

INSTALLATION LOCATION.

IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW

AND UNDERSTAND ALL OF THESE REQUIREMENTS.

FAILURE TO DO SO COULD CREATE A HAZARD

RESULTING IN PROPERTY DAMAGE, BODILY INJURY,

OR DEATH.

INSTALLATION

INSTRUCTIONS

Page 2: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 2 of 73

CONTENTS

Getting Other Information and Publications .............. 4

WG Series Model Nomenclature............................... 5

Ventilation Options .................................................... 5

Air Conditioning Module Options ............................... 6

1. Important ............................................................ 6

2. Application .......................................................... 6

3. Duct Work .................................................. 6 & 10

4. High Altitude Applications ................................. 10

5. Transportation Damage .................................... 10

6. Installation ........................................................ 10

7. Wall Mounting .................................................. 11

8. Mounting the Unit ............................................. 11

9. Clearances ....................................................... 17

10. Vent Terminal and Combustion Inlet Hood ....... 18

11. Optional Vertical Venting .................................. 18

12. Vent Resizing Instructions ................................ 19

13. Fresh Air Intake ................................................ 19

14. Condensate Drain ............................................ 19

15. Wiring – Main Power ........................................ 20

16. Wiring – Low Voltage Wiring ............................ 21

17. Thermostats ...................................................... 21

18. Gas Supply & Piping ........................................ 24

19. Manifold Pressure Adjustment .......................... 25

20. Checking Gas Input Rate ......................... 25 & 26

21. Standard Orifice Sizing & HighAltitude Derate .................................................. 27

22. Conversion of Gas Input BTUH From Highto Low Rating ................................................... 30

23. Measuring Air Temperature Rise ...................... 30

24. Filters ................................................................ 31

25. Compressor Control Module..................... 31 & 32

26. Lighting & Shutdown Instructions ..................... 33

27. Service Agency Procedures ............................. 34

28. Maintaining Unit in Good Working Order .. 34 & 35

29. Replacement Parts ............................................ 35

30. Sequence of Operation – Heating .................... 36

31. Sequence of Operation – Cooling .................... 36

32. Indoor Blower Operation .................................. 37

33. Pressure Service Ports ..................................... 45

34. Refrigerant Charge ........................................... 46

35. Fan Blade Setting Dimensions ......................... 46

36. Low NOx Burner Assembly "N" SuffixModels Only – U.S. Installations Only .............. 46

Index – Wiring Diagrams ......................................... 47

Wiring Diagrams ............................................. 48 – 73

Page Page

Page 3: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 3 of 73

CONTENTS

FIGURES

Figure 1 Unit Dimensions ..................................... 9

Figure 2 Mounting Instructions – WG24-36 ....... 12

Figure 2A Mounting Instructions – WG42-60 ....... 13

Figure 3 Combustible Clearance – WG24-36 .... 14

Figure 3A Combustible Clearance – WG42-60 .... 14

Figure 4 Wall Mounting Instructions ................... 15

Figure 5 Wall Mounting Instructions ................... 15

Figure 6 Common Wall Mounting Installations ... 16

Figure 7 Location of Vent Terminal in Shipping .. 17

Figure 8 Vent Terminal & Combustion

Air Intake .............................................. 18

Figure 9 Fresh Air Damper ................................. 19

Figure 10 Installation of Flexible Conduit ............. 21

Figure 11 Low Voltage Wiring .............................. 22

Figure 12 Gas Pipe Connection ........................... 23

Figure 13 Proper Piping Practice ......................... 24

Figure 14 Access Internal Filter through

Upper Service Door .............................. 31

Figure 15 Lighting & Shutdown Instruction Label . 33

Figure 16 Top View of Gas Control ...................... 34

Figure 17 Sequence of Operation – ElectronicBlower Control ...................................... 36

Figure 18 Furnace Control Board &Blower Control ...................................... 37

Figure 19 Fan Blade ............................................. 46

Figure 20 Low NOx Insert .................................... 46

TABLES

Table 1 Specifications – WG24-36 Models ........... 7

Table 1A Specifications – WG42-60 Models ........... 8

Table 2 Minimum Installation Clearances ........... 17

Table 3 Thermostat Wire Size ............................ 21

Table 4 Wall Thermostat ..................................... 21

Table 5 Length of Standard Pipe Threads .......... 24

Table 6 Gas Pipe Sizes – Natural Gas ............... 24

Table 7 Natural Gas Derate CapacitiesFor All Models ........................................ 27

Table 8 Natural Gas Orifice Tables – WG24-36 .. 28

Table 8A Natural Gas Orifice Tables – WG42-60 .. 29

Table 9 Motor Speed Taps .................................. 37

Table 10 WG24 Indoor Blower Performance ........ 38

Table 11 WG30 Indoor Blower Performance ........ 39

Table 12 WG36 Indoor Blower Performance ........ 40

Table 13 WG42 Indoor Blower Performance ........ 41

Table 14 WG48 Indoor Blower Performance ........ 42

Table 15 WG60 Indoor Blower Performance ........ 43

Table 16 Integrated Furnace & BlowerControl Operation ................................... 44

Table 17 Cooling Pressure Table .......................... 45

Table 18 Refrigerant Charge ................................ 46

Table 19 Fan Blade Dimension ............................. 46

Page Page

Page 4: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 4 of 73

Getting Other Information and Publications

FOR MORE INFORMATION, CONTACTTHESE PUBLISHERS:

ACCA Air Conditioning Contractors of America

1712 New Hampshire Avenue, NW

Washington, DC 20009

Telephone: (202) 483-9370

ANSI American National Standards Institute

11 West Street, 13th Floor

New York, NY 10036

Telephone: (212) 642-4900

Fax: (212) 302-1286

ASHRAE American Society of Heating Refrigerating,

and Air Conditioning Engineers, Inc.

1791 Tullie Circle, NE.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA National Fire Protection Association

Batterymarch Park

P.O. Box 9101

Quincy, MA 02269-9901

Telephone: (800) 344-3555

Fax: (617) 984-7057

CSA Canadian Standards Association

178 Rexdale Boulevard

Rexdale, Ontario

Canada. M9W 1R3

Telephone: (416) 447-4044

COPYRIGHT SEPTEMBER 2003

BARD MANUFACTURING COMPANY, INC.

BRYAN, OHIO 43506 USA

Manufactured under the following U.S. patent numbers:

5,485,878; 5,002,116; 4,924,934; 4,875,520; 4,4825,936

These publications can help you install the furnace. You

can usually find these at your local library or purchase

them directly from the publisher. Be sure to consult

current edition of each standard.

National Fuel Gas Code ......... ANSI Z223.1 / NFPA 54

National Electrical Code ..................... ANSI / NFPA 70

Standard for the Installation ............. ANSI / NFPA 90A

of Air Conditioning and Ventilating Systems

Standard for Warm Air ..................... ANSI / NFPA 90B

Heating and Air Conditioning Systems

Standard for Chimneys, ................................. NFPA 211

Fireplaces, Vents, and Solid Fuel Burning Appliances

Load Calculation for ............................ ACCA Manual J

Residential Winter and Summer Air Conditioning

Duct Design for Residential ............... ACCA Manual D

Winter and Winter Air Conditioning and Equipment

Selection

Canadian Electrical Code ............................. CSA C22.1

Canadian Installation Code……………CAN/CGA B149

Page 5: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 5 of 73

WG 42 1 – A X C X X X X X X

WALL MOUNT GAS/ELECTRIC GENERAL

MODEL NUMBER NOMENCLATURE

1 Low ambient control is required with economizer for low temperature compressor operation.

VENTILATION OPTIONS

sledoM 63GW,03W,42GW 06GW,84GW,24GW

noitpircseDdellatsnIyrotcaF

.oNedoCdellatsnIdleiF

.oNtraPdellatsnIdleiF

.oNtraP

repmaDriAhserFcirtemoraB X 3-DAFGW 5-DAFGW

etalPffO-knalB B 3-POBGW 5-POBGW

repmaDriAhserFdezirotoM M 3-DAFMGW 5-DAFMGW

nruteRgnirpS-rotalitneVlaicremmoC V 3-SVRCGW 5-SVRCGW

nruteRrewoP-rotalitneVlaicremmoC P 3-PVRCGW 5-PVRCGW

gnitaludoMylluF-rezimonocE 1 E 3-MFIEGW 5-MFIEGW

tloV032-rotalitneVyrevoceRygrenE R 3A-VREGW 5A-VREGW

tloV064-rotalitneVyrevoceRygrenE R 3C-VREGW 5C-VREGW

MODEL

Wall Mount Gas/Electric

CONTROL OPTIONS

(See Table page 6)

VENT

(See Table Below)

COOLING CAPACITY

24 = 2 ton

30 = 2½ ton

36 = 3 ton

42 = 3½ ton

48 = 4 ton

60 = 5 ton

OUTLET

X = Front (Standard)

T = Top

COIL OPTIONS

X = Standard

1 = Phenolic coated evaporator

2 = Phenolic coated condenser

3 = Phenolic coated both coils

COLOR

X = Beige

(Standard)

4 = Gray

FILTER

X = 2" Pleated (Standard)

W = 1" Washable

VOLTAGE

A = 230/208-60-1

B = 230/208-60-3

C = 460-60-3

REVISION

FEATURE

(-) = Standard

D = Dehumidification

C = Canadian Approval

EMISSIONS

X = Standard

N = NOx Certified

*125,000 BTU input model is not NOx certified.

HEATING INPUT

2 - 3 Ton 3.5 - 5 Ton

A = 45,000 B= 75,000

B = 67,500 C= 100,000

C = 90,000 D= 125,000*

Page 6: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 6 of 73

1. IMPORTANT

The equipment covered in this manual is to be installed

by trained, experienced service and installation

technicians. All duct work or portions thereof not in

the conditioned space should be properly insulated in

order to both conserve energy and prevent condensation

or moisture damage.

2. APPLICATION

This is a fan-assisted forced air gas furnace with

electric air conditioning for outdoor installation. A

fan-assisted furnace is equipped with an integral

mechanical means to draw products of combustion

through the combustion chamber and heat exchanger.

The furnace installation must conform with local

building codes and ordinances or, in their absence, with

the National Fuel Gas Code ANSI Z223.1 or CAN/

CGA-B149.1, latest edition, and the National Electrical

Code ANSI/NFPA-7 or CSA C22.1, latest edition. It is

the personal responsibility and obligation of the

purchaser to contact a qualified installer to assure that

installation is adequate and is in conformance with

governing codes and ordinances.

3. DUCT WORK

The unit is designed for use with or without duct work.

See Warning on Page 10. Flanges are provided for

attaching the supply and return ducts. These

instructions explain the recommended method to install

the air cooled self-contained electric air conditioning

and gas heating unit and the electrical wiring

connections and gas piping to the unit. The refrigerant

system is completely assembled and charged. All

internal wiring is complete.

These instructions and any instructions packaged with

any separate equipment required to make up the entire

heating/cooling system should be carefully read before

beginning the installation. Note particularly “Starting

Procedure” and any tags and/or labels attached to the

equipment.

All duct work, supply and return, must be properly sized

for the design airflow requirement of the equipment.

Air Conditioning Contractors of America (ACCA) is an

excellent guide to proper sizing.

Refer to Tables 10, 11, 12, 13, 14 and 15 in this Manual

for maximum static pressure available for duct design.

AIR CONDITIONING MODULE OPTIONS

STD = Standard equipment.1 CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break

timer. On initial power up, or any time the power is interrupted, the delay-on-make

will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout

feature (with 1 retry) for high and/or low pressure controls, and a 2 minute timed

bypass for low pressure control.2 HPC High pressure control is auto reset. Always used with compressor control module

(CCM) which is included. See note 1.

3 LPC Low pressure control is auto reset. Always used with compressor control module(CCM) which is included. See note 1.

4 LAC Low ambient control permits cooling operation down to 0°F.

1

MCC2

CPH3

CPL4

CALdellatsnIyrotcaF

edoCdellatsnIdleiF

traP

DTS DTS � G 61-AMC

DTS DTS � � H 81-AMC

DTS DTS � I 6-AMC

CAUTIONDuring the initial firing of the burners there will probably be some amount of smoke issued to thecirculating air stream as the result of residual oil burning off of the heat exchanger tubes. This oilis required during the forming process of the stainless steel heat exchanger tubes to facilitate thebending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. Invapor form this may be irritating to the eyes or could cause headaches. This is a one-timeoccurrence, and ventilation of the space may be required depending upon the space beingconditioned.

Page 7: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 7 of 73

TA

BL

E

1

SP

EC

IFIC

AT

ION

S

WG

24

, W

G3

0 A

ND

WG

36

MO

DE

LS

*

75

de

gre

e C

Co

pp

er

wir

e s

ize

** M

axim

um

tim

e d

ela

y f

use

or

HA

CR

Typ

e c

ircu

it b

rea

ke

r

led

oM

A-242G

WB-242

GW

C-342G

WA-203

GW

B-203G

WC-303

GW

A-263G

WB-263

GW

C-363G

W

ZH06

–gnita

RlacirtcelE

1-06-802/0323-06-802/032

3-06-0641-06-802/032

3-06-802/0323-06-064

1-06-802/0323-06-802/032

3-06-064

egnaR

egatloV

gnitarepO

352-791352-781

605-414352-791

352-781605-414

352-791352-781

605-414

yticapm

AtiucriC

mumini

M81

317

3271

962

819

*ezi

Seri

Wdlei

F01

2141

0121

418

0141

eziS

eriW

dnuorG

0121

4101

2141

0101

41

**.xa

M–

esuF

yaleD

5202

5104

5251

0452

51

rosserpmo

C

epyTrosserp

moC

.pceR

.pceR

.pceR

llorcS

llorcS

llorcS

.pceR

.pceR

.pceR

stloV

802/032802/032

064802/032

802/032064

802/032802/032

064

spm

AdaoL

detaR

5.01/5.96.6/2.6

3.35.31/5.21

5.9/0.95

61/4101/5.9

5

tnerruC

noitceleStiucri

Chcnar

B5.01

7.65.3

1.415.9

561

015

spm

Aroto

RkcoL

65/6515/15

5237/37

36/3613/13

87/8727/27

54/54

rosserpmo

Cdna

rotoM

naF

DP

S/M

PR/

PH

–roto

Mna

F1/

0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

1/0501/5/1

spm

A–

rotoM

naF

5.15.1

8.05.1

5.18.0

5.15.1

8.0

MF

C/AI

D–

naF

0091–

"020091

–"02

0091–

"020091

–"02

0091–

"020091

–"02

0091–

"020091

–"02

0091–

"02

rotaropavE

dnaroto

M

DP

S/M

PR/

PH

–roto

Mre

wolB

3/059/

4/13/

059/4/1

3/059/

4/13/5701/

3/13/5701/

3/13/5701/

3/13/5701/

3/13/5701/

3/13/5701/

3/1

spm

A–

rotoM

rewol

B8.1

8.18.0

2.22.2

1.12.2

2.21.1

.P.S.

E&

gnilooC

MF

C52.

–008

52.–

00852.

–008

53.–

000153.

–0001

53.–

000152.

–0011

52.–

001152.

–0011

)sehcnI(sezi

Sretli

F2

x52

x02

2x

52x

022

x52

x02

2x

52x

022

x52

x02

2x

52x

022

x52

x02

2x

52x

022

x52

x02

).zo22-

R(egrah

C77

7777

7979

7968

6868

Page 8: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 8 of 73

*

75

de

gre

e C

Co

pp

er

wir

e s

ize

** M

axim

um

tim

e d

ela

y f

use

or

HA

CR

Typ

e c

ircu

it b

rea

ke

r

TA

BL

E

1A

SP

EC

IFIC

AT

ION

S

WG

42

, W

G4

8 A

ND

WG

60

MO

DE

LS

led

oM

A-324G

WB-324

GW

C-424G

WA-284

GW

B-284G

WC-384

GW

A-206G

WB-206

GW

C-306G

W

ZH06

–gnita

RlacirtcelE

1-06-802/0323-06-802/032

3-06-0641-06-802/032

3-06-802/0323-06-064

1-06-802/0323-06-802/032

3-06-064

egnaR

egatloV

gnitarepO

352-

791352

-781

605-

414352

-791

352-

781605

-414

352-

791352

-781

605-

414

yticapm

AtiucriC

mumini

M43

6231

5342

2154

2351

*/

eziS

eriW

dleiF

88

418

841

88

21

eziS

eriW

dnuorG

0101

4101

0141

0101

21

**.xa

M–

esuF

yaleD

0553

5105

5351

0654

02

rosserpmo

C

epyTrosserp

moC

llorcS

llorcS

llorcS

llorcS

llorcS

llorcS

llorcS

llorcS

llorcS

stloV

802/032802/032

064802/032

802/032064

802/032802/032

064

spm

AdaoL

detaR

5.91/125.41/5.31

85.12/12

31/5.212.6

03/725.91/71

9

tnerruC

noitceleStiucri

Chcnar

B12

516.7

2231

4.603

5.919

spm

Aroto

RkcoL

721/72188/88

44131/131

18/1964

961/961731/731

26

rosserpmo

Cdna

rotoM

naF

DP

S/M

PR/

PH

–roto

Mna

F2-058-3/1

2-058-3/11-058-3/1

2-058-3/12-058-3/1

1-058-3/12-058-3/1

2-058-3/11-058-3/1

spm

A–

rotoM

naF

5.25.2

3.15.2

5.23.1

5.25.2

3.1

MF

C/AI

D–

naF

0072-"420072-"42

0072-"420072-"42

0072-"420072-"42

0072-"420072-"42

0072-"42

rotaropavE

dnaroto

M

DP

S/M

PR/

PH

–roto

Mre

wolB

3-0501-2/13-0501-2/1

3-0501-2/13-0501-2/1

3-0501-2/13-0501-2/1

3-0501-2/13-0501-2/1

3-0501-2/1

spm

A–

rotoM

rewol

B4.3

4.35.1

4.34.3

5.14.3

4.35.1

.P.S.

E&

gnilooC

MF

C53.

-0031

53.-

003153.

-0031

83.-

055183.

-0551

83.-

055103.

-0561

03.-

056103.

-0561

)sehcnI(sezi

Sretli

F2

x03

x02

2x

03x

022

x03

x02

2x

03x

022

x03

x02

2x

03x

022

x03

x02

2x

03x

022

x03

x02

).zo22-

R(egrah

C101

101101

611611

611341

341341

Page 9: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 9 of 73

II Q

F G

N

P

D

DD

FF

GG

A

M

I C KJL

HH

H

S S S SR SVYAA

U Z

X

CC

BB

BE

EO

E

W

T

B

HIG

H V

OLT

AG

E E

NT

RA

NC

ES

RIG

HT

SID

E

DIS

CO

NN

EC

T A

CC

ES

S

RE

TU

RN

OP

EN

ING

FR

ON

T

PA

NE

L (L

OC

KA

BLE

)

PA

NE

L

BA

CK

SU

PP

LY O

PE

NIN

G

PA

NE

L D

OO

R

GA

S

EN

TR

AN

CE

S

CO

ND

EN

SE

R

AIR

INLE

TC

ON

DE

NS

ER

AIR

OU

TLE

TS

4 D

EG

. PIT

CH

IN T

OP

VE

ST

IBU

LED

OO

R

SE

RV

ICE

/FIL

TE

RH

ING

ED

DO

OR

CO

MB

US

TIO

NA

IR E

XH

AU

ST

CO

MB

US

TIO

NA

IR IN

TA

KE

CO

NT

RO

L

LOW

VO

LTA

GE

EN

TR

AN

CE

SC

IRC

UIT

BR

EA

KE

R/

VE

NT

OP

TIO

N

MIS

-212

3 A

UN

ITA

BC

DE

FG

HI

JK

LM

NO

WG

24

-W

G3

0-W

G3

67

.88

27

.88

13

.88

24

.25

40

25

.63

81

.63

27

.38

27

.53

9.2

5

WG

42

-W

G4

8-W

G6

09

.88

29

.88

15

.88

27

.25

43

.81

31

.63

87

.53

3.3

82

8.7

54

2.8

8

UN

ITS

TU

VW

XY

ZA

AB

BC

CD

DE

EF

FG

G

WG

24

-W

G3

0-W

G3

61

2 -

7 H

OL

ES

2.8

82

2.9

38

17

.84

4.4

41

1.4

49

36

.25

WG

42

-W

G4

8-W

G6

01

6 -

6 H

OL

ES

3.8

82

4.9

42

17

.34

8.4

41

2.1

91

04

0.2

51

.25

7.2

51

.13

3.7

52

.25

3.2

5

15

.31

14

.88

30

14

.12

15

.44

FIG

UR

E

1

UN

IT D

IME

NS

ION

S

Page 10: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 10 of 73

See Figure 3 and clearance information in Section 9

and Table 2 for additional information.

Design the duct work according to methods given by

the Air Conditioning Contractors of America (ACCA).

When duct runs through unheated spaces, it should be

insulated with a minimum of one-inch of insulation.

Use insulation with a vapor barrier on the outside of

the insulation. Flexible joints should be used to

connect the duct work to the equipment in order to

keep the noise transmission to a minimum.

A one-inch clearance to combustible material for the

first three feet of duct attached to the outlet air frame is

required. See Wall Mounting Instructions and Figures

2, 2A, 3 and 3A for further details.

Ducts through the walls must be insulated and all joints

taped or sealed to prevent air or moisture entering the

wall cavity.

Some installations may not require any return air duct.

A metallic return air grille is required with installations

not requiring a return air duct. The spacing between

louvers on the grille shall not be larger than 5/8 inch.

Any grille that meets with the 5/8 inch louver criteria

may be used. It is recommended that Bard Return Air

Grille or Return Filter Grille be installed when no

return duct is used. Contact distributor or factory for

ordering information. If using a return air filter grille,

filters must be of sufficient size to allow a maximum

velocity of 400 fpm.

NOTE: If no return air duct is used, applicable

installation codes may limit this cabinet to

installation only in a single story structure.

4. HIGH ALTITUDE APPLICATIONS

Ratings of gas utilization equipment are based on sea

level operation and need not be changed for operation

at elevations up to 6,000 feet. For operation at

elevations above 6,000 feet and in the absence of

specific recommendations from the local authority

having jurisdiction, equipment ratings shall be reduced

as specified in Section 21.

5. TRANSPORTATION DAMAGE

All units are packed securely in shipping container.

All units should be carefully inspected upon arrival for

damage. In the event of damage, the consignee should:

1. Note on delivery receipt of any damage to container.

2. Notify carrier promptly, and request an inspection.

3. In case of concealed damage, the carrier must be

notified as soon as possible within 15 days after

delivery.

4. Claims for any damage, apparent or concealed,

should be filed with the carrier, using the following

supporting documents:

A. Original Bill of Lading, certified copy, or

indemnity bond.

B. Original paid freight bill of indemnity in lieu

thereof.

C. Original invoice or certified copy thereof

showing trade and other discounts or

deductions.

D. Copy of the inspection report issued by

carrier’s representative at the time damage is

reported to carrier.

6. INSTALLATION

Size of unit for proposed installation should be based

on heat loss/heat gain calculations made according to

methods of Air Conditioning Contractors of America

(ACCA). The air duct should be installed in

accordance with the Standards of the National Fire

Protection Association for the Installation of Air

Conditioning and Ventilating Systems of Other Than

Residence Type, NFPA No. 90A, and Residence Type

Warm Air Heating and Air Conditioning Systems,

NFPA No. 90B. Where local regulations are at a

variance with instructions, installer should adhere to

local codes.

WARNING In all cases, there must be a metal ductconnection made to the supply air flange, anda one inch clearance to combustibles must bemaintained to this duct connection. For free blow applications, a metal sleevemust be used in the wall opening itself, againmaintaining a one inch clearance tocombustibles. Failure to use the sheet metal can causefire resulting in property damage, injury, ordeath.

Page 11: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 11 of 73

7. WALL MOUNTING INFORMATION

1. Two holes for the supply and return air

openings must be cut through the wall as

detailed in Figure 4.

2. On wood-frame walls, the wall construction

must be strong and rigid enough to carry the

weight of the unit without transmitting any unit

vibration.

3. Concrete block walls must be thoroughly

inspected to insure that they are capable of

carrying the weight of the installed unit.

8. MOUNTING THE UNIT

1. These units are secured by wall mounting

brackets which secure the unit to the outside

wall surface at both sides. A bottom mounting

bracket is provided for ease of installation but

is not required.

2. The WG42, WG48 and WG60 models are

suitable for 0 inch clearance on the installation

mounting wall and to the top. For all models the

supply air duct flange and the first 3 feet of

supply air duct require a minimum of 1-inch

clearance to combustible material. The WG24,

WG30 and WG36 models are suitable for 0 inch

clearance on the installation mounting wall, but

require 1-inch clearance to the top if combustible

material overhang projects above the unit. See

Figure 3 and 3A. If a combustible wall, use a

minimum of Figure 1 “A” dimension plus 2

inches and “B” dimension plus 2 inches. See

Figures 4 and 5 for details.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.

Top rain flashing is shipped secured to the right

side of the back.

6. Position unit in opening and secure with 5/16

lag bolts; use 7/8 inch diameter flat washers on

the lag bolts. Use lag bolts long enough to

support the unit’s weight when mounted to the

structure. This length may be dependant on the

type of construction.

7. Secure rain flashing to wall and caulk across

entire length of top. See Figure 3.

8. On side-by-side installations, maintain a

minimum of 20 inches clearance on right side

to allow access to control panel and burner

compartment, and to allow proper airflow to the

outdoor coil. Additional clearance may be

required to meet local or national codes.

CAUTIONIf the bottom bracket is used, be certain thebracket is secured to the outside wall surfacein a way sufficient to support the entire weightof the unit during installation until sidemounting brackets are secured.

WARNINGFailure to provide the one inch clearancebetween the supply duct and a combustiblesurface for the first three feet of duct canresult in fire causing damage, injury or death.

Page 12: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 12 of 73

FIG

UR

E

2

MO

UN

TIN

G I

NS

TR

UC

TIO

NS

FO

R W

G2

4,

WG

30

AN

D W

G3

6

39 3

/16"

29 3

/4"

4 11

/16"

12"

12"

12"

12"

12"

12"

2"

2 1/

4"

10"

28 5

/16"

15"

27"

17 1

5/16

"

11 5

/16"

8 5/

8"

2 15

/16"

2 1/

4"

30"

29"

5 1/

16"

7/16

"

5 9/

16"

4 9/

16"

4 1/

2"

2 15

/16"

18 1

5/16

"

4 9/

16"

SU

PP

LYA

IR D

UC

T

RE

TU

RN

AIR

DU

CT

Ø2

3/4"

GA

S

OP

EN

ING

(OP

TIO

NA

L)

Ø2

3/4"

HIG

HV

OLT

AG

E(O

PT

ION

AL)

Ø2"

LO

W V

OLT

AG

E(O

PT

ION

AL)

(12)

FLA

NG

ES

CR

EW

S

UN

IT S

UP

PO

RT

1" M

IN.

NE

CC

ES

SA

RY

NO

CLE

AR

AN

CE

SU

PP

LYA

IR D

UC

T

RE

TU

RN

AIR

DU

CT

CO

NT

RO

L P

AN

EL

VE

ST

IBU

LED

OO

R

WA

LLS

TR

UC

TU

RE

(OU

TS

IDE

)

1" C

LEA

RA

NC

E O

N A

LLF

OU

R S

IDE

S O

F S

UP

PLY

AIR

DU

CT

IS R

EQ

UIR

ED

FR

OM

CO

MB

US

TA

BLE

MA

TE

RIA

LS

NO

TE

: IT

IS R

EC

OM

ME

ND

ED

TH

AT

A B

EA

DO

F S

ILIC

ON

E C

AU

LKIN

G B

E P

LAC

ED

BE

HIN

DT

HE

SID

E M

OU

NT

ING

FLA

NG

ES

AN

D U

ND

ER

TO

P F

LAS

HIN

G A

T T

IME

OF

INS

TA

LLA

TIO

N

RIG

HT

SID

E

VIE

W W

ITH

UN

IT

OU

TS

IDE

WA

LL

WIT

H

UN

IT R

EM

OV

ED

RA

IN F

LAS

HIN

GS

UP

PLI

ED

SE

AL

WIT

H B

EA

D O

F C

AU

LKIN

G

ALO

NG

EN

TIR

E L

EN

GT

H O

F T

OP

TO

P

FO

AM

AIR

SE

AL

WA

LL

MIS

-168

1

Page 13: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 13 of 73

FIG

UR

E

2A

MO

UN

TIN

G I

NS

TR

UC

TIO

NS

FO

R W

G4

2,

WG

48

AN

D W

G6

0

Page 14: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 14 of 73

FIGURE 3

COMBUSTIBLE CLEARANCE

FOR WG24, WG30 AND WG36 MODELS

FIGURE 3A

COMBUSTIBLE CLEARANCE

FOR WG42, WG48 AND WG60 MODELS

WARNINGA minimum of one (1) inch clearance must be maintained between the supply air duct and combustible materials.

This is required for the first three (3) feet of ducting.

It is important to insure that the one (1) inch minimum spacing is maintained at all points.

Failure to do this could result in overheating the combustible material and may result in a fire causing damage,

injury or death.

Page 15: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 15 of 73

FIGURE 4

WALL MOUNTING INSTRUCTIONS

FIGURE 5

WALL MOUNTING INSTRUCTIONS

Page 16: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 16 of 73

FIGURE 6

COMMON WALL MOUNTING INSTALLATIONS

Page 17: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 17 of 73

9. CLEARANCES

Minimum clearances, as specified in Table 2, must be

maintained from adjacent structures to provide

adequate fire protection, adequate combustion air, and

room for service personnel.

While minimum clearances are acceptable for safety

reasons, they may not allow adequate air circulation

around the unit for proper operation in the cooling

mode. Whenever possible, it is desirable to allow

additional clearance, especially around the condenser

inlet and discharge openings. DO NOT install the unit

in a location that will permit discharged air from the

condenser to recirculate to the condenser inlet.

TABLE 2

MINIMUM INSTALLATION CLEARANCES

)slairetamelbitsubmocmorf(tcuDteltuO teef3tsrifhcni1

)slairetamelbitsubmocmorf(lanimreTtneV * sehcni71

teltuOresnednoC sehcni02

poT 3erugiFeeS

ecivreSrenruB sehcni02

B,AssalCrodooW(esaBelbitsubmoC)lairetamgnirevocfoorCro sehcni0

* A3dna3serugiFeeS

FIGURE 7

LOCATION OF VENT TERMINAL IN SHIPPING

WARNINGClearances from combustible materials mustbe maintained as specified. Failure tomaintain clearances could cause fire resultingin property damage, injury, or death.

Page 18: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 18 of 73

10. VENT TERMINAL AND COMBUSTIONAIR INLET HOOD

The vent terminal is shipped in the burner

compartment. See Figure 7. Remove the two shipping

screws and separate the two-piece assembly. Install the

vent terminal by using the four screws provided. Do

not cut or trim gasket. Make sure gasket is in place.

See Figure 8. The combustion air intake hood is factory

installed.

11. OPTIONAL VERTICAL VENTING

With the optional vertical venting kit (VVK-5) this unit

may be vented vertically through a roof or overhang.

The kit includes a stainless steel transition drain tee,

silicone sealant, and drain tubing.

If unit is installed with vertical vent kit, annually

inspect the vent system and drain. Replace any portion

of the vent system that shows signs of deterioration.

Make sure drain is open and free of obstruction.

FIGURE 8

VENT TERMINAL AND COMBUSTION AIR INTAKE

CAUTIONVent terminal must be installed as shown in Figure 8 for proper operation of the heating system.

NOTE: The inner vent hood gasket is designed to stretch over and seal around the combustionair blower outlet. This is a very critical seal to prevent water and flue products from entering theunit. Care must be taken to insure this gasket is in place and sealing properly.

Page 19: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 19 of 73

12. VENT RESIZING INSTRUCTIONS

When an existing furnace is removed from a venting

system servicing other appliances, the venting system is

likely to be too large to properly vent the remaining

attached appliances.

The following steps shall be followed with each of the

appliances remaining connected to the common venting

system, placed in operation one at a time while the

other appliances remaining connected to the common

venting system are not in operation.

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and

horizontal pitch, as required in the National Fuel Gas

code, ANSI Z223.1 or the CAN/CGA B149

Installation Codes and these instructions. Determine

that there is no blockage or restriction, leakage,

corrosion and other deficiencies which could cause

an unsafe condition.

3. In so far as is practical, close all building doors and

windows and all doors between the space in which

the appliance(s) connected to the venting system are

located and other spaces of the building. Turn on

clothes dryers and any appliances not connected to

the venting system. Turn on any exhaust fans, such

as range hoods and bathroom exhausts, so they will

operate at maximum speed. Do not operate a

summer exhaust fan. Close fireplace dampers.

4. Follow the lighting instructions. Place the appliance

being inspected in operation. Adjust thermostat so

appliance shall operate continuously.

5. Test for draft hood equipped appliance spillage at the

draft hood relief opening after 5 minutes of main

burner operation. Use the flame of a match or

candle.

6. After it has been determined that each appliance

connected to the venting system properly vents when

tested as outlined above, return doors, windows,

exhaust fans, fireplace dampers and any other gas-

burning appliances to their previous conditions of

use.

7. If improper venting is observed during any of the

above tests, the venting system must be corrected.

13. FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in

the service panel.

If the unit is equipped with a fresh air damper

assembly, the assembly is shipped already attached to

the unit. The damper blade is locked in the closed

position. To allow the damper to operate, the

maximum and minimum blade position stops must be

installed. See Figure 9.

All capacity, efficiency and cost of operation

information as required for Department of Energy

“Energyguide” Fact Sheets is based upon the fresh air

blank-off plate in place and is recommended for

maximum energy efficiency.

The blank-off plate is available upon request from the

factory and is installed in place of the fresh air damper

shipped with each unit.

One of several other ventilation options may be

installed. Refer to model number and/or supplemental

installation instructions.

14. CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the

top of the unit down to the unit base. There are

openings in the unit base for the drain hose to pass

through. In the event the drain hose is connected to a

drain system of some type, it must be an open or vented

type system to assure proper drainage.

FIGURE 9

FRESH AIR DAMPER

Page 20: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 20 of 73

ELECTRICAL GROUNDING

When installed, the furnace must be electrically

grounded in accordance with local codes or in the

absence of local codes, with the National Electrical

Code, ANSI/NFPA 70, or Canadian Electrical Code,

CSA22.1, latest edition. Use a copper wire from green

ground wire on the furnace to a grounded connection in

the service panel or a properly driven and electrically

grounded ground rod. See Tables 1 & 1A for proper

ground wire size.

FIELD INSTALLED EQUIPMENT

Wiring to be done in the field between the furnace and

devices not attached to the furnace, or between separate

devices which are field installed and located, shall

conform with the temperature limitation for Type T

wire {63 degrees F rise (36 degrees C)} when installed

in accordance with the manufacturer’s instructions.

INSTALLATION OF FLEXIBLE CONDUITTHROUGH RETURN AIR OPENING

NOTE: To allow proper clearance between the

control panel and any vent options, 90°

conduit fittings must be used on the back of

the control panel.

INSTALLING CONDUIT (See Figure 10.)

1. Remove conduit access panel if required to gain

access to area behind control panel.

2. Remove low voltage and high voltage knockouts

located in rear of control panel.

3. Run low voltage conduit through 7/8 bushing located

in conduit entrance plate and secure to low voltage

opening in rear of control panel.

4. Run high voltage conduit through 1-3/4 bushing

located in conduit entrance plate and secure to high

voltage opening in rear of control panel.

5. Replace conduit access panel if required to complete

installation.

6. Seal around conduit in conduit entrance plate.

WARNINGFailure to provide a proper electrical groundcould result in electric shock or fire.

15. WIRING – MAIN POWER

Refer to unit rating plate for wire sizing information

and maximum fuse or “HACR” type circuit breaker

size. Each outdoor unit is marked with a “Minimum

Circuit Ampacity”. This means that the field wiring

used must be sized to carry that amount of current. All

models are suitable only for connection with copper

wire. Each unit and/or wiring diagram will be marked -

“Use Copper Conductors Only”. These instructions

must be adhered to. Refer to the National Electrical

Code (NEC) for complete current carrying capacity

data on the various insulation grades of wiring material.

All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C

copper) for all models.

The unit rating plate lists a “Maximum Time Delay

Relay Fuse” or “HACR” type circuit breaker that is to

be used with the equipment. The correct size must be

used for proper circuit protection and also to assure that

there will be no nuisance tripping due to the momentary

high starting current of the compressor motor.

The disconnect access door on this unit may be locked

to prevent unauthorized access to the disconnect. To

convert for the locking capability bend the tab located

in the bottom left hand corner of the disconnect opening

under the disconnect access panel straight out. This tab

will now line up with the slot in the door. When shut, a

padlock may be placed through the hole in the tab

preventing entry.

See “Start Up” section for important information on

three phase scroll compressor start ups.

WARNINGFor your personal safety, turn off electricpower at service entrance panel beforemaking any electrical connections. Failure todo so could result in electric shock or fire.

WARNINGFailure to provide an electrical power supplyshut off means could result in electric shockor fire.

Page 21: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 21 of 73

NOTE: The voltage should be measured at the field

power connection point in the unit and while

the unit is operating at full load (maximum

amperage operating condition).

PAT EGNAR

042 602–352

802 781–022

17. THERMOSTATS

16. WIRING – LOW VOLTAGE WIRING

Low Voltage Connection

These units use a 24-volt AC low voltage circuit.

The “R” terminal is the hot terminal and the “C”

terminal is grounded.

“G” terminal is the fan input.

“Y” terminal is the compressor input.

“R” terminal is 24 VAC hot.

“C” terminal is 24 VAC grounded.

“F” terminal is the ventilation input. This terminal

energizes any factory or field installed vent option.

230/208 VOLT UNITS

All models are equipped with dual primary voltage

transformers. All equipment leaves the factory wired

on 240V tap. For 208V operation, reconnect from

240V to 208V tap. The acceptable operating voltage

range for the 240V and 208V taps are:

460 VOLT UNITS

All models are equipped with single primary voltage

transformers and no rewiring is required.

TABLE 3

THERMOSTAT WIRE SIZE

remrofsnarTAV ALF eguaGeriW

mumixaMecnatsiDteeFnI

55 3.2 eguag02eguag81eguag61eguag41eguag21

5406001061052

FIGURE 10

INSTALLATION OF FLEXIBLE CONDUIT

TABLE 4

WALL THERMOSTAT

tatsomrehT serutaeFetanimoderP

750-30480401D0113HT

loocegats1,taehegats1otua-no:naFlooc-ffo-taeh:metsyS

elbammargorP-noNcinortcelE

060-3048544-0211

taehegats3;loocegats3cinortcelEelbammargorP-noN/elbammargorP

lanoitnevnoCroPHrevoegnahclaunaMrootuA

Direct Digital Controls (DDC)For total and proper control using DDC, a total of 5

controlled outputs are required (4 if no ventilation is

installed).

LOW VOLTAGE CONNECTIONS FOR DDC CONTROL

Fan Only Energize G

Cooling Mode Energize G, Y

Heating Mode Energize W1

Ventilation Energize G, F

Page 22: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 22 of 73

FIGURE 11

LOW VOLTAGE WIRING

Page 23: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 23 of 73

FIGURE 12

GAS PIPE CONNECTION

Page 24: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 24 of 73

18. GAS SUPPLY AND PIPING

GENERAL RECOMMENDATIONS

1. Be sure the gas line complies with the local codes

and ordinances, or in their absence with the National

Fuel Gas Code, ANSI Z223.1, or Natural Gas

Installation Code, CAN/CGA B149.1, or Propane

Installation Code B149.2, latest edition.

2. A sediment trap or drip leg must be installed in the

supply line to the furnace.

3. A ground joint union shall be installed in the gas line

adjacent to and upstream from the gas valve and

downstream from the manual shut off valve.

4. An 1/8" NPT plugged tapping accessible for test

gauge connection shall be installed immediately

upstream of the gas supply connection to the furnace

for the purpose of determining the supply gas

pressure. This can be omitted if local codes permit

use of plugged tapping in gas valve inlet.

5. Install listed manual shut off valve in the supply gas

line external to and immediately upstream of the

furnace. See Figure 12.

6. Use steel or wrought iron pipe and fittings.

7. DO NOT thread pipe too far. Valve distortion or

malfunction may result from excess pipe within the

control. Use pipe joint compound resistant to the

action of liquefied petroleum gases on male threads

only. DO NOT use Teflon tape. See Table 5 and

Figure 13.

TABLE 5

LENGTH OF STANDARD

PIPE THREADS (INCHES)

eziSepiPhtgneLevitceffE

daerhTfohtgneLllarevO

daerhTfo

8/3 2/1 61/9

4/3 61/9--2/1 61/31

1 61/9 1

fohtgneLteeF-epiP

eziSepiPtupnIruoHrepUTB-yticapaCepiP

"2/1 "4/3 "1 "4/1-1

01 000,231 000,872 000,025 000,050,1

02 000,29 000,091 000,053 000,037

03 000,37 000,251 000,582 000,095

04 000,36 000,031 000,542 000,005

05 000,65 000,511 000,512 000,044

06 000,05 000,501 000,591 000,004

07 000,64 000,69 000,081 000,073

08 000,34 000,09 000,071 000,053

001 000,83 000,97 000,051 000,503

TABLE 6

GAS PIPE SIZES - NATURAL GAS

CHECKING THE GAS PIPING

Before turning gas under pressure into piping, all

openings from which gas can escape should be closed.

Immediately after turning on gas, the system should be

checked for leaks. This can be done by watching the 1/2

cubic foot test dial and allowing 4 minutes to show any

movement, and by soaping each pipe connection and

watching for bubbles. If a leak is found, make the

necessary repairs immediately and repeat the above test.

The furnace must be isolated from the gas supply piping

system by closing the manual shut off valve on the

combination gas control valve during pressure testing of

the gas supply piping system at pressures up to 1/2

PSIG. The furnace and its individual shut off valve must

be disconnected from supply piping and supply piping

capped during any pressure testing of supply piping

system at test pressures in excess of 1/2 PSIG.

Defective pipes or fittings should be replaced and not

repaired. Never use a flame or fire in any form to locate

gas leaks; use a soap solution.

After the piping and meter have been checked

completely, purge the system of air. DO NOT bleed air

inside the furnace. Be sure to check and relight all the

gas pilots on other appliances that may have been

extinguished because of interrupted gas supply.

FIGURE 13

PROPER PIPING PRACTICE

8. Refer to Table 6 for Gas Pipe Sizes for natural gas.

If more than one appliance is supplied from a single

line size, capacity must equal or exceed the

combined input to all appliances, and the branch

lines feeding the individual appliances properly sized

for each input.

MIS-897

THIS PRODUCT MUST BE GAS PIPED BY

A LICENSED PLUMBER OR GAS FITTER

IN THE COMMONWEALTH OF

MASSACHUSETTS.

Page 25: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 25 of 73

19. MANIFOLD PRESSUREADJUSTMENT

You will need a 0 to 15 inch water manometer with 0.1

inch resolution and a 1/8" NPT manual shut off valve to

measure actual manifold pressure.

Depending on your local gas heating value and

elevation, you may need to adjust manifold pressure or

change orifices to get proper gas input rate. Check

with your local gas supplier to determine heating value

(BTU/cu. ft.) of natural gas in your area.

NOTE: If furnace is being installed at an altitude of

more than 6,000 feet above sea level, you

must derate the furnace. See Section 21

“Standard Orifice Sizing and High Altitude

Derate”.

20. CHECKING GAS INPUT RATE

It is the installer's responsibility to see that the BTU

input rate of the furnace is properly adjusted. Under-

firing could cause inadequate heat, excessive

condensation or ignition problems. Overfiring could

cause sooting, flame impingement or overheating of

heat exchanger.

1. Turn off gas at equipment shut off valve in gas

supply line just ahead of furnace.

2. Remove plug from outlet pressure tap in gas control

or gas manifold.

3. Install 1/8" NPT manual shut off valve in hole

vacated by plug. Make sure shut off valve is in off

position.

4. Attach manometer to 1/8" NPT manual shut off

valve just installed.

PROPANE (LP) GAS CONVERSION

This unit may be converted in the field for

use with Propane (LP) gas. Propane gas

conversion kit number WGCK-1 is designed

for conversions of units installed from

0 – 6,000 feet elevations. Propane gas

conversion kit number WGCK-2 is designed

for conversions of units installed from 6,001

– 10,000 feet elevations. These kits may

be purchased from your local distributor.

5. Slowly open equipment shut off valve in gas supply

line just ahead of furnace. Start furnace following

“Operating Instructions” on front door.

6. Slowly open 1/8" NPT manual shut off valve leading

to manometer.

7. Read manifold pressure on manometer.

8. Adjust manifold pressure by turning gas control

regulator adjusting screw clockwise to increase

pressure or turning counterclockwise to decrease

pressure. Manifold pressure must be within

allowable range as follows:

• Natural gas manifold pressure must be between

3.2 and 3.8 inches W.C. Rated pressure is 3.5

inches.

• Propane gas (LP) manifold pressure must be

between 9.7 and 10.3 inches W.C. Rated

pressure is 10 inches.

NOTE: For natural gas, if gas flow rate can't be

properly set within these pressure ranges

then you must change main burner orifices to

obtain proper gas flow rate.

9. Shut off furnace. Turn off gas at equipment shut off

valve in gas supply line just ahead of furnace. Install

outlet pressure tap plug in gas control. Turn on gas.

10. Check regulator adjustment cover screw and gas

control plug for gas leaks. Use a commercial soap

solution made for leak detection.

WARNINGFailure to adjust furnace to the proper firingrate could cause heat exchanger failure.

WARNINGWhen converting from propane (LP) gas tonatural gas, the gas orifice spuds and gasvalve spring must be replaced and the gasvalve regulator pressure must be adjustedcorrectly. Failure to do so can result in fire,injury or death. Refer to Tables 8 and 8A forproper orifice sizing.

Natural gas spring kit, Part number 5603-007,can be purchased through your localdistributor.

WARNINGCorrect manifold pressure is necessary forproper ignition and burner operation. Failureto accurately adjust pressure could causeheat exchanger failure.

Page 26: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 26 of 73

NATURAL GAS INPUT RATE

Natural gas heating value (BTU/cu. ft.) can vary

significantly. Before starting natural gas input check,

obtain gas heating value at your location from local

supplier. You will need a stopwatch to measure actual

gas input.

1. Gas supply pressure must be between 5 and 7 inches

W.C. for natural gas.

2. Turn off all other gas appliances. You may leave

pilots on.

3. Start furnace following “Operating Instructions” on

front door.

4. Let furnace warm up for 6 minutes.

5. Locate gas meter. Determine which dial has the

least cubic feet of gas and how many cubic feet per

revolution it represents. This is usually one-half, one

or two cubic feet per revolution.

6. With stopwatch, measure time it takes to consume

two cubic feet of gas.

• If dial is one-half cubic foot per revolution,

measure time for four revolutions.

• If dial is one cubic foot per revolution, measure

time for two revolutions.

• If dial is two cubic feet per revolution, measure

time for one revolution.

7. Divide this time by two. This gives average time for

one cubic foot of gas to flow through meter.

Example: If it took 58 seconds for two cubic feet to

flow, it would take 29 seconds for one cubic foot to

flow.

8. Calculate gas input using this formula:

Gas Heating Value (BTU/cu. ft.) x 3,600 sec/hr

Gas input = = BTU/hour Time (Seconds for one

cubic foot of gas)

Example:

Assume it took 29 seconds for one cubic foot of gasto flow and heating value of 1,000 BTU/cu. ft.

1,000 x 3,600 Gas input = = 124,138 BTU 29

If you left no other pilots on, this is the furnace gasinput.

PROPANE (LP) GAS INPUT RATE

1. Make sure you have proper main burner orifices.

2. Gas supply pressure must be between 11 and 13

inches W.C. for propane (LP) gas.

3. Start furnace following “Operating Instructions” on

front door.

4. Let furnace warm up for 6 minutes.

5. Adjust manifold pressure to 10.0 W.C. ± 0.3 inches

W.C. See Section 19, “Manifold Pressure

Adjustment”.

WARNINGPropane (LP) gas installations do not havegas meters to double check input rate.Measure manifold pressure adjustment withan accurate manometer. Failure to accuratelyadjust pressure could cause heat exchangerfailure, asphyxiation, fire or explosion,resulting in damage, injury or death.

WARNINGDo not set Propane (LP) manifold pressure at11.0 inches W.C. It could cause heatexchanger failure.

9. If you left water heater, dryer or range pilots on,

allow for them in calculating correct furnace gas

input. A quick way is to allow 1,000 BTU per hour

for a water heater, 500 BTU per hour for dryer and

500 BTU per hour for each range burner pilot.

Example:

If you left gas water heater, dryer, two range burner

pilots and one oven pilot on, allow:

Water heater pilot 1,000 BTU per hour

Dryer pilot 500 BTU per hour

2 range burner pilots 1,000 BTU per hour

1 range oven pilot 500 BTU per hour

3,000 BTU per hour

Subtracting 3,000 BTU per hour from 124,138 BTU

per hour measured above equals 121,138 BTU per

hour. This would be the correct furnace gas input

after allowing for pilots left on.

10. Manifold pressure may be adjusted within the range

of 3.2 inches W.C. to 3.8 inches W.C. to get rated

input ± 2 percent. See Section 19, “Manifold

Pressure Adjustment”. If you cannot get rated input

with manifold pressure within the allowable range,

you must change orifices.

Page 27: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 27 of 73

21. STANDARD ORIFICE SIZING AND HIGH ALTITUDE DERATE

This furnace is shipped with fixed gas orifices for use

with Natural Gas and sized for 1000 BTU/cubic foot

gas. Make sure actual gas input does not exceed rating

plate input. You may need to change orifices to get

correct gas input. Whether you do or not depends on

input, and your gas heat value at standard conditions

and elevation. Consult your local gas supplier for gas

heat value and any special derating requirements. See

Section 20 for more information.

At higher altitudes, the density of the air is reduced.

Therefore, for proper combustion, the quantity of gas

burned in the furnace must also be reduced. This is

called derating. This unit must be derated when

installed at altitudes greater than 6,000 feet above sea

level. A high altitude pressure switch must also be

installed for operation above 6,000 feet. High altitude

pressure switch kit number 8620-189 is designed for

this application.

TABLE 7

NATURAL GAS DERATE CAPACITIES

FOR ALL MODELS

detaRGWtupnI

aeSleveL 000,1 000,2 000,3 000,4 000,5 000,6 000,7 000,8 000,9 000,01

000,14000,54

005,04000,54

402,93065,34

809,73021,24

216,63086,04

046,53006,93

299,43088,83

281,43089,73

696,33044,73

840,33027,63

346,23072,63

670,23046,53

000,16000,86

057,06005,76

608,85043,56

268,65081,36

819,45020,16

064,35004,95

884,25023,85

372,15079,65

445,05061,65

275,94080,55

569,84504,45

411,84064,35

000,57000,18

000,57000,18

006,27804,87

002,07618,57

008,76422,37

000,66082,17

008,46489,96

003,36463,86

004,26293,76

002,16690,66

054,06682,56

004,95251,46

000,09000,001

000,09000,001

021,78008,69

042,48006,39

063,18004,09

002,97000,88

067,77004,68

069,57004,48

088,47002,38

044,37006,18

045,27006,08

082,17002,97

000,311000,521

005,211000,521

009,801000,121

003,501000,711

007,101000,311

000,99000,011

002,79000,801

059,49005,501

006,39000,401

008,19000,201

576,09057,001

001,98000,99

It is the installer’s responsibility to see that the furnace

input rate is adjusted properly. Derating must be

achieved by reducing the size of the main burner

orifices. Derating the furnace by adjusting the manifold

pressure lower than the range specified in the Section

19, “Manifold Pressure Adjustment” is considered to be

an improper procedure.

Above 6,000 feet elevation orifice changes are required,

and capacity reductions are a function of altitude

impact and orifice change. Pressure switch change is

required above 6,000 feet elevation. For Natural Gas

see the Altitude Table 7 below and the Orifice Tables 8

and 8A on following pages.

Page 28: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 28 of 73

All other orifice sizes shown are available as individual items. See Orifice charts below for part numbers and number required.

TABLE 8

NATURAL GAS ORIFICE TABLES

FOR MODELS WG24, WG30 AND WG36

yrotcaFdradnatS

tupnIeulaV*taeHsaG

.tF.uC/UTB

oNteeF000,6otpUtpecxEsegnahCtnetnoCUTBrof

teeF000,8ot100,6hctiwSerusserPseriuqeRegnahCecifirOdnaegnahC

tnetnoCUTBnodesaB t

teeF000,01ot100,8hctiwSerusserPseriuqeRegnahCecifirOdnaegnahC

tnetnoCUTBnodesaB t

UTB00522renruBreP

947-007 57.2 07.2 06.2

997-057 07.2 06.2 05.2

948-008 06.2 05.2 54.2

998-058 05.2 54.2 53.2

949-009 54.2 53.2 )03.2(

999-059 53.2 )03.2( 52.2

**9401-0001 )03.2( 52.2 ]02.2[

0011-0501 52.2 ]02.2[ 51.2

hctiwSerusserP )55.(dradnatS )24.(tiKhctiwSerusserPedutitlAhgiH981-0268redrO

ezisecifirodellatsniyrotcafdradnatsehtsi)03.2( dellatsnidleifroftinuehthtiwdeppihserasecifiro]02.2[etared%01lanoitpo

lanoitpOdleiF%01detrevnoC

etareDeulaV*taeHsaG

.tF.uC/UTB

oNteeF000,6otpUtpecxEsegnahCtnetnoCUTBrof

teeF000,8ot100,6hctiwSerusserPseriuqeRegnahCecifirOdnaegnahC

tnetnoCUTBnodesaB

teeF000,01ot100,8hctiwSerusserPseriuqeRegnahCecifirOdnaegnahC

tnetnoCUTBnodesaB

UTB05202renruBreP

947-007 06.2 05.2 54.2

997-057 05.2 54.2 04.2

948-008 54.2 04.2 )03.2(

998-058 04.2 )03.2( 52.2

949-009 )03.2( 52.2 ]02.2[

999-059 52.2 ]02.2[ 51.2

**9401-0001 ]02.2[ 51.2 01.2

0011-0501 51.2 51.2 01.2

hctiwSerusserP )55.(dradnatS )24.(tiKhctiwSerusserPedutitlAhgiH981-0268redrO

dellatsnidleifroftinuehthtiwdeppihserasecifiro]02.2[.etartupni%01lanoitpo

tupnidetarllufrofezisecifirodellatsniyrotcafehtsi)03.2(

***

.ytivargcificeps06.,detarutas,F06,yrucreMsehcni00.03:snoitidnocdradnatstAlevelaesdnasagtfuc/UTB5201lanimonnodesabsgnitartupnidradnatsdnagnizisecifiroyrotcafsaGlarutaNllA

snoitidnoc

.oNtraPdraB )mm(eziSecifirO retemaiDecifirO

290-0109 01.2 6280.0

880-0109 51.2 6480.0

780-0109 02.2 6680.0

680-0109 52.2 5880.0

280-0109 03.2 5090.0

580-0109 53.2 5290.0

970-0109 04.2 5490.0

480-0109 54.2 4690.0

390-0109 05.2 4890.0

490-0109 06.2 4201.0

590-0109 07.2 3601.0

690-0109 57.2 2801.0

790-0109 08.2 2011.0

890-0109 09.2 2411.0

deriuqeRsecifirOfo.oNgnitaRtupnItinUnodesaB

000,14 )2(

000,54 )2(

000,16 )3(

000,86 )3(

000,57 )3(

000,18 )4(

000,09 )4(

000,001 )4(

000,311 )5(

000,521 )5(

Page 29: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 29 of 73

All other orifice sizes shown are available as individual items. See Orifice charts on Page 28 for part numbers and number required.

TABLE 8A

NATURAL GAS ORIFICE TABLES

FOR MODELS WG42, WG48 AND WG60

yrotcaFdradnatS

tupnI

*taeHsaGeulaV

.tF.uC/UTB

oNteeF000,6otpUtpecxEsegnahCtnetnoCUTBrof

teeF000,8ot100,6hctiwSerusserPseriuqeR

ecifirOdnaegnahCegnahC

tnetnoCUTBnodesaB t

teeF000,01ot100,8hctiwSerusserPseriuqeR

ecifirOdnaegnahCegnahC

tnetnoCUTBnodesaB t

UTB00052renruBreP

947-007 09.2 08.2 07.2

997-057 08.2 07.2 06.2

948-008 07.2 06.2 05.2

998-058 06.2 05.2 54.2

949-009 05.2 54.2 )04.2(

999-059 54.2 )04.2( 53.2

**9401-0001 )04.2( 53.2 ]03.2[

0011-0501 ]03.2[ 52.2 02.2

hctiwSerusserP )55.(dradnatS )24.(tiKhctiwSerusserPedutitlAhgiH981-0268redrO

ezisecifirodellatsniyrotcafdradnatsehtsi)04.2( dellatsnidleifroftinuehthtiwdeppihserasecifiro]03.2[etared%01lanoitpo

lanoitpOdleiF%01detrevnoC

etareD

*taeHsaGeulaV

.tF.uC/UTB

oNteeF000,6otpUtpecxEsegnahCtnetnoCUTBrof

teeF000,8ot100,6hctiwSerusserPseriuqeR

ecifirOdnaegnahCegnahC

tnetnoCUTBnodesaB

teeF000,01ot100,8hctiwSerusserPseriuqeR

ecifirOdnaegnahCegnahC

tnetnoCUTBnodesaB

UTB00522renruBreP

947-007 57.2 07.2 06.2

997-057 07.2 06.2 05.2

948-008 06.2 05.2

998-058 05.2 54.2 )04.2(

949-009 )04.2( 53.2 ]03.2[

999-059 53.2 ]03.2[ 52.2

**9401-0001 ]03.2[ 52.2 02.2

0011-0501 52.2 52.2 02.2

hctiwSerusserP )55.(dradnatS )24.(tiKhctiwSerusserPedutitlAhgiH981-0268redrO

dleifroftinuehthtiwdeppihserasecifiro]03.2[.etartupni%01lanoitpodellatsni

tupnidetarllufrofezisecifirodellatsniyrotcafehtsi)04.2(

***

.ytivargcificeps06.,detarutas,F06,yrucreMsehcni00.03:snoitidnocdradnatstAaesdnasagtfuc/UTB5201lanimonnodesabsgnitartupnidradnatsdnagnizisecifiroyrotcafsaGlarutaNllA

snoitidnoclevel

Page 30: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 30 of 73

23. MEASURING AIR TEMPERATURERISE

Air temperature rise (supply air temperature minus

return air temperature) must be within allowable air

temperature rise range specified on furnace rating plate

and in Table 1.

You will need 2 thermometers with 1 degree resolution

capable of reading up to 200 degrees F. Check

thermometers to make sure they agree, or compensate

accordingly.

Follow this procedure:

1. Open supply air registers and return air grilles.

Make sure the registers and grilles are free of

obstruction from rugs, carpets, drapes or furniture.

22. CONVERSION OF GAS INPUT BTUHFROM HIGH TO LOW RATING

All the derated WG series units are produced with

maximum BTUH input orifices installed. To field

convert input, a change to main burner orifices is

required.

NOTE: No change to air orifices is necessary. A set

of low input orifices is shipped with every

unit. They will be found packaged in a bag

behind the burner door. Refer to the unit

rating plate to confirm the proper orifice size.

Proper installation of the orifices is detailed

as follows:

A. Shut off electrical supply to the unit.

B. Shut off gas supply to the unit.

C. Remove burner access panel.

D. Disconnect gas valve from gas supply piping.

E. Disconnect the two wires from the gas valve.

F. Remove the manifold assembly so that orifices are

now accessible and remove orifices.

G. Apply a modest amount of pipe compound to the

new orifices and screw them into the manifold.

H. To assemble burner reverse steps A through G.

2. Set balancing dampers in supply duct system.

3. Check duct work for obstructions or leaks.

4. Make sure filters are clean and in place.

5. Place one thermometer in supply air plenum

approximately 2 feet from furnace. Locate

thermometer tip in center of plenum to insure proper

temperature measurement.

6. Place second thermometer in return air duct

approximately 2 feet from furnace. Locate

thermometer tip in center of duct to insure proper

temperature measurement.

7. Set room thermostat on highest temperature setting.

Operate furnace 10 minutes. Record supply air and

return air temperatures.

8. Calculate air temperature rise by subtracting return

air temperature from supply air temperature.

• If air temperature rise is above the temperature

rise range on rating plate, furnace is overfired

or has insufficient airflow. Check gas input

following the instructions in Section, “Checking

Gas Input Rate”. If air temperature rise is still

above temperature rise rangespecified, more

heating airflow is needed. Check duct work and

grilles to make sure all are properly sized.

• If air temperature rise is below the temperature

rise range on rating plate, furnace is underfired

or has too much airflow. Check gas input

following the instructions in Section, “Checking

Gas Input Rate”. If air temperature rise is still

below temperature rise range specified, less

heating airflow is needed. Adjust dampers or

grilles as needed.

• After making adjustments, you must check air

temperature rise to verify that resulting air

temperature rise is within allowable range. If

air temperature rise is still outside the

temperature rise range specified on rating

plate, check duct system design with a

qualified heating engineer. It may be

necessary to re-size the duct work. Recheck

air temperature rise after revising duct systems.

9. Set room thermostat to desired setting.

10. Remove thermometers and seal duct work holes.

NOTE: Failure to seal holes could result in reduced

system performance.

WARNINGFailure to follow these instructions couldcreate a hazard resulting in property damage,bodily injury, or death.

Page 31: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 31 of 73

24. FILTERS

A 2" thick throwaway filter is supplied with each unit.

This filter is installed by opening the main service door.

(See Figure 14.)

Replacement filters are available through your dealer.

25. COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout

timer with high and low pressure switch monitoring and

alarm output.

ADJUSTABLE DELAY-ON-MAKE AND BREAKTIMER

On a call for compressor operation the delay-on-make

period begins which will be 10% of the delay-on-break

setting. When the delay-on-make is complete and the

high pressure switch (and low pressure switch if

employed) is closed, the compressor contactor is

energized. Upon shutdown, the delay-on-break timer

starts and prevents restart until the delay-on-break and

delay-on-make periods have expired.

HIGH PRESSURE SWITCH AND LOCKOUTSEQUENCE (Standard Feature)

If the high pressure switch opens, the compressor

contactor will de-energize immediately. The lockout

timer will go into a soft lockout and stay in soft lockout

until the high pressure switch closes and the delay-on-

make time has expired. If the high pressure switch

opens again in this same operating cycle the unit will

go into manual lockout condition and the alarm circuit

will energize. Recycling the wall thermostat resets the

manual lockout.

LOW PRESSURE SWITCH, BYPASS, ANDLOCKOUT SEQUENCE

NOTE: The low pressure switch is an optional

control and the bypass and lockout sequence

are part of the standard compressor control

module.

If the low pressure switch opens for more that 120

seconds, the compressor contactor will de-energize and

go into a soft lockout. Regardless the state of the low

pressure switch, the contactor will reenergize after the

delay-on-make time delay has expired. If the low

pressure switch remains open or opens again for longer

than 120 seconds the unit will go into manual lockout

condition and the alarm circuit will energize.

Recycling the wall thermostat resets the manual

lockout.

FIGURE 14

ACCESS INTERNAL FILTER

THROUGH UPPER SERVICE DOOR

Page 32: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 32 of 73

ALARM OUTPUT

Alarm terminal is output connection for applications

where alarm signal is desired. This terminal is powered

whenever compressor is locked out due to HPC or LPC

sequences as described.

NOTE: Both high and low pressure switch controls

are inherently automatic reset devices. The

high pressure switch and low pressure switch

cut out and cut in settings are fixed by

specific air conditioner or heat pump unit

model. The lockout features, both soft and

manual, are a function of the Compressor

Control Module.

ADJUSTMENTS

ADJUSTABLE DELAY-ON-MAKE ANDDELAY-ON-BREAK TIMER

The potentiometer is used to select Delay-on-Break

time from 30 seconds to 5 minutes. Delay-on-Make

(DOM) timing on power-up and after power

interruptions is equal to 2 minutes plus 10% of Delay-

on-Break (DOB) setting:

0.5 minute (30 seconds) DOB = 123 second DOM

1.0 minute (60 seconds) DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM

3.0 minute (160 seconds) DOB = 138 second DOM

4.0 minute (240 seconds) DOB = 144 second DOM

5.0 minute (300 seconds) DOB = 150 second DOM

PHASE MONITOR

All units with three phase scroll compressors are

equipped with a three phase line monitor to prevent

compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two

LEDs. If the “Y” signal is present at the phase monitor

and phases are correct, the green LED will light.

If phases are reversed, the red fault LED will be lit and

compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply

leads to the unit. Do not reverse any of the unit factory

wires as damage may occur.

Page 33: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 33 of 73

26. LIGHTING AND SHUTDOWN INSTRUCTIONS

FIGURE 15

INSTRUCTION LABEL

Page 34: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 34 of 73

27. SERVICE AGENCY PROCEDURES

MAIN BURNER

Observe the main burners in operation. The flame

should be mostly “blue” with possibly a little orange

(not yellow) at the tips of the flame. The flames should

be in the center of the heat exchanger tubes and not

impinging on the heat exchanger surfaces themselves.

Observe the fire until the blower starts (there is anormal delay period until the heat exchanger warmsup). There should be no change in the size or shape ofthe flame. If there is any wavering or blowing of theflame on blower start-up, it is an indication of apossible leak in the heat exchanger.

28. MAINTAINING UNIT IN GOODWORKING ORDER

The unit should be inspected annually by a qualified

service agency.

BURNERS / HEAT EXCHANGER / FLUE GAS

PASSAGE WAYS

The burners, heat exchanger and interior flue gas

passages may be inspected using a light on small mirror

or an extension handle. Remove the screws securing

the inducer and collector box. Now inspect the upper

tubes of the heat exchanger.

Check the exterior of the heat exchanger and the

interior flue gas passages for any evidence of

deterioration due to corrosion, cracking or other causes.

If signs of sooting exist, remove the burners and clean

the heat exchanger, as required.

MIS-165

FIGURE 16

TOP VIEW OF GAS CONTROL

CAUTIONLabel all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation. Verify

proper operation after servicing.

WARNINGFollow these procedures before inspecting

furnace.

• Turn room thermostat to its lowest or off

setting.

• Turn off manual gas shut off valve.

• Wait at least 5 minutes for furnace to cool

if it was recently operating.

• Turn off furnace electrical power; failure

to do so could result in injury or death.

WARNINGUse replacement parts listed in theReplacement Parts list only. The use ofincorrect parts could cause improper unitoperation, resulting in damage, injury ordeath.

Page 35: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 35 of 73

ROUTINE MAINTENANCE

1. Air Filters – Check the condition at least monthly

when the unit is in use, and replace as necessary.

2. Lubrication Requirements – The indoor circulating

air blower motor and outdoor circulating air fan

motor are permanently lubricated and requires no re-

oiling. The combustion air blower motor requires no

re-oiling.

ROUTINE INSPECTION

1. Inspect the physical support of the unit annually to

make sure it is securely fastened to the building.

Also look for any obvious signs of deterioration.

2. Inspect the main burners at the beginning of each

heating season and clean as necessary.

3. Inspect the vent terminal and combustion air intake

hood for any obvious deterioration, to make sure it is

free and clear of any obstructions.

29. REPLACEMENT PARTS

ANNUAL MAINTENANCE

Routine inspection and maintenance procedures are the

responsibility of the user and are outlined below.

1. Before inspecting unit:

a. Turn room thermostat to lowest or off setting.

b. Turn off equipment gas shut off valve.

c. Wait for unit to cool if it was recently

operating.

d. Turn off electrical power to unit.

2. Inspect the following:

a. Vent terminal and combustion air intake

terminal. Make sure both are free from

obstructions.

b. Vertical Vent Applications – Inspect venting

system. Make sure system has no holes, is

physically sound and free from obstructions.

c. Make sure the supply and return air flange

sleeves or duct work are securely fastened to

unit and physically sound.

d. Supply and return grilles must be open and

free from obstructions.

e. Inspect to make sure the unit is securely

fastened to the wall. Seal any possible leaks

between unit and wall with appropriate

exterior sealing material.

f. Inspect burners, heat exchanger, induced

draft blower, and induced draft blower

collector box. There must be no obvious

signs of deterioration.

g. Inspect all electrical connections and wiring.

h. Check all gas piping for leaks with soap

solution used to detect leaks.

i. Inspect, clean, and repair as needed the entire

blower assembly, air filters, draft inducer,

cooling coils, and vent options (if installed).

Replacement parts for the gas/electric units are

available through local distributors.

A replacement parts list manual is supplied with each

unit. When ordering parts or making inquires

pertaining to any of the units covered by these

instructions, it is very important to always supply the

complete model number and serial number of the unit.

This is necessary to assure that the correct parts (or an

approved alternate part) are issued to the service

agency.

WARNINGDisconnect electrical power before servicingunit. Failure to do so could result in electricalshock or death.

WARNINGTurn off electrical power supply to preventinjury from moving parts or electric shock.

WARNINGUse replacement parts listed in ReplacementParts list. Failure to do so could causeimproper furnace operation, resulting inproperty damage, personal injury, or death.

Page 36: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 36 of 73

30. SEQUENCE OF OPERATION –HEATING

On a call for heat from the thermostat, the induced draft

blower is energized. Once sufficient draft is

established, the pressure switch contacts close and the

ignition system is energized. The direct spark ignitor

will be energized allowing gas to flow. At the same

time the main valve is energized, a 30-second blower

delay timer is activated.

After this delay, the heating speed blower relay

energizes. The blower will begin operating and remain

in operation until the set delay time after the call for

heat has been satisfied. (See Tables 10-15 for selectable

blower off time delays.) This timing sequence

guarantees blower on, blower off operation.

This unit is equipped with a flame roll-out switch,

which is wired in series with the control circuit. This is

a manual reset switch and is used for the purpose of

preventing possible fire hazard in the event of a system

malfunction. If this switch has opened the control

circuit, there could be a possible system malfunction.

Some of the conditions that might cause a roll-out to

occur are blockage or sooting of primary heat

exchanger, overfiring of furnace due to improper main

burner orifices or incorrect manifold pressure,

insufficient combustion air, or installation deficiencies

with respect to return air duct design or sizing.

Once the problem has been resolved, reset the switch by

pressing down on the reset button on top of the switch.

See Figure 17 for additional information.

31. SEQUENCE OF OPERATION –COOLING

On a call for cooling from the room thermostat, the high

speed blower relay will be energized as well as the

compressor contactor. Following termination of the

cooling cycle, the blower motor will continue to run for

one minute.

See Figure 17 for additional information.

The unit may be equipped with a low ambient control

for lower outdoor temperature operation in the cooling

mode. If equipped with this optional control the

condenser fan will not operate immediately upon

compressor start-up, and will cycle on and off until the

condensing pressure remains above 180 PSIG. LAC

energizes the fan motor at 280 PSIG, de-energizes at

180 PSIG.

FIGURE 17

SEQUENCE OF OPERATION

ELECTRONIC BLOWER CONTROL

NOITCA ESNOPSERMETSYS

.taehrofsllactatsomrehT).dezigrenesilanimretW(

•••••

.dezigrenesirewolbrianoitsubmoC.dehsilbatsesiwolfriA.sekamhctiwsgnivorpriA

.dezigrenesimetsysnoitingI.sthgilrenrubniamdnasnepoevlavsaG

sinafgnitalucriceht,etelpmocsignimitnehW.snigebgnimityalednonaftaeH.deepstaehtadezigrene

.taehrofllacsdnetatsomrehT •••

.sesolcevlavsagdnadezigrene-edsimetsysnoitingI.gnimitegruptsopretfadezigrene-edsirewolbrianoitsubmoC

sinafgnitalucriceht,etelpmocsignimitnehW.snigebgnimityaledffonaftaeH.dezigrene-ed

.loocrofllacsnigebtatsomrehT).dezigrene-erslanimretYdnaG(

••

.dezigrenesirotcatnocgnilooC.gnimityalednonafloocretfadeepsloocnodezigrenesinafgnitalucriC

.nafrofllacsdnetatsomrehT).dezigrene-edsilanimretG(

• dezigrene-edsinafgnitalucriC

.snepo)tuolloremalf(timiL ••

.sesolcevlavsagdnadezigrene-ederametsysnoitingidnatatsomrehTnarewolbrianoitsubmoC d .dezigreneeradeepstaehnafgnitalucric

tuolloremalfro)teserotua(timiL.desolctiucric)teserlaunam(

•••

.gnimitegruptsoprofdezigrenesniamerrrewolbrianoitsubmoC.gnimitffoyaleddetcelesehtrofdezigrenesniamernafnoitalucricehT

.semusernoitarepolamroN

Page 37: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 37 of 73

32. INDOOR BLOWER OPERATION

All models have multiple speed direct drive blower

motors. If supply and return ducts are connected to the

unit, the ducts must be of adequate size. Refer to the

appropriate blower tables. See Tables 10, 11, 12, 13,

14 and 15 for maximum static pressures acceptable.

Note the minimum CFM for cooling operation.

If voltage and duct design permit, (see blower tables)

single speed operation can be achieved as follows:

BLOWER MOTOR SPEED CHANGE

1. Disconnect power supply to unit.

2. Place desired blower motor speed lead wire to

“COOL” terminal of integrated furnace control

board.

3. Place desired blower motor speed lead wire to

“HEAT” terminal of integrated furnace control

board.

4. Place unused blower motor speed lead wire to

“UNUSED” terminal of integrated furnace control

board.

5. Energize the system in cooling and heating modes to

check for proper blower operation.

If it is desirable to have both HEAT/COOL blower

motor speed at the same speed, install a jumper wire

between “HEAT” and “COOL” terminals of the

integrated furnace control board, and place both unused

motor speed lead wires on the two “UNUSED” terminals

on the integrated furnace control board. (See Figure 18.)

sdeepS rotoMrewolBdeepS-3

woL deR

muideM eulB

hgiH kcalB

sdeepS rotoMrewolBdeepS-3

woL deR

muideM eulB

hgiH kcalB

*noitalosI egnarO

*noitalosI elpruP

FIGURE 18

FURNACE CONTROL BOARD AND BLOWER CONTROL

TABLE 9

230 VOLT MOTOR SPEED TAPS

460 VOLT MOTOR SPEED TAPS

* NOTE: On 460 Volt motors, there are two motor isolation leads. The orange must connect with the black high

speed blower motor lead wire for medium and low speed blower operation. The purple wire must

connect with the blue medium speed blower motor lead wire for low speed blower operation. This is all

automatically accomplished with blower relays HSBR, MSBR and LSBR, and speed changes are all

made by changes at the integrated furnace control board.

Page 38: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 38 of 73

TABLE 10

WG24 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG24 cooling airflow range at rated 800 CFM @ 0.15 ESP (WC) is 680 - 920 CFM

Factory set on Low Speed for cooling and High for heating.

Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment – Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,09 tupnIUTB000,18

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 098 0531 0211 --- --- 0211 049

1.0 --- --- 028 0621 0601 --- --- 0601 078

2.0 --- 059 077 0021 0101 --- 0021 0101 ---

3.0 --- 088 007 0211 --- --- 0211 049 ---

4.0 --- 097 --- 0301 --- --- 0301 068 ---

5.0 019 017 --- --- --- --- 059 --- ---

6.0 008 --- --- --- --- --- 048 --- ---

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,86 tupnIUTB000,16

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 098 0531 0211 049 --- 0211 049

1.0 --- --- 028 0621 0601 078 --- 0601 078

2.0 --- 059 077 0021 0101 --- --- 0101 018

3.0 --- 088 007 0211 019 --- 0211 049 ---

4.0 --- 097 --- 0301 --- --- 0301 068 ---

5.0 019 017 --- 059 --- --- 059 087 ---

6.0 008 --- --- --- --- --- 048 --- ---

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,54 tupnIUTB000,14

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 098 --- 0211 049 --- 0211 049

1.0 --- --- 028 0621 0601 078 --- 0601 078

2.0 --- 059 077 0021 0101 018 0021 0101 018

3.0 --- 088 007 0211 019 --- 0211 049 057

4.0 --- 097 --- 0301 068 --- 0301 068 086

5.0 019 017 --- 059 087 --- 059 087 ---

6.0 008 --- --- 048 --- --- 048 --- ---

Page 39: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 39 of 73

TABLE 11

WG30 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG30 cooling airflow range at rated 1000 CFM @ 0.35 ESP (WC) is 820 - 1150 CFM

Factory set on Medium Speed for cooling and for heating.

Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment – Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,09 tupnIUTB000,18

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- 0531 0211

1.0 --- --- 0001 --- 0621 0601 --- 0621 0601

2.0 --- 0611 059 0731 0021 0101 --- 0021 0101

3.0 --- 0801 088 0921 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 --- 0911 0301 068

5.0 0501 019 --- 0901 059 --- 0901 059 ---

6.0 049 --- --- 089 --- --- 089 048 ---

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,86 tupnIUTB000,16

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- --- 0211

1.0 --- --- 0001 --- 0621 0601 --- --- 0601

2.0 --- 0611 059 --- 0021 0101 --- --- 0101

3.0 --- 0801 088 --- 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 068 --- 0301 068

5.0 0501 019 --- 0901 059 087 0901 059 087

6.0 049 --- --- 089 048 --- 089 048 066

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,54 tupnIUTB000,14

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- --- 0211

1.0 --- --- 0001 --- 0621 0601 --- --- 0601

2.0 --- 0611 059 --- 0021 0101 --- 0021 0101

3.0 --- 0801 088 0921 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 068 --- 0301 068

5.0 0501 019 --- 0901 059 087 0901 059 087

6.0 049 --- --- 089 048 066 089 048 066

Page 40: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 40 of 73

TABLE 12

WG36 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG36 cooling airflow range at rated 1100 CFM @ 0.250 ESP (WC) is 935 - 1265 CFM

Factory set on Medium Speed for cooling and for heating.

Voltage adjustment – Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment – Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment – Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment – Reduce airflow by 100 CFM for SG-3 and RG-3 installations

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,09 tupnIUTB000,18

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- 0531 0211

1.0 --- 0221 0001 --- 0621 0601 --- 0621 0601

2.0 --- 0611 059 0731 0021 0101 --- 0021 0101

3.0 0521 0801 --- 0921 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 --- 0911 0301 068

5.0 0501 --- --- 0901 059 --- 0901 059 ---

6.0 049 --- --- 089 --- --- 089 048 ---

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,86 tupnIUTB000,16

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- --- 0211

1.0 --- 0221 0001 --- 0621 0601 --- --- 0601

2.0 --- 0611 059 --- 0021 0101 --- --- 0101

3.0 0521 0801 --- --- 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 068 --- 0301 068

5.0 0501 --- --- 0901 059 087 0901 059 087

6.0 049 --- --- 089 048 --- 089 048 066

PSEsehcnI

H2O

EDOMGNILOOC EDOMGNITAEHdnaNAFLAUNAM

lioCteW tupnIUTB000,54 tupnIUTB000,14

hgiH muideM woL hgiH muideM woL hgiH muideM woL

0.0 --- --- 0601 --- 0531 0211 --- --- 0211

1.0 --- 0221 0001 --- 0621 0601 --- --- 0601

2.0 --- 0611 059 --- 0021 0101 --- 0021 0101

3.0 0521 0801 --- 0921 0211 049 --- 0211 049

4.0 0511 099 --- 0911 0301 068 --- 0301 068

5.0 0501 --- --- 0901 059 087 0901 059 087

6.0 049 --- --- 089 048 066 089 048 066

Page 41: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 41 of 73

TABLE 13

WG42 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG42 cooling airflow range at rated 1300 CFM @ .35 ESP (WC) is 1500 - 1030 CFM

Factory set on Medium Speed for heating and cooling

Voltage adjustment – Reduce airflow by 130 CFM for 208 Volt

Top outlet adjustment – Increase airflow by 65 CFM for top outlet models

SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,521 tupnIUTB000,311

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- 0451 0411 --- 0461 0321 --- 0461 0321

01. --- 0841 0901 --- 0851 0811 --- 0851 0811

02. --- 0141 0301 0881 0151 --- --- 0151 0901

03. --- 0631 --- 0671 0641 --- --- 0641 ---

04. --- 0521 --- 0761 0431 --- 0761 0431 ---

05. 0641 0511 --- 0651 0421 --- 0651 0421 ---

06. 0431 0401 --- 0341 0311 --- 0341 0311 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW UTB000,001 tupnIUTB000,09

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- --- 0911 --- 0961 0821 --- 0961 0821

01. --- 0351 0411 --- 0361 0321 --- 0361 0321

02. --- 0641 0701 --- 0651 0611 --- 0651 0611

03. --- 0141 0501 0181 0151 0411 --- 0151 0411

04. --- 0031 --- 0271 0931 --- 0271 0931 0201

05. 0151 0021 --- 0161 0921 --- 0161 0921 079

06. 0931 0901 --- 0841 0811 --- 0841 0811 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,57 tupnIUTB000,86

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- --- 0421 --- 0471 0331 --- 0471 0331

01. --- --- 0911 --- 0861 0821 --- 0861 0821

02. --- 0151 0211 --- 0161 0121 --- 0161 0121

03. --- 0641 0011 0681 0651 0911 --- 0651 0911

04. --- 0431 --- 0771 0441 0701 --- 0441 0701

05. --- 0621 --- 0661 0431 079 0661 0431 079

06. 0441 0411 --- 0351 0321 --- 0351 0321 ---

Page 42: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 42 of 73

TABLE 14

WG48 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG48 cooling airflow range at rated 1550 CFM @ .38 ESP (WC) is 1750 - 1280 CFM

Factory set on High Speed for cooling and Medium Speed for heating.

Voltage adjustment – Reduce airflow by 130 CFM for 208 Volt

Top outlet adjustment – Increase airflow by 65 CFM for top outlet models

SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,521 tupnIUTB000,311

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- 0451 --- --- 0461 0321 --- 0461 0321

01. --- 0841 --- --- 0851 0811 --- 0851 0811

02. 0871 0141 --- 0881 0151 --- --- 0151 0111

03. 0761 0631 --- 0671 0641 --- --- 0641 0901

04. 0751 0521 --- 0761 0431 --- 0761 0431 ---

05. 0641 --- --- 0651 0421 --- 0651 0421 ---

06. 0431 --- --- 0341 --- --- 0341 0311 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW UTB000,001 tupnIUTB000,09

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- 0951 --- --- 0961 0821 --- 0961 0821

01. --- 0351 --- --- 0361 0321 --- 0361 0321

02. --- 0641 --- --- 0651 0611 --- 0651 0611

03. 0071 0141 --- 0181 0151 0411 --- 0151 0411

04. 0261 0031 --- 0271 0931 --- 0271 0931 0201

05. 0151 --- --- 0161 0921 --- 0161 0921 079

06. 0931 --- --- 0841 0811 --- 0841 0811 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,57 tupnIUTB000,86

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- --- 0461 --- 0471 0331 --- 0471 0331

01. --- 0851 --- --- 0861 0821 --- 0861 0821

02. --- 0151 --- --- 0161 0121 --- 0161 0121

03. 0571 0641 --- 0681 0651 0911 --- 0651 0911

04. 0761 0431 --- 0771 0441 0701 --- 0441 0701

05. 0651 0621 --- 0661 0431 079 0661 0431 079

06. 0441 --- --- 0351 0321 --- 0351 0321 ---

Page 43: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 43 of 73

TABLE 15

WG60 INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS

Recommended WG60 cooling airflow range at rated 1650 CFM @ .30 ESP (WC) is 1910 - 1340 CFM

Factory set on High Speed for cooling and Medium Speed for heating.

Voltage adjustment – Reduce airflow by 130 CFM for 208 Volt

Top outlet adjustment – Increase airflow by 65 CFM for top outlet models

SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,521 tupnIUTB000,311

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. 0391 0451 --- --- 0461 0321 --- 0461 0321

01. 0581 0841 --- --- 0851 0811 --- 0851 0811

02. 0871 0141 --- 0881 0151 --- --- 0151 0111

03. 0761 0631 --- 0671 0641 --- --- 0641 0901

04. 0751 --- --- 0761 0431 --- 0761 0431 ---

05. 0641 --- --- 0651 0421 --- 0651 0421 ---

06. 0431 --- --- 0341 --- --- 0341 0311 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW UTB000,001 tupnIUTB000,09

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- 0951 --- --- 0961 0821 --- 0961 0821

01. 0091 0351 --- --- 0361 0321 --- 0361 0321

02. 0381 0641 --- --- 0651 0611 --- 0651 0611

03. 0071 0141 --- 0181 0151 0411 --- 0151 0411

04. 0261 --- --- 0271 0931 --- 0271 0931 0201

05. 0151 --- --- 0161 0921 --- 0161 0921 079

06. 0931 --- --- 0841 0811 --- 0841 0811 ---

PSEsehcnI

HsO

EDOMGNILOOC NAFLAUNAM dna EDOMGNITAEH

lioCteW tupnIUTB000,57 tupnIUTB000,86

hgiH muideM woL hgiH muideM woL hgiH muideM woL

00. --- 0461 --- --- 0471 0331 --- 0471 0331

01. 0591 0851 --- --- 0861 0821 --- 0861 0821

02. 0881 0151 --- --- 0161 0121 --- 0161 0121

03. 0571 0641 --- 0681 0651 0911 --- 0651 0911

04. 0761 0431 --- 0771 0441 0701 --- 0441 0701

05. 0651 --- --- 0661 0431 079 0661 0431 079

06. 0441 --- --- 0351 0321 --- 0351 0321 ---

Page 44: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 44 of 73

TABLE 16

INTEGRATED FURNACE AND BLOWER CONTROL OPERATION

LORTNOCECNEUQESNOITINGI

ecruoSnoitingI ISDCAV42

gnisneSemalF etomeR

sgnimiT

-------

-----

--

egruperPegruptsoP

egruplairt-retnIdoirepgnivorphctiwserusserP

noitingirofslairTnoitingiroflairT

tuokcolecneuqesnoitingI

yaled-norewolbtaeHyaled-fforewolbtaeHyaled-norewolblooCyaled-fforewolblooCsnoitareponaflaunaM

noitarepolortnoctimilhgiHnoitarepohctiwstuolloremalF

510351063706-

03,09

706

sdnoces)"no"evlaverofebdetanimretelcycfi0(sdnoces

sdnocessdnoces

ecneuqesnoitingirepemalfevorpotemitlatotsdnoces

teserotua,)noitingirofslairt3retfa(setunimgninepoybdoireptuokcoletunim06ehtgnirudteserebnac

eromrosdnoces3roftiucrictatsomreht)ffoselcycrotinginehwstratsgnimit(sdnoces021tatesyrotcaf;elbatcelessdnocs051,021

sdnocessdnoces

gnirudffoselcycdnadeepsgnitaehdetcelesnosetarepO.ecneuqesputratsrenrubronoitingi

.1etoNeeS.tratserecneuqesnoitingi,tesercitamotuAyllaunamsihctiwsretfadetaitiniecneuqesnotingi,teserlaunaM

.1etoNeeS.teser:1ETON yaledruoh1aeblliwerehttaehrofllacneviganopirttimilhtruofehtretfA

emalfrohctiwstimilhgihrehtieretfA.tratserlliwecneuqesnoitingiehterofebdnaegruptsopdnoces03ehtrofetarepolliwrecudniehtnoitautcahctiwstuollor

naFlaunaMnofI.yaledffodetcelesehtrofetarepolliwrewolbriatrofmoceht.etarepooteunitnoclliwrewolbriatrofmoceht,noitarepo

STINUYTEFAS

tuolloR/timilhgiHhctiwserusserP

tloV42niTSPSkcehctratsefas,TSPS

LORTNOCNAFTROFMOC

naFdeepSgnitaeHnoitarepolamroN

yaledNO-

yaledFFO-

noitarepOtimiL

esneSemalF

03

3

dezigrene-edretinginehwstratsgnimiT.dexifsdnoces

09otdegnahcebnacdradnatssdnoces021-sgnimitelbatceles.sdnoces051ro

NEPOtimilnehwNOSESOLCtimilnehwyaledFFOretfaFFO

desnessiemalffiNO dna .taehrofllaconsiereht

naFdeepSgnilooC- yaledNO

yaledFFO-

7

06

sdnoces

sdnoces

naFlaunaM nafeht,loocrofllacnehW.deepsGNITAEHnoylsuounitnocNO,deifsitastatsomrehtnehwnehT.deepsGNILOOCotsehctiwsFFOGNILOOCretfadeepsGNITAEHotkcabsehctiwsnafeht

.yaled

ROTACIDNICITSONGAID

:swollofsastluafmetsysetacidniotdedivorpsiDELderAsedomnafrolooc,taehrofllac,ybdnatsniyakolortnoC-NOydaetS

.lortnocnoesufA3kcehcoslA.rewoponrotluaflortnoclanretnI-FFOydaetSstuopordemalfronoitingideliafoteudtuokcoL-hsalf1

norecudnihtiwnepohctiwserusserP-sehsalf2fforecudnihtiwdesolcsihctiwserusserP-sehsalf3

neposihctiwstimiL-sehsalf4desolcevlavsaghtiwdetcetedemalF-sehsalf5

remitgnigats/elcyctrohsmorfdeyaledtuptuorosserpmoC-sehsalf6.sedochsalfneewtebesuapsdnoces0.2htiwffosdnoces52.0,nosdnoces52.0sietarhsalfehT

.sedochsalfneewtebesuapsdnoces0.2htiwffosdnoces52.0,nosdnoes52.0sietarhsalfehT

Page 45: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 45 of 73

33. PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all

units so that the system operating pressures can be

observed. Table 17 outlines expected pressures at

various indoor and outdoor temperatures.

Low side pressure ± 2 PSIGHigh side pressure ± 5 PSIG

TABLE 17

COOLING PRESSURE TABLE

ledoMriAnruteRerutarepmeT erusserP 57 08 58 09 59 001 501 011 511

42GW

BD.ged57BW.ged26

ediSwoLediShgiH

27102

47612

67132

77642

97362

18082

28792

38513

58533

BD.ged08BW.ged76

ediSwoLediShgiH

67702

97122

18732

38352

58072

78782

88603

09423

19443

BD.ged58BW.ged27

ediSwoLediShgiH

28412

58922

78542

98262

19082

39892

59613

79633

89653

03GW

BD.ged57BW.ged26

ediSwoLediShgiH

67812

77132

87542

97162

18872

28592

48413

58433

78653

BD.ged08BW.ged76

ediSwoLediShgiH

18322

28732

38152

58762

78582

88303

09223

19343

39563

BD.ged58BW.ged27

ediSwoLediShgiH

78232

88642

09162

19772

39592

49313

69333

89553

001873

63GW

BD.ged57BW.ged26

ediSwoLediShgiH

27222

47832

57552

67272

87092

97803

18623

28643

38663

BD.ged08BW.ged76

ediSwoLediShgiH

77822

97542

18262

28972

48892

58613

78533

88553

98573

BD.ged58BW.ged27

ediSwoLediShgiH

38732

58452

68172

88982

09803

19723

39643

59763

69883

24GW

BD.ged57BW.ged26

ediSwoLediShgiH

66602

96122

17632

37152

57762

67282

87003

97513

18233

BD.ged08BW.ged76

ediSwoLediShgiH

27112

47622

67242

87752

08472

18092

48703

58323

78143

BD.ged58BW.ged27

ediSwoLediShgiH

87912

08432

28052

48662

68382

78992

98613

19433

39253

84GW

BD.ged57BW.ged26

ediSwoLediShgiH

96991

07412

27922

37442

47162

57872

67492

77213

97133

BD.ged08BW.ged76

ediSwoLediShgiH

47502

57022

67532

87152

97862

08582

28203

38123

58043

BD.ged58BW.ged27

ediSwoLediShgiH

08012

18622

38242

48952

58772

68492

88413

98233

19253

06GW

BD.ged57BW.ged26

ediSwoLediShgiH

96132

07842

27562

37382

47103

57913

67833

77653

97673

BD.ged08BW.ged76

ediSwoLediShgiH

47732

57452

67272

77092

97903

08723

18643

28663

48683

BD.ged58BW.ged27

ediSwoLediShgiH

08542

18362

28282

38003

58023

68933

78063

88973

09993

Page 46: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 46 of 73

"A"

AIRFLOW

MIS-1724

34. REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit

rating plate. Optimum unit performance will occur

with a refrigerant charge resulting in a suction line

temperature (6" from compressor) as shown in

Table 18.

The suction line temperatures in Table 18 are based

upon 80 degrees F dry bulb / 67 degree wet bulb (50%

R.H.) temperature and rated airflow across the

evaporator during cooling cycle.

Total system charge for these models can be found in

Table 1.

35. FAN BLADE SETTING DIMENSIONS

Shown in Figure 19 is the correct fan blade setting

dimension for proper air delivery across the outdoor

coil.

ledoMnoisnemiD

A

42GW 1

03GW 1

63GW 1

24GW 1

84GW 1

06GW 1

TABLE 19

FAN BLADE DIMENSION

FIGURE 19

FAN BLADE

36. LOW-NOX BURNER ASSEMBLY “N”SUFFIX MODELS ONLY – U.S.INSTALLATIONS ONLY

NATURAL GAS MODELS ONLY

Model numbers designated with an “N” are designed

for low NOx emissions which comply with all

California Air Quality Management District regulations

for nitrogen oxide emission levels. Refer to Figure 20

for NOx insert information.

* * IMPORTANT * *

For propane (LP) conversions the NOxreduction screen inserts shown below mustbe removed. This is accomplished byremoving the burner box assembly andremoving the NOx screens. Reassemble unitproperly before firing. Failure to remove theNOx screens can result in improper operationand malfunction of the burner system.

FIGURE 20

LOW NOX INSERT

TABLE 18

REFRIGERANT CHARGE

ledoMdetaRwolfriA

F.geD59.pmeTDO

F.geD28.pmeTDO

42GW 008 95-15 26-06

03GW 0001 06-85 26-06

63GW 0011 95-65 26-06

24GW 0031 75-55 86-66

84GW 0551 65-45 66-46

06GW 0561 85-65 86-66

Page 47: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 47 of 73

INDEX

WIRING DIAGRAMS

and LADDER DIAGRAMS

tinU.oNledoM

cisaBmargaiDgniriW

launaM.oNegaP

cisaBmargaiDreddaL

launaM.oNegaP

A-242GW A431-5804 84 A531-5804 94

B-242GW A432-5804 05 A532-5804 15

C-342GW 143-5804 25 A243-5804 35

A-203GW E031-5804 45 B121-5804 55

B-203GW G032-5804 65 B122-5804 75

C-303GW 343-5804 85 A443-5804 95

A-263GW A831-5804 06 A531-5804 94

B-263GW A832-5804 16 A532-5804 15

C-363GW 543-5804 26 A643-5804 36

A-324GW D621-5804 46 A721-5804 56

B-324GW D622-5804 66 A722-5804 76

C-424GW 743-5804 86 A843-5804 96

A-284GW E021-5804 07 B121-5804 55

B-284GW D022-5804 17 B122-5804 75

C-384GW 943-5804 27 A053-5804 37

A-206GW E021-5804 07 B121-5804 55

B-206GW D022-5804 17 B122-5804 75

C-306GW 943-5804 27 A053-5804 37

Page 48: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 48 of 73

WG242-A 230/208-60-1

Page 49: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 49 of 73

WG242-A, WG362-A 230/208-60-1

Page 50: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 50 of 73

WG242-B 230/208-60-3

Page 51: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 51 of 73

WG242-B, WG362-B 230/208-60-3

Page 52: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 52 of 73

WG243-C 460-60-3

Page 53: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 53 of 73

WG243-C 460-60-3

Page 54: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 54 of 73

WG302-A 230/208-60-1

Page 55: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 55 of 73

WG302-A, WG482-A, WG602-A 230/208-60-1

Page 56: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 56 of 73

WG302-B 230/208-60-3

Page 57: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 57 of 73

WG302-B, WG482-B, WG602-B 230/208-60-3

Page 58: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 58 of 73

WG303-C 460-60-3

Page 59: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 59 of 73

WG303-C 460-60-3

Page 60: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 60 of 73

WG362-A 230/208-60-1

Page 61: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 61 of 73

WG362-B 230/208-60-3

Page 62: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 62 of 73

WG363-C 460-60-3

Page 63: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 63 of 73

WG363-C 460-60-3

Page 64: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 64 of 73

WG423-A 230/208-60-1

Page 65: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 65 of 73

WG423-A 230/208-60-1

Page 66: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 66 of 73

WG423-B 230/208-60-3

Page 67: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 67 of 73

WG423-B 230/208-60-3

Page 68: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 68 of 73

WG424-C 460-60-3

Page 69: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 69 of 73

WG424-C 460-60-3

Page 70: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 70 of 73

WG482-A, WG602-A 230/208-60-1

Page 71: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 71 of 73

WG482-B, WG602-B 230/208-60-3

Page 72: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 72 of 73

WG483-C, WG603-C 460-60-3

Page 73: 2100-365(Q) (2008 05) - Bard HVACQ).pdf · Manual 2100-365Q Page 7 of 73 TABLE 1 SPECIFICATIONS WG24, WG30 AND WG36 MODELS * 75 degree C Copper wire size ** Maximum time delay fuse

Manual 2100-365Q

Page 73 of 73

WG483C, WG603-C 460-60-3